Binder 1
Binder 1
Panelboards
Catalog
2110CT9701R02/16
2016
Class 2110
CONTENTS
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page
Product Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 2
Features and Benefits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 6
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 7
General and Application Information . . . . . . . . . . . . . . . . . . . . . . . Page 8
Dimensions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 13
™
I-Line™ Circuit Breaker Panelboards
Product Description
Product Description
Standards
Standard Description
UL 50 Standard for enclosures for electrical equipment
UL 67 Standard for panelboards
CSA C22.2, Nos. 29 and 94—1989 Standard for panelboards and enclosed panelboards
NFPA 70 National Electrical Code (NEC)
NEMA PB 1 Standard for panelboards
W–P 115C Type 1 Class 1 Specification for circuit breaker panelboards
2000 IBC US standard for seismic requirements
1995 NBCC Canadian standard for seismic requirements
Service
Panelboard Types
Maximum
Maximum Mains Branch Circuit Enclosure
Ampacity Breaker Frame Dimensions b
Panelboard Size a
Type
Main
Width Depth
Main Lugs Circuit Left Right
IN (mm) IN (mm)
Breakers
8.25 (210)/
HCM 800 A 800 A JD JD 32 (813)
9.50 (241)
HCP-SU 800 A 800 A c MG, PG None 26 (600) 9.50 (241)
HCP 1200 A 800 A c MG, PG JD 42 (1067) 9.50 (241)
HCR-U 1200 A 1200 A c RG JD 44 (1118) 9.50 (241)
a For a complete listing of applicable circuit breaker types, refer to the dimensions section.
b Refer to the Dimensions section for standard panelboard heights.
c Available as a main circuit breaker panelboard when provided with a branch mounted back-fed
main circuit breaker.
Type HCP-SU
800 A Main Circuit Beaker Type HCM—400 A Main Lugs
3
02/2016 © 1998–2016 Schneider Electric
All Rights Reserved
™
I-Line™ Circuit Breaker Panelboards
Product Description
Enclosure Types
HCM, HCP, HCP-SU, and HCR-U surface and flush trims available as
four-piece construction, standard (door not included). An optional four-
piece trim with door is also available.
Fronts:
Finished with gray-baked enamel electrodeposited over cleaned
Type 1 phosphatized steel (ANSI 49).
Enclosures
Directory card holders provided with all fronts.
Types 1 and 2 Enclosure with Optional Door Galvanized steel in 26, 32, 42, and 44-inch (660, 813, 1067, and 1118
Boxes: mm) widths.
Removable endwalls without knockouts.
Gasketed door with vault handle and directory card holder.
Three-point latching.
4
02/2016 © 1998–2016 Schneider Electric
All Rights Reserved
™
I-Line™ Circuit Breaker Panelboards
Product Description
Solid Neutral
Full capacity bonding • Mounts in main lug or main circuit breaker compartment.
strap for use on service
entrance applications • Does not take up interior circuit breaker mounting space.
• UL/CSA Listed for use with Al or Cu conductors.
• Copper or aluminum neutral available.
Typical Solid Neutral
• 200% rated neutral available as a factory-assembled option.
5
© 1998–2016 Schneider Electric 02/2016
All Rights Reserved
™
I-Line™ Circuit Breaker Panelboards
Features and Benefits
Featured below are just a few of the many features and benefits of
Square D™-brand I-Line™ circuit breaker panelboards.
Circuit Breakers
I-Line circuit breakers, with their exclusive bus connection design, provide
superior reliability and performance advantages.
Circuit breaker
mounting
bracket—an
integral part of
each circuit
breaker; securely
supports and
aligns load end of
circuit breaker.
Push-to-Trip
Blow-On Connections
All circuit breaker connections are “blow-on” type. Under high-level short
Blow-On Connections circuit conditions, the magnetic forces developed tend to draw the connector
jaws together, gripping the I-Line bus bar more firmly.
6
02/2016 © 1998–2016 Schneider Electric
All Rights Reserved
™
I-Line™ Circuit Breaker Panelboards
Accessories
Accessories
I-Line Plug-On Unit with Surgelogic TVSS
A wide variety of accessories are available for field or factory installation of
I-Line panelboards.
Box Extensions
Box extensions provide additional end gutter for feeding cables into the end
of the cabinet; they are UL/CSA Listed.
Blank Fillers
Typical Box Extensions Blank fillers are required to cover unused mounting space in I-Line
panelboards.
Primarily for use in Canada, these barriers provide additional protection for
backfed main breakers.
7
© 1998–2016 Schneider Electric 02/2016
All Rights Reserved
™
I-Line™ Circuit Breaker Panelboards
General and Application Information
8
02/2016 © 1998–2016 Schneider Electric
All Rights Reserved
™
I-Line™ Circuit Breaker Panelboards
General and Application Information
Circuit Breaker Frame Size Ampere Rating Terminal Lug Wire Size
FA 100 A 15–30 #14-#4 Cu or #12-#4 Al
FA 100 A 35–100 #14-1/0 Cu or #12-1/0 Al
FH 100 A 15–30 #14-#4 Cu or #12-#4 Al
FH 100 A 35–100 #14-1/0 Cu or #12-1/0 Al
BD, BG, BJ 125 A 15–125 #14–2/0 Al/Cu
BK 125 A 15–30 #14–2/0 Al/Cu
HD, HG, HJ, HL, HR 150 A 15–150 #14-3/0 Al/Cu
QB, QB, QG, QJ 225 A 70–225 #4-300 kcmil Al/Cu
JD, JG, JJ, JL 250 A 150–175 #4/0 Al/Cu
JD, JG, JJ, JL, JR 250 A 200–250 #3/0-350 kcmil Al/Cu
(1) #1-600 kcmil or
LA, LH 400 A 125–400
(2) #1-250 kcmil Al/Cu
LD, LG, LJ, LL, LR 400 A 250 (1) #2-600 kcmil CU or (1) #2-500 kcmil AL
LD, LG, LJ, LL, LR 600 A 400–600 (2) #2-500kcmil AL/CU
MG, MJ 800 A 300–800 (3) 3/0-500 kcmil Al/Cu
PG, PJ, PKd, PL 1200 A 250–800 (3) 3/0-500 kcmil Al/Cu
PG, PJ, PKd, PL 1200 A 1000–1200 (4) 3/0-500 kcmil Al/Cu
RG, RJ, RKd, RL 1200 A 1000–1200 (4) 3/0-600 kcmil Al/Cu
NOTE: Lugs are rated for 75 °C wire, except FA (15–30 A) and FI (20–30 A), which are rated for 60/75 °C. Torque values are listed
on the circuit breaker faceplate tables.
d Canada only.
• Shunt trip
• Undervoltage trip
• Alarm switch
• Auxiliary contacts
• Ground-fault shunt trip
9
© 1998–2016 Schneider Electric 02/2016
All Rights Reserved
™
I-Line™ Circuit Breaker Panelboards
General and Application Information
NOTE: All accessories, except for the Ground-fault shunt trip are
field-installable for LA, LH circuit breakers.
For detailed information on circuit breakers and accessories, refer to the
Digest.
10
02/2016 © 1998–2016 Schneider Electric
All Rights Reserved
™
I-Line™ Circuit Breaker Panelboards
General and Application Information
MG, MJ
2- and 3-Pole; 300–800 A
11
© 1998–2016 Schneider Electric 02/2016
All Rights Reserved
™
I-Line™ Circuit Breaker Panelboards
General and Application Information
Main Lugs and Main Circuit Breaker Ratings and Lug Sizes
12
02/2016 © 1998–2016 Schneider Electric
All Rights Reserved
™
I-Line™ Circuit Breaker Panelboards
Dimensions
Dimensions
3/8 Dia.
Solid Neutral
When
Required
C
End of
Main Lugs D
E
22.00 8.25 Typical 4-Piece Trim
559 210
with Optional Door
Typical Box with Interior Typical Box Side View
Typical Endwall
5.00 5.00
127 127 Af
Bf
Cf
Typical Mounting of BD, BG, BJ, BK, FA, FH,
HD, HG, HJ, HL, HR, JD, JG, JJ, JL, JR, QB, QD, QG, QJ Typical Wiring Diagram
Circuit Breakers
Branch connection phasing is
determined by circuit breaker Typical 4-Piece Trim
INCHES selection. without Optional Door
Dual Dimensions: Millimeters
Catalog Number H A B C D E
Main
Lugs 4-Piece
Ampere Trim 4-Piece Trim
Interior Box in. mm in. mm in. mm in. mm in. mm in. mm
Rating without with Door ‡
Door ‡
HCM14482N b HC3248B HCM48T( ) HCM48T( )D 48.00 1219 13.50 343 30.00 762 21.85 555 14.43 367 9.30 236
HCM23642N HC3264B HCM64T( ) HCM64T( )D 64.00 1626 22.50 572 39.00 991 29.85 758 17.93 455 12.80 325
225
HCM32732N HC3273B HCM73T( ) HCM73T( )D a 73.00 1854 31.50 800 48.00 1219 22.90 582 17.93 455 12.80 325
HCM50912N HC3291B HCM91T( ) HCM91T( )D a 91.00 2311 49.50 1257 66.00 1676 28.90 734 17.93 455 12.80 325
HCM14484 b HC3248B HCM48T( ) HCM48T( )D 48.00 1219 13.50 343 30.00 762 21.85 555 14.90 378 9.30 236
HCM23644 HC3264B HCM64T( ) HCM64T( )D 64.00 1626 22.50 572 39.00 991 29.85 758 18.40 467 12.80 325
400
HCM32734 b HC3273B HCM73T( ) HCM73T( )D a 73.00 1854 31.50 800 48.00 1219 22.90 582 18.40 467 12.80 325
HCM50914 HC3291B HCM91T( ) HCM91T( )D a 91.00 2311 49.50 1257 66.00 1676 28.90 734 18.40 467 12.80 325
Continued on next page
13
© 1998–2016 Schneider Electric 02/2016
All Rights Reserved
™
I-Line™ Circuit Breaker Panelboards
Dimensions
Catalog Number H A B C D E
Main
Lugs 4-Piece
Ampere Trim 4-Piece Trim
Interior Box in. mm in. mm in. mm in. mm in. mm in. mm
Rating without with Door ‡
Door ‡
HCM14486 b HC3248B HCM48T( ) HCM48T( )D 48.00 1219 13.50 343 30.00 762 21.85 555 16.50 419 9.30 236
HCM23646 HC3264B HCM64T( ) HCM64T( )D 64.00 1626 22.50 572 39.00 991 29.85 758 20.00 508 12.80 325
600
HCM32736 b HC3273B HCM73T( ) HCM73T( )D a 73.00 1854 31.50 800 48.00 1219 22.90 582 20.00 508 12.80 325
HCM50916 HC3291B HCM91T( ) HCM91T( )D a 91.00 2311 49.50 1257 66.00 1676 28.90 734 20.00 508 12.80 325
HCM14488 HC3248B HCM48T( ) HCM48T( )D 48.00 1219 13.50 343 30.00 762 21.85 555 15.32 389 9.30 236
HCM23648 HC3264B HCM64T( ) HCM64T( )D 64.00 1626 22.50 572 39.00 991 29.85 758 18.82 478 12.80 325
800
HCM32738 HC3273B HCM73T( ) HCM73T( )D a 73.00 1854 31.50 800 48.00 1219 22.90 582 18.82 478 12.80 325
HCM50918 HC3291B HCM91T( ) HCM91T( )D a 91.00 2311 49.50 1257 66.00 1676 28.90 734 18.82 478 12.80 325
‡ Replace parentheses with “F” for flush or “S” for surface.
a Two flush locks are supplied.
b Add Cu to suffix for copper bus.
14
02/2016 © 1998–2016 Schneider Electric
All Rights Reserved
™
I-Line™ Circuit Breaker Panelboards
Dimensions
3/8 Dia.
C
A
D
E
22.00 8.25 Typical 4-Piece Trim
559 210
with Optional Door
Typical Box with Interior Typical Box Side View
Typical Endwall
5.00 5.00
127 127 Af
Bf
Cf
Typical Mounting of BD, BG, BJ, BK, FA, FH,
HD, HG, HJ, HL, HR, JD, JG, JJ, JL, JR, QB, QD, QG, QJ Typical Wiring Diagram
KA, KH, QB, QD, QG, QJ, or QO
Circuit Breakers Branch connection phasing is
determined by circuit breaker Typical 4-Piece Trim
selection. without Optional Door
Dual Dimensions: INCHES
Millimeters
15
© 1998–2016 Schneider Electric 02/2016
All Rights Reserved
™
I-Line™ Circuit Breaker Panelboards
Dimensions
3/8 Dia.
A Flush
51
Surface Mounting H
B H
Solid Neutral
When
Required
Service Entrance
Barrier
(Canada only)
End of C
Main Circuit
Breaker Lugs
D
E
22.00 9.50 Typical 4-Piece Trim
559 241
with Optional Door
Typical Box with Interior Typical Box Side View
Typical Endwall
5.00 5.00
127 127 Af
Bf
Cf
Typical Mounting of BD, BG, BJ, BK, FA, FH,
HD, HG, HJ, HL, HR, , JD, JG, JJ, JL, JR, QB, QD, QG, QJ Typical Wiring Diagram
Circuit Breakers
Branch connection phasing is
determined by circuit breaker
selection.
