ABB Medium Voltage Cubicle
ABB Medium Voltage Cubicle
UniMix
Medium voltage air-insulated switchgear
TM
Indice
4
1. General characteristics
4
General
4
Versions available
4
Fields of application
4
Compliance with Standards
4 Normal service conditions
6 Protection against internal arc
6 Main characteristics
6 Surface treatment
7 Degrees of protection
7 Technical documentation
8 Electrical characteristics
8 Apparecchiature per adeguamento alla
Norma CEI 0-16
8 Quality Assurance System
8 Environmental Management System
8 Health and Safety Management System
8 Test laboratory
15
9
2. Typical units
9 Compartments
9 Busbar compartment (A)
9 Isolator/switch-disconnector compartment (B)
10 Feeder compartment (C)
10 Auxiliary circuits (D)
11 P3 - Unit with switch-disconnector
12 P2 - Unit with switch-disconnector and fuses
13 P1F - Unit with fixed circuit-breaker with
right-hand side operating mechanism
14 P1E - Unit with withdrawable circuit-breaker
with front operating mechanism
26
3. Main components
Circuit-breakers VD4/Unimix-F and HD4/Unimix-F
26
27 Circuit-breakers VD4/US and HD4/US
28 Switch-disconnectors
29 Isolators
29 Earthing switches
29 Main busbars
29 Voltage transformers
29 Current transformers
30 Combined voltage/current sensors
31 REF542plus unit
1. General characteristics
Allgemein
Versions available
UniMix switchgear is available in the following versions:
standard(*)
arc proof according to the IEC 62271-200 Standards in the
following two versions:
arc proof on the four sides: IAC AFLR
arc proof only on the front: IAC AF(**) (up to 12.5 kA for 1s).
Fields of application
UniMix switchgear is used in medium voltage secondary
power distribution.
In particular, it can be used for transformer substations and
for control and protection of feeders and power transformers.
(*)
(**)
No IAC version: WARNING! Do not enter the switchgear room during service.
WARNING! Do not access the side part or rear of the switchgear when in service.
1. General characteristics
Main characteristics
Surface treatment
The UniMix units are made of pre-galvanized sheet. The doors
of the front panels are painted grey RAL 7035. The surface
appearance is semi-gloss.
On request, the sides are available painted RAL 7035.
Degrees of protection
IP2X inside the switchgear
IP3X on the external housing (operation seats excluded)
IP2XC on operation seats.
Technical documentation
To obtain in-depth information about technical and application
aspects of the apparatus used in UniMix switchgear, please
ask for the following publications:
VD4/R circuit-breakers
Cat. 1VCP000037
HD4/R circuit-breakers
Cat. 1VCP000028
VD4/US circuit-breakers
Cat. 1VCP000002
HD4/US circuit-breakers
Cat. 1VCP000004
SHS2 switching and isolation apparatus Cat. 1VCP000046
PR512 protection device
Cat. 1VCP000055
REF542plus unit
Cat. 1VTA100001
1. General characteristics
kV
12
17.5
kV
28
38
50
kV
75
95
125
Hz
50-60
50-60
50-60
Rated frequency
Rated main busbar current
(1)
24
400/630/800/1250
630 -1250
630 -1250
switch-disconnectors
400/630
400/630
400/630
isolators
400/630
400/630
400/630
kA (1s)
12.5 - 16 - 20 - 25
kA (3s)
Peak current
630 -1250
12.5 - 16 - 20
kA
31.5 - 40 -50 - 63
(1)
(2)
500 - 750 mm
kA x 0.5 s
500 - 750 mm
kA x 1 s
12.5 - 16 - 20
12.5 - 16
375 mm
kA x 0.5 s
12.5 - 16
375 mm
kA x 1 s
12.5 - 16 (2)
The values indicated are valid for a maximum ambient temperature of 40C. For higher temperatures, please contact us.
Only for intermediate units.
Quality Assurance
system
Complies with ISO 9001
Standards, certified by an
independent organisation.
Environmental
Management
System
Test laboratory
Complies with UNI CEI EN
ISO/IEC 17025 Standards,
certified by an independent
organisation.
2. Typical units
Compartments
The structure of each unit is made entirely using pregalvanized metal sheets.
