CLH 5
CLH 5
Flexible conductive level probe 1 to 5 electrodes User defined electrode length Isolated or unisolated electrodes 1 1/2 pipe thread according to ISO 228/1-G11/2A
Product Description
A compact and flexible level probe for measuring the level of conductive liquids, i.e overfill, dry run protection or pump control. A total measurements system consist of a multiple probehead, 1-5 electrodes and a control unit. The electrode length can be freely defined be means of electrode extention units with or without isolation.
Ordering Key
Type Head mounting Number of electrodes
CLH 5
Electrode without isolation Electrode with isolation, Kynar (PVDF) Electrode with isolation, Polyolefine (FR) Description
Specifications
Probe Head Material No of electrodes Electrode connection Tightening torque Cable connection Electrodes Material Length CLE1 CLE2 PP (Polypropylen) 3 5 M4 2.7 Nm by hand -K & -P Screw terminals Stainless steel AISI316/DIN1.4401 1000 mm 2000 mm Diameter Isolation CLE.K. CLE.P. 4 mm Kynar (PVDF) Polyolefine (FR) III (IEC 60664) IP 65 IP 68 2(IEC 60664/60664A, 60947-1) -20 to +90C (-4 to +194F) -40 to +100C (-40 to +212F) 5 bar at 60C
CLH3 CLH5
Environment Overvoltage category Degree of protection Housing Electrode connections Pollution degree Operating temperature Storage temperature Pressure
Specifications (cont.)
Weight Probe Head Electrodes CE marking 260 g 107 g IEC 529
Mode of Operation
Functionality - example The diagram shows the level control system connected as max. and min control, i.e. registration of 2 levels + 2 alarm levels. The relays react to the low alternating current created when the electrodes is in contact with the liquid. The reference (Ref) must be connected to the container or if the container are made of a nonconductive material, to an additional electrode. In the diagram this electrode is shown by the dotted line. Electrodes Cut or extend the electrodes Example not to damage the isolation material of the isolated electrodes. Probe
Y4 12 14 Pump on/off A1 11 21 Y3 Y2 Y1 24 Alarm on/off A2 Y5 LoLo REF Lo HiHi Hi
Control Unit
Power Supply
to the desirable length. If using extended electrodes, place the enclosed isolation tube over the extension joint,
and heat it with a heat gun. Mount the electrodes in the probehead by means of the M4 screw inserts. Take care
Connection cable 2, 3, 4 or 5 conductor PVC cable, normally screened. Cable length: max. 100 m. The resistance between the cores and the ground must be at last 200k. In normal cases it is recommended to use screened cable between probe and controller, e.g. where the cable is placed in parallel to the load cables (mains). The screen has to be connected to Y5 (reference).
Dimensions
M12 x 1.5
Accessories
Extension joint 4 60 mm Kynar for isolation 60 mm Polyolefine for isolation M12 Cable Gland M20 Cable Gland VD VDK VDP M12 Cable Gland M20 Cable Gland
Delivery Contents
Probe Head M20 Cable Gland M12 Blind flange Installation Instruction M20 x 1.5