Dual Dimensions: INCHES
Millimeters
Typical 4-Piece Trim
without Optional Door
16
02/2016 © 1998–2016 Schneider Electric
All Rights Reserved
™
I-Line™ Circuit Breaker Panelboards
Dimensions
End of
Main Lugs
C
D
10.30
262
Typical Endwall
8.00 8.00 Af
203 203 Bf
Cf
Typical Mounting of BD, BG, BJ, BK, FA, FH,
HD, HG, HJ, HL, JD, JG, JJ, JL, LA, LD, LG, LJ, LL, LR, MG, MJ, Typical Wiring Diagram
PG, PJ, PK, PL, QB, QD, QG, QJ Branch connection phasing is
Circuit Breakers determined by circuit breaker
selection. Typical 4-Piece Trim
without Optional Door
INCHES
Dual Dimensions: Millimeters
17
© 1998–2016 Schneider Electric 02/2016
All Rights Reserved
™
I-Line™ Circuit Breaker Panelboards
Dimensions
27/64 Dia.
Vault
Lock
C
End of
Main Lugs
C
D
10.30
262
Typical Endwall
10.35 5.41 Af
263 137 Bf
Cf
18
02/2016 © 1998–2016 Schneider Electric
All Rights Reserved
™
I-Line™ Circuit Breaker Panelboards
Dimensions
Vault
C Lock
51
Surface Mounting H
Solid H
Neutral
When B
Required
Service Entrance
Barrier
(Canada only)
End of
Main Circuit
Breaker Lugs
C
10.30 D
262
30.00 9.50
762
241
Typical 4-Piece Trim
with Optional Door
Typical Box with Interior Typical Box Side View
Typical Endwall
8.00 8.30 Af
203 211 Bf
Cf
Typical Mounting of BD, BG, BJ, BK, FA, FH, Typical Wiring Diagram
HD, HG, HJ, HL, JD, JG, JJ, JL, LA, LD, LG, LJ, LL, LR, Branch connection phasing is
MG, MJ, PG, PJ, PK, PL, QB, QD, QG, QJ
determined by circuit breaker
Circuit Breakers selection.
INCHES
Dual Dimensions: Millimeters Typical 4-Piece Trim
without Optional Door
19
© 1998–2016 Schneider Electric 02/2016
All Rights Reserved
™
I-Line™ Circuit Breaker Panelboards
Dimensions
Service Entrance
Barrier
(Canada only) C
Directory
B
A
85.75
Flush 2178
H Lock Surface
Mounting
.25
(6)
S/
N
Typical Mounting of BD, BG, BJ, BK, FA, FH, A B C
HD, HG, HJ, HL, JD, JG, JJ, JL, LA, LD, LG, LJ, LL, LR, Front Center Rear
Bus Bus Bus
MG, MJ, PG, PJ, PK, PL, QB, QD, QG, QJ
Circuit Breakers
Af
Bf
Cf
10.30
262
Typical Endwall
S/
Flush Mounting 46.25 N
1175 A B C
Front Center Rear
Surface Mounting 44.25 Bus Bus Bus
1124
Af
11.04 5.25 Bf
280 133 Cf
Typical Mounting of BD, BG, BJ, BK, FA, FH, Typical Wiring Diagram
HD, HG, HJ, HL, JD, JG, JJ, JL, LA, LD, LG, LJ, LL, LR, Branch connection phasing is
MG, MJ, PG, PJ, PK, PL, QB, QD, QG, QJ, RG, RJ, RK, RL determined by circuit breaker
Circuit Breakers selection.
NOTE: The back-fed RG, RJ, and RL Main Circuit Breaker or Main Lugs Kit takes up 15 in. (381 mm) of mounting space, leaving 93 in. (2362 mm) of branch circuit
breaker mounting space. The back-fed PG, PJ, PL Main Circuit Breaker takes up 9 in. (229 mm) of mounting spaces, leaving 99 in. (2515 mm) of branch circuit
breaker mounting space.
21
© 1998–2016 Schneider Electric 02/2016
All Rights Reserved
™
I-Line™ Circuit Breaker Panelboards
22
02/2016 © 1998–2016 Schneider Electric
All Rights Reserved
™
I-Line™ Circuit Breaker Panelboards
23
© 1998–2016 Schneider Electric 02/2016
All Rights Reserved
™
Schneider Electric USA, Inc.
800 Federal Street Schneider Electric and Square D are trademarks owned by Schneider Electric Industries SAS or its
Andover, MA 01810 USA affiliated companies. All other trademarks are the property of their respective owners.
888-778-2733 2110CT9701R02/16 Replaces 2110CT9701R10/04
www.schneider-electric.us © 1998–2016 Schneider Electric All Rights Reserved
02/2016
NF Circuit Breaker Panelboards
Catalog
1670CT0701
2008
Class 1670
CONTENTS
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page
Standards and Ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Main Circuit Breakers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Branch Circuit Breakers (Bolt-on). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Interiors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Neutrals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Ground Bar Kits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Surge Protection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Enclosures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Single Row (Column-Width) Panelboards . . . . . . . . . . . . . . . . . . . . . . . . 16
Terminal Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Typical Wiring Diagrams. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
NF Circuit Breaker Panelboards
Standards and Ratings
Standards
208Y/120 Vac 3φ4W
NF circuit breaker panelboards are designed, manufactured, and tested to
comply with the following standards:
• UL 67—Standard for Panelboards
• UL 50—Enclosures for Electrical Equipment
3φ4W
240/120 Vac • UL Listed Class CTL panelboard
Delta
• CSA C22.2, No. 29-M1989—Panelboards and Enclosed Panelboards
• CSA C22.2, No. 94-M91—Special Purpose Enclosures
• NEMA PB 1—Panelboards
3φ3W
240 Vac
Delta
• NFPA 70—National Electrical Code® (NEC®)
• Federal Specification W-P-115C Type I Class 1—Circuit
Breaker Panelboards
3φ3W • 2003 IBC, NFPA 5000, ASCE/SE17—Seismic Qualification
240 Vac Grounded Bφ
Delta
Ratings
600Y/347 Vac 3φ4W
• Main lugs: 125–800 A
• Main circuit breaker: 125–600 A
3
© 2008 Schneider Electric 08/2008
All Rights Reserved
NF Circuit Breaker Panelboards
Main Circuit Breakers
Main Circuit Breakers
• 125 A maximum field-installable EDB, EGB, or EJB (110 A max at 600Y/347 Vac)
• 100 A maximum field-installable FI
• 125 A maximum field-installable HDL, HGL, HJL, or HLL
• 250 A maximum field-installable JDL, JGL, JJL, or JLL
• 400 A maximum field-installable LAL or LHL
• 400 A or 600 A maximum factory-installed LCL or LIL (LCL is 480Y/277 Vac maximum)
HDL
Factory-Installed Circuit Breaker Accessories
FIL, HDL, HGL, HJL, HLL, JDL, JGL, JJL, JLL, and KIL circuit breakers are available with shunt trip,
ground fault shunt trip, undervoltage trip, time delay, auxiliary switches, and alarm switches.
Table 1: Main Circuit Breaker Adapter Kits (Circuit Breaker Not Included)
JDL
NOTE: See “Main Circuit Breaker Terminal Data” on page 18.
Field-installable undervoltage release, alarm switch, shunt trip, and auxiliary contacts are available for
LAL, LHL, LCL, and LIL 400 A main circuit breaker interiors.
NOTE: See Supplemental Digest for additional accessories.
LAL
N250MJ Main Circuit Breaker Kit N400M Main Circuit Breaker Kit
4
08/2008 © 2008 Schneider Electric
All Rights Reserved
NF Circuit Breaker Panelboards
Branch Circuit Breakers (Bolt-on)
5
© 2008 Schneider Electric 08/2008
All Rights Reserved
NF Circuit Breaker Panelboards
Interiors
Interiors
Main Lug Interiors
6
08/2008 © 2008 Schneider Electric
All Rights Reserved
NF Circuit Breaker Panelboards
Interiors
Main Circuit Breaker Interiors
400 A Main Lugs Interior with 400 A Main Circuit Breaker and Adapter Kit
7
© 2008 Schneider Electric 08/2008
All Rights Reserved
NF Circuit Breaker Panelboards
Interiors
Field-Installable Options
• Feed-Through Lug Kits
— NF125FTL, NF250FTL, NF400FTL available for 125–400 A,
1φ or 3φ interiors
• Sub-Feed Circuit Breaker Kits
— NF250SFBH allows a single sub-feed HDL, HGL, HJL, or HLL circuit
breaker on 250 A interiors
— NF250SFBJ allows a single sub-feed JDL, JGL, JJL, or JLL circuit
breaker on 250 A interiors
— NF600SFBH allows twin sub-feed HDL, HGL, HJL OR HLL circuit
breaker on 400 A main lug or main circuit breaker interiors and 600A
main lug interiors
— N600SFBJ allows twin sub-feed JDL, JGL, JJL, or JLL circuit
breakers on 400 A main lug or main circuit breaker interiors and
600 A main lug interiors
• Sub-Feed Lug Kits
1
400 A Main Lug Interior with Sub-Feed Lugs 200% neutrals not available with FTL, SFL, or SFB.
Compression Lugs
Compression lugs are available for 125–600 A main lug interiors and
100–400 A main circuit breaker interiors.
Compression Lugs
8
08/2008 © 2008 Schneider Electric
All Rights Reserved
NF Circuit Breaker Panelboards
Neutrals
Neutrals
Neutral Assembly
The bonding strap may be field installed for UL service equipment requirements on 125–800 A
interiors. Not applicable for CSA service entrance panels in Canada.
Table 5: Copper 100% Neutral Kits for Use with Single or Three Phase 125-600 A Interiors
Table 6: 200% Neutral Kits for Use with Single or Three Phase 125-400 A Interiors
NFNL2
9
© 2008 Schneider Electric 08/2008
All Rights Reserved
NF Circuit Breaker Panelboards
Ground Bar Kits
• The insulator kit isolates the standard panelboard ground bar from
the panelboard
• The insulator kit is field installable, and panelboard enclosures have
ground bar mounting provisions in all four corners
Terminals
Approximate Distance Between
Catalog
Number of Quantity Available for Each Size Overall Length Mounting Holes
Number
Terminals Inches (mm) Inches (mm)
Material I / II1
PK23GTAL 24 AL 23 / 1 9.125 (232) 3.125 (79)
PK27GTA 27 AL 24 / 1 9.125 (232) 3.125 (79)
PK27GTACU 27 CU 27 / 0 9.125 (232) 3.125 (79)
1
See wire range table below.
Size Cu Al
I (1) #14 to #4 or (2) #14 or #12 (1) #12 to #4 or (2) #12 or #10
II (1) #1 to 4/0 (1) #1 to 4/0
10
08/2008 © 2008 Schneider Electric
All Rights Reserved
NF Circuit Breaker Panelboards
Surge Protection
Surge Protection
The Surgelogic® IMA series surge protective device is a modular parallel
transient voltage surge suppressor (TVSS). The IMA device is a multi-stage
suppression circuit consisting of field-proven, fast-acting, 34 mm metal oxide
varistors (MOVs).
Max Circuit TVSS Rating Components for Adding a Vertical Main Circuit Breaker
Mains Interior Catalog
Breaker
Rating Voltage Surge Rating Number2 Main Circuit Breaker Kit Main Circuit Breaker Frames
Spaces
120 NF442L2TVS412 N150MH3 HD, HG, HJ or HL
480Y/277 Vac
250 A 42 160 NF442L2TVS416 N250MJ JD, JG, JJ or, JL
600Y/347 Vac 120 NF442L2TVS812 N250MKC KI
120 NF442L4TVS412
480Y/277 Vac LAL/LHL
400 A 42 160 NF442L4TVS416 N400M
(LC and LI F/A only)
600Y/347 Vac 120 NF442L4TVS812
1 These interiors are available as catalog numbered devices. TVSS is not available as a field-installable kit.
2
To order an interior with copper bus, add a “C” to the end of the catalog number (example: NR442L2TVS412C).
3
RTI kit accepts maximum 125 A H-frame circuit breaker.
11
© 2008 Schneider Electric 08/2008
All Rights Reserved
NF Circuit Breaker Panelboards
Surge Protection
Option Description
Displays the combined total number of transient voltage surges detected from L–G, L–L, L–N,
Surge Counter
and N–G since the counter was last reset.
Displays the alarm status of the surge protective device up to 1,000 ft. (305 m) away from the
Remote Monitor
unit. This option uses the dry contacts.
Design Features
12
08/2008 © 2008 Schneider Electric
All Rights Reserved
NF Circuit Breaker Panelboards
Enclosures
Enclosures
Enclosure Types
MH type Box
• Standard boxes are 20 in. (508 mm) wide by 5.75 in. (223 mm) deep
• NF interiors with an LC or LI main circuit breaker or with an 800 A MLO interior require an
8.75 in. (223 mm) deep box — therefore, they are available factory-assembled and
fully-assembled only
• Boxes are galvanized steel with removable endwalls. On standard 5 3/4 inch depth boxes, one
endwall is provided with knockouts, and the other endwall is blank. On deeper boxes, both are
blank. Endwalls are removable and interchangeable
• Box and interior mounting instructions are included in the documentation shipped with the interior
• Keyhole slots are located in the box backwall to ease installation
NOTE: Interiors mount directly to studs in MH boxes. No interior mounting brackets are required.