Each unit consists of several compartments with metal
segregations between them.
Each unit is preset with special holes for fixing to the floor and
is provided with back closure fitted with special openings for
medium voltage cable passage.
All the units fitted with a door have a mechanical interlock
which only allows door opening under safe conditions.
If the low voltage compartment (control auxiliaries) is not
provided, the busbar compartment can be reached from the
roof and also from the front as well, by dismantling the special
metallic cover.
There is a special metal wiring duct in each unit to segregate
the low voltage circuits from the medium voltage circuits.
A box for incoming cables from above - only for standard
versions up to 630 A - can e requested to complete the basic
product.
Isolator switch-disconnector
compartment (B)
This contains the live parts of the isolator or switchdisconnector and is metallically segregated from the busbar
compartment and from the feed compartment by means
of the stainless steel housing of the isolator or switchdisconnector itself.
B
4
1
6
5
6
A
B
Busbar compartment
Isolator, switch-disconnector
compartment
C Feeder compartment
1 Circuit-breaker
2 Isolator
3 Current sensors
4 Switch-disconnector
5 Fuses
6 Earthing switch
2. Typical units
For example:
terminal boxes, wiring ducts and cables to connect the
auxiliary circuits of the unit;
auxiliary accessories of the circuit-breaker and unit
(measuring instruments, protection relays, control and
signalling devices, fuses, auxiliary circuit protection circuitbreakers, etc.).
Depending on the quantity of apparatus to be housed in
it, the instrument compartment can be selected from two
different solutions:
235 mm depth
350 mm depth.
Cable passage for inter-panel connections is made by means
of special holes provided in the walls of the instrument
compartment itself.
On request, to complete the basic product, a top wiring duct
for incoming auxiliary cables from the top.
1
3
Incoming/outgoing circuit-breaker
unit with front operating mechanism
10
A
C
D
1
3
6
Busbar compartment
Feeder compartment
Auxiliary circuit compartment
Circuit-breaker
Current transformers
Earthing switch
Switch-disconnector(*) (5)
Unit
SHS2/T1 - SHS2/T1M - SHS2/T2 - SHS2/T2M
500 mm
375 mm
(*)
Standard
Arc proof
Unit
(4)
(4)
500 mm
375 mm
Ir
Ik
12-17.5-24 kV
400 A
12.5 kA
12-17.5-24 kV
400 A
16 kA
12-17.5-24 kV
400 A
20 kA
12-17.5-24 kV
400 A
25 kA
12-17.5-24 kV
630 A
16 kA
12-17.5-24 kV
630 A
20 kA
12-17.5-24 kV
630 A
25 kA
Note
(1)
See CT and VT configuration table.
(2)
Ducting for gas exhaust. Only provided for unit with arc proofing on the four sides.
(3)
Application of toroidal phase CTs on the medium voltage cables is made with a
special support on the back of the panel.
(4)
Interchangeable with DIN Combisensor.
(5)
Class E1 for earthing switch.
(6)
Not possible when the unit is either the first or the last one.
11
2. Typical units
(5)
Switch-disconnector(*)
Unit
SHS2/T2F - SHS2/T2FM
500 mm
SHS2/T2F/N - SHS2/T2FM/N
375 mm
(*)
(5)
Standard
Arc proof
Unit
Toroidal CTs(3)
DIN VT(7)
DIN busbar CT(6)
(4)
(4)
500 mm
375 mm
Ir
Ik
IkAp (5)
12-17.5-24 kV
400 A
12.5 kA
2.5 kA
12-17.5-24 kV
400 A
16 kA
2.5 kA
12-17.5-24 kV
400 A
20 kA
2.5 kA
12-17.5-24 kV
400 A
25 kA
2.5 kA
12-17.5-24 kV
630 A
16 kA
2.5 kA
12-17.5-24 kV
630 A
20 kA
2.5 kA
12-17.5-24 kV
630 A
25 kA
2.5 kA
12
Note
(1)
(2)
Ducting for gas exhaust. Only provided for unit with arc proofing on the four sides.
(3)
Application of toroidal phase CTs on the medium voltage cables is made with a
special support on the back of the panel.
(4)
Interchangeable with DIN Combisensor.
(5)
Withstand current for class E1 earthing switch.
