SACE FORMULA
New low voltage moulded-case
circuit-breakers up to 630A
Main characteristics
Accessories
Wiring diagrams
Overall dimensions
Glossary
7
1SDC210032D0204
Formula_00_indice+avanticat.indd 1
21/02/2011 9.36.25
SACE FORMULA.
Simplicity and Quality in a Single Product.
Formula_00_indice+avanticat.indd 2
21/02/2011 9.36.29
Formula_00_indice+avanticat.indd 3
21/02/2011 9.36.35
SACE FORMULA.
The Easy and Precise Choice.
Formula_00_indice+avanticat.indd 4
21/02/2011 9.36.46
SACE FORMULA.
Winners in All Applications.
Formula_00_indice+avanticat.indd 5
21/02/2011 9.36.52
Main characteristics
Content
General information ............................................................................................................. 1/2
Regulations and reference Standards ................................................................................ 1/3
Identication of the SACE FORMULA circuit-breakers ..................................................... 1/4
1/1
1SDC210032D0204
Formula_01_caratteristiche.indd 1
21/02/2011 9.37.31
Construction characteristics
General information
1SDC210610F0001
The references in round brackets (Gx.x) in the technical catalogue refer to the Glossary in the final charter of the technical
catalogue.
1SDC210611F0001
Double insulation
Installation positions
All the moulded-case circuit-breakers in the SACE FORMULA family are constructed in accordance with the following construction characteristics:
double insulation(G1.4);
positive operation(G1.5);
isolation behaviour (G1.6);
electromagnetic compatibility(G1.7);
tropicalization(G1.8);
power supply from the top towards the bottom or vice versa;
versatility of the installation. It is possible to mount the circuit-breaker either in the horizontal,
vertical, or lying down position without undergoing any derating of the rated characteristics;
no nominal performance derating for use up to an altitude of 2000m. Above 2000m, the
properties of the atmosphere (composition of the air, dielectric strength, cooling power and
pressure) change, having an impact on the main parameters which define the circuit-breaker.
The table below gives the changes to the main performance parameters;
Altitude
2000m
1SDC210612F0001
A1
Positive operation
A
B
1SDC210613F0001
Protection degrees
3000m
4000m
5000m
A2-A3
A1
A2-A3
A1
A2-A3
A1
A2-A3
[V]
500
550
440
484
390
429
340
374
100
100
98
98
95
95
90
90
Circuit-breaker
without front (1)
Circuit-breaker
with RHE RHD
IP 40
IP 20
IP 40
IP 40
IP 40
IP 40
IP 20
IP 20
IP 20
IP 40
IP 30
IP 20
1SDC210612F0001
circuit-breaker weights;
Test pushbotton
Weights
A1 [Kg]
A2 [Kg]
A3 [Kg]
Circuit-breaker 1 pole
0.245
0.37
Circuit-breaker 2 poles
0.47
0.73
Circuit-breaker 3 poles
0.7
1.1
3.25
Circuit-breaker 4 poles
0.925
1.145
4.15
all the SACE FORMULA circuit-breakers are fitted with a Test pushbutton which allows
the release test to be done. This test must be carried out with the circuit-breaker closed.
1/2
1SDC210032D0204
Formula_01_caratteristiche.indd 2
21/02/2011 9.37.34
Construction characteristics
Regulations and reference Standards
Hologram
1/3
1SDC210032D0204
Formula_01_caratteristiche.indd 3
21/02/2011 9.37.35
Construction characteristics
Identication of the SACE FORMULA circuit-breakers
The characteristics of the circuit-breakers are given on the label on the front of the circuitbreaker, and on the side label.
Front label
4
3
13
5
6
7
1
9
1SDC210614F0001
10
11
In=100A
14
12
Side label
1.
7
4
2.
3.
4.
5.
1SDC210615F0001
6.
5
13
10
15
14
7.
8.
9.
10.
11.
12.
13.
14.
15.
1/4
1SDC210032D0204
Formula_01_caratteristiche.indd 4
21/02/2011 9.37.35
Content
General characteristics ..................................................................................................... 2/2
Thermomagnetic trip units ............................................................................................... 2/4
Ordering codes ................................................................................................................ 2/5
Electronic trip units ............................................................................................................ 2/9
Ordering codes ................................................................................................................ 2/9
2/1
1SDC210032D0204
Formula_02_gamma.indd 1
21/02/2011 9.38.07
SACE FORMULA A1
1 pole
2 poles
3 poles
4 poles
SACE FORMULA A2
1 pole
2 poles
3 poles
4 poles
SACE FORMULA A3
3 poles
4 poles
2/2
1SDC210032D0204
Formula_02_gamma.indd 2
21/02/2011 9.38.13
Frame size
(G2.1)
[A]
Rated current, In
(G2.2)
(G2.3)
A2
A3
250
400/630
[A]
15...125
125...250
320...630
[Nr]
1, 2, 3, 4
1, 2, 3, 4
3, 4
(AC) 50-60 Hz
[V]
550
(DC)
[V]
250
[V]
690
690
690
Poles
Rated service voltage, Ue
A1
125
(G2.4)
[kV]
Versions
Performance Level
Poles
[Nr]
3/4
3/4
Fixed
Fixed
Fixed
3/4
B
3/4
3/4
C
1
N
3/4
3/4
3/4
3/4
(G2.6)
[kA]
10
25
18
30
25
50
100
25
18
50
25
50
85
85
100
[kA]
10
18
2.5
25
36 (5)
36 (5)
18
2.5
25
36
36
36
50
[kA]
10
18
2.5
25
36 (5)
36 (5)
18
2.5
25
36
36
36
50
[kA]
15
20
25
25
15
20
25
25
36
50
[kA]
7.5
10
15
18
18
15
18
18
25
25
35
[kA]
10
10
10
10
20
25
[kA]
10
10
10
10
15
20
[kA]
10
10
[kA]
10
10
10
18
25
10
36
36
50
(G2.7)
[kA] 50% 50% 50% 50% 50% 50% 50% 50% 50% 50% 50% 50% 50% 50% 50%
[kA] 50% 50% 50% 50% 50% 50% 50% 50% 100% 50% 50% 50% 50% 50% 50%
[kA] 50% 25% (1) 50% 25% (2) 25% 25% 25% 50% 100% 50% 50% 50% 50% 50% 50%
25%
50%
25%(1)
50%
25%(3)
50%
25%(3)
50%
[kA] 50% 50% 50% 50% 50% 50% 50% 50% 50% 50% 50% 50% 50% 50% 50%
(G2.8)
36
63
52.5
105
[kA]
17
36
3.8
52.5
7.5
75.6 75.6
[kA]
17
[kA] 13.6
36
3.8
52.5
7.5
30
40
[kA] 12.8
17
30
36
[kA]
7.5
7.5
13.6
17
[kA]
7.5
7.5
13.6
17
[A]
Reference Standard
63
220
63
52.5
36
105
52.5
105
187
220
36
3.8
52.5
7.5
187
105
36
3.8
52.5
7.5
105
30
40
105
17
30
36
36
17
7.5
13.6
17
17
40
17
7.5
13.6
17
17
30
52.5 52.5
15...100
125...250
300-400(4)
IEC 60947-2
IEC 60947-2
IEC 60947-2
Q
Isolation behaviour
DIN EN 50022
DIN EN 50022
[No. operations]
8500
10000
5000
[No. operations]
2000
Mechanical life
(G2.10)
1500
4000
15
15
15
[ms]
15
15
< 25
1 pole
[mm]
25.4x60x130
35x60x150
2 poles
[mm]
50.8x60x130
70x60x150
3 poles
[mm]
76.2x60x130
105x60x150
139.5x
103.5x
205
4 poles
[mm]
101.6x60x130
140x60x150
186x
103.5x
205
1 pole
[kg]
0.245
0.370
2 poles
[kg]
0.470
0.730
3 poles
[kg]
0.700
1.100
3.25
4 poles
[kg]
0.925
1.450
4.15
Weight
5kA;
(2)
9kA;
(3)
Q(up to 500A)
Q(up to 630A)
2/3
1SDC210032D0204
Formula_02_gamma.indd 3
21/02/2011 9.38.15
1SDC210626F0001
Magnetic protection
symbol
Thermal protection
symbol
Thermal protection
value
Magnetic protection
value
I1= 1xIn
I3= 10xIn
In [A]
15
16
20
25
30
32
40
50
60
63
70
80
90
100
15
16
20
25
30
32
40
50
60
63
70
80
90
100
125
I3 [A]
300
300
300
300
300
320
400
500
600
630
700
800
900
1000
1250
300
300
300
300
300
320
400
500
600
630
700
800
900
1000
1250
TMF
TMF
I1= 1xIn
In [A]
125
150
160
175
200
225
250
125
150
160
175
200
225
250
I3 [A]
I3= 10xIn
I1= 1xIn
Neutral [A] - 100% 1250 1500 1600 1750 2000 2250 2500
I3= 10xIn
125
In [A]
320
400
320
400
500
500
I3 [A]
3200
4000
5000
3200
4000
5000
2/4
1SDC210032D0204
Formula_02_gamma.indd 4
21/02/2011 9.38.16
1SDC210627F0001
1SDA...R1
In
I3
C (18kA)
15
400
066485
16
400
068745
20
400
066486
066686
25
400
066487
066687
30
400
066488
066688
32
400
068754
068755
40
400
066489
066689
50
500
066490
066690
60
600
066491
066691
63
630
068765
068766
70
700
066492
066692
80
800
066493
066693
90
900
066494
066694
100 1000
066495
125 1250
(1)
066496
N (25kA)
066695
(1)
066696
(1)
A1 125A - Fixed (F) 2 poles - Front terminals (F) - Hold 100% In at 50C
Thermomagnetic trip unit - TMF Icu (415 V)
1SDC210628F0001
1SDA...R1
In
I3
15
400
16
400
068790
20
400
066497
25
400
066498
30
400
066499
32
400
068756
40
400
066500
50
500
066501
60
600
066502
63
630
068767
70
700
066503
80
800
066504
90
900
066505
100 1000
066506
N (36kA)
068789
125 1250
(1)
066507
(2)
(2)
(1)
30kA
2/5
1SDC210032D0204
Formula_02_gamma.indd 5
21/02/2011 9.38.17
1SDC210629F0001
1SDA...R1
In
I3
A (10kA)
B (18kA)
C (25kA)
N (36kA)
15
300
066510
066697
066709
066721
(2)
16
300
068746
068747
068748
068749
(2)
20
300
066511
066698
066710
066722
25
300
066512
066699
066711
066723
30
300
066513
066700
066712
066724
32
320
068757
068758
068759
068760
40
400
066514
066701
066713
066725
50
500
066515
066702
066714
066726
60
600
066516
066703
066715
066727
63
630
068768
068769
068770
068771
70
700
066517
066704
066716
066728
80
800
066518
066705
066717
066729
90
900
066519
066706
066718
066730
100 1000
066520
066707
066719
066731
125 1250
066521 (1)
066708 (1)
066720 (1)
066732 (1)
(1)
(2)
30kA
A1 125A - Fixed (F) 4 poles - Front terminals (F) - Hold 100% In at 50C
Thermomagnetic trip unit - TMF Icu (415 V)
1SDC210630F0001
1SDA...R1
In
I3
A (10kA)