NOTE: 800 A interiors and interiors that have LC/LI main circuit breakers require elevating
brackets, due to the requirement of an 8.75 in. (223 mm) deep box.
• Type 2 boxes include a drip hood (available with surface mounted trim only)
13
© 2008 Schneider Electric 08/2008
All Rights Reserved
NF Circuit Breaker Panelboards
Enclosures
• Finished with gray-baked enamel electrodeposited over cleaned, phosphatized steel (ANSI 49)
• Order flush or surface mounted
• Door with flush lock; uses NSR-251 key
• Directory card located on the inside of the door
• Mono-Flat® fronts on 100–250 A interiors mount to the interior trim with trim screws. Both trim
mounting screws and door hinges are concealed; fronts are not removable with the door closed
and locked
• Fronts for 400–800 A interiors are ventilated and mount to the enclosure with trim screws; door
hinges are concealed
• Fronts 56 in. (1422 mm) high or more on 250 A interiors or 74 in. (1880 mm) high or more on 600 A
and 800 A interiors have two flush locks
• Fronts 68 in. (1727 mm) high or more on interiors with LC/LI main circuit breakers or LC sub-feed
circuit breakers use a sliding vault lock with 3-point latching
Key NSR-251 Concealed Hinge for 100–800 A Trim Fronts Interiors Mount Directly to Enclosure Studs
(Catalog No. LP9618)
Standard Flush Lock Optional Sliding Vault Lock (Catalog No. PK5FL) MH Box
(Catalog No. PK4FL)
14
08/2008 © 2008 Schneider Electric
All Rights Reserved
NF Circuit Breaker Panelboards
Enclosures
Rainproof (Type 3R) Dust tight (Type 5 and 12)
15
© 2008 Schneider Electric 08/2008
All Rights Reserved
NF Circuit Breaker Panelboards
Single Row (Column-Width) Panelboards
Ratings
Interiors
Column-Width Enclosures
Panelboard
• 8-5/8 in. (219 mm) wide by 5-5/8 in. (143 mm) deep for 10 in. (254 mm) H- or I-beam
• Galvanized steel
• Removable endwalls
Trim Fronts
• Screw mounted
• Door with two flush latches
• Finish: gray-baked enamel electrodeposited over cleaned, phosphatized steel
Line Lugs
16
08/2008 © 2008 Schneider Electric
All Rights Reserved
NF Circuit Breaker Panelboards
Single Row (Column-Width) Panelboards
Cable Trough
Pull Box
(catalog number MPX81542)
17
© 2008 Schneider Electric 08/2008
All Rights Reserved
NF Circuit Breaker Panelboards
Terminal Data
Terminal Data
Aluminum Copper
Aluminum
Aluminum Mechanical Copper Mechanical Copper Compression
Amperes Compression
Panelboard Ampere
Circuit Breaker Type Lug Wire Range
Type Rating
100 A FIL (1) #14-1/0 Cu or (1) #12-1/0 Al
125 A1 EDB, EGB, EJB (1) #14-2/0 Al/Cu
150 A HDL, HGL, HJL, HLL (1) #14-3/0 Al/Cu
NF 250 A JDL, JGL, JJL, JLL, KI (1) 3/0-350 kcmil Al/Cu
400 A LAL, LHL (1) #1-600 kcmil Al/Cu or (2) #1-250 kcmil Al/Cu
600 A LCL, LIL, LEL, LXL LXIL (2) 4/0-500 kcmil Al/Cu
800 A 800 A main breaker panelboard not available.
1
110 A maximum at 600Y/347 Vac.
Panelboard Ampere
Circuit Breaker Type Catalog No. Lug Wire Range
Type Rating
100 A FC, FI VC100FA (1) #8-1/0 Al/Cu
125 A1 ED, EG, EJ VC100FD (1) #8-1/0 Al/Cu
150 A HDL, HGL, HJL, HLL YA150HD (1) #1–4/0 Al/Cu
250 A JDL, JGL, JJL, JLL YA250J35 (1) 3/0–350 kcmil Al/Cu
NF
250 A KI VC250KA3 (1) #4-300 kcmil Al/Cu
400 A LA, LH VC400LA52 (1) 2/0-500 kcmil Al/Cu
600 A LC, LI, LE, LX, LXI — —
800 A 800 A main breaker panelboard not available.
1
110 A maximum at 600Y/347 Vac.
2
Other lug sizes available.
18
08/2008 © 2008 Schneider Electric
All Rights Reserved
NF Circuit Breaker Panelboards
Typical Wiring Diagrams
S S
S S S S N N
N N N N
125–250 A Main Lugs 125 A EDB Main Circuit Breaker 100–250 A Main Circuit Breaker
(110 A max. at 600/347 Vac) Types FIL, HDL, HGL, HJL, HLL,
JDL, JGL, JJL, JLL, KIL
S/N
S/N
1-Phase, 3-Wire
S S
S S S S
N N
N N N N
125–250 A Main Lugs 125 A EDB Main Circuit Breaker 100–250 A Main Circuit Breaker
(110 A max. at 600/347 Vac) Types FIL, HDL, HGL, HJL, HLL,
JDL, JGL, JJL, JLL, KIL
S/N
S/N
3-Phase, 4-Wire
19
© 2008 Schneider Electric 08/2008
All Rights Reserved
Schneider Electric USA Schneider Electric Canada "Surgelogic", "Mono-Flat", and "I-Limiter" are trademarks or registered trademarks of
252 North Tippecanoe 19 Waterman Avenue, Schneider Electric and/or its affiliates in the United States and/or other countries. Other
Peru, IN 46970 USA M4B 1 Y2 marks used herein may be the property of their respective owners.
1-888-SquareD Toronto, Ontario
(1-888-778-2733) 1-800-565-6699 1670CT0701 © 2008 Schneider Electric All Rights Reserved
www.us.SquareD.com www.schneider-electric.ca Replaces 1670CT0701 dated 03/2008
08/2008
NQ Circuit Breaker Panelboards
Catalog
1640CT0801
2008
Class 1640
CONTENTS
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page
Standards and Ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 3
Interiors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 4
Branch Circuit Breakers (Bolt-On) . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 8
Neutrals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 10
Ground Bar Kits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 12
Surge Protection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 13
Enclosures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 15
Single Row (Column-Width) Panelboards . . . . . . . . . . . . . . . . . . . . Page 17
Typical Wiring Diagrams. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 18
NQ Circuit Breaker Panelboards
Standards and Ratings
Ratings
3
© 2008 Schneider Electric 12/2008
All Rights Reserved
NQ Circuit Breaker Panelboards
Interiors
Interiors
4
12/2008 © 2008 Schneider Electric
All Rights Reserved
NQ Circuit Breaker Panelboards
Interiors
Main Circuit Breaker Adapter Kits Table 1: Main Circuit Breaker Adapter Kits
(Order Circuit Breaker Separately)
Catalog No. Ampere Rating Main Circuit Breaker
A B
C
NQMB2Q 100–225 A QBL, QDL, QGL, QJL
NQMB2HJ 100–225 A HDL, HGL, HJL, HLL, JDL, JGL, JJL, JLL
NQMB2KI 110–225 A KIL
NQMB4LA 125–400 A LAL, LHL
MAIN
Main circuit breakers are not included in the adapter kits, order separately.
PRINCIPAL
H 80
80
11
G
E
8
0
1
2
8
0
1
1
0
11
0-
32
0-
32
7-
03
Table 2: Main Circuit Breakers
F 2
-1
2
-3
2
7
7-
03
5 -0
-0
1 3
Field-installable shunt trip, alarm switch, and auxiliary contacts are available
for LAL 400 A main circuit breaker interiors. Refer to the Square D Digest
for additional information.
5
© 2008 Schneider Electric 12/2008
All Rights Reserved
NQ Circuit Breaker Panelboards
Interiors
Interior Accessories
• 100 A (NQSFL1)
• 225 A (NQSFL2)
• 400 A (NQSFL4)
NOTE: Refer to the Digest for the correct box size.
Factory-Installed Options
• Sub-Feed Lugs are available on 1φ or 3φ, 100–400 A main lug interiors only.
• Feed-Through Lugs are available on 1φ or 3φ 225–600 A main lug, or 225–600 A main circuit breaker
interiors.
• Sub-Feed Circuit Breakers
— Available on 1φ or 3φ main lugs 225–600 A, or main circuit breaker interiors 225–600 A.
— One sub-feed circuit breaker for each 225 A panelboard.
— Two sub-feed circuit breakers for each 400–600 A panelboard.
— Sub-feed circuit breakers may be type HDL, HGL, HJL, HLL, QBL, QDL, QGL, QJL, JDL, JGL,
JJL, OR JLL circuit breakers.
7
© 2008 Schneider Electric 12/2008
All Rights Reserved
NQ Circuit Breaker Panelboards
Branch Circuit Breakers (Bolt-on)
8
12/2008 © 2008 Schneider Electric
All Rights Reserved
NQ Circuit Breaker Panelboards
Branch Circuit Breakers (Bolt-on)
QO arc-fault circuit breakers provide branch feeder protection (i.e., QO115AFI) or combination
protection (i.e. QO115CAFI) as required by the NEC and local code adoption, and comply with
UL 1699.
NOTE:
• Lugs suitable for 75° C wire.
• Torque QOB connector mounting screws to 18–21 lb-in.
• Torque labels are included on the circuit breakers with load side lug torque requirements.
1
HACR type for use with air conditioning, heating and refrigeration equipment having motor group combinations and marked for
use with HACR type circuit breakers.
9
© 2008 Schneider Electric 12/2008
All Rights Reserved
NQ Circuit Breaker Panelboards
Neutrals
Neutrals
• All lugs suitable for copper or aluminum wire.100–600 A interiors have split neutral located on
same end as mains.
• Bondable for use as service entrance (in Canada, available as factory-assembled only).
• Branch terminals suitable for #12-#4 aluminum and #14-#4 copper.
• Provisions for larger branch terminal lugs with use of auxiliary neutral lugs.
• Suitable lug provided on neutrals for termination of grounding conductor.
• All unused neutral terminals may be used to terminate equipment grounding conductors when
panelboard is used as service entrance.
• 100% rated neutrals. One neutral termination provided per circuit in panelboard.
• 200% rated neutrals are available as factory-assembled options or as kits.
10
12/2008 © 2008 Schneider Electric
All Rights Reserved
NQ Circuit Breaker Panelboards
Neutrals
Lugs are suitable for copper or aluminum wire and are field-installable on
neutral assembly.
400 A 600 A
11
© 2008 Schneider Electric 12/2008
All Rights Reserved
NQ Circuit Breaker Panelboards
Ground Bar Kits
The insulator kit is field installable and may be used with equipment ground
bar kits. NQ panelboard enclosures have equipment ground bar mounting
provisions in all four corners.
Terminals
Distance Between
Qty Each Size (For Wire Range Approximate Overall Length
Catalog Number Total Qty Mounting Holes
see Table 16:) in (mm)
in (mm)
I II
PK23GTAL 24 23 1 9.125 (232) 3.125 (79)
PK27GTA 27 27 — 9.125 (232) 3.125 (79)
PK27GTACU 27 27 — 9.125 (232) 3.125 (79)
Size Cu Al
I (1) #14 to #4 or (2) #14 or #12 (1) #12 to #4 or (2) #12 or #10
II (1) #1 to 4/0 (1) #1 to 4/0
12
12/2008 © 2008 Schneider Electric
All Rights Reserved
NQ Circuit Breaker Panelboards
Surge Protection
Surge Protection
The Surgelogic™ IMA series surge protective device is a modular parallel transient voltage surge
suppressor (TVSS). The IMA device is a multi-stage suppression circuit consisting of field-proven, fast-
acting, 34 mm metal oxide varistors (MOVs). A surge suppression path is provided for each mode,
line-to-neutral (L-N), line-to-line (L-L), line-to-ground (L-G), and neutral-to-ground (N-G). Each surge
suppression mode is individually fused and uses circuitry with thermal cutouts to isolate the TVSS and
ensure shutdown in the event of MOV damage during severe overvoltages, even when operated on
high fault current power systems. The suppression elements are encapsulated in a UL recognized
potting material—another performance element that provides additional protection. A filter provides a
high level of EMI/RFI noise attenuation. On-line diagnostics continuously monitor the device status,
and LEDs signal loss of a suppression circuit. An audible alarm with an enable/disable feature and dry
contacts are included in the standard diagnostic package.
13
© 2008 Schneider Electric 12/2008
All Rights Reserved
NQ Circuit Breaker Panelboards
Surge Protection
Option Description
Displays the combined total number of transient voltage surges detected from
Surge Counter
L–G, L–L, L–N, and N–G since the counter was last reset.
Displays the alarm status of the surge protective device up to 1,000 ft (305 m) away from the unit.
Remote Monitor
This option uses the dry contacts.
Design Features
14
12/2008 © 2008 Schneider Electric
All Rights Reserved
NQ Circuit Breaker Panelboards
Enclosures
Enclosures
Boxes (MH):
• Galvanized steel with removable endwalls. One is provided with
knockouts and the other is blank.