(6)
Not possible when the unit is either the first or the last one.
(7)
DIN VT positioned on the base plate for bus tie unit.
P1F - Unit with fixed circuit-breaker with right-hand side operating mechanism
(1)
(6)
Isolator(*)
SHS2/IB
Standard
(*)
(6)
Arc proof
Unit
Types available
Ur
Ir
Ik
IkAp
12-17.5-24 kV
400 A
12.5 kA
31.5 kA
12-17.5-24 kV
400 A
16 kA
40 kA
12-17.5-24 kV
400 A
20 kA
50 kA
12-17.5-24 kV
400 A
25 kA
63 kA
12-17.5-24 kV
630 A
16 kA
40 kA
12-17.5-24 kV
630 A
20 kA
50 kA
12-17.5-24 kV
630 A
25 kA
63 kA
(4)
(4)
750 mm
On-board
circuit-breaker
current sensors
Circuit-breaker (*)
VD4/UniMix F - VD4/UniMix R(7)
HD4/UniMix F - HD4/UniMix R(7)
(*)
Types available
Ur
Ir
Ik
12 kV
... 630 A
... 25 kA
17.5-24 kV
... 630 A
... 20 kA (*)
(*)
Notes
(1)
See CT and VT configuration table.
(2)
Ducting for gas exhaust. Only provided for unit with arc proofing on the four sides.
(3)
Application of toroidal phase CTs on the medium voltage cables is made with a
special support on the back of the panel.
(4)
Interchangeable with DIN Combisensor.
(5)
DIN VTs or current sensors on-board the circuit-breaker can be installed for the bus
tie unit.
(6)
Class E1 for earthing switch.
(7)
With wheel kit and connector.
Tested in switchgear at 25 kA x 1 s, 20 kA x 3 s.
13
2. Typical units
HD4/US
or
VD4/US
HD4/US
or
VD4/US
Incoming/outgoing unit
Bus-tie unit
Circuit-breaker (*)
VD4/US - HD4/US
(*)
Standard
For a detailed description, please see the VD4 - HD4 technical catalogue.
Arc proof
Unit
750 mm
(3)
(3)
Types available
Ur
Ir
Ik
IkAp
12-17.5-24 kV
400 A
12.5 kA
31.5 kA
12-17.5-24 kV
400 A
16 kA
40 kA
12-17.5-24 kV
400 A
20 kA
50 kA
12-17.5-24 kV
400 A
25 kA
63 kA
12-17.5-24 kV
630 A
12.5 kA
31.5 kA
12-17.5-24 kV
630 A
16 kA
40 kA
12-17.5-24 kV
630 A
20 kA
50 kA
12-17.5-24 kV
630 A
25 kA
63 kA
12-17.5-24 kV
1250 A
12.5 kA
31.5 kA
12-17.5-24 kV
1250 A
16 kA
40 kA
12-17.5-24 kV
1250 A
20 kA
50 kA
12-17.5-24 kV
1250 A
25 kA
63 kA
14
Notes
(1)
See CT and VT configuration table.
(2)
Application of toroidal phase CTs on the medium voltage cables is made with a
special support on the back of the panel.
(3)
Interchangeable with DIN Combisensor.
(4)
For the bus-tie unit, it is not possible to install DIN VT.
(5)
Arc proof version 20 kA x 0.5 s on the four sides, not available.
(6)
Class E1 for earthing switch.
Unit arrivo/partenza
Unit congiuntore
Circuit-breaker (*)
VD4/US - HD4/US
(*)
Standard
Arc proof
Unit
750 mm
(3)
(3)
Types available
Ur
Ir
Ik
IkAp
12-17.5-24 kV
400 A
12.5 kA
31.5 kA
12-17.5-24 kV
400 A
16 kA
40 kA
12-17.5-24 kV
400 A
20 kA
50 kA
12-17.5-24 kV
400 A
25 kA
63 kA
12-17.5-24 kV
630 A
12.5 kA
31.5 kA
12-17.5-24 kV
630 A
16 kA
40 kA
12-17.5-24 kV
630 A
20 kA
50 kA
12-17.5-24 kV
630 A
25 kA
63 kA
12-17.5-24 kV
1250 A
12.5 kA
31.5 kA
12-17.5-24 kV
1250 A
16 kA
40 kA
12-17.5-24 kV
1250 A
20 kA
50 kA
12-17.5-24 kV
1250 A
25 kA
63 kA
Notes
(1)
See CT and VT configuration table.