B (18kA)
C (25kA)
N (36kA)
15
300
066524
066733
066745
066757
(2)
16
300
068750
068751
068752
068753
(2)
20
300
066525
066734
066746
066758
25
300
066526
066735
066747
066759
30
300
066527
066736
066748
066760
32
320
068761
068762
068763
068764
40
400
066528
066737
066749
066761
50
500
066529
066738
066750
066762
60
600
066530
066739
066751
066763
63
630
068772
068773
068774
068775
70
700
066531
066740
066752
066764
80
800
066532
066741
066753
066765
90
900
066533
066742
066754
066766
100 1000
066534
066743
066755
066767
125 1250
066535 (1)
066744 (1)
066756 (1)
066768 (1)
(1)
(2)
30kA
2/6
1SDC210032D0204
Formula_02_gamma.indd 6
21/02/2011 9.38.18
A2 250A - Fixed (F) 1 pole - Front terminals (F) - Hold 100% In at 50C
Thermomagnetic trip unit - TMF Icu (240 V)
1SDA...R1
1SDC210631F0001
In
I3
C (18kA)
N (25kA)
125 1250
066536
066769
150 1500
068776
068777
160 1600
066537
066770
175 1750
066538
066771
200 2000
066539
066772
225 2250
066540
066773
250 2500
066541
066774
A2 250A - Fixed (F) 2 poles - Front terminals (F) - Hold 100% In at 50C
Thermomagnetic trip unit - TMF Icu (415 V)
1SDA...R1
1SDC210632F0001
In
I3
N (36kA)
125 1250
066542
150 1500
068778
160 1600
066543
175 1750
066544
200 2000
066545
225 2250
066546
250 2500
066547
A2 250A - Fixed (F) 3 poles - Front terminals (F) - Hold 100% In at 50C
Thermomagnetic trip unit - TMF Icu (415 V)
1SDA...R1
1SDC210633F0001
In
I3
B (18kA)
C (25kA)
N (36kA)
125 1250
066548
066775
066781
150 1500
068779
068780
068781
160 1600
066549
066776
066782
175 1750
066550
066777
066783
200 2000
066551
066778
066784
225 2250
066552
066779
066785
250 2500
066553
066780
066786
A2 250A - Fixed (F) 4 poles - Front terminals (F) - Hold 100% In at 50C
Thermomagnetic trip unit - TMF Icu (415 V)
1SDA...R1
1SDC210634F0001
In
I3
B (18kA)
C (25kA)
N (36kA)
125 1250
066554
066787
066793
150 1500
068782
068783
068784
160 1600
066555
066788
066794
175 1750
066556
066789
066795
200 2000
066557
066790
066796
225 2250
066558
066791
066797
250 2500
066559
066792
066798
2/7
1SDC210032D0204
Formula_02_gamma.indd 7
21/02/2011 9.38.21
I3
N (36kA)
S (50kA)
320 3200
066560
066562
400 4000
066561
066563
I3
500 5000
N (36kA)
S (50kA)
066564
066565
I3
N (36kA)
S (50kA)
320 3200
066568
066570
400 4000
066569
066571
1SDC210636F0001
I3
500 5000
N (36kA)
S (50kA)
066572
066573
I3
N (36kA)
S (50kA)
300 3000
068809
068960
400 4000
068810
068961
2/8
1SDC210032D0204
Formula_02_gamma.indd 8
21/02/2011 9.38.22
1SDC210637F0001
Protection against
overload value
Protection against
short-circuit value
Socket for
TT1 test unit
Trip threshold
Trip curve
Excludability
Relation
Fixed threshold
I1=630A
Tolerance: trip between
1.1...1.30xI1
t1= 12 s at 6xI1
Tolerance:
10% up to 6xIn
20% above 6xIn
no
t=k/l 2
Fixed threshold
I3=6000A
Tolerance: 10%
instantaneous
no
t=k
I3
630 6000
N (36kA)
S (50kA)
066566
066567
1SDC210638F0001
I3
630 6000
N (36kA)
S (50kA)
066574
066575
1SDA...R1
037121
2/9
1SDC210032D0204
Formula_02_gamma.indd 9
21/02/2011 9.38.25
Accessories
Content
Panorama of accessories ................................................................................................... 3/2
Mechanical accessories
Connection terminals .............................................................................................................. 3/4
Ordering codes ................................................................................................................ 3/6
Terminal covers, phase separators and sealable screws ......................................................... 3/7
Ordering codes ................................................................................................................ 3/7
Rotary handle operating mechanism....................................................................................... 3/8
Ordering codes ................................................................................................................ 3/8
Front for lever operating mechanism ....................................................................................... 3/9
Ordering codes ................................................................................................................ 3/9
Locks ..................................................................................................................................... 3/9
Ordering codes ................................................................................................................3/10
Bracket for xing onto DIN rail ................................................................................................3/11
Ordering codes ................................................................................................................3/11
Electrical accessories
Service releases......................................................................................................................3/12
Ordering codes ................................................................................................................3/13
Auxiliary contacts for electric signals .......................................................................................3/14
Ordering codes ................................................................................................................3/14
FORMULA Link .....................................................................................................................3/16
Ordering codes ................................................................................................................3/19
3/1
1SDC210032D0204
Formula_03_accessori.indd 1
21/02/2011 9.39.08
Accessories
Panorama of the accessories
SACE FORMULA A1 - A2
1 pole accessories
1SDC210639F0001
11
3
1
4
4
10
12
SACE FORMULA A1 - A2
2 poles accessories
11
1SDC210640F0001
1
4
10
9
8
7
12
The assembly of all the SACE FORMULA accessories has to be provided by the Customer.
3/2
1SDC210032D0204
Formula_03_accessori.indd 2
21/02/2011 9.39.09
SACE FORMULA A1 - A2 - A3
3poles/4poles accessories
7
5
3
11
2
4
1
4
4
4
10
8
13
1SDC210641F0001
14
Caption
12
7 Sealable screw
8 AUX-C/AUE-C: auxiliary contact
16
12
15
12
16
16
The assembly of all the SACE FORMULA accessories has to be provided by the Customer.
3/3
1SDC210032D0204
Formula_03_accessori.indd 3
21/02/2011 9.39.10
Accessories
Mechanical accessories
Connection terminals
The connection terminals allow the circuit-breaker to be connected to the plant in the most
suitable way in relation to installation requirements.
The front terminals allow cables or busbars to be connected acting directly from the front of
the circuit-breaker (cable lugs to be provided by the Customer).
Different types of terminals can be combined (one type for the line and a different one for the
load side).
Standard version of circuit-breaker is supplied with front terminals (F). By ordering the special
kits or half-kits, it is also possible to select among the following types:
front extended terminals (EF);
front extended spread terminals (ES);
front terminals for Copper and Aluminium cables (FCCuAl).
Front terminals - F
Cable
lug
[mm]
Busbar dimensions
MAX
Type
Poles
Tightening torques
[Hole dimension] and [Nm]
Terminal
Terminal covers
[mm]
Cable or busbar
7.5
50
Separators
[mm]
60
50
80
100
200
-
A1
1234
15
6.5
15
6.5
M6
A2 (1)
1234
25
8.5
24
8.5
M8
A3
34
35
11
10
10.5
35
10.5
M10
28
Terminal F
1SDC210644F0001
1SDC210643F0001
1SDC210642F0001
(1) Insulation of the switchboard door and insulating plate on the back of the circuit-breaker for use at Uet415 V mandatory.
Poles
Cable
lug
[mm]
W
Tightening torques
[Hole dimension] and [Nm]
Terminal
Terminal covers
[mm]
Cable or busbar
7.5
50
Separators
[mm]
60
50
80
100
200
-
A1
1234
15
8.5
15
8.5
M6
M8
[2]
A2 (1)
1234
25
NA
NA
M8
M8
[2]
A3
34
30
11
30
11
M10
28
M10
18
Terminal EF
1SDC210646F0001
1SDC210645F0001
(1) Insulation of the switchboard door and insulating plate on the back of the circuit-breaker for use at Uet415 V mandatory.
(2) In EF terminal kit the phase separators are not provided, but for a correct installation it is necessary to use the phase separators already provided with the circuit-breakers base.
S
R
=
=
=
=
=
=
=
Not available
Width
Hole heigth
Depth
Diameter
Standard
On request
3/4
1SDC210032D0204
Formula_03_accessori.indd 4
21/02/2011 9.39.13
Busbar dimensions
MAX
Type
Poles
A1
234
20
8.5
20
8.5
A2
(1)
Tightening torques
[Hole dimension] and [Nm]
Terminal
M6
Terminal covers
[mm]
Separators
[mm]
Cable or busbar
7.5
50
60
50
80
100
200
M8
234
30
10.5
NA
NA
M8
M10
18
34
40
10
11
11
11
M10
28
M10
18
A3
Terminal ES
1SDC210649F0001
1SDC210648F0001
1SDC210647F0001
(1) Insulation of the switchboard door and insulating plate on the back of the circuit-breaker for use at Uet415 V mandatory.