• Standard box sizes:
— 20 in. (508 mm) wide x 5.75 in. (146 mm) deep,
600 A main lug interior max. or 400 A main circuit breaker max
— 20 in. (508 mm) wide x 8.75 in. (223 mm) deep,
600 A main circuit breaker interior, factory-assembled only
• Box and interior mounting instructions are found in the information
Mono-Flat Front
Front (Type 1) Enclosure (Type 1 Enclosure)
manual shipped with the interior.
for 400–600 A Interiors for 100–250 A Interiors • Interiors mount directly to studs in the MH box. Interior mounting
Indoor Enclosures brackets are not required.
• Type 2 enclosure includes a driphood.
— Surface-mounted trim only.
NOTE: Also available with knockouts / blank endwalls both ends.
Trims:
Flush Lock (standard)
(Catalog No. PK4FL) • Finished with gray baked enamel electrodeposited over cleaned
phosphatized steel (ANSI 49).
• Flush or surface mounted (Type 2 surface only).
Key NSR-251 • Door has flush lock. Uses NSR-251 key.
(Catalog No. LP9618)
• Directory card located on the inside of the door.
• Mono-Flat® trims on 100–225 A interiors mount to the interior trim with
Sliding Vault Lock (optional) trim screws. Both trim screws and door hinges are concealed. Trims are
(Catalog No. PK5FL) not removable with the door closed and locked.
• Trims for 400–600 A interiors are vented and mount to the enclosure
Concealed Hinge
with trim screws. Door hinges are concealed.
Used on 100–600 A Fronts • Optional hinged trims are available. These meet door-in-door specs.
Indoor Enclosure Accessories
15
© 2008 Schneider Electric 12/2008
All Rights Reserved
NQ Circuit Breaker Panelboards
Enclosures
Rainproof (Type 3R) and
Dusttight (Type 5 and 12) Enclosures
Corrosion-Resistant Fiberglass-Reinforced
Polyester Enclosures (Type 4X)
Corrosion-Resistant Fiberglass-Reinforced
Polyester Enclosure
Stainless Steel Enclosures (Type 4 and 4X)
Cable Trough
• Stackable
• 8.625 in. (219 mm) wide by 5.00 in. (127 mm) deep for 10” WF Beams
• Galvanized steel trough uses enclosure end wall
• Two-piece front trim
— 15 in. (381mm) long top piece of front trim removable for pull box mounting
• Finish: gray-baked enamel electrodeposited over cleaned, phosphatized steel
• Cable troughs are standard with a trough barrier
Pull Box
17
© 2008 Schneider Electric 12/2008
All Rights Reserved
NQ Circuit Breaker Panelboards
Typical Wiring Diagrams
S S
N N
S S S S
N N N N
100–225 A Main Lugs 100 A QOB Main Circuit Breaker 70–225 A Main Circuit Breaker
Types QBL, JDL, HDL
S/N S/N
1-Phase, 3-Wire
S S
N N
S S S S
N N N N
100–225 A Main Lugs 100 A QOB Main Circuit Breaker 70–225 A Main Circuit Breaker
Types QBL, JDL, HDL
S/N S/N
3-Phase, 4-Wire
18
12/2008 © 2008 Schneider Electric
All Rights Reserved
Notes
Notes
Notes
Notes
Schneider Electric USA Schneider Electric Canada
252 North Tippecanoe 19 Waterman Avenue,
Peru, IN 46970 USA M4B 1 Y2
1-888-SquareD Toronto, Ontario
(1-888-778-2733) 1-800-565-6699 1640CT0801 © 2008 Schneider Electric. All Rights Reserved.
www.schneider-electric.us www.schneider-electric.ca
12/2008
Surgelogic SurgeLoc
Advanced power and equipment protection
For Square D NQ panelboards
Surgelogic SurgeLoc
Utility industry experts estimate that power quality problems, including those
resulting from transient voltage surges, cost North American companies a
stunning $80 billion annually. That figure not only includes the high price of
direct damage to electrical distribution systems, electronic equipment, software,
and tools, but also the crippling cost of lost productivity. Facility downtime, lost
data, lost orders, and the disruption of critical processes can seriously reduce
productivity. Minimizing the risk of damage from electrical surges is an absolute
priority for companies of all types.
The Square D Surgelogic brand is a 30-year pioneer in the surge protective
device industry. Building on a history and reputation for reliability, Surgelogic
SurgeLoc surge protective devices exceed competitor brands with outstanding
specifications in a compact device.
billion
annually
The estimated cost of power quality problems
for North American companies
Easy installation, space-saving,
money-saving design
Setting a new standard for commercial internal surge
mounted devices, the Square D Surgelogic™ product line
from Schneider Electric™ has revolutionized commercial
surge protection with the new SurgeLoc product.
Engineered with input from contractors and specifiers, the innovative
SurgeLoc device saves time and money normally required when SPDs
are factory-installed on any project.
Installs in two minutes or less, a significant reduction from the
typical 20 minutes.
Specifications:
Surge Modes of
Model Number Voltage Protection Type I(n) SCCR VPR
Current
SSP01BIA08PBQ1 120 / 240 V 80 kA 6 1 20 kA 200 kA 700 L-N, L-G, N-G / 1200 L-L
SSP02BIA08PBQ1 208 Y / 120 V 80 kA 10 1 20 kA 200 kA 700 L-N, L-G, N-G / 1200 L-L
SSP03BIA08PBQ1 240 / 120 HLD 80 kA 10 1 20 kA 200 kA 700 L-N, L-G, N-G / 1200 L-L, H-N, H-L, H-G
SSP01BIA10PBQ1 120 / 240 V 100 kA 6 1 20 kA 200 kA 700 L-N, L-G, N-G / 1200 L-L
SSP02BIA10PBQ1 208 Y / 120 V 100 kA 10 1 20 kA 200 kA 700 L-N, L-G, N-G / 1200 L-L
SSP03BIA10PBQ1 240 / 120 HLD 100 kA 10 1 20 kA 200 kA 700 L-N, L-G, N-G / 1200 L-L, H-N, H-L, H-G
SSP01BIA12PBQ1 120 / 240 V 120 kA 6 1 20 kA 200 kA 700 L-N, L-G, N-G / 1200 L-L
SSP02BIA12PBQ1 208 Y / 120 V 120 kA 10 1 20 kA 200 kA 700 L-N, L-G, N-G / 1200 L-L
SSP03BIA12PBQ1 240 / 120 HLD 120 kA 10 1 20 kA 200 kA 700 L-N, L-G, N-G / 1200 L-L, H-N, H-L, H-G
SSP01BIA16PBQ1 120 / 240 V 160 kA 6 1 20 kA 200 kA 700 L-N, L-G, N-G / 1200 L-L
SSP02BIA16PBQ1 208 Y / 120 V 160 kA 10 1 20 kA 200 kA 700 L-N, L-G, N-G / 1200 L-L
SSP03BIA16PBQ1 240 / 120 HLD 160 kA 10 1 20 kA 200 kA 700 L-N, L-G, N-G / 1200 L-L, H-N, H-L, H-G
SSP01BIA20PBQ1 120 / 240 V 200 kA 6 1 20 kA 200 kA 700 L-N, L-G, N-G / 1200 L-L
SSP02BIA20PBQ1 208 Y / 120 V 200 kA 10 1 20 kA 200 kA 700 L-N, L-G, N-G / 1200 L-L
SSP03BIA20PBQ1 240 / 120 HLD 200 kA 10 1 20 kA 200 kA 700 L-N, L-G, N-G / 1200 L-L, H-N, H-L, H-G
SSP01BIA24PBQ1 120 / 240 V 240 kA 6 1 20 kA 200 kA 700 L-N, L-G, N-G / 1200 L-L
SSP02BIA24PBQ1 208 Y / 120 V 240 kA 10 1 20 kA 200 kA 700 L-N, L-G, N-G / 1200 L-L
SSP03BIA24PBQ1 240 / 120 HLD 240 kA 10 1 20 kA 200 kA 700 L-N, L-G, N-G / 1200 L-L, H-N, H-L, H-G
Unmatched surge suppression.
Unequaled experience.
With the rapid growth of the internet and web-hosting facilities,
and an explosion in the use of sensitive electronic equipment
and controls in manufacturing plants, offices, hospitals, and
water/wastewater facilities, there is a universal demand for
reliable power. Schneider Electric is the world’s leader in power
protection. From residential surge circuit breakers to large
commercial surge protection, Square D Surgelogic brand
products are dedicated to advancing technology to safely
deliver and control electrical power for all of our customers
around the world.
Take the next step to dependable power and equipment security with SurgeLoc surge protective
©2013 Schneider Electric. All Rights Reserved. Schneider Electric, Square D, and Surgelogic are trademarks owned by Schneider Electric
devices. Whatever your requirements for products are, Schneider Electric has a solution to meet
your needs. For more information, call us at 1-800-577-7353.
Industries SAS or its affiliated companies. All other trademarks are property of their respective owners. 998-1218717_US
Snap this QR code to access
the Surgelogic website.
Schneider Electric USA Schneider Electric Canada, Inc. Schneider Electric México, S.A. de C.V.
1751 South 4800 West 5985 McClaughlin Road Calz. J. Rojo Gómez 1121-A
Salt Lake City, UT 84104 Mississauga, Col. Gpe. del Moral
Tel: 801-977-9009 Ontario L5R 1B8 09300 México, D.F.
Fax: 801-977-0200 Tel: 1-800-565-6699 Tel. 55-5804-5000
www.schneider-electric.com/us www.schneider-electric.com/ca www.schneider-electric.com/mx
Catalog
1310CT0201R05/09
2009
Class 1310
CONTENTS
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page
Product Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Application Information. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Selection and Specifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Replacement Parts. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Dimensions and Weights . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Surgelogic® Surge Protective Device
Product Description
Product Description
Design Features
2
06/2009 © 2009 Schneider Electric
All Rights Reserved
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Surgelogic® Surge Protective Device
Application Information
Application Information
The effects of lightning and the damage caused by lightning-generated transients are well known. The
failure of electronic equipment in a facility located in a high lightning area can easily be attributed
directly to lightning-generated transients. Transient protection can be installed on the power
distribution system to protect this equipment from these externally generated transients. Lower
magnitude transients generated within a facility and their effect on microprocessor-based equipment
are less obvious than the transients induced by lightning. Transient voltage generated from inductive
motors, pumps, electric welders, etc., may not be large enough to cause immediate damage, but they
can cause equipment to malfunction.
A damaging transient voltage can enter a facility from several locations. The highest level of protection
should be provided at the service entrance. A second level of protection should be provided at
distribution points serving critical areas, for example, computer rooms, accounting areas, and
laboratories. Other facility entry points that should be protected include panels serving outdoor lights,
or outdoor equipment such as motors. Protection should also be provided for critical areas with
equipment essential to the company.
Square D® brand SPD products offered by Schneider Electric provide protection at every level of the
electrical distribution system. Typical applications include:
3
© 2009 Schneider Electric 06/2009
All Rights Reserved
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Surgelogic® Surge Protective Device
Selection and Specifications
The model number format consists of: Device Type, Voltage Code, SPD
FC 4 IMA 16 C
Model, Surge Current Rating Code, and Option Code. The possible device
types and codes are shown in the tables below.
Option Code
In the example at left, FC4IMA16C is an integral suppressor for 480Y/ 277 Vac
Surge Current Rating Code
3-phase 4-wire 160 kA surge capacity with surge counter.
SPD Model (IMA only)
Voltage Code Specifications
Device Type
Interrupting Rating
Device Continuous
Type at 240 Vac at 480 Vac at 600Y/347 Vac Current Rating
FC 100 kA 65 kA — 60 A
FI 200 kA 200 kA 100 kA 60 A
Per Mode
Surge Current Rating Code Per Phase
L–N L–G N–G
12 120 kA 60 kA 60 kA 120 kA
16 160 kA 80 kA 80 kA 120 kA
24 240 kA 120 kA 120 kA 120 kA
4
06/2009 © 2009 Schneider Electric
All Rights Reserved
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Surgelogic® Surge Protective Device
Selection and Specifications
Partial
Catalog Voltage Service L–N L–G N–G L–L MCOV▲
Number
FC1IMA 120/240 Vac,
400 400 400 800 150
FI1IMA 1-phase, 3-wire
FC2IMA 208Y/120 Vac,
400 400 400 800 150
FI2IMA 3-phase, 3- or 4-wire
240/120 Vac,
FC3IMA
3-phase, 4-wire 800/400 800/400 400 1500/800 275/150
FI3IMA
(high leg Delta)
FC4IMA 480Y/277 Vac,
800 800 800 1600 320
FI4IMA 3-phase, 3- or 4-wire
FC7IMA 380Y/220 Vac
800 800 800 1600 320
FI7IMA 3-phase, 3- or 4-wire
600Y/347 Vac,
FI8IMA ■ 1200 1200 1200 2000 420
3-phase, 3- or 4-wire
Surgelogic® I-Line® Plug-on SPD Unit ▲ MCOV = Maximum Continuous Operating Voltage.
■ Not available as FC device.