(2)
Application of toroidal phase CTs on the medium voltage cables is made with a
special support on the back of the panel.
(3)
Interchangeable with DIN Combisensor.
(4)
For the bus-tie unit, it is not possible to install DIN VT.
(5)
Arc proof version 20 kA x 0.5 s on the four sides, not available.
(6)
Class E1 for earthing switch.
(7)
LSC2B (Loss of Service Continuity): possibility of accessing the circuit-breaker compartment during ordinary maintenance without putting the following out of service:
1. the cable compartment
2. the busbars and adjacent functional units.
PI (Partition made of Insulating material), mechanical and electrical segregation of
the cable compartment, busbar compartment and circuit-breaker compartment by
means of insulating shutters.
15
2. Typical units
(1)
(6)
(3)
(2)
Isolator(*)
SHS2/A
(*)
Standard
DIN busbar CT
On-board circuit-breaker
current sensors
Types available
Ur
Ir
Ik
12-17.5-24 kV
400 A
12.5 kA
12-17.5-24 kV
400 A
16 kA
12-17.5-24 kV
630 A
16 kA
Arc proof
Unit
(4)
750 mm
Circuit-breaker (*)
VD4/UniMix F - VD4/UniMix R(7)
HD4/UniMix F - HD4/UniMix R(7)
(*)
Types available
Ur
Ir
Ik
12 kV
... 630 A
... 25 kA
17.5-24 kV
... 630 A
... 20 kA
16
Notes
(1)
See CT and VT configuration table.
(2)
Ducting for gas exhaust. Only provided for unit with arc proofing on the four sides.
(3)
Application of toroidal phase CTs on the medium voltage cables is made with a
special support on the back of the panel.
(4)
Interchangeable with DIN Combisensor.
(5)
Arc proof version on the front, not available.
(6)
Class E0 for earthing switch.
(7)
With wheel kit and connector.
Isolator(*) (5)
Unit
SHS2/I
500 mm
SHS2/I/N
375 mm
(*)
Standard
Arc proof
Unit
(4)
(4)
500 mm
375 mm
Ir
Ik
12-17.5-24 kV
400 A
12.5 kA
12-17.5-24 kV
400 A
16 kA
12-17.5-24 kV
400 A
20 kA
12-17.5-24 kV
400 A
25 kA
12-17.5-24 kV
630 A
16 kA
12-17.5-24 kV
630 A
20 kA
12-17.5-24 kV
630 A
25 kA
Notes
(1)
See CT and VT configuration table.
(2)
Ducting for gas exhaust. Only provided for unit with arc proofing on the four sides.
(3)
Application of toroidal phase CTs on the medium voltage cables is made with a
special support on the back of the panel.
(4)
Interchangeable with DIN Combisensor.
(5)
Class E0 for earthing switch.
(6)
Not possible when the unit is either the first or the last one.
17
2. Typical units
Earthing switch(*)(5)
SHS2/ES
(*)
Standard
Arc proof
Unit
500 mm
(4)
(4)
Ir
Ik
12-17.5-24 kV
400 A
12.5 kA
12-17.5-24 kV
400 A
16 kA
12-17.5-24 kV
630 A
16 kA
12-17.5-24 kV
630 A
20 kA
12-17.5-24 kV
630 A
25 kA
12-17.5-24 kV
800/1250 A
20 kA
12-17.5-24 kV
800/1250 A
25 kA
18
Notes
(1)
See CT and VT configuration table.
(2)
Ducting for gas exhaust. Only provided for unit with arc proofing on the four sides.
(3)
Application of toroidal phase CTs on the medium voltage cables is made with a
special support on the back of the panel.
(4)
Interchangeable with DIN Combisensor.
(5)
Class E1 for earthing switch.
