Determining the performance of a commercial air purification system for reducing airborne contamination using model micro-organisms: a new test methodology

J Hosp Infect. 2005 Nov;61(3):242-7. doi: 10.1016/j.jhin.2005.03.004. Epub 2005 Jul 11.

Abstract

The performance of a duct-mounted air disinfection system, designed to reduce airborne pathogens in the hospital environment, was determined using a new testing methodology. The methodology places the equipment in a test duct, a microbial aerosol is generated and then sampled simultaneously before and after the test system. This allows a percentage efficiency value to be calculated. The air disinfection system is a novel chemical-coated filter and ultraviolet (UV) radiation air purification system, operating at a flow rate of 500 m(3)/h, against aerosols of MS2 phage and Mycobacterium vaccae (surrogates of viral and mycobactericidal pathogens). A three UV lamp system was effective against airborne phages, removing an average of 97.34% of the aerosolized challenge. With the UV component switched off, the average efficiency dropped to 61.46%. This demonstrates that the chemical-coated filter component plays a more significant role than the UV radiation in destroying phages. When six UV lamps were used, the system was able to remove mycobacteria with an efficiency exceeding 99.99%. This test methodology can be used to assess manufacturers' claims of efficacy of equipment against airborne micro-organisms in the hospital environment.

Publication types

  • Evaluation Study
  • Research Support, Non-U.S. Gov't

MeSH terms

  • Air Microbiology*
  • Air Pollution, Indoor / prevention & control*
  • Cross Infection / prevention & control*
  • Disinfection / methods*
  • Filtration*
  • Levivirus / growth & development
  • Mycobacterium / growth & development