Feature Description
Relative humidity: 0 to 95% non condensing
Operating frequency: 47–63 Hz
Environmental
Surge suppression operating temperature: -40–+65 °C (-40–+149 °F) ✪
Storage temperature: -40–+65 °C (-40–+149 °F)
UL 1449, Second Edition, UL 1283
Compliance
standards cULus Listed as a circuit breaker in compliance with UL 489/CSA C22.2 No. 0.5
(SPD unit only)
Meets 2002 NEC® Article 285.6
Fused
suppression Fused with individual surge-rated fuses (200 kAIR)
paths
Thermal
Thermal cutout for low current faults
protection
On-line test functions
Diagnostics Indication per phase
Service indicator shown on the front panel of each SPD unit
5
© 2009 Schneider Electric 06/2009
All Rights Reserved
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Surgelogic® Surge Protective Device
Replacement Parts
Replacement Parts
MA Module Replacements
Surgelogic® Device
Mounted in Panel with
4-Piece Trim Installed
6
06/2009 © 2009 Schneider Electric
All Rights Reserved
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Surgelogic® Surge Protective Device
Dimensions and Weights
7
© 2009 Schneider Electric 06/2009
All Rights Reserved
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Schneider Electric USA Schneider Electric Canada
1601 Mercer Road 19 Waterman Avenue,
Lexington, KY 40511 USA M4B 1 Y2
1-888-SquareD Toronto, Ontario
(1-888-778-2733) 1-800-565-6699 1310CT0201R05/09 © 2009 Schneider Electric All Rights Reserved
www.schneider-electric.us www.schneider-electric.ca Replaces 1310CT0201R5/07 dated May 2007.
06/2009
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Product data sheet SSP02EBA24
Characteristics Surge Protect - EBA - 240kA - 208Y/120VAC -
3P4W - T1
Product availability : Stock - Normally stocked in distribution facility
Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Main
Product Surge protection device
Device Short Name EBA
Complementary
Surge Current 240 kA
System Voltage 208Y/120 V AC
Phase 3 phases
Wiring Configuration 4-wire
Connection Wire AWG 10 copper
MCOV 150 V
SCCR 200 kA
Local Signalling Status LED, green = normal operation per phase
Status LED, red = fault per phase
Provided Equipment Surge counter
Alarm enable/disable switch
Dry contacts
Device Mounting Surface
Height 13.32 in (338.3 mm)
Width 5.74 in (145.8 mm)
Depth 4.42 in (112.3 mm)
Environment
Enclosure Rating NEMA 1
Enclosure Material Painted sheet steel, colour : grey
Standards UL 1283
UL 96A ed. 12
UL 1449 ed. 4
CSA C22.2 No 8
Ambient Operating 104 °F (40 °C)
Offer Sustainability
California proposition 65 WARNING: This product can expose you to chemicals including:
- - - - - - - Substance 1 DINP which is known to the State of California to cause cancer and
- - - - - - - Substance 2 DIDP which is known to the State of California to cause birth defects or other reproductive harm.
- - - - - - - More information For more information go to www.p65warnings.ca.gov
2
2D Drawing Index 09/19/2018 22:19:54
Project #97321: 3ER PUENTE NEMA4X 304
Item# Designation Material Qty Description Drawing(s)
1 TUPSW,TU NQ ML 2 NQ Panelboard O97321-0001-01-1.PDF
PSE PNLB
(INT,ENCL)
2 TPSA, NQ ML 2 NQ Panelboard O97321-0002-01-1.PDF
TPSB PNLB
(INT,ENCL)
3 TAB 4CH NF ML 1 NF Panelboard O97321-0003-01-1.PDF
PNLB
(INT,ENCL)
4 TAB 4D NF ML 1 NF Panelboard O97321-0004-01-1.PDF
PNLB
(INT,ENCL)
5 TAB 4AB NF ML 1 NF Panelboard O97321-0005-01-1.PDF
PNLB
(INT,ENCL)
6 TAB C NQ MB 1 NQ Panelboard O97321-0006-01-1.PDF
PNLB
(INT,BOX,F
RT)
7 TAB A, B NQ MB 2 NQ Panelboard O97321-0007-01-1.PDF
PNLB
(INT,ENCL)
8 4PLC0 NF MB 1 NF Panelboard O97321-0008-01-1.PDF
PNLB
(INT,ENCL)
9 4PLCE NF MB 1 NF Panelboard O97321-0009-01-1.PDF
PNLB
(INT,ENCL)
10 4TL NF MB 1 NF Panelboard O97321-0010-01-1.PDF
PNLB
(INT,BOX,F
RT)
11 4MDPB NF MB 1 NF Panelboard O97321-0011-01-1.PDF
PNLB
(INT,ENCL)
12 4MDPA ILINE MB 1 I-Line Panelboard O97321-0012-01-1.PDF
PNLB
(INT,ENCL)
13 4MDP ILINE MB 1 I-Line Panelboard O97321-0013-01-1.PDF
PNLB
(INT,BOX,F O97321-0013-01-2.PDF
RT)
Product data sheet HC4286WP
Characteristics HCP 42 INCH WIDE by 86 INCH HIGH
TYPE3R/12 I-LINE PANELBOARD ENCLOSURE
Product availability : Stock - Normally stocked in distribution facility
Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Main
Range of product I-Line
Product or component type Enclosure
Device application Panelboard
Device short name HCP
Complementary
Line Rated Current 800 A
1200 A
400 A
600 A
Enclosure nominal width 1067 mm
Enclosure nominal height 2184 mm
Enclosure nominal depth 241 mm
Environment
NEMA degree of protection NEMA 3R/12
Standards CSA
UL
Offer Sustainability
Sustainable offer status Green Premium product
RoHS (date code: YYWW) Compliant - since 1419 - Schneider Electric declaration of conformity
Schneider Electric declaration of conformity
REACh Reference not containing SVHC above the threshold
Reference not containing SVHC above the threshold
Product environmental profile Available
Product end of life instructions Need no specific recycling operations
California proposition 65 WARNING: This product can expose you to chemicals including:
- - - - - - - Substance 1 Nickel compounds, which is known to the State of California to cause cancer, and
- - - - - - - Substance 2 Bisphenol A (BPA), which is known to the State of California to cause birth defects or other
reproductive harm.
- - - - - - - More information For more information go to www.p65warnings.ca.gov
Contractual warranty
Warranty period 18 months
REV DESCRIPTION BY DATE
,----\ ~
\ 0
8
H +1.20
~
[J1] A
~ I I ___i_
8
I ~ w :.8. ~ I
~ [2>]~
JYP!CAI FRONT VIEW
rtpiCAI ENDWAII
BOX: GRAY BAKED ENAMEL FINISH ELECTRODEPOSITED OVER CLEANED PHOSPHATIZED STEEL
INCLUDES HINGED COVER. MOUNTS TO WALL WITH MOUNTING CHANNEL AND SWINGABLE
MOUNTING BRACKET.
LOCK: CHROME-PLATED HANDLE LOCK. NSR-251 KEY CHANGE. NO PROVISIONS FOR PADLOCK. DUAL DIMENSIONS: INCHES
MIWMETERS
NOTE: NEMA TYPE JR/12 ENCLOSURE FOR HCN, HCM, AND HCP 1-UNE PANELBOARDS.
Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Main
Range I-Line
Product or Component Type Trim
Parts Quantity 4
Complementary
Product Destination Panelboard HCP 42 in 68 in
Device Mounting Surface
Number of Door 1
Environment
Standards CE
cULus
Offer Sustainability
Sustainable offer status Green Premium product
RoHS (date code: YYWW) Compliant - since 1419 - Schneider Electric declaration of conformity
Contractual warranty
Warranty period 18 months
Product data sheet HC4268DB
Characteristics HCP 42 INCH WIDE by 68 INCH HIGH TYPE1 I-
LINE PANELBOARD ENCLOSURE
Product availability : Stock - Normally stocked in distribution facility
Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Main
Range of product I-Line
Product or component type Enclosure
Device application Panelboard
Device short name HCP
Complementary
Line Rated Current 1200 A
400 A
600 A
800 A
Enclosure nominal width 1067 mm
Enclosure nominal height 1727 mm
Enclosure nominal depth 241 mm
Environment
NEMA degree of protection NEMA 1
Standards CSA
UL
Offer Sustainability
Sustainable offer status Green Premium product
RoHS (date code: YYWW) Compliant - since 1419 - Schneider Electric declaration of conformity
Schneider Electric declaration of conformity
REACh Reference not containing SVHC above the threshold
Reference not containing SVHC above the threshold
Product environmental profile Available
Product end of life instructions Need no specific recycling operations
California proposition 65 WARNING: This product can expose you to chemicals including:
- - - - - - - Substance 1 Nickel compounds, which is known to the State of California to cause cancer, and
- - - - - - - Substance 2 Bisphenol A (BPA), which is known to the State of California to cause birth defects or other
reproductive harm.
- - - - - - - More information For more information go to www.p65warnings.ca.gov
Contractual warranty
Warranty period 18 months
REV DESCRIPTION BY DATE ----
---- -- -- ----
0 • • •
• • •
s s DIRECTORY • •
0 [DJ [DJ 0
LOCK
[DJ [DJ
L - ...J
H (!)
[DJ [DJ
• z
:r:F
LJ.I (!) ~ '5
0 0
CJ~-'o
< I- u...::::;;
u.:z
a,:::,
:::,0
V)::::;;
• - -• - •
0 0
• • • • •
2.00
1.701
[43]
• 42.00
[1067] •
11.70
[43] [51]
~ 9.50
[241] ~ lYPICAL FRQNT
( 4 PIECE TRIM - WITH DOOR)
1~
JYPICAL BQX WITH INIERIQR
'.Id
lYPICAL BQX
SIPE VIEW
•
•
-== -== -==
s
•
s
•
•
I [DJ [DJ
s s
•
( 4 PIECE TRIM - NO DOOR)
iiiiiiiiiiiiiii
•
•
REFER TO DP CATALOG CLASS 2110 FOR ADDITIONAL INFORMATION
PG 01 OF 01 REV -
DRAWING STATUS:
Product data sheet M800S
Characteristics TYPE 1 300 to 800A SURFACE MOUNT
MOULDED CASE CIRCUIT BREAKER
ENCLOSURE
Product availability : Stock - Normally stocked in distribution facility
Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Main
Circuit breaker type MGL
MJL
PGL
PJL
PKL
PLL
Complementary
Enclosure material Steel
Width 533.4 mm
Height 1025.52 mm
Depth 247.65 mm
Line Rated Current 300...800 A
Device mounting Surface
Poles description 2P
3P
Environment
NEMA degree of protection NEMA 1
Product certifications CSA
UL
Offer Sustainability
Sustainable offer status Green Premium product
RoHS (date code: YYWW) Compliant - since 1434 - Schneider Electric declaration of conformity
Schneider Electric declaration of conformity
REACh Reference not containing SVHC above the threshold
Reference not containing SVHC above the threshold
Product environmental profile Available
Product end of life instructions Need no specific recycling operations
California proposition 65 WARNING: This product can expose you to chemicals including:
- - - - - - - Substance 1 Lead and lead compounds, which is known to the State of California to cause cancer and birth
defects or other reproductive harm.
- - - - - - - More information For more information go to www.p65warnings.ca.gov
Contractual warranty
Warranty period 18 months
Product data sheet AL800SN
Characteristics NEUTRAL ASSEMBLY 1000A
Product availability : Stock - Normally stocked in distribution facility
Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Main
Circuit breaker type Standard
Complementary
AWG gauge AWG 6...250 kcmil 1 aluminium
AWG 3/0...500 kcmil 6 aluminium/copper
Offer Sustainability
RoHS (date code: YYWW) Will be compliant on 3Q2014
Will be compliant on 3Q2014
REACh Reference not containing SVHC above the threshold
Reference not containing SVHC above the threshold
California proposition 65 WARNING: This product can expose you to chemicals including:
- - - - - - - Substance 1 Lead and lead compounds, which is known to the State of California to cause cancer and birth
defects or other reproductive harm.
- - - - - - - More information For more information go to www.p65warnings.ca.gov
21.00
[533] 1/~ASHED LINE
NOICATES HOOD A
I:~: r))r B
.un
:~:
)))
------------------------- ---------
,, -r bb 'J.'Ul
\.44 = DIA
[11] I CIRCUIT
CIRCUIT BREAKER lERMINAL LUG DATA
WIRE SIZE
BREAKER AMPERE CONDUCTORS (AWG/KCt.tiL) lYPE
(4 HOLES) COVER HANDLESJ CATALOG NO. RATING PER PHASE
PREFIX MAX MIN
(2) PLACES
[Q
MGL,t.1JL J00-800A AL
PGL.PJL.PKL.PLL 250-800A 3 500 3/0 OR
40.38 40.38 cu
[1026]
35.16 [1026]
[893]
FIELD INSTALLABLE NEUTRAL ASSEMBUES AND GROUND KIT
WIRE SIZE
CATALOG t.IAXIMUM NUMBER OF CONDUCTORS
AMPERE PER
(AWG/KCMIL) lYPE
NUMBER RATING TERt.tiNALS lERMINAL MAX MIN
•
500 3/0
I
= ' l 2.00
[51] • SNBOOSNI AND
(2) SN1200 BOOA
16
(B IN 8 OUT)
2
1
•
250
500 '
3/0 AL
,, ,,
•• S33576 AND B
2
1
350
500 '
3/0
OR
cu
2.0~j
[5l] 2.16
j _16.0?,- L2.16
1-- ::jT
9.75
[248]
SJ3576MK
PKOGTA4 ...
BOOA (4 IN-4 OUT)
4
2
1
• 300
300
4
6
[55] [406] [55] . INCHES
DUAL DIMENSIONS. MILUMETERS
MJL
A 300-800 100K 65K 65K 25K
- - - X
20.32 NO KNOCKOUTS B - - -
[516]
PGL
• A
B
250-800 65K 35K 35K 1BK
- - - X
NOlES:
FINISH - GRAY BAKED ENAt.tEL ELECTRODEPOSITED OVER CLEANED PHOSPHATIZED STEEL.