R - Riser unit
Ur
Ir
Ik
12-17.5-24 kV
400 A
12.5 kA
Toroidal CTs
12-17.5-24 kV
400 A
16 kA
DIN VT
12-17.5-24 kV
400 A
20 kA
DIN CT
12-17.5-24 kV
400 A
25 kA
12-17.5-24 kV
630 A
16 kA
12-17.5-24 kV
630 A
20 kA
12-17.5-24 kV
630 A
25 kA
12-17.5-24 kV
800-1250 A (*)
20 kA
12-17.5-24 kV
800-1250 A (*)
25 kA
(*)
Standard
Arc proof
Unit
500 mm
Notes
(1)
See CT and VT configuration table.
(2)
Ducting for gas exhaust. Only provided for unit with arc proofing on the four sides.
19
2. Typical units
Ur
Ir
Ik
12-17.5-24 kV
400 A
12.5 kA
12-17.5-24 kV
400 A
16 kA
DIN VT
12-17.5-24 kV
400 A
20 kA
DIN CT
12-17.5-24 kV
400 A
25 kA
12-17.5-24 kV
630 A
16 kA
12-17.5-24 kV
630 A
20 kA
12-17.5-24 kV
630 A
25 kA
12-17.5-24 kV
800/1250 A (*)
20 kA
12-17.5-24 kV
800/1250 A (*)
25 kA
(*)
20
Standard
Arc proof
Unit
500 mm
(4)
(4)
375 mm
Notes
(1)
See CT and VT configuration table.
(2)
Ducting for gas exhaust. Only provided for unit with arc proofing on the four sides.
(3)
Application of toroidal phase CTs on the medium voltage cables is made with a
special support on the back of the panel.
(4)
Interchangeable with DIN Combisensor.
M - Measurement unit
SHS2/IF
(*)
Standard
Arc proof
DIN VT
DIN busbar CT
(3) (5)
(3) (5)
Unit
500 mm
Types available
Ur
Ir
Ik
12-17.5-24 kV
400 A
12.5 kA
12-17.5-24 kV
400 A
16 kA
12-17.5-24 kV
400 A
20 kA
12-17.5-24 kV
400 A
25 kA
12-17.5-24 kV
630 A
16 kA
12-17.5-24 kV
630 A
20 kA
12-17.5-24 kV
630 A
25 kA
Notes
(1)
See CT and VT configuration table.
(2)
Ducting for gas exhaust. Only provided for unit with arc proofing on the four sides.
(3)
Interchangeable with DIN Combisensor.
(4)
Withstand current for class E1 earthing switch.
(5)
Not possible when the unit is either the first or the last one.
21
2. Typical units
W [mm]
D [mm]
H [mm]
TR1
1600
1150
1950
TR2
2000
1150
1950
TR3
2000
1300
2250
TR4
2200
1500
2250
TR5
2200
1800
2250
P
L
T [C]
No-load losses
Wo [W]
Load losses
Wcc [W]
Load factor
Rated current
In [A]
Total losses
Ptot. = Wo + a2 x Wcc
Type of box
T=120 C
T=140 C
TR1
5,000
6,000
7,000
TR2
6,000
7,500
8,500
TR3
7,500
9,000
10,500
TR4
8,500
10,000
11,500
TR5
9,000
10,500
12,500
22
Unit
W [mm]
D [mm]
H [mm]
150
975
1950
150
975
1950
W [mm]
D [mm]
H [mm]
375
975
300
AC2
500
975
300
AC3
750
975
300
AC1
(1)
(1)
Front
Front
Switchgear version
A [mm]
B [mm]
C [mm]
D [mm]
Standard
50
100 (3)
50
1550
(1)
Arc proof
600
100
50
1550
(1)
600
100
1550
(1)
(1)
(2)
(3)
(3)
(2)(3)
(3)
100
Weight [kg]
Weight [kg]
Weight [kg]
375 [mm]
500 [mm]
750 [mm]
Basic
A.P.
Basic
A.P.
Basic
160
200
A.P.
P2
190
230
205
245
P3
170
215
185
230
ASR
150
200
175
215
290
335
130
160
125
165
Rac
120
170
135
190
P1F
370
425
P1E
500
530
WCB
580
630
WSB
580
650
P1A
370
425
23
2. Typical units
Foundations
375 mm
Width:
500 mm
Width:
750 mm
Type:
P2 - P3 - ASR - A - Rac
Type:
P2 - P3 - ASR - A - Rac
Type:
P1F - P1A
Width:
500 mm
Width:
750 mm
Type:
R-M
Type:
24
The UniMix panels are prepared for connection of singlecore medium voltage cables with solid extruded elastomer
insulation (type G7 or XLPE).