Assembly
A1
Internal
Poles
Rigid
1 (1) 2 (1) 3 4
(1)
(1)
1x1..25
Tightening torques
[Hole dimension] and [Nm]
Flexible
1x2.5..25
Terminal
M6
Cable or busbar
1-4mm2: 1Nm
5-25mm 2: 3Nm
Length of
Cable
stripping
[mm]
7.5
50
60
50
16
S (1)
(1)
Separators
[mm]
Terminal covers
[mm]
80 100 200
-
A1
Internal
1 2 34
1x25..50
1x25..50
M6
16
A2 (3)
Internal
1 (2) 2 (2) 3 4
1x50..150
1x70..120
M8
15
20
S (1)
A2 (3)
Internal
M8
20
22
S (1)
A3
Internal
34
1x185..300
M10
18
M16
43
23.5
A3
External
34
2x95..240
M10
18
M22
31
30
1cable
/70
2cable
Terminal FCCuAl
NA
W
H
D
S
R
=
=
=
=
=
=
=
1SDC210653F0001
1SDC210652F0001
1SDC210651F0001
1SDC210650F0001
(1) The Terminal covers are not supplied for 1p and 2p, the use of phase separators, supplied with the standard circuit-breaker, and the insulating of switchboard door are necessary.
(2) Insulation plate on the back of the circuit-breaker as mandatory.
(3) If terminals are mounted on top of circuit-breaker, Icu=50% and Ics=Icu.
Not available
Width
Hole heigth
Depth
Diameter
Standard
On request
3/5
1SDC210032D0204
Formula_03_accessori.indd 5
21/02/2011 9.39.18
Accessories
Mechanical accessories
Ordering codes connection terminals
Terminals
1SDA...R1
Front terminals - F
1 piece
2 pieces
3 pieces
4 pieces
6 pieces
8 pieces
A1
066200
066201
066202
066203
066204
066205
A2
066206
066207
066208
066209
066210
066211
055012
055013
055010
055011
A3
1SDA...R1
Front Extended Terminals - EF
1 piece
2 pieces
3 pieces
4 pieces
6 pieces
8 pieces
A1
066212
066213
066214
066215
066216
066217
A2
066218
066219
A3
066220
066221
066222
066223
055036
055037
055034
055035
1SDA...R1
Front Extended Spread Terminal - ES
2 pieces
3 pieces
4 pieces(1)
6 pieces
8 pieces
A1
066224
066225
066226
066227
066228
A2
066229
066230
066231
066232
066233
055040
055041
055038
055039
A3
1SDA...R1
Front Terminals for copper aluminium cables - FCCuAl
1 piece
2 pieces
3 pieces
4 pieces
6 pieces
8 pieces
A1 1 x 1...25 mm 2
066234
066235
066236
066237
066238
066239
A1 1 x 25...50 mm 2
066240
066241
066242
066243
066244
066245
A2 1 x 50...150 mm 2 (2)
066246
066247
066248
066249
066250
066251
A2 1 x 125...185 mm 2 (2)
066252
066253
066254
066255
066256
066257
A3 1 x 185...300 mm 2
055024
055025
055022
055023
A3 2 x 95...240 mm2
055032
055033
055030
055031
3/6
1SDC210032D0204
Formula_03_accessori.indd 6
21/02/2011 9.39.19
1SDC210654F0001
1SDC210654F0001
The lead sealing kit consists of screws which, when applied onto the terminal covers or onto
the circuit-breaker front, prevent their removal, acting as a protection against direct contacts
and tampering. The screws can be locked with a wire and sealed with lead.
1SDC210657F0001
1SDC210655F0001
Sealable screw
1SDC210658F0001
The compulsory and optional phase separators and terminal covers needed for correct installation and insulation of the circuit-breaker are indicated in the Connection terminals section
of the Accessories chapter and in the Overall dimension chapter, in correspondence with
each usable terminal.
1SDA...R1
A1
3 poles
A2
4 poles
HTC 60mm
HTC 50mm
066190
066185
LTC 7.5mm
066181
066182
A3
3 poles
4 poles
3 poles
4 poles
066186
066189
054960
054961
066183
066184
054968
054969
LTC 2mm
Sealable screws for terminal cover
066673
066673
068214
068214
051504
Phase separators
1SDA...R1
A1
A2
A3
066191
066194
066197
066193
066196
066199
PS 80mm
PS 100mm
PS 200mm
066192
066195
066198
066193
066196
066199
054970
054971
054972
054973
3/7
1SDC210032D0204
Formula_03_accessori.indd 7
21/02/2011 9.39.21
Accessories
Mechanical accessories
1SDC210659F0001
The rotary handles, in the direct and transmitted version, are available for the three-pole and
four-pole A1, A2 and A3 circuit-breakers both in the standard version (grey) and in the emergency version (red on a yellow background) suitable for controlling machine tools.
1SDC210660F0001
A3
066154
066155
066156
066157
066158
066159
066160
066161
066164
068952
066162
066163
066165
066167
066166
066168
3/8
1SDC210032D0204
Formula_03_accessori.indd 8
21/02/2011 9.39.22
1SDC210661F0001
1SDC210662F0001
1SDC210663F0001
Locks
Devices (with padlocks or keys) which prevent the circuit-breaker closing or opening operation. They can be applied:
directly onto the front of the circuit-breaker;
onto the direct/transmitted rotary handle operating mechanism;
onto the front for lever operating mechanisms.
All the locks of the circuit-breaker in the open position ensure isolation of the circuit according to the IEC 60947-2 Standard. The locks in closed position do not prevent release of the
mechanism following a fault.
1SDC210664F0001
Optional/
CircuitCB lock
Polarity Standard
breaker
position
Supply
Type of lock
OPEN
padlocks-max 3 padlocks
stem 7mm (not supplied)
Optional
OPEN
padlocks-max 3 padlocks
stem 7mm (not supplied)
3,4
Standard
OPEN
padlocks-max 3 padlocks
stem 7mm (not supplied)
3,4
Standard
CLOSED
Door lock(1)
3,4
Optional
OPEN
OPEN
3,4
Optional
OPEN
OPEN
A1-A2
3,4
Optional
OPENCLOSED
OPEN/
CLOSED
A3
3,4
Standard
OPEN
padlocks-max 3 padlocks
stem 6mm (not supplied)
A3
3,4
Standard
CLOSED
Door lock
A3
3,4
Optional
OPEN
OPEN
A3
3,4
Optional
OPEN
OPEN
A1-A2
3, 4
Optional
A1-A2
3, 4
Optional
PLL- Removable
padlock
A1-A2
1,2,3,4
Padlock in open
position
A1-A2-A3
Withdrawability
of Key
Type of Lock
OPENpadlocks-max 3 padlocks
CLOSED stem 7mm (not supplied)
066179
(1) Function can be completely excluded by the Customer during assembly of the handle [A1 and A2].
3/9
1SDC210032D0204
Formula_03_accessori.indd 9
21/02/2011 9.39.24
Accessories
Mechanical accessories
Ordering codes locks
Padlocks for lever operating mechanism of the circuit-breaker
1SDA...R1
1SDC210665F0001
A1-A2
066259
066171
066172
1SDC210666F0001
A1-A2
A3
066173
054939
066174
054940
066175
054941
066176
054942
066177
054943
066178
1SDC210671F0001
1SDC210670F0001
1SDC210667F0001
Fixed padlock in
open/closed position
Fixed padlock in
open/closed position
1SDC210672F0001
Removable padlock in
open position
1SDC210669F0001
Fixed padlock in
open position
1SDC210673F0001
1SDC210668F0001
3/10
1SDC210032D0204
Formula_03_accessori.indd 10
21/02/2011 9.39.28
1SDC210674F0001
1SDC210676F0001
066180
1SDC210675F0001
1SDC210678F0001
1SDC210677F0001
3/11
1SDC210032D0204
Formula_03_accessori.indd 11
21/02/2011 9.39.30
Accessories
1SDC210679F0001
Electrical accessories
Service releases
The cabled shunt opening release SOR-C allows circuit-breaker opening by means of a nonpermanent electrical control. Operation of the release is guaranteed for a voltage between
70% and 110% of the power supply rated voltage value Un, in both alternating and direct
current. It is fitted with an integrated limit contact for cutting off the power supply. The SOR-C
mechanical life is 10% of the corresponding circuit-breaker.
The cabled undervoltage release UVR-C ensures circuit-breaker opening for lack/lowering of
the release power supply voltage. Opening is guaranteed when the voltage is between 70% and
35% of Un as specified in the Standard. After tripping, the circuit-breaker can be closed again
starting from a voltage higher than 85% of Un. With the undervoltage release de-energised,
it is impossible to close the circuit-breaker and/or the main contacts. The UVR-C mechanical
life is 10% of the corresponding circuit-breaker.
The service releases SOR-C and UVR-C for A1, A2 and A3, which can be mounted as an alternative between each other, are only available in the cabled version (20 AWG cable section/0.5mm2),
with free cables 1 m long. For A1 and A2, snap-on assembly is carried out in the special slot
of the circuit-breaker without using any screws. In the following circuit-breakers:
two-pole (A1, A2), the SOR-C or UVR-C can be mounted as an alternative in the right-hand
slot;
three-pole (A1 A2 A3), the SOR-C or UVR-C can be mounted as an alternative in the lefthand slot;
four-pole (A1,A2,A3), the SOR-C or UVR-C can be housed as an alternative, in the slot of
the third pole.