PJL
• A
B
250-800 100K 65K 65K 25K
-
-
-
-
-
- X
~~ 3432
DECEMBER 2014
Product data sheet MH26WP
Characteristics NQNF Panelboard Enclosure Box, Type 3R/5/12,
20 x 26 x 6.5 in
Product availability : Stock - Normally stocked in distribution facility
Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Main
Product Enclosure
Complementary
Material Steel
Width 20 in
Height 26 in
Depth 6.5 in
Device mounting Surface
Environment
Enclosure Rating NEMA 3R/5/12
Product certifications CULus
Offer Sustainability
Sustainable offer status Green Premium product
RoHS (date code: YYWW) Compliant - since 1419 - Schneider Electric declaration of conformity
Contractual warranty
Warranty period 18 months
REV DESCRIPTION BY DATE
'-INTERIOR
MOUNTING STUDS
H+1.46 H+.86
A
~
H [37] [22]
X
SEE
NOTE
BELOW
1.00
0 0
[25]
0 0
L....:.......J
II II L....:.......J
~n1~~;~j 6.88
[175]
1 0.44=-J
[265]
15.44
[392]
I I
20.34
[517]
TYPICAL MOUNTING OF TYPICAL ENDWALL
QO, QOB BREAKERS
INCHES
DUAL DIMENSIONS: MILLIMITERS
Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Main
Product Enclosure
Complementary
Material Steel
Width 20 in
Height 32 in
Depth 6.5 in
Device mounting Surface
Environment
Enclosure Rating NEMA 3R/5/12
Product certifications CULus
Offer Sustainability
Sustainable offer status Green Premium product
RoHS (date code: YYWW) Compliant - since 1419 - Schneider Electric declaration of conformity
Contractual warranty
Warranty period 18 months
REV DESCRIPTION BY DATE
'-INTERIOR
MOUNTING STUDS
H+1.46 H+.86
A
~
H [37] [22]
X
SEE
NOTE
BELOW
1.00
0 0
[25]
0 0
L....:.......J
II II L....:.......J
~n1~~;~j 6.88
[175]
1 0.44=-J
[265]
15.44
[392]
I I
20.34
[517]
TYPICAL MOUNTING OF TYPICAL ENDWALL
QO, QOB BREAKERS
INCHES
DUAL DIMENSIONS: MILLIMITERS
Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Main
Product Enclosure
Complementary
Material Steel
Width 20 in
Height 38 in
Depth 5.75 in
Environment
Enclosure Rating NEMA 1
Product certifications CULus
Offer Sustainability
Sustainable offer status Green Premium product
RoHS (date code: YYWW) Compliant - since 1419 - Schneider Electric declaration of conformity
Schneider Electric declaration of conformity
Sep 20, 2018
REACh Reference not containing SVHC above the threshold
Reference not containing SVHC above the threshold
Product environmental profile Available
Product end of life instructions Need no specific recycling operations
Contractual warranty
Warranty period 18 months
REV DESCRIPTION BY DATE - ---- -- -- --
- ---- -- -- -- - ---- -- -- --
19.12 KNOCKOUTS
2.50
[ 486]
±.20 __J [64]
TYP
SYMBOL
CONDUIT SIZE
IN MM
KNOCKOUT DIA
IN MM
A .50 13 .88 22
O® G) ®
B .75 19 1.12 28
c:=::J D 1.25 32 1.75 44
E 1.50 38 2.00 51
• •
F 2.00 51 2.50 64
G 2.50 64 3.00 76
H 3.00 76 3.62 92
3.50 89 4.12 105
L
M • • s
• •
0 ® G) ® ---Ft---~
3.00
[76]
TYP
L- 10.44
[265]
20.12
[511] --
4.78
[121]
PG 1 OF 1 REV -
DRAWING STATUS:
Product data sheet MH38WP
Characteristics NQNF Panelboard Enclosure Box, Type 3R/5/12,
20 x 38 x 6.5 in
Product availability : Stock - Normally stocked in distribution facility
Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Main
Product Enclosure
Complementary
Material Steel
Width 20 in
Height 38 in
Depth 6.5 in
Device mounting Surface
Environment
Enclosure Rating NEMA 3R/5/12
Product certifications CULus
Offer Sustainability
Sustainable offer status Green Premium product
RoHS (date code: YYWW) Compliant - since 1419 - Schneider Electric declaration of conformity
Contractual warranty
Warranty period 18 months
REV DESCRIPTION BY DATE
'-INTERIOR
MOUNTING STUDS
H+1.46 H+.86
A
~
H [37] [22]
X
SEE
NOTE
BELOW
1.00
0 0
[25]
0 0
L....:.......J
II II L....:.......J
~n1~~;~j 6.88
[175]
1 0.44=-J
[265]
15.44
[392]
I I
20.34
[517]
TYPICAL MOUNTING OF TYPICAL ENDWALL
QO, QOB BREAKERS
INCHES
DUAL DIMENSIONS: MILLIMITERS
Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Main
Product Enclosure
Complementary
Material Steel
Width 20 in
Height 50 in
Depth 6.5 in
Device mounting Surface
Environment
Enclosure Rating NEMA 3R/5/12
Product certifications CULus
Offer Sustainability
Sustainable offer status Green Premium product
RoHS (date code: YYWW) Compliant - since 1419 - Schneider Electric declaration of conformity
Contractual warranty
Warranty period 18 months
REV DESCRIPTION BY DATE
'-INTERIOR
MOUNTING STUDS
H+1.46 H+.86
A
~
H [37] [22]
X
SEE
NOTE
BELOW
1.00
0 0
[25]
0 0
L....:.......J
II II L....:.......J
~n1~~;~j 6.88
[175]
1 0.44=-J
[265]
15.44
[392]
I I
20.34
[517]
TYPICAL MOUNTING OF TYPICAL ENDWALL
QO, QOB BREAKERS
INCHES
DUAL DIMENSIONS: MILLIMITERS
Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Main
Product Enclosure
Complementary
Material Steel
Width 20 in
Height 74 in
Depth 6.5 in
Device mounting Surface
Environment
Enclosure Rating NEMA 3R/5/12
Product certifications CULus
Offer Sustainability
Sustainable offer status Green Premium product
RoHS (date code: YYWW) Compliant - since 1419 - Schneider Electric declaration of conformity
Contractual warranty
Warranty period 18 months
REV DESCRIPTION BY DATE
'-INTERIOR
MOUNTING STUDS
H+1.46 H+.86
A
~
H [37] [22]
X
SEE
NOTE
BELOW
1.00
0 0
[25]
0 0
L....:.......J
II II L....:.......J
~n1~~;~j 6.88
[175]
1 0.44=-J
[265]
15.44
[392]
I I
20.34
[517]
TYPICAL MOUNTING OF TYPICAL ENDWALL
QO, QOB BREAKERS
INCHES
DUAL DIMENSIONS: MILLIMITERS
Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Main
Product Surface cover
Color Grey
Cover type Surface cover
Complementary
Material Steel
Width 20 in
Height 38 in
Environment
Enclosure Rating NEMA 1
Product certifications CULus
Offer Sustainability
Sustainable offer status Green Premium product
RoHS (date code: YYWW) Compliant - since 1419 - Schneider Electric declaration of conformity
Contractual warranty
Warranty period 18 months
CATALOG A B C
NUMBER IN MM IN MM IN MM
NC26S 26.12 663 17.70 436 6.16 156
NC32S 32.12 816 23.70 602 9.16 233
NC38S 38.12 968 29.70 754 12.16 309
NC44S 44.12 1121 35.70 907 15.16 385
NC50S 50.12 1273 41.70 1059 18.16 461
NC56S 56.12 1425 47.70 1212 21.16 537
NC62S 62.12 1578 53.70 1364 24.16 614
NC68S 68.12 1730 59.70 1516 27.16 690
NC74S 74.12 1883 65.70 1669 30.16 766
NC80S 80.12 2035 71.70 1821 33.16 842
NC26F 27.52 699 17.70 436 6.16 156
NC32F 33.52 851 23.70 602 9.16 233
NC38F 39.52 1004 29.70 754 12.16 309
NC44F 45.52 1156 35.70 907 15.16 385
NC50F 51.52 1309 41.70 1059 18.16 461
NC56F 57.52 1461 47.70 1212 21.16 537
NC62F 63.52 1613 53.70 1364 24.16 614
NC68F 69.52 1766 59.70 1516 27.16 690
NC74F 75.52 1918 65.70 1669 30.16 766
NC80F 81.52 2071 71.70 1821 33.16 842
B REF NC86S 86.12 2187 77.70 1974 36.16 918
NC86F 87.52 2071 77.70 1974 36.16 918
C REF
.05 NC35S 35.12 892 26.70 678 10.66 271
2.00
[1] [51] NC35F 36.52 928 26.70 678 10.66 271
TYP
NC41S 41.12 1044 32.70 831 13.66 347
NC41F 42.52 1080 32.70 831 13.66 347
NC92S 92.12 2340 83.70 2126 39.16 995
= .. = = c:::::::::)c.=)c.=) •• c:::::::::)
= = c:::::::::) •• c:::::::::)c:::::::::)c:::::::::)
= = .. = 20.12
[511]
(.'.)
12.93 w 21.52
2.77 u<( z
3.44
[87] D [70]
[328]
REF LL z
Ct'.
=:)
U)
f-
=:)
0
2
[547]
:r: z
U)
(.'.)
f-
=:) z
= = = === = = = = === = = = _J =:)
LL 0
2
l
=
-----------------------A REF------------------------
= =
DUAL DIMENSIONS: INCHES
MILLIMETERS
,.