1 Screw
2 Plate
3
Anchoring bolt
Unit
Description
Rac
Without CT and VT
P3
Width 375 mm
Width 500 mm
Width 750 mm
A [mm]
B [mm]
A [mm]
B [mm]
A [mm]
B [mm]
960
187.5
875
250
With DIN CT
540
250
540
250
Without CT and VT
908
187.5
732
250
With DIN CT
530
250
530
250
Without VT
960
187.5
820
250
With DIN VT
530
250
P2
455
187.5
455
250
Without VT
960
187.5
820
250
With DIN VT
530
250
With DIN CT
530
250
732
250
With DIN VT
530
250
P1E
440 - 495
WCB
440 - 495
WSB
ASR
P1F
P1A
440 - 495
385
250
25
3. Main components
Performances
VD4/UniMix-F 12
HD4/UniMix-F 12
VD4/UniMix-F 17
HD4/UniMix-F 17
VD4/UniMix-F 24
HD4/UniMix-F 24
24
kV
12
17.5
Withstand voltage
kV (50 Hz)
28
38
50
kV
75
95
125
Rated frequency
Hz
50-60
50-60
50-60
Rated current
A (40 C)
630
630
630
kA
12.5
12.5
12.5
16
16
16
20
20
20
25
25 (2)
Breaking capacity
Rated short-time
withstand current (3 s)
kA
12.5
Operation sequence
kAp
12.5
16
16
16
20
20
20(1)
25
Making capacity
12.5
31.5
25(2)
31.5
31.5
40
40
40
50
50
50
63
63(2)
VD4/R
O-0.3min-CO-3min-CO/O-0.3s-CO-3min-CO
HD4/R
O-0.3min-CO-3min-CO/O-0.3s-CO-15s-CO
Opening time
ms
45
45
45
Arc duration
ms
10-15
10-15
10-15
ms
55-60
55-60
55-60
Closing time
ms
80
80
80
kPa
380
380
380
Technical catalogue
VD4/R
1VCP000263
1VCP000263
1VCP000263
HD4/R
1VCP000028
1VCP000028
1VCP000028
26
Performances
VD4/US
Rated and insulation voltage
kV
HD4/US
24
24
Withstand voltage
kV (50 Hz)
50
50
kV
125
125
Rated frequency
Hz
50-60
Rated current
A (40 C)
630
1250
630
1250
kA
16
16
16
16
20
20
20
20
25
25
25
25
16
16
16
16
20
20
20
20
25
25
25
25
40
40
40
40
50
50
50
50
63
63
63
63
Breaking capacity
Rated short-time
withstand current (3 s)
Making capacity
Operation sequence
kA
kAp
VD4/US
50-60
O-0.3s-CO-3min-CO
HD4/US
O-0.3s-CO-15s-CO
Opening time
ms
40 ... 60
45
Arc duration
ms
10 ... 15
10-15
ms
50 ... 75
55-60
Closing time
ms
60 ... 80
80
kPa
380
Technical catalogue
VD4
1VCP000002
HD4
1VCP000004
27
3. Main components
Switch-disconnectors
SHS2 series switch-disconnectors are used in the P2 and P3
units.
The SHS2 series of switch-disconnectors have three positions
with insulation in SF6 gas and a stainless steel housing.
Installation of this type of apparatus carries out metallic segregation and earthing between the busbar compartment and
the feeder compartment of the unit guaranteeing maximum
personnel safety in the case of interventions in the feeder
compartment even with the main busbars supplied with power, for example to replace one or more fuses or to check the
cables.
The operating mechanism can be accessed directly from the
front and allows installation/replacement of accessories.