AC [VA]
SOR-C
A3
DC [W]
12 VDC
AC [VA]
DC [W]
50
150
24...30 VAC/DC
50...65
50...65
130...180
130...180
48...60 VAC/DC
60
60
130...180
130...180
50
50
120...150
120...150
50...60
50...60
100...150
100...150
380...440 VAC
55
130...180
480...525 VAC*
55
150
* A3 up to 500 VAC
UVR-C
A3
AC [VA]
DC [W]
AC [VA]
DC [W]
1.5
1.5
48 VAC/DC
60 VAC/DC
2.5
2.5
24...30 VAC/DC
380...440 VAC
480...525 VAC*
* A3 up to 500 VAC
3/12
1SDC210032D0204
Formula_03_accessori.indd 12
21/02/2011 9.39.31
A1-A2
A3
SOR-C 12 VDC
066133
054869
066134
054870
066135
054871
066136
054872
066137
054873
066138
054874
066141
054875
* A3 up to 500 VAC
A1-A2
A3
066143
054887
UVR-C 48 VAC/DC
066144
054888
UVR-C 60 VAC/DC
067114
054889
066145
054890
066146
054891
066147
054892
066148
054893
Two-pole circuit-breaker
SOR-C/UVR-C
Three-pole circuit-breaker
1SDC210682F0001
1SDC210681F0001
SOR-C/UVR-C
1SDC210680F0001
* A3 up to 500 VAC
SOR-C/UVR-C
Four-pole circuit-breaker
3/13
1SDC210032D0204
Formula_03_accessori.indd 13
21/02/2011 9.39.33
Accessories
Electrical accessories
1SDC210684F0001
1Q+1SY (A1)
2Q+1SY (A2)
1Q+1SY (A1,A2,A3)
2Q+1SY (A1,A2)
3Q+1SY (A3)
1Q+1SY (A1,A2,A3)
1SDC210686F0001
1SDC210685F0001
1SDC210683F0001
2Q+1SY (A1,A2)
3Q+1SY (A3)
Voltage
Current
[V]
[A]
AC-12/AC-13/AC-14
125
AC-15
125
AC-12/AC-13/AC-14
250
AC-15
250
DC-12
110
0,5
DC-14
110
0,05
DC-12
250
0,3
DC-14
250
0,03
3/14
1SDC210032D0204
Formula_03_accessori.indd 14
21/02/2011 9.39.36
A2
3-4 poles
A3
2 poles
3-4 poles
3-4 poles
066149
054910
066152
066150
066151
066149
066150
054911
066258
066258
066258
066258
1SDC210687F0001
The cabled early auxiliary contacts (AUE-C) are normally open contacts, early in relation to
closing, which allow the undervoltage release to be supplied in advance in relation to closing
of the main contacts in conformity with the IEC 60204-1, VDE 0113 Standards.
It is possible to insert up to two early auxiliary contacts on closing inside the direct and transmitted rotary handle operating mechanism for circuit-breakers A1, A2, A3 in the three-pole
and four-pole version. The contacts, supplied in the cabled version, with cables 1 m long (20
AWG cable section/0.5mm2), must be ordered in combination with an undervoltage release.
AUE -C Electrical characteristics
Current [A]
Voltage [V]
AC
DC
125 DC
0.5
250 AC/DC
12
0.3
400 AC
066153
054925
1SDC210688F0001
AUE-C
A1-A2
3/15
1SDC210032D0204
Formula_03_accessori.indd 15
21/02/2011 9.39.36
Accessories
FORMULA Link
FORMULA Link is a component of a power distribution system which divides the main power
supply over different users. The FORMULA Link is characterised on the supply side by a main
circuit-breaker which protects the whole distribution system, and on the load side by smaller
sized circuit-breakers, dedicated to the individual users. All the copper components are tin
plated. FORMULA Link has been realizad in accordance with IEC 60439 Standard.
Looses components
Outgoing kit
connection
protection
Phase separators
FORMULA Link
main busbar
Incoming kit
connections
Busbar holder
Circuit-breakers
fixing rail
T6
A3
Incoming
breaker
A2
Phase
separators
Incoming
kit connection
Outgoing
kit connection A2
Outgoing
circuit-breaker
LOA
LOA
1SDC210697F0001
FORMULA Link
useful lenght:
F1 = 154mm;
F2 = 230.5mm
F3 = 307.5mm;
F4 = 384mm
F5 = 461mm
Outgoing
circuit-breaker
D
Outgoing
kit connection A1
3/16
1SDC210032D0204
Formula_03_accessori.indd 16
21/02/2011 9.39.45
Three different frames of FORMULA Links are available according to the incoming current of
the system:
250A FORMULA Link, usable with SACE FORMULA A2 circuit-breaker as incoming breaker;
400A FORMULA Link, usable with SACE FORMULA A3 circuit-breaker as incoming breaker;
630/800A FORMULA Link, usable with SACE Tmax T6 circuit breaker up 800A as incoming
breaker.
FORMULA Link - Mechanical characteristics
FORMULA Link frame
[A]
Length
Number of outgoing circuit-breaker
(SACE FORMULA A1)
250
400
630/800
F1
F2
F3
F4
F5
F1
F2
F3
F4
F5
F1
F2
F3
F4
F5
1p
12
18
24
30
36
12
18
24
30
36
12
18
24
30
36
2p
12
14
18
12
14
18
12
14
18
3p
10
12
10
12
10
12
250
400
Incoming Breaker
[A]
A2
A3
630/800
T6
Outgoing Breaker
A1
A1-A2
A1-A2
[V]
550 AC
550 AC
550 AC
[V]
690 AC
690 AC
690 AC
[kA]
30
40
40
1SDC210698F0001
To connect the main circuit-breaker to the FORMULA Link, it is necessary to use the special
incoming kit connections.
The connection kits change in relation to the incoming breaker choosen. They are available:
for SACE FORMULA A2 circuit-breaker;
for SACE FORMULA A3 circuit-breaker;
for SACE Tmax T6 circuit-breaker;
Its possible to connect the cables directly to the FORMULA Link using the dedicated incoming
kit connection for lugs (lugs not supplied).
1SDC210699F0001
Having six connection terminals, each kit allows connection of two three-pole or of six singlepole circuit-breakers.
3/17
1SDC210032D0204
Formula_03_accessori.indd 17
21/02/2011 9.39.47
1SDC210700F0001
Accessories
FORMULA Link
Each FORMULA Link frame is available in five different useful length for the assembling of the
outgoing kit connections:
F1: 154mm;
F2: 230.5mm;
F3: 307.5mm;
F4: 384mm;
F5: 461mm.
FORMULA Link
The length of the FORMULA Link is connected to the number and type of circuit-breakers (A1
or A2, in single-pole, two-pole or three-pole versions) that have to be installed.
In the table below all the possible combinations of three-pole outgoing circuit-breakers are
shown. Starting from the number of outgoing ways required, it is possible to obtain the number
of connection kit and the length of the FORMULA Link needed.
Outgoing Ways
Number A1 3p
Number A2 3p
Number of
A1 Outgoing
kit connections
Number of
A2 Outgoing
kit connections
10
12
Frame
length
F1
[154 mm]
F2
[230.5 mm]
F3
[307.5 mm]
F4
[384 mm]
F5
[461 mm]
3/18
1SDC210032D0204
Formula_03_accessori.indd 18
21/02/2011 9.39.48
During the ordering stage, it is necessary to specify the codes of the following components
which are already preassembled:
incoming kit connections according to the incoming current;
outgoing kit connections according to the type and number of outgoing circuit-breakers
(the code of the outgoing kit connection includes the base made of thermoplastic material,
copper connections and hammer screws for fixing and six outgoing kit connection protections);
FORMULA Link frame according to the length needed and the incoming current (the code
includes: 3 main busbars, 2 busbars holder supports, 2 circuit-breakers fixing rails, screws,
all ready to be assembled).
066822
066823
066824
068744
068839
068840
066841
066842
F2
F3
F4
F5
066825
066827
066828
066829
066830
066831
066832
066833
066834
066835
066836
066837
066838
066839
066840
Loose components
1SDA...R1
Aluminium fixing bar L=1.2m
066847
Busbar holder
066843
066844
066845
066846
066848
067538
067539
068740
068741
3/19
1SDC210032D0204
Formula_03_accessori.indd 19
21/02/2011 9.39.48
Accessories
FORMULA Link
Examples of order
EXAMPLE 1
1SDC210701F0001
Composition to be made
Incoming breaker: A3 400A;
Outgoing ways: 4 A1 3p.
Ordering code:
1SDA066823R1 (Quantity 1) - Incoming kit connections A3 400A;
1SDA066841R1 (Quantity 2) - Outgoing kit connections A1: each kit to be used for 2 SACE
FORMULA A1 3 poles;
1SDA066831R1 (Quantity 1) - Frame 400A, with a useful length F1=154 mm.
Step 1: Selection of the incoming kit connections code.
Since as incoming breaker there is a 400A SACE FORMULA circuit-breaker, it is necessary to
order the proper kit of terminal useful to connect the FORMULA Link and the incoming breaker.
Incoming kit connection
1SDA...R1
066822
066823
066824
068744
068839
068840
Step 2: Definiction of the number of the necessary outgoing kit connection, according to the
number of outgoing ways and defining length of the frame. To connect 4 SACE FORMULA A1
3 poles circuit-breakers as outgoing ways, it is necessary to order two outgoing kit connections A1 and the frame 400A with useful length F1.
Number A1 3p
Number A2 3p
Number of
A1 Outgoing
kit connections
4
0
6
2
0
8
4
2
10
6
4
0
12
8
6
2
0
0
2
0
2
4
0
2
4
0
2
4
6
0
2
4
6
8
2
0
3
1
0
4
2
1
5
3
2
0
6
4
3
1
0
Outgoing Ways
Number of
A2 Outgoing
kit connections
0
1
0
1
2
0
1
2
0
1
2
3
0
1
2
3
4
Frame
length
F1
[154 mm]
F2
[230.5 mm]
F3
[307.5 mm]
F4
[384 mm]
F5
[461 mm]
1SDA...R1
FORMULA Link ensemble 250A for A1
FORMULA Link ensemble 400A for A1-A2
FORMULA Link ensemble 630/800A for A1-A2
F1
066825
066831
066836
F2
066827
066832
066837
F3
066828
066833
066838
F4
066829
066834
066839
F5
066830
066835
066840
3/20
1SDC210032D0204
Formula_03_accessori.indd 20
21/02/2011 9.39.49
Examples of order
EXAMPLE 2
1SDC210702F0001
Composition to be made
Incoming breaker: Tmax T6 630A;
Outgoing ways: 4 A1 3p + 2 A2 3p.