PANELBOARD COVER SQUARE E:]
TRIM TYPE 1 by Schnelder Electric
SURFACE/FLUSH
DWG#
NO. PWFDS-SYTl-0164
OCTOBER 2017 NC26S
Product data sheet EDB14020
Characteristics E-Frame Brkr 20A, 1P, 277V, 18/25kA, Bolt-on
Mnt
Product availability : Stock - Normally stocked in distribution facility
Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Main
Range of product 125 A Frame EDB-EGB-EJB
Product or component type Miniature circuit-breaker
Device short name EDB
Module type E-Frame
Trip unit rating 875 A
Complementary
Line Rated Current 20 A
System Voltage 277 V AC
AWG gauge AWG 14...AWG 6 copper
AWG 12...AWG 6 aluminium
Breaking capacity 18 kA 277 V AC
18 kA 240 V AC
25 kA 120 V AC
18 kA 120/240 V AC
Circuit breaker application HACR rated
Switching Duty rated
HID rated
Depth 4.05 in
Electrical connection Lugs
Height 5.66 in
Holding current 270 A
Local signalling Trip indicator
Mounting mode Bolt-on
Number of poles 1
Number of spaces 1
Number of spaces required 1
Product destination Panelboard NF
Sep 19, 2018
Product weight 2 lb(US)
Protection type Short-circuit
Overload
Width 0.98 in
Trip unit technology Thermal-magnetic
Breaking capacity code D
Environment
Product certifications CULus
IEC
Ambient air temperature for operation 104 °F (40 °C)
Offer Sustainability
Sustainable offer status Green Premium product
RoHS (date code: YYWW) Compliant - since 1423 - Schneider Electric declaration of conformity
Schneider Electric declaration of conformity
REACh Reference not containing SVHC above the threshold
Reference not containing SVHC above the threshold
Product environmental profile Available
Product end of life instructions Need no specific recycling operations
Contractual warranty
Warranty period 18 months
Product data sheet QOB120
Characteristics QO Mini CB 20 A 1P 120/240 V 10 kA Bolt-on
Mount
Product availability : Stock - Normally stocked in distribution facility
Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Main
Product Miniature circuit-breaker
Range QO
Line Rated Current 20 A
System Voltage 120 V AC
120/240 V AC
48 V DC
Mounting Type Bolt-on
Number of Poles 1P
Circuit Breaker Type Standard
Ratings HACR and Switching Duty rated
Electrical Connection Pressure plate
Complementary
Inturrupt Rating 10 kA at: 120/240 V AC
5 kA at: 48 V DC
10 kA at: 120 V AC
Number of Panel Spaces 1
Wire Size AWG 14...AWG 8 (copper or aluminium)
Height 3 in
Depth 2.91 in
Width 0.75 in
Environment
Certifications CSA
UL listed
Ambient Rating 104 °F (40 °C)
Offer Sustainability
Sustainable offer status Green Premium product
RoHS (date code: YYWW) Compliant - since 0701 - Schneider Electric declaration of conformity
Schneider Electric declaration of conformity
REACh Reference not containing SVHC above the threshold
Reference not containing SVHC above the threshold
Product environmental profile Available
Product end of life instructions Need no specific recycling operations
Contractual warranty
Warranty period 18 months
Product data sheet QOB220H
Characteristics QO Mini CB 20 A 2P 120/240 V 10 kA Bolt-on
Mount
Product availability : Stock - Normally stocked in distribution facility
Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Main
Product Miniature circuit-breaker
Range QO
Line Rated Current 20 A
System Voltage 120 V AC
120/240 V AC
240 V AC
Mounting Type Bolt-on
Number of Poles 2P
Circuit Breaker Type Standard
Ratings HACR rated
Electrical Connection Pressure plate
Complementary
Inturrupt Rating 10 kA at: 120/240 V AC
10 kA at: 120 V AC
10 kA at: 240 V AC
Number of Panel Spaces 2
Wire Size AWG 14...AWG 8 (copper or aluminium)
Height 3 in
Depth 2.91 in
Width 1.5 in
Environment
Certifications UL listed
CSA
Ambient Rating 104 °F (40 °C)
Offer Sustainability
Sustainable offer status Green Premium product
RoHS (date code: YYWW) Compliant - since 1323 - Schneider Electric declaration of conformity
Schneider Electric declaration of conformity
REACh Reference not containing SVHC above the threshold
Reference not containing SVHC above the threshold
Product environmental profile Available
Product end of life instructions Need no specific recycling operations
Contractual warranty
Warranty period 18 months
Product data sheet EJB34020
Characteristics E-Frame Brkr 20A, 3P, 480Y/277V, 65/100kA,
Bolt-on Mnt
Product availability : Stock - Normally stocked in distribution facility
Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Main
Range of product 125 A Frame EDB-EGB-EJB
Product or component type Miniature circuit-breaker
Device short name EJB
Module type E-Frame
Trip unit rating 875 A
Complementary
Line Rated Current 20 A
System Voltage 480Y/277 V AC
AWG gauge AWG 14...AWG 6 copper
AWG 12...AWG 6 aluminium
Breaking capacity 65 kA 277 V AC
65 kA 480Y/277 V AC
100 kA 120 V AC
100 kA 120/240 V AC
100 kA 240 V AC
Circuit breaker application HID rated
HACR rated
Depth 4.05 in
Electrical connection Lugs
Height 5.66 in
Holding current 270 A
Local signalling Trip indicator
Mounting mode Bolt-on
Number of poles 3
Number of spaces 3
Number of spaces required 3
Product destination Panelboard NF
Sep 20, 2018
Product weight 4 lb(US)
Protection type Short-circuit
Overload
Width 2.94 in
Trip unit technology Thermal-magnetic
Breaking capacity code J
Environment
Product certifications CULus
Ambient air temperature for operation 104 °F (40 °C)
Offer Sustainability
Sustainable offer status Green Premium product
RoHS (date code: YYWW) Compliant - since 1423 - Schneider Electric declaration of conformity
Schneider Electric declaration of conformity
REACh Reference not containing SVHC above the threshold
Reference not containing SVHC above the threshold
Product environmental profile Available
Product end of life instructions Need no specific recycling operations
Contractual warranty
Warranty period 18 months
Product data sheet QOB230H
Characteristics QO Mini CB, 30A, 2P, 120/240V, 10kA, Bolt-on
Mount
Product availability : Stock - Normally stocked in distribution facility
Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Main
Product Miniature circuit-breaker
Range QO
Line Rated Current 30 A
System Voltage 120 V AC
120/240 V AC
240 V AC
Mounting Type Bolt-on
Number of Poles 2P
Circuit Breaker Type Standard
Ratings HACR rated
Electrical Connection Pressure plate
Complementary
Inturrupt Rating 10 kA at: 120/240 V AC
10 kA at: 120 V AC
10 kA at: 240 V AC
Number of Panel Spaces 2
Wire Size AWG 14...AWG 8 (copper or aluminium)
Height 3 in
Depth 2.91 in
Width 1.5 in
Environment
Certifications CSA
UL listed
Ambient Rating 104 °F (40 °C)
Offer Sustainability
Sustainable offer status Green Premium product
RoHS (date code: YYWW) Compliant - since 1323 - Schneider Electric declaration of conformity
Schneider Electric declaration of conformity
REACh Reference not containing SVHC above the threshold
Reference not containing SVHC above the threshold
Product environmental profile Available
Product end of life instructions Need no specific recycling operations
Contractual warranty
Warranty period 18 months
Product data sheet BJL36030LU
Characteristics PowerPact-circuit breaker-30A 3P AC 65kA at
480/440V(UL/IEC)-TMD-EverLink lug
Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Main
Range PowerPact
Product name PowerPact B
Device short name BJ 030
Product or component type Circuit breaker
Device application Distribution
Complementary
[In] rated current 30 A
Poles description 3P
Protected poles description 3t
Control type Toggle
Mounting mode By screws for plate
Clip-on for 35 mm symmetrical DIN rail
Network type AC
Network frequency 50/60 Hz
Breaking capacity code J
Breaking capacity 100 kA at 240 V AC 50/60 Hz according to UL 489
65 kA at 480 V AC 50/60 Hz according to UL 489
Icu : 100 kA at 220...240 V AC 50/60 Hz according to IEC 60947-2
Icu : 65 kA at 380...415 V AC 50/60 Hz according to IEC 60947-2
Icu : 65 kA at 440 V AC 50/60 Hz according to IEC 60947-2
Icu : 25 kA at 500...525 V AC 50/60 Hz according to IEC 60947-2
Icu : 10 kA at 690 V AC 50/60 Hz according to IEC 60947-2
65 kA at 480Y/277 V AC 50/60 Hz according to UL 489
25 kA at 600Y/347 V AC 50/60 Hz according to UL 489
100 kA at 208Y/120 V AC 50/60 Hz according to UL 489
[Ue] rated operational voltage 690 V AC 50/60 Hz according to IEC 60947-2
[Ics] rated service breaking capacity 100 kA : at 220...240 V AC 50/60 Hz according to IEC 60947-2
65 kA : at 380...415 V AC 50/60 Hz according to IEC 60947-2
65 kA : at 440 V AC 50/60 Hz according to IEC 60947-2
25 kA : at 500...525 V AC 50/60 Hz according to IEC 60947-2
Environment
Product certifications UL
CSA
CCC
EAC
NOM
IEC
IP degree of protection IP40 (front cover) according to IEC 60529
IK degree of protection IK07 according to IEC 62262
Pollution degree 3 according to IEC 60947-1
Ambient air temperature for operation -25...70 °C
Ambient air temperature for storage -50...85 °C
Operating altitude 5000 m with derating
2000 m without derating
Offer Sustainability
Sustainable offer status Green Premium product
RoHS (date code: YYWW) Compliant - since 1644 - Schneider Electric declaration of conformity
Schneider Electric declaration of conformity
REACh Reference not containing SVHC above the threshold
Reference not containing SVHC above the threshold
Product environmental profile Available
Product end of life instructions Need no specific recycling operations
Product data sheet EJB34030
Characteristics E-Frame Brkr 30A, 3P, 480Y/277V, 65/100kA,
Bolt-on Mnt
Product availability : Stock - Normally stocked in distribution facility
Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Main
Range of product 125 A Frame EDB-EGB-EJB
Product or component type Miniature circuit-breaker
Device short name EJB
Module type E-Frame
Trip unit rating 875 A
Complementary
Line Rated Current 30 A
System Voltage 480Y/277 V AC
AWG gauge AWG 14...AWG 6 copper
AWG 12...AWG 6 aluminium
Breaking capacity 65 kA 277 V AC
65 kA 480Y/277 V AC
100 kA 120 V AC
100 kA 120/240 V AC
100 kA 240 V AC
Circuit breaker application HACR rated
HID rated
Depth 4.05 in
Electrical connection Lugs
Height 5.66 in
Holding current 270 A
Local signalling Trip indicator
Mounting mode Bolt-on
Number of poles 3
Number of spaces 3
Number of spaces required 3
Product destination Panelboard NF
Sep 20, 2018
Product weight 4 lb(US)
Protection type Short-circuit
Overload
Width 2.94 in
Trip unit technology Thermal-magnetic
Breaking capacity code J
Environment
Product certifications CULus
Ambient air temperature for operation 104 °F (40 °C)
Offer Sustainability
Sustainable offer status Green Premium product
RoHS (date code: YYWW) Compliant - since 1423 - Schneider Electric declaration of conformity
Schneider Electric declaration of conformity
REACh Reference not containing SVHC above the threshold
Reference not containing SVHC above the threshold
Product environmental profile Available
Product end of life instructions Need no specific recycling operations
Contractual warranty
Warranty period 18 months
Product data sheet HDL36030SA
Characteristics PowerPact H Circuit
Breaker,ThermMagn,30A,3P,600V,14kA, Shunt
Trip
Product availability : Non-Stock - Not normally stocked in distribution facility
Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Main
Product or component type Circuit breaker
Range of product PowerPact H
Trip Unit Type Thermal-magnetic
Breaking capacity code D
Options Shunt trip 120 V AC
Complementary
Line Rated Current 30 A
Number of Poles 3P
Interrupt Rating 18 kA at 480 V AC
25 kA at 240 V AC
14 kA at 600 V AC
20 kA at 250 V DC
System Voltage 250 V DC
600 V AC
Continuous current rating 80 %
Mounting mode Unit mount
Electrical connection Lugs load
Lugs line
Wire Gauge AWG 14...AWG 3/0 (aluminium/copper)
Magnetic hold current 350 A
Magnetic tripping current 750 A
Height 6.4 in
Width 4.12 in
Depth 4.36 in
Offer Sustainability
Sustainable offer status Green Premium product
RoHS (date code: YYWW) Compliant - since 0832 - Schneider Electric declaration of conformity
Schneider Electric declaration of conformity
REACh Reference not containing SVHC above the threshold
Reference not containing SVHC above the threshold
Product environmental profile Available
Product end of life instructions Need no specific recycling operations
California proposition 65 WARNING: This product can expose you to chemicals including:
- - - - - - - Substance 1 DINP, which is known to the State of California to cause cancer, and
- - - - - - - Substance 2 DIDP, which is known to the State of California to cause Birth Defects or other reproductive harm.
- - - - - - - More information For more information go to www.p65warnings.ca.gov
Contractual warranty
Warranty period 18 months
Product data sheet HJL36030T
Characteristics PowerPact H Circuit
Breaker,ThermMagn,30A,3P,600V,25kA,
Removable TU
Product availability : Non-Stock - Not normally stocked in distribution facility
Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Main
Product or component type Circuit breaker
Range of product PowerPact H
Trip Unit Type Thermal-magnetic
Breaking capacity code J
Complementary
Line Rated Current 30 A
Number of Poles 3P
Interrupt Rating 65 kA at 480 V AC
25 kA at 600 V AC
100 kA at 240 V AC
20 kA at 250 V DC
System Voltage 250 V DC
600 V AC
Continuous current rating 80 %
Trip Unit Field installable trip unit
Mounting mode Unit mount
Electrical connection Lugs load
Lugs line
Wire Gauge AWG 14...AWG 3/0 (aluminium/copper)
Magnetic hold current 350 A
Magnetic tripping current 750 A
Height 6.4 in
Width 4.12 in
Depth 4.36 in
Offer Sustainability
Sustainable offer status Green Premium product
RoHS (date code: YYWW) Compliant - since 0832 - Schneider Electric declaration of conformity
Schneider Electric declaration of conformity
REACh Reference not containing SVHC above the threshold
Reference not containing SVHC above the threshold
Product environmental profile Available
Product end of life instructions Need no specific recycling operations
California proposition 65 WARNING: This product can expose you to chemicals including:
- - - - - - - Substance 1 DINP, which is known to the State of California to cause cancer, and
- - - - - - - Substance 2 DIDP, which is known to the State of California to cause Birth Defects or other reproductive harm.