They are available with a manual operating mechanism or
kV
24
kV
50
kV
125
Rated frequency
Hz
50-60
400/630
Rated short-time
withstand current (1 s)
kA
12.5
16
20
25
kA
31.5
40
50
63
Breaking capacity
Mainly active load
400/630
No-load transformers
4 ... 16
No-load cables/feeders
50/25
Ring circuits
400/630
SHS2/T1N
SHS2/T1
SHS2/T1MN
SHS2/T1M
SHS2/T2FN
SHS2/T2F
SHS2/T2N
SHS2/T2
SHS2/T2FMN
SHS2/T2FM
SHS2/T2MN
SHS2/T2M
Operating mechanism
T1
T1M
T2
T2
T2
T2
UniMix Unit
P3
P3
P2
P3
P2
P3
Motorisation
24 V DC
48 V AC/DC
110 V AC/DC
220 V AC/DC
28
24 V AC/DC
48 V AC/DC
110 V AC/DC
220 V AC/DC
Isolators
Main busbars
SHS2 series isolators are used in the M, ASR, P1/F and P1/A
units. The SHS2 series of isolators have three positions with
insulation in SF6 gas and a stainless steel housing. Installation
of this type of apparatus carries out segregation between the
busbar compartment and the circuit-breaker/feeder compartment of the unit.
The operating mechanism can be accessed directly from the
front and allows installation/replacement of accessories.
The SHS2 isolators are used:
in combination with fuses, for protection of instrument
transformers
in combination with VD4/UniMix-F, VD4/UniMix-R or HD4/
UniMix-F, HD4/UniMix-R series of circuit-breakers.
The busbars are made of flat bare electrolytic copper and are
sized to withstand the thermal and electrodynamic stresses
caused by the short-circuit currents. The busbars pass from
one unit to the adjacent one without any partitions being interposed, so as to make a continuous duct.
Current transformers
SHS2
Rated voltage
kV
24
kV
50
kV
125
Rated frequency
Hz
50-60
400
kA
12.5
Voltage transformers
The voltage transformers are of the type insulated in resin
and are used to supply power to measuring instruments and
protections.
They comply with the IEC 60044-2 Standards.
The dimensions are in accordance with the DIN 42600 standard.
630
16
20
25
Operating mechanism
Isolator
SHS2/IF
SHS2/I
Operating mechanism
T3
T3
T4
V1
UniMix Unit
ASR
P1/F
P1/A
Earthing switches
The A, P1/F, P1/E, WCB, WBS, P1/A, P2, M units can be
fitted with an earthing switch. The operating device of the earthing switch is normally placed on the front of the switchgear.
Operation of the earthing switch takes place from the front
and is interlocked mechanically with any line-side isolator and
with the feeder compartment door.
3. Main components
Toroidal transformers
Application of toroidal phase transformers is possible in all
the switchgear units to supply the measuring instruments and
protections with power.
The toroidal transformers can be installed on the back of the
compartment on a special supporting structure.
Transformers on-board the switchgear
These are of the type insulated in resin and are used to supply
power to measuring instruments and protections.
They comply with the IEC 60044-1 Standards.
Their dimensions are in accordance with the DIN 42600
standard.
30
REF542plus unit
The REF542plus unit carries out integration of all the secondary functions relative to a switchgear unit in a single module
fitted with watchdog.
Thanks to the flexibility of its software, the unit is able to satisfy a vast range of installation requirements.
The high functionality of the REF542plus unit is supported by
a simple and easy-to-use user interface.
Thanks to the use of the REF542plus unit, each medium
voltage UniMix panel becomes an integrated and independent
unit able to carry out all the required functions.
Main characteristics:
integration of all the functions in a single instrument:
protection, measurement, switching, signalling,
interlocking, automation and communication;
a single interface between switchgear and operator for
all the installation panels: feeder, transformer, motor,
generator, power factor correction banks, bus-tie and
measurement units;
a single type of spare parts and accessories: a single
hardware unit;
reduced maintenance: drastic reduction in preventive
maintenance, great limitation of the faults caused by
tampering and errors;
simple modification and adaptation of the functions: by
means of the unit configuration software, even with the
switchgear in service.
The possibility of connecting the switchgear directly to the
installation management system fully implements the concept
of an integrated installation and at the highest levels.
REF542plus unit
31
ABB S.p.A.
Power Products Division
Unit Operativa Sace-MV
Via Friuli, 4
I-24044 Dalmine
Tel: +39 035 6952 111
Fax: +39 035 6952 874
E-mail: [email protected]
www.abb.it