Ordering code:
1SDA066824R1 (Quantity 1) - Incoming kit connections Tmax T6 630A;
1SDA066841R1 (Quantity 2) - Outgoing kit connections A1: each kit to be used for 2 SACE
FORMULA A1 3 poles;
1SDA066842R1 (Quantity 1) - Outgoing kit connections A2: each kit to be used for 2 SACE
FORMULA A2 3 poles;
1SDA066838R1 (Quantity 1) - Frame 630A, with a useful length F3=307.5 mm.
Step 1: Selection of the incoming kit connections code.
Since as incoming breaker there is a 630A Tmax T6 circuit-breaker, it is necessary to order
the proper kit of terminal useful to connect the FORMULA Link and the incoming breaker.
Incoming kit connection
1SDA...R1
066822
066823
066824
068744
068839
068840
Step 2: Definiction of the number of the necessary outgoing kit connection, according to the
number of outgoing ways and defining length of the frame. To connect 4 SACE FORMULA A2
3 poles circuit-breakers as outgoing ways, it is necessary to order two outgoing kit connections A1 and the frame 630A with useful length F3.
Number A1 3p
Number A2 3p
Number of
A1 Outgoing
kit connections
4
0
6
2
0
8
4
2
10
6
4
0
12
8
6
2
0
0
2
0
2
4
0
2
4
0
2
4
6
0
2
4
6
8
2
0
3
1
0
4
2
1
5
3
2
0
6
4
3
1
0
Outgoing Ways
Number of
A2 Outgoing
kit connections
0
1
0
1
2
0
1
2
0
1
2
3
0
1
2
3
4
Frame
length
F1
[154 mm]
F2
[230.5 mm]
F3
[307.5 mm]
F4
[384 mm]
F5
[461 mm]
1SDA...R1
FORMULA Link structure 250A for A1
FORMULA Link structure 400A for A1-A2
FORMULA Link structure 630/800A for A1-A2
F1
066825
066831
066836
F2
066827
066832
066837
F3
066828
066833
066838
F4
066829
066834
066839
F5
066830
066835
066840
3/21
1SDC210032D0204
Formula_03_accessori.indd 21
21/02/2011 9.39.49
Formula_03_accessori.indd 22
21/02/2011 9.39.50
Content
Examples of curve readings ............................................................................................. 4/2
Temperature performance ................................................................................................ 4/3
Trip curves for power distribution
Trip curves with thermomagnetic and electronic trip units ................................................ 4/5
Specific let-through energy curves
230V ..................................................................................................................................... 4/5
415V - 440V .......................................................................................................................... 4/6
500V - 550V .......................................................................................................................... 4/7
Limitations curves
230V ..................................................................................................................................... 4/8
415V - 440V .......................................................................................................................... 4/9
500V - 550V ..........................................................................................................................4/10
Technical Information
Dissipated powers ...............................................................................................................4/13
Coordination tables (back-up)
Notes for use .........................................................................................................................4/14
MCCB-MCB (415V) ...............................................................................................................4/15
MCCB-MCCB (415V) ............................................................................................................4/16
4/1
1SDC210032D0204
Formula_04_curve.indd 1
21/02/2011 9.40.23
103
~200s
102
10
~9.9s
2 x I1
1
10-1
10-2
Example 2 A1 125
Specific let-through energy curve
~62.5s
1SDC210703F0001
t [s]
104
10
10-1
102
x I1
I2t[106A2s]
102
10
125A
0.70
10-1
1SDC210704F0001
Example 1 A2 250
Trip curves for power distribution
(thermomagnetic trip unit)
10-2
Example 3 A1 125
Limitation curves
10
20
100
Irms [kA]
50
Ip[kA]
102
Curve A
40kA
= 25kA
~ 15kA
125A
Curve B
10
1SDC210705F0001
The following gure gives the trend of the limiting curve of the
A2 125 In = 125A circuit-breaker.
The r.m.s. value of the prospective symmetrical short-circuit
current is given on the diagram abscissas, whereas the peak
value of the short-circuit current is indicated on the ordinates.
The limiting effect can be assessed by comparing, at the same
value of symmetrical short-circuit current, the peak value corresponding to the prospective short-circuit current (curve A) with
the peak value limited (curve B). The A1 125 circuit-breaker with
thermomagnetic trip unit In = 125A at a voltage of 400V/415V,
for a fault current of 20kA limits the prospective short-circuit
peak current to 15kA, with a reduction compared with the peak
value of the prospective short-circuit current of 25kA.
10
20
50
100
Irms [kA]
4/2
1SDC210032D0204
Formula_04_curve.indd 2
21/02/2011 9.40.24
Temperature performances
All the SACE FORMULA circuit-breakers can be used under the following environmental conditions:
-25 C +70 C: range of temperature where the circuit-breaker is installed;
-40 C +70 C: range of temperature where the circuit-breaker is stored.
The SACE FORMULA circuit breaker has been designed to hold 100% In at 50C without tripping
in normal condition (except for A1 125A).
To determinate tripping time using time/current curves, use I tC values indicated in the tables
below.
SACE FORMULA
In [A]
5
10
15
16
20
25
30
32
40
50
60
63
70
80
90
100
125
A1 circuit-breaker
10C
6.5
12.9
19.4
20.7
24.6
29.2
36.8
39.3
46.7
58.3
70.0
73.5
81.7
91.0
102.4
116.7
146.6
40C
5.4
10.8
16.2
17.3
21.2
25.9
31.8
33.9
41.5
51.9
62.2
65.4
72.6
82.1
92.4
103.7
125.0
50C
5
10
15
16
20
25
30
32
40
50
60
63
70
80
90
100
116.9
60C
4.8
9.6
14.4
15.3
19.2
24.0
28.8
30.7
38.3
47.9
57.5
60.4
67.1
76.7
86.3
95.9
108.3
70C
4.5
9.0
13.5
14.4
18.0
22.5
27.0
28.8
36.0
45.0
54.0
56.7
63.0
72.0
81.0
90.0
98.8
40C
135
159
169
185
212
243
270
50C
125
150
160
175
200
225
250
60C
114
138
148
160
183
205
228
70C
102
126
135
144
165
184
204
SACE FORMULA A3 circuit-breaker with termomagnetic trip unit TMF (special version 50C)
In [A]
10C
20C
30C
40C
50C
300
393
372
350
326
300
400
516
490
462
432
400
60C
272
365
70C
241
327
60C
285
355
400
70C
263
325
345
40C
320
400
500
50C
305
380
450
The circuit-breaker fitted with electronic trip units do not undergo any variations in performance
as the temperature varies, but in the case of temperatures exceeding +40C, the used rated
current must be reduced to protect the copper parts of the circuit-breaker.
SACE FORMULA A3 circuit-breakers with electronic trip unit ELT LI
In [A]
630
35C
630
40C
630
45C
630
50C
580
55C
555
60C
529
65C
502
70C
478
4/3
1SDC210032D0204
Formula_04_curve.indd 3
21/02/2011 9.40.24
Temperature performances
Using a circuit breaker A1 125A with In=70A, to define the tripping time for an overcurrent
I=200A you have to calculate the multiplier of I1.
Reference Temperature 50C (hot trip)
I=200A
I 50C = 70A
I/I 50C = 200A/70A = 2.86
A1 125A - TMF
In=70 A - Ambient temperature=50C - hot trip
t [s]
104
103
102
t=20s
10
t=1,2s
1
10-2
10-1
I/I1=2.86
10
102
103
x I1
1SDC210706BF0001
10-1
A1 125A - TMF
In=70 A - Ambient temperature=40C - hot trip
t [s]
104
103
102
t=28s
10
t=1,5s
1
10-2
10-1
I/I1=2.75
10
102
103
x I1
1SDC210706AF0001
10-1
4/4
1SDC210032D0204
Formula_04_curve.indd 4
21/02/2011 9.40.25
Trip curves
Trip curves with thermomagnetic and electronic trip units
A1 125A - TMF
A1 125A - TMF
In=1570 A
In=80100 A
I3=10In
t [s]
t [s]
104
104
103
103
102
102
10
10
In=15A
In=16A
In=20A
In=25A
10
102
103
x I1
10-2
10-1
A1 125A - TMF
A2 250A - TMF
In=125 A
In=125250 A
I3=10In
I3=10In
t [s]
103
103
102
102
10
10
10-1
10-1
10
102
103
x I1
1SDC210708F0001
104
10-1
102
103
x I1
10
102
103
x I1
t [s]
104
10-2
10
10-2
10-1
1SDC210709F0001
10-1
1SDC210706F0001
10-2
10-1
In=30-70A
1SDC210707F0001
10-1
4/5
1SDC210032D0204
Formula_04_curve.indd 5
21/02/2011 9.40.26
Trip curves
Trip curves with thermomagnetic and electronic trip units
A3 630A - TMF
A3 630A - TMF
Special version 50C
In=320500 A
In=300400 A
I3=10In
I3=10In
t [s]
103
103
102
102
10
10
10-1
10-1
10-2
10-1
10
102
103
x I1
10
102
103
x In
1SDC210710F0001
104
10-2
10-1
10
102
103
x I1
1SDC210710AF0001
t [s]
104
A3 630A - ELT LI
I3=10In
t [s]
104
103
102
10
10-2
10-1
1SDC210711F0001
10-1
4/6
1SDC210032D0204
Formula_04_curve.indd 6
21/02/2011 9.40.27
A1 125A
A2 250A
230V
230V
I2t [106A2s]
I2t [106A2s]
10
10
10-2
10
10
102
103
Irms [kA]
-1
10-2
10
102
103
Irms [kA]
1SDC210713F0001
-1
1SDC210712F0001
10
A3 630A
230V
I2t [106A2s]
10
10-1
1
10
102
103
Irms [kA]
1SDC210714F0001
4/7
1SDC210032D0204
Formula_04_curve.indd 7
21/02/2011 9.40.28
A1 125A
A2 250A
415-440V
415-440V
I2t [106A2s]
I2t [106A2s]
10
10
10-2
10
10
102
103
Irms [kA]
10
102
103
Irms [kA]
-1
10-2
10
102
103
Irms [kA]
1SDC210716F0001
-1
1SDC210715F0001
10
A3 630A
415-440V
I2t [106A2s]
10
10-1
1
1SDC210717F0001
4/8
1SDC210032D0204
Formula_04_curve.indd 8
21/02/2011 9.40.29
A1 125A
A2 250A
500-550V
500-550V
I2t [106A2s]
I2t [106A2s]
10
10
10-2
10
10
102
103
Irms [kA]
-1
10-2
10
102
103
Irms [kA]
1SDC210719F0001
-1
1SDC210718F0001
10
A3 630A
500-550V
I2t [106A2s]
10
10-1
1
10
102
103
Irms [kA]
1SDC210720F0001
4/9
1SDC210032D0204
Formula_04_curve.indd 9
21/02/2011 9.40.30
Limitation Curves
A1 125A
A2 250A
230V
230V
Ip [kA]
Ip [kA]
103
103
Curve A
Curve A
102
102
Curve B
Curve B
10
10
103
Irms [kA]
102
10
102
103
Irms [kA]
1SDC210722F0001
1SDC210721F0001
10
A3 630A
230V
Ip [kA]
Curve A
102
Curve B
10
102
103
Irms [kA]
1SDC210723F0001
10
4/10
1SDC210032D0204
Formula_04_curve.indd 10
21/02/2011 9.40.31
A1 125A
A2 250A
415-440V
415-440V
Ip [kA]
Ip [kA]
103
103
Curve A
102
102
Curve A
Curve B
Curve B
10
102
103
Irms [kA]
10
102
103
Irms [kA]
1SDC210725F0001
10
1SDC210724F0001
10
A3 630A
415-440V
Ip [kA]
Curve A
102
Curve B
10
102
103
Irms [kA]
1SDC210726F0001
10
4/11
1SDC210032D0204
Formula_04_curve.indd 11
21/02/2011 9.40.32
Limitation Curves
A1 125A
A2 250A
500-550V
500-550V
Ip [kA]
Ip [kA]
103
103
102
102
Curve A
Curve A
Curve B
10
102
103
Irms [kA]
1SDC210727F0001
10
Curve B
10
102
103
Irms [kA]
1SDC210728F0001
10
A3 630A
500-550V
Ip [kA]
Curve A
102
Curve B
10
102
103
Irms [kA]
1SDC210729F0001
10
4/12
1SDC210032D0204
Formula_04_curve.indd 12
21/02/2011 9.40.33
Technical information
Dissipated powers
For each circuit-breaker, the table gives the dissipated power values for a single pole circuitbreaker (G2.12).
