Aims: To determine Legionella pollution prevalence, describe the amount of Legionellae with respect to temperature in Shanghai cooling tower water (CTWs) in various types of public sites.
Methods and results: Six urban districts were selected as the study fields, adopting multiple-phase sampling methods. Routine culture was used to identify Legionellae. Of the samples, 58.9% (189/321) were observed to be positive, 19.9% were isolated over 100 CFU ml(-1). Legionella pneumophila serogroup 1 was the most frequently isolated species (155/189, 82.0%), followed by Leg. micdadei that was at the second place (44/189, 23.3%). The mean CFU ml(-1) of Legionellae in CTWs reached its peak from July to September. Over all 15.4% of the samples exceeding 100 CFU ml(-1) were observed in a hospital setting.
Conclusions: The prevalence of Legionella pollution in CTWs, especially in CTWs of subway stations and hospitals, is worrying, and the positive rate and CFU ml(-1) of Legionellae in CTWs have a close relationship with air temperature.
Significance and impact of the study: The study demonstrates pollution prevalence rates in different types of sites and various seasons, and provides a proportion of different serogroups of Legionellae. It illuminates an urgent need for dealing with the potential risk of legionellosis in Shanghai, through improved control and prevention strategies.