This paper presents an alternative approach to the Transformer Assessment Index (TAI) by proposing a relatively simple rating method called the Exploitation Perspective Index (EPI). The method provides two numerical indicators: the first reflects the overall technical condition of the particular unit, and the second shows the condition of the unit in the context of the entire fleet. The objective of the EPI method is to support the decision-making process regarding the technical condition assessment of each of the transformers in the target population, considering not only technical but also economic aspects of transformer maintenance. Application of the method is described step by step, including input data, parametrization of the weights, and interpretation of the output results it provides. The proposed method is evaluated by two representative use cases and compared with two other methods. As a result, EPI confirms its applicability, and it has already been successfully implemented by the electric power industry. EPI can be potentially freely adopted for any transformer fleet, as well as for the specific situation of the utility, by adjusting the relevant parameters.
Keywords: condition assessment; fault diagnostics; high voltage; measurements; power transformer.