The maximum total dissipated power of a two-pole, three-pole or four-pole circuit-breaker
used at 50/60Hz is equal to the dissipated power for the single pole multiplied by the number
of poles.
Power [W/pole]
TMF
ELT LI
In [A]
A1
A2
A3
15
2.5
16
2.8
20
25
30
32
40
4.5
50
5.5
60
63
70
80
90
100
125
11
150
160
175
10
200
12
225
14
250
16
320
13.6
400
19.5
500
28.8
630
41
4/13
1SDC210032D0204
Formula_04_curve.indd 13
21/02/2011 9.40.33
Icu [kA]
10
18
25
36
50
Caption
MCB = miniature circuit-breakers (S2, S800)
MCCB = moulded-case circuit-breakers (FORMULA)
For miniature circuit-breakers:
B
= trip characteristic (Im=3...5In)
C
= trip characteristic (Im=5...10In)
D
= trip characteristic (Im=10...20In)
K
= trip characteristic (Im=8...14In)
Z
= trip characteristic (Im=2...3In)
For solutions not shown in these tables, please contact ABB SACE Division.
4/14
1SDC210032D0204
Formula_04_curve.indd 14
21/02/2011 9.40.33
MCCB-MCB @ 415 V
Supply S.
A1
Version
Load S.
Char.
S200
B,C,K,Z
S200M
B,C
In (A)
0.510
13...63
0.510
13...63
0.510
Icu (kA)
10
15
A2
A1
A2
A1
18
A2
N
25
36
16
16
25
25
30
36
16
16
25
25
30
36
25
30
36
30
36
S200P
B,C,D,K,Z
13...25
3263
15
16
16
25
25
30
36
S280
B,C
80100
16
16
16
16
16
36
16
16
25
25
30
36
S290
C,D
80125
15
S800N
B,C,D
10125
36
S800S
B,C,D,K
10125
50
4/15
1SDC210032D0204
Formula_04_curve.indd 15
21/02/2011 9.40.33
MCCB-MCCB @ 415 V
Supply S.
A2
A2
Version
A2
A3
A3
Load S.
Char.
Icu (kA)
18
25
36
36
50
A1
10
18
25
36
25
25
25
36
A1
A2
A1
A2
A1
A2
B
C
N
18
18
25
25
36
25
36
25
36
36
50
36
50
36
50
36
50
4/16
1SDC210032D0204
Formula_04_curve.indd 16
21/02/2011 9.40.33
Wiring diagrams
Content
Information for reading and graphic symbols .................................................................... 5/2
Wiring diagrams of the circuit-breakers .............................................................................. 5/3
Electrical accessories .......................................................................................................... 5/4
5/1
1SDC210032D0204
Formula_05_schemi.indd 1
21/02/2011 9.41.17
Thermal effect
Terminal
Electromagnetic effect
Circuit-breaker with
automatic release
Operating device
(general symbol)
Operated by pushing
Current transformer
Instantaneous overcurrent
or rate-of-rise relay
Operated by turning
Make contact
Connection of conductors
Break contact
5/2
1SDC210032D0204
Formula_05_schemi.indd 2
21/02/2011 9.41.18
Operating status A1 A2
Operating status A3
Caption
Q
K51
=
=
TI/L1
TI/L2
TI/L3
TI/N
X0
YO1
=
=
=
=
=
=
Main circuit-breaker
Electronic trip unit ELT LI, with the following protection functions:
L overload protection with inverse long time-delay trip
I short-circuit protection with instantaneous time-delay trip
Current transformer placed on phase L1
Current transformer placed on phase L2
Current transformer placed on phase L3
Current transformer placed on the neutral
Connector for the YO1 trip coil
Trip coil of the electronic trip unit
5/3
1SDC210032D0204
Formula_05_schemi.indd 3
21/02/2011 9.41.19
Electrical accessories
Figure:
1)
2)
3)
4)
Notes
B) The undervoltage release is supplied for power supply branched on the supply side of the circuit-breaker
or from an independent source: circuit-breaker closing is only allowed with the release energised (the
lock on closing is made mechanically).
C) The S4/1 and S4/2 contacts shown in figures 3-4 open the circuit with circuit-breaker open and
close it when a manual closing command is given by means of the rotary handle in accordance with
the Standards regarding machine tools (closing does not take place in any case if the undervoltage
release is not supplied).
F) Additional external undervoltage resistor supplied at 250V DC or 380/440V AC.
Caption
Q/0
R
S4/1-2
SO
V1
V4
=
=
=
=
=
=
XV
YO
YU
=
=
=
5/4
1SDC210032D0204
Formula_05_schemi.indd 4
21/02/2011 9.41.20
Figure:
1)
2)
3)
4)
Notes
B) The undervoltage release is supplied for power supply branched on the supply side of the circuit-breaker
or from an independent source: circuit-breaker closing is only allowed with the release energised (the
lock on closing is made mechanically).
C) The S4/1 and S4/2 contacts shown in figures 3-4 open the circuit with circuit-breaker open and
close it when a manual closing command is given by means of the rotary handle in accordance with
the Standards regarding machine tools (closing does not take place in any case if the undervoltage
release is not supplied).
F) Additional external undervoltage resistor supplied at 250V DC or 380/440V AC.
Caption
Q/0
R
S4/1-2
SO
V1
V4
=
=
=
=
=
=
XV
YO
YU
X1, X8
=
=
=
=
Formula_05_schemi.indd 5
21/02/2011 9.41.20
Electrical accessories
Auxiliary contacts A1 A2
Figure:
5) Two changeover contacts for electrical signalling of circuit-breaker open/closed and one changeover
contact for signalling circuit-breaker in tripped position due to thermomagnetic trip unit or SOR-C or
UVR-C intervention (2Q+1SY)
6) One changeover contact for electrical signalling of circuit-breaker open/closed and one changeover
contact for signalling circuit-breaker in tripped position due to thermomagnetic trip unit or SOR-C or
UVR-C intervention (1Q+1SY)
Caption
Q/1, 2
SY
=
=
V1
V4
XV
=
=
=
5/6
1SDC210032D0204
Formula_05_schemi.indd 6
21/02/2011 9.41.20
Auxiliary contacts A3
Figure:
5) Three changeover contacts for electrical signalling of circuit-breaker open/closed and one changeover contact for signalling circuit-breaker in tripped position due to thermomagnetic trip unit or SORC or UVR-C intervention (3Q+1SY)
6) One changeover contact for electrical signalling of circuit-breaker open/closed and one changeover
contact for signalling circuit-breaker in tripped position due to thermomagnetic trip unit or SOR-C or
UVR-C intervention (1Q+1SY)
Caption
Q/1, 2, 3
SY
=
=
V1
V4
XV
X2, X7
=
=
=
=
5/7
1SDC210032D0204
Formula_05_schemi.indd 7
21/02/2011 9.41.21
Overall dimensions
Content
FORMULA A1
Circuit-breaker and terminals .................................................................................................. 6/2
Accessories ............................................................................................................................ 6/8
FORMULA A2
Circuit-breaker and terminals .................................................................................................. 6/9
Accessories ............................................................................................................................6/15
FORMULA A3
Circuit-breaker and terminals ..................................................................................................6/16
Accessories ............................................................................................................................6/20
FORMULA Link
FORMULA Link 250A .............................................................................................................6/22
FORMULA Link 400A .............................................................................................................6/23
FORMULA Link 630A .............................................................................................................6/24
FORMULA Link 800A .............................................................................................................6/25
Distances to be respected ...................................................................................................6/26
6/1
1SDC210032D0204
Formula_06_dimensioni.indd 1
21/02/2011 9.42.12
Overall dimensions
A1 - Circuit-breaker and terminals
Fixing onto the back plate
3-4 poles
Distance between compartment door and
back of switchboard
I-II-III-IV poles
Without flange
I-II-III-IV poles
2 poles
A [mm]
69
61
1 pole
The circuit-breaker installed at:
- A=69 mm has the face around the operating lever extending from the compartment door;
- A=61 mm has the face around the operating lever and steel with construction
characteristics extending from the compartment door.
3-4 poles
2 poles
1 pole
Caption
1 Fixing bracket
6/2
1SDC210032D0204
Formula_06_dimensioni.indd 2
21/02/2011 9.42.12
1-3-4 poles
2 poles
A = 69mm
1-2 poles
A = 61mm
1 pole
A = 61mm
2 poles
A = 69mm
3-4 poles
A = 61mm
3 poles
A = 61mm
4 poles
6/3
1SDC210032D0204
Formula_06_dimensioni.indd 3
21/02/2011 9.42.13
Overall dimensions
A1 - Circuit-breaker and terminals
F Terminals
3-4 poles
2 poles
1 pole
Caption
1 50mm insulating barriers
between the terminals
(compulsory) supplied
EF Terminals
3-4 poles
2 poles
1 pole
Caption
1 50mm insulating barriers
between the terminals
(compulsory) not supplied with
EF terminals kit, but with the
circuit-breaker in base version
2 Top terminal covers with IP40
degree of protection (on request)
3 Front extended terminals
6/4
1SDC210032D0204
Formula_06_dimensioni.indd 4
21/02/2011 9.42.14
ES Terminals
4 poles
3 poles
2 poles
Caption
1 Front extended spread terminals
2 100mm insulating barriers
between the terminals
(compulsory) supplied
6/5
1SDC210032D0204
Formula_06_dimensioni.indd 5
21/02/2011 9.42.14
Overall dimensions
A1 - Circuit-breaker and terminals
FCCuAl 1x25...50mm2 Terminals
3-4 poles
3-4 poles
1-2 poles
1-2 poles
Caption
1-2 poles
1-2 poles
Without flange
A [mm]
B [mm]
C [mm]
69
33
66
1 POLE
69
58
91
2 POLES
61*
33
66
1 POLE
61*
58
91
2 POLES
6/6
1SDC210032D0204
Formula_06_dimensioni.indd 6
21/02/2011 9.42.15
3-4 poles
3-4 poles
1-2 poles
1-2 poles
Caption
1-2 poles
1-2 poles
Without flange
A [mm]
B [mm]
C [mm]
69
33
66
1 POLE
69
58
91
2 POLES
61*
33
66
1 POLE
61*
58
91
2 POLES
6/7
1SDC210032D0204
Formula_06_dimensioni.indd 7
21/02/2011 9.42.16
Overall dimensions
A1 - Accessories
Rotary handle operating mechanism on circuit-breaker and compartment door drilling template (RHD)
3-4 poles
3-4 poles
Caption
3 Rotary handle operating
mechanism on circuit-breaker
5 Template for drilling
compartment with direct handle
Rotary handle operating mechanism on compartment door and compartment door drilling template (RHE)
3-4 poles
Caption
1 Transmission group
2 Transmitted rotary handle
operating mechanism
4 Template for drilling
compartment with transmitted
rotary handle
6/8
1SDC210032D0204
Formula_06_dimensioni.indd 8
21/02/2011 9.42.17
Overall dimensions
A2 - Circuit-breaker and terminals
Fixing on the back plate
Caption
3-4 poles
2 poles
1 pole
A [mm]
69
61
Without flange
A [mm]
B [mm]
C [mm]
61
61
61
61
42.5
77.5
77.5
77.5
42.5
77.5
77.5
77.5
85
120
155
190
85
120
155
190
69
69
69
69
1 POLE
2 POLES
3 POLES
4 POLES
1 POLE
2 POLES
3 POLES
4 POLES
3-4 poles
2 poles
1 pole
Caption
1 Fixing bracket
6/9
1SDC210032D0204
Formula_06_dimensioni.indd 9
21/02/2011 9.42.18
Overall dimensions
A2 - Circuit-breaker and terminals
Drilling templates for support sheet
1-3-4 poles
2 poles
A = 69mm
1-2-3-4 poles
A = 61mm
1 pole
A = 61mm
2 poles
A = 61mm
3 poles
A = 61mm
4 poles
6/10
1SDC210032D0204
Formula_06_dimensioni.indd 10
21/02/2011 9.42.18
F Terminals
2-3-4 poles
1 poles
Caption
1 80mm insulating barriers
between the terminals
(compulsory) supplied
EF Terminals
8
8
2 poles
1 pole
Caption
3-4 poles
6/11
1SDC210032D0204
Formula_06_dimensioni.indd 11
21/02/2011 9.42.19
Overall dimensions
A2 - Circuit-breaker and terminals
ES Terminals
4 poles
3 poles
2 poles
Caption
1 Front extended spread
terminals
2 100mm insulating barriers
between the terminals
(compulsory) supplied
6/12
1SDC210032D0204
Formula_06_dimensioni.indd 12
21/02/2011 9.42.20
3-4 poles
3-4 poles
1 poles
2 poles
1-2 poles
Caption
1-2 poles
Without flange
1-2 poles
A [mm]
B [mm]
69
42.5
C [mm]
85
1 POLE
69
77.5
120
2 POLES
61
42.5
85
1 POLE
61
77.5
120
2 POLES
6/13
1SDC210032D0204
Formula_06_dimensioni.indd 13
21/02/2011 9.42.20
Overall dimensions
A2 - Circuit-breaker and terminals
FCCuAl 1x50...150mm2 Terminals
3-4 poles
3-4 poles
1 poles
2 poles
1-2 poles
Caption
1-2 poles
Without flange
1-2 poles
A [mm]
B [mm]
69
42.5
C [mm]
85
1 POLE
69
77.5
120
2 POLES
61
42.5
85
1 POLE
61
77.5
120
2 POLES
6/14
1SDC210032D0204
Formula_06_dimensioni.indd 14
21/02/2011 9.42.21
Overall dimensions
A2 - Accessories
Rotary handle operating mechanism on compartment door and compartment door drilling template (RHD)
3-4 poles
minimum rotation radius
for door fulcrum
Caption
3 Rotary handle operating
mechanism on circuit-breaker
5 Template for compartment
drilling with direct handle
Rotary handle operating mechanism on circuit-breaker and compartment door drilling template (RHE)
Caption
3-4 poles
1 Transmission group
2 Transmitted rotary handle
operating mechanism
4 Template for drilling
compartment with transmitted
rotary handle
6/15
1SDC210032D0204
Formula_06_dimensioni.indd 15
21/02/2011 9.42.22
Overall dimensions
A3 - Circuit-breaker and terminals
Fixing onto back plate
3-4 poles
Distance between compartment door and
back of switchboard
I-II-III-IV poles
Without flange
I-II-III-IV poles
A [mm]
105
114
3 poles
4 poles
6/16
1SDC210032D0204
Formula_06_dimensioni.indd 16
21/02/2011 9.42.23
A=114
3-4 poles
A=105
3-4 poles
F Terminals
3-4 poles
Caption
1 Front terminals for busbar
connection
6/17
1SDC210032D0204
Formula_06_dimensioni.indd 17
21/02/2011 9.42.23
Overall dimensions
A3 - Circuit-breaker and terminals
EF Terminals
Caption
1 100mm insulating barriers
between terminals (compulsory)
supplied
2 High terminal covers with
degree of protection IP40
(on request)
3 Front extended terminals
3-4 poles
ES Terminals
4 poles
3 poles
Caption
5 Front extended spread terminals
6 Insulating barriers between
terminals (compulsory) supplied
6/18
1SDC210032D0204
Formula_06_dimensioni.indd 18
21/02/2011 9.42.23
3-4 poles
Caption
1 Front terminals for busbar
connection 300mm2 CuAl
3-4 poles
Caption
1 60mm high terminal covers
(compulsory) supplied
6/19
1SDC210032D0204
Formula_06_dimensioni.indd 19
21/02/2011 9.42.24
Overall dimensions
A3 - Accessories
Rotary handle operating mechanism on circuit-breaker + Compartment door drilling template (RHD)
3-4 poles
3-4 poles
Caption
3 Rotary handle operating
mechanism on circuit-breaker
5 Template for drilling
compartment with direct handle
Rotary handle operating mechanism on compartment door + Compartment door drilling template (RHE)
Caption
1 Transmission unit
2 Rotary transmitted handle
operating machanism
3 Rotary handle operating
mechanism on circuit-breaker
4 Template for drilling
compartment with transmitted
rotary handle
5 Drilling for door template with
direct handle
3-4 poles
minimum rotation
radius for door fulcrum
6/20
1SDC210032D0204
Formula_06_dimensioni.indd 20
21/02/2011 9.42.24
3-4 poles
6/21
1SDC210032D0204
Formula_06_dimensioni.indd 21
21/02/2011 9.42.25
Overall dimensions
FORMULA Link 250A
FORMULA Link A1 250A
Caption
1 Main SACE FORMULA A2 250
circuit-breaker
2 Busbar holder for SACE
FORMULA A1
Frame 250A
A [mm]
B [mm]
C [mm]
F1
154
179
150
F2
230.5
255.5
226.5
F3
307.5
332.5
303
F4
384
409
380
F5
461
486
456.5
6/22
1SDC210032D0204
Formula_06_dimensioni.indd 22
21/02/2011 9.42.25
Overall dimensions
FORMULA Link 400A
FORMULA Link A1-A2 400A
Caption
Frame 400A
A [mm]
B [mm]
F1
154
179
C [mm]
150
F2
230.5
255.5
226.5
F3
307.5
332.5
303
F4
384
409
380
F5
461
486
456.5
With A1 only
600
800
6/23
1SDC210032D0204
Formula_06_dimensioni.indd 23
21/02/2011 9.42.26
Overall dimensions
FORMULA Link 630A
FORMULA Link A1-A2 630A
Caption
Frame 630A
A [mm]
B [mm]
F1
154
179
C [mm]
150
F2
230.5
255.5
226.5
F3
307.5
332.5
303
F4
384
409
380
F5
461
486
456.5
With A1 only
600
800
6/24
1SDC210032D0204
Formula_06_dimensioni.indd 24
21/02/2011 9.42.27
Overall dimensions
FORMULA Link 800A
FORMULA Link A1-A2 800A
Caption
Frame 800A
A [mm]
B [mm]
F1
154
179
C [mm]
150
F2
230.5
255.5
226.5
F3
307.5
332.5
303
F4
384
409
380
F5
461
486
456.5
With A1 only
800
800
6/25
1SDC210032D0204
Formula_06_dimensioni.indd 25
21/02/2011 9.42.28
Overall dimensions
Distances to be respected
Insulation distances to be respected for installation in cubicles
[mm]
[mm]
[mm]
A1
45
20
35
A2
60
25
60
A3
30
25
25
Ue<415V
Uet440V
[mm]
[mm]
[mm]
A1
45
20
35
A2
180
25
60
A3
60
25
25
Centre distance I
[mm]
1
pole
2
poles
3
poles
4
poles
1
pole
2
poles
3
poles
4
poles
A1
25.4
50.8
76.2
101.2
25.4*
50.8*
76.2*
101.2*
A2
36
70
105
140
36*
70*
105*
140*
A3
140
184
140**
184**
80
100 (Ue<415V)
A3
260 (Uet415V)
160
Caption
1 Connection not insulated
2 Insulated cable
3 Cable terminal
6/26
1SDC210032D0204
Formula_06_dimensioni.indd 26
21/02/2011 9.42.29
Glossary
Content
G1 - Circuit-breaker ............................................................................................................ 7/2
G2 - Performance Parameters ........................................................................................... 7/4
G3 - Releases and Protections ........................................................................................... 7/6
G4 - Regulations and Standards ........................................................................................ 7/7
7/1
1SDC210032D0204
Formula_07_glossario.indd 1
21/02/2011 9.43.10
Glossary
G1 - Circuit-breaker
G1.1 Circuit-breaker
A mechanical switching device, capable of making, carrying and breaking currents under
normal circuit conditions and also making, carrying for a specified time and breaking
currents under specified abnormal circuit conditions such as short-circuit.
G1.2 Protection degree (IP)
The IP protection degree indicates the level of protection for apparatus against contact
with live parts and penetration of liquids and solid foreign bodies.
G1.3 Rate of contact wear
Percentage of contacts wear, indicatively gives the state of durability of the circuitbreaker contacts.
G1.4 Double insulation
A double insulation between the live power parts and the front parts of the apparatus
where the operator works during normal plant service is present in all the circuit-breakers,
so as to eliminate the risk of contacts with live parts. The seat of each electrical accessory is completely segregated from the power circuit. In particular, the operating unit
is completely insulated in relation to the voltage circuits. Furthermore, both between
the internal live parts and in the area of the connection terminals, the circuit-breaker
has redundant insulation. In fact, the distances between the connection terminals are
greater than those required by the IEC Standards and conform to what is prescribed
by the American UL 489 Standard.
G1.5 Positive operation
The operating lever always indicates the actual position of the mobile circuit-breaker
contacts:
red line (I): Closed position;
green line (O): Open position;
yellow-green line: Trip Position, open due to release trip or test pushbotton.
The indications are precise and reliable, in conformity with what is prescribed by the
IEC 60073 and IEC 60417-2 Standards.
Tripping of the releases automatically opens the mobile contacts and makes the lever
move into the Trip position: to reclose the circuit-breaker it must be reset, by pushing
the operating lever from the trip position to the Open position.
The operating mechanism of the circuit-breaker has free trip, independent of the pressure on the lever and of the speed of the operation.
From this position it is possible to close the circuit-breaker.
G1.6 Isolation behaviour
Characteristic of a mechanical operating device which, in the open and trip position,
carries out a disconnection function and guarantees an insulation distance (distance
between fixed and mobile contacts) sufficient to guarantee safety.
G1.7 Electromagnetic compatibility
In conformity with the IEC 60947-2 Standards (Annex B + Annex F, European
Directive No. 89/336) relative to electromagnetic compatibility EMC, the circuitbreakers used with electronic trip units and residual current releases are guaranteed
to function in the presence of disturbances caused by:
electromagnetic apparatus;
atmospheric disturbances which flow through power networks;
interferences from radio waves;
discharges of electrical type.
Furthermore, the circuit-breakers does not generate disturbances to other electronic
apparatus near the place of installation.
7/2
1SDC210032D0204
Formula_07_glossario.indd 2
21/02/2011 9.43.10
G1.8 Tropicalization
All the circuit-breakers can be used in the most severe environmental conditions
defined by the following standards:
IEC 60721-2-1 (climograph 8);
IEC 60068-2-30;
IEC 60068-2-2;
IEC 60068-2-52.
Tropicalization is guaranteed by:
synthetic resin insulating boxes reinforced with fibreglass;
anti-corrosion treatment of the main metallic parts;
galvanisation Fe/Zn (UNI ISO 2081), protected by a conversion layer without hexavalent
chromium (in conformity with the ROHS) with the same corrosion resistance guaranteed
by ISO 4520 class 2c;
application of anti-condensation protection for electronic overcurrent releases and
relative accessories.
7/3
1SDC210032D0204
Formula_07_glossario.indd 3
21/02/2011 9.43.10
Glossary
G2 - Performance Parameters
G2.1 Frame size
A term designating a group of circuit-breakers, the external physical dimensions of which
are common to a range of current ratings (considering the same number of poles). Frame
size is expressed in amperes corresponding to the highest current rating of the group.
G2.2 Rated current (In)
For the circuit-breakers the rated current represent the current which the circuit-breaker
can carry in uninterrupted duty.
G2.3 Rated service voltage (Ue)
The a rated service voltage of an equipment is the voltage value which, together with
the rated service current, determines the use of the equipment and which the applicable
tests and the utilization category refer to.
G2.4 Rated insulation voltage (Ui)
The rated insulation voltage of an equipment is the value of voltage to which dielectric
tests and the surface creepage distances are referred. In no case the maximum value
of the rated operating voltage shall exceed that of the rated insulation voltage.
G2.5 Rated impulse withstand voltage (Uimp)
The peak value of an impulse voltage of prescribed form and polarity which the equipment is capable of withstanding without failure under specified test conditions and to
which the clearance values are referred.
G2.6 Rated ultimate short-circuit breaking capacity (Icu)
The rated ultimate short-circuit breaking capacity of a circuit-breaker is the maximum
short-circuit current value which the circuit-breaker can break twice (in accordance with
the cycle O t CO), at the corresponding rated operational voltage. After the indicated
sequence the circuit-breaker is not required to carry its rated current.
G2.7 Rated service short-circuit breaking capacity (Ics)
The rated service short-circuit breaking capacity of a circuit-breaker is the maximum
short-circuit current value which the circuit-breaker can break three times in accordance with a sequence of opening, pause and closing operations (O - t - CO - t CO) at
a defined rated service voltage (Ue) and at a defined power factor. After the indicated
sequence the circuit-breaker is required to carry its rated current.
G2.8 Rated short-circuit making capacity (Icm):
The rated short-circuit making capacity of an equipment is the value, stated by the
manufacturer, at the rated service voltage, at rated frequency, and at a specified power
factor for alternating current or time constant direct current. It is expressed as the
maximum peak value of the prospective current under specified conditions.
7/4
1SDC210032D0204
Formula_07_glossario.indd 4
21/02/2011 9.43.10
Kategorie
Typical application
AC-12
AC-13
AC-14
AC-15
DC-12
DC-13
Control of electromagnets
DC-14
Alternating current
Direct current
7/5
1SDC210032D0204
Formula_07_glossario.indd 5
21/02/2011 9.43.10
Glossary
G3 - Releases and Protections
G3.1 Trip unit
Device, mechanically connected to a mechanical operating mechanism, which release
the latching parts and allows the opening or closing of the operating device.
G3.2 Thermomagnetic trip unit
Thermomagnetic trip units use a bimetal and an electromagnet to detect overloads
and short-circuits. They are suitable for protection of both alternating and direct current networks.
G3.3 Electronic trip unit
Trip units connected to current transformers (three or four according to the number
of conductors to be protected) positioned inside the circuit-breaker, which carry out
the double function of supplying the power supply needed for correct operation of the
release (self-supply) and of detecting the value of the current which flows through the
live conductors. However, they are only compatible with alternating current networks.
The signal coming from the transformers and from the Rogowsky coils is appropriately processed by the electronics (microprocessor) which compares it with the set
thresholds. When the signal exceeds the thresholds, the trip of the circuit-breaker is
operated through an opening solenoid which acts directly on the circuit-breaker operating mechanism unit.
In the case of an auxiliary power supply in addition to self-supply, the voltage must
have a value of 24V DC 20%.
G3.4 Thermal Protection L
Protection against overloads with long inverse time delay trip.
G3.5 Magnetic Protection I
Protection against short-circuit with instantaneous trip.
7/6
1SDC210032D0204
Formula_07_glossario.indd 6
21/02/2011 9.43.10
Glossary
G4 - Regulations and Standards
G4.1 Standards
Technical specification approved by a recognised organisation with the task of defining the state-of-the-art characteristics (dimensional, environmental, safety, etc.) of a
product or service.
G4.2 Directive
Ensemble of rules which define the essential requirements regarding safety which the
products must comply with in order to guarantee user safety.
G4.3 RoHS Directive
European Directive 2002/95/EC of 27 January 2003 (Dlgs 25 July 2005 no. 151)
which aims at eliminating or reducing the use of hazardous substances in electrical
and electronic apparatus.
It imposes manufacturers and companies to adapt to the relative prescriptions drawing