- - - - - - - More information For more information go to www.p65warnings.ca.gov
Contractual warranty
Warranty period 18 months
Product data sheet BJL36040LU
Characteristics PowerPact-circuit breaker-40A 3P AC 65kA at
480/440V(UL/IEC)-TMD-EverLink lug
Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Main
Range PowerPact
Product name PowerPact B
Device short name BJ 040
Product or component type Circuit breaker
Device application Distribution
Complementary
[In] rated current 40 A
Poles description 3P
Protected poles description 3t
Control type Toggle
Mounting mode By screws for plate
Clip-on for 35 mm symmetrical DIN rail
Network type AC
Network frequency 50/60 Hz
Breaking capacity code J
Breaking capacity 100 kA at 240 V AC 50/60 Hz according to UL 489
65 kA at 480 V AC 50/60 Hz according to UL 489
Icu : 100 kA at 220...240 V AC 50/60 Hz according to IEC 60947-2
Icu : 65 kA at 380...415 V AC 50/60 Hz according to IEC 60947-2
Icu : 65 kA at 440 V AC 50/60 Hz according to IEC 60947-2
Icu : 25 kA at 500...525 V AC 50/60 Hz according to IEC 60947-2
Icu : 10 kA at 690 V AC 50/60 Hz according to IEC 60947-2
65 kA at 480Y/277 V AC 50/60 Hz according to UL 489
25 kA at 600Y/347 V AC 50/60 Hz according to UL 489
100 kA at 208Y/120 V AC 50/60 Hz according to UL 489
[Ue] rated operational voltage 690 V AC 50/60 Hz according to IEC 60947-2
[Ics] rated service breaking capacity 100 kA : at 220...240 V AC 50/60 Hz according to IEC 60947-2
65 kA : at 380...415 V AC 50/60 Hz according to IEC 60947-2
65 kA : at 440 V AC 50/60 Hz according to IEC 60947-2
25 kA : at 500...525 V AC 50/60 Hz according to IEC 60947-2
Environment
Product certifications UL
CSA
CCC
EAC
NOM
IEC
IP degree of protection IP40 (front cover) according to IEC 60529
IK degree of protection IK07 according to IEC 62262
Pollution degree 3 according to IEC 60947-1
Ambient air temperature for operation -25...70 °C
Ambient air temperature for storage -50...85 °C
Operating altitude 5000 m with derating
2000 m without derating
Offer Sustainability
Sustainable offer status Green Premium product
RoHS (date code: YYWW) Compliant - since 1644 - Schneider Electric declaration of conformity
Schneider Electric declaration of conformity
REACh Reference not containing SVHC above the threshold
Reference not containing SVHC above the threshold
Product environmental profile Available
Product end of life instructions Need no specific recycling operations
Product data sheet EJB34050
Characteristics E-Frame Brkr 50A, 3P, 480Y/277V, 65/100kA,
Bolt-on Mnt
Product availability : Stock - Normally stocked in distribution facility
Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Main
Range of product 125 A Frame EDB-EGB-EJB
Product or component type Miniature circuit-breaker
Device short name EJB
Module type E-Frame
Trip unit rating 1800 A
Complementary
Line Rated Current 50 A
System Voltage 480Y/277 V AC
AWG gauge AWG 12...AWG 2/0 aluminium
AWG 14...AWG 2/0 copper
Breaking capacity 65 kA 277 V AC
65 kA 480Y/277 V AC
100 kA 120 V AC
100 kA 120/240 V AC
100 kA 240 V AC
Circuit breaker application HID rated
HACR rated
Depth 4.05 in
Electrical connection Lugs
Height 5.66 in
Holding current 630 A
Local signalling Trip indicator
Mounting mode Bolt-on
Number of poles 3
Number of spaces 3
Number of spaces required 3
Product destination Panelboard NF
Sep 19, 2018
Product weight 4 lb(US)
Protection type Short-circuit
Overload
Width 2.94 in
Trip unit technology Thermal-magnetic
Breaking capacity code J
Environment
Product certifications CULus
Ambient air temperature for operation 104 °F (40 °C)
Offer Sustainability
Sustainable offer status Green Premium product
RoHS (date code: YYWW) Compliant - since 1423 - Schneider Electric declaration of conformity
Schneider Electric declaration of conformity
REACh Reference not containing SVHC above the threshold
Reference not containing SVHC above the threshold
Product environmental profile Available
Product end of life instructions Need no specific recycling operations
Contractual warranty
Warranty period 18 months
Product data sheet BJL36060LU
Characteristics PowerPact-circuit breaker-60A 3P AC 65kA at
480/440V(UL/IEC)-TMD-EverLink lug
Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Main
Range PowerPact
Product name PowerPact B
Device short name BJ 060
Product or component type Circuit breaker
Device application Distribution
Complementary
[In] rated current 60 A
Poles description 3P
Protected poles description 3t
Control type Toggle
Mounting mode By screws for plate
Clip-on for 35 mm symmetrical DIN rail
Network type AC
Network frequency 50/60 Hz
Breaking capacity code J
Breaking capacity 100 kA at 240 V AC 50/60 Hz according to UL 489
65 kA at 480 V AC 50/60 Hz according to UL 489
Icu : 100 kA at 220...240 V AC 50/60 Hz according to IEC 60947-2
Icu : 65 kA at 380...415 V AC 50/60 Hz according to IEC 60947-2
Icu : 65 kA at 440 V AC 50/60 Hz according to IEC 60947-2
Icu : 25 kA at 500...525 V AC 50/60 Hz according to IEC 60947-2
Icu : 10 kA at 690 V AC 50/60 Hz according to IEC 60947-2
65 kA at 480Y/277 V AC 50/60 Hz according to UL 489
25 kA at 600Y/347 V AC 50/60 Hz according to UL 489
100 kA at 208Y/120 V AC 50/60 Hz according to UL 489
[Ue] rated operational voltage 690 V AC 50/60 Hz according to IEC 60947-2
[Ics] rated service breaking capacity 100 kA : at 220...240 V AC 50/60 Hz according to IEC 60947-2
65 kA : at 380...415 V AC 50/60 Hz according to IEC 60947-2
65 kA : at 440 V AC 50/60 Hz according to IEC 60947-2
25 kA : at 500...525 V AC 50/60 Hz according to IEC 60947-2
Environment
Product certifications UL
CSA
CCC
EAC
NOM
IEC
IP degree of protection IP40 (front cover) according to IEC 60529
IK degree of protection IK07 according to IEC 62262
Pollution degree 3 according to IEC 60947-1
Ambient air temperature for operation -25...70 °C
Ambient air temperature for storage -50...85 °C
Operating altitude 5000 m with derating
2000 m without derating
Offer Sustainability
Sustainable offer status Green Premium product
RoHS (date code: YYWW) Compliant - since 1644 - Schneider Electric declaration of conformity
Schneider Electric declaration of conformity
REACh Reference not containing SVHC above the threshold
Reference not containing SVHC above the threshold
Product environmental profile Available
Product end of life instructions Need no specific recycling operations
Product data sheet EJB34060
Characteristics E-Frame Brkr 60A, 3P, 480Y/277V, 65/100kA,
Bolt-on Mnt
Product availability : Stock - Normally stocked in distribution facility
Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Main
Range of product 125 A Frame EDB-EGB-EJB
Product or component type Miniature circuit-breaker
Device short name EJB
Module type E-Frame
Trip unit rating 1800 A
Complementary
Line Rated Current 60 A
System Voltage 480Y/277 V AC
AWG gauge AWG 12...AWG 2/0 aluminium
AWG 14...AWG 2/0 copper
Breaking capacity 65 kA 277 V AC
65 kA 480Y/277 V AC
100 kA 120 V AC
100 kA 120/240 V AC
100 kA 240 V AC
Circuit breaker application HACR rated
Depth 4.05 in
Electrical connection Lugs
Height 5.66 in
Holding current 630 A
Local signalling Trip indicator
Mounting mode Bolt-on
Number of poles 3
Number of spaces 3
Number of spaces required 3
Product destination Panelboard NF
Environment
Product certifications CULus
Ambient air temperature for operation 104 °F (40 °C)
Offer Sustainability
Sustainable offer status Green Premium product
RoHS (date code: YYWW) Compliant - since 1423 - Schneider Electric declaration of conformity
Schneider Electric declaration of conformity
REACh Reference not containing SVHC above the threshold
Reference not containing SVHC above the threshold
Product environmental profile Available
Product end of life instructions Need no specific recycling operations
Contractual warranty
Warranty period 18 months
Product data sheet HDL36060SA
Characteristics PowerPact H Circuit
Breaker,ThermMagn,60A,3P,600V,14kA, Shunt
Trip
Product availability : Non-Stock - Not normally stocked in distribution facility
Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Main
Product or component type Circuit breaker
Range of product PowerPact H
Trip Unit Type Thermal-magnetic
Breaking capacity code D
Options Shunt trip 120 V AC
Complementary
Line Rated Current 60 A
Number of Poles 3P
Interrupt Rating 18 kA at 480 V AC
25 kA at 240 V AC
14 kA at 600 V AC
20 kA at 250 V DC
System Voltage 250 V DC
600 V AC
Continuous current rating 80 %
Mounting mode Unit mount
Electrical connection Lugs load
Lugs line
Wire Gauge AWG 14...AWG 3/0 (aluminium/copper)
Magnetic hold current 800 A
Magnetic tripping current 1450 A
Height 6.4 in
Width 4.12 in
Depth 4.36 in
Offer Sustainability
Sustainable offer status Green Premium product
RoHS (date code: YYWW) Compliant - since 0832 - Schneider Electric declaration of conformity
Schneider Electric declaration of conformity
REACh Reference not containing SVHC above the threshold
Reference not containing SVHC above the threshold
Product environmental profile Available
Product end of life instructions Need no specific recycling operations
California proposition 65 WARNING: This product can expose you to chemicals including:
- - - - - - - Substance 1 DINP, which is known to the State of California to cause cancer, and
- - - - - - - Substance 2 DIDP, which is known to the State of California to cause Birth Defects or other reproductive harm.
- - - - - - - More information For more information go to www.p65warnings.ca.gov
Contractual warranty
Warranty period 18 months
~-6.40
[162,6]
¢.20
~-5.66
[5,1]
[143,8] (MOUNTING HOLE}
.74
[18,8]
1.38
1.38 [35,0]
[35,0]
2.06 f
[52,4] + - - - - - + - - - 4.12
[104,7]
.44
1.38 [11,3]
[35,0] 1.37
1.20 [34,8]
[30,5]
2.04
[51,9]
4.99 ISOMETRIC VIEW
[126,7] SCALE 1:2
5.20
[132,1]
~-5.96
[151,3]
l~ r~~O]
.43
19.5° [10,8]
ON
SEEDETAIL A
t
'
"
4.36
3.44 3.74 [110,8]
[87,4] 1.91 [95,1] .62
[15,9]
[48,5]
~3.69 DETAIL A
[93,8] SCALE 1:1
t-CA:_:r_M.OG
__ N_UM_B_ER_:_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _--t~ E3 THIRD
DESCRIPTION: H-Frame 15A- 150A 3P Toggle Lug-Lug ~ ANGLE
"THE SQUARE D COMPANY HAS PROPRIETARY RIGHTS TO THE INFORMATION
CONTAINED HEREON. THIS INFORMATION REMAINS THE PROPERTY OF
BA'IARE D
DRAWN BY: LRG DATE: 12AUG2003
SQUARED COMPANY AND MAY BE USED ONLY IN CONFORMANCE WITH
INSTRUCTlONS ISSUED BY SQUARE D CO. DO NOT SCALE DRAWING Schneider Electric
USER SHOULD VERIFY DRAWINGS ARE TO THE LATEST/CURRENT CHECKED BY: RLS DATE: 11 MAR2004 UNLESS OTHERWISE SPECIFIED
REVISION PRIOR TO INCORPORATlNG IN A DESIGN FILE: DIMENSIONS ARE
DRAWING FILE: 48996-012-01 .DRW _Hi_ DRAWING NUMBER _ _ REVISION
ECN: J582 mm 48996 012 0 1 0
Product data sheet HJL36060C
Characteristics PowerPact H Circuit
Breaker,ThermMagn,60A,3P,600V,25kA
Product availability : Non-Stock - Not normally stocked in distribution facility
Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Main
Product or component type Circuit breaker
Range of product PowerPact H
Trip Unit Type Thermal-magnetic
Breaking capacity code J
Complementary
Line Rated Current 60 A
Number of Poles 3P
Interrupt Rating 65 kA at 480 V AC
25 kA at 600 V AC
100 kA at 240 V AC
20 kA at 250 V DC
System Voltage 250 V DC
600 V AC
Continuous current rating 100 %
Mounting mode Unit mount
Electrical connection Lugs load
Lugs line
Wire Gauge AWG 14...AWG 3/0 (aluminium/copper)
Magnetic hold current 800 A
Magnetic tripping current 1450 A
Height 6.4 in
Width 4.12 in
Depth 4.36 in
Environment
Product certifications CE
Offer Sustainability
Sustainable offer status Green Premium product
RoHS (date code: YYWW) Compliant - since 0832 - Schneider Electric declaration of conformity
Schneider Electric declaration of conformity
REACh Reference not containing SVHC above the threshold
Reference not containing SVHC above the threshold
Product environmental profile Available
Product end of life instructions Need no specific recycling operations
Contractual warranty
Warranty period 18 months
Product data sheet EJB34070
Characteristics E-Frame Brkr 70A, 3P, 480Y/277V, 65/100kA,
Bolt-on Mnt
Product availability : Stock - Normally stocked in distribution facility
Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Main
Range of product 125 A Frame EDB-EGB-EJB
Product or component type Miniature circuit-breaker
Device short name EJB
Module type E-Frame
Trip unit rating 1800 A
Complementary
Line Rated Current 70 A
System Voltage 480Y/277 V AC
AWG gauge AWG 12...AWG 2/0 aluminium
AWG 14...AWG 2/0 copper
Breaking capacity 65 kA 277 V AC
65 kA 480Y/277 V AC
100 kA 120 V AC
100 kA 120/240 V AC
100 kA 240 V AC
Circuit breaker application HACR rated
Depth 4.05 in
Electrical connection Lugs
Height 5.66 in
Holding current 630 A
Local signalling Trip indicator
Mounting mode Bolt-on
Number of poles 3
Number of spaces 3
Number of spaces required 3
Product destination Panelboard NF
Environment
Product certifications CULus
Ambient air temperature for operation 104 °F (40 °C)
Offer Sustainability
Sustainable offer status Green Premium product
RoHS (date code: YYWW) Compliant - since 1423 - Schneider Electric declaration of conformity
Schneider Electric declaration of conformity
REACh Reference not containing SVHC above the threshold
Reference not containing SVHC above the threshold
Product environmental profile Available
Product end of life instructions Need no specific recycling operations
Contractual warranty
Warranty period 18 months
Product data sheet BJL36080LU
Characteristics PowerPact-circuit breaker-80A 3P AC 65kA at
480/440V(UL/IEC)-TMD-EverLink lug
Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Main
Range PowerPact
Product name PowerPact B
Device short name BJ 080
Product or component type Circuit breaker
Device application Distribution
Complementary
[In] rated current 80 A
Poles description 3P
Protected poles description 3t
Control type Toggle
Mounting mode By screws for plate
Clip-on for 35 mm symmetrical DIN rail
Network type AC
Network frequency 50/60 Hz
Breaking capacity code J
Breaking capacity 100 kA at 240 V AC 50/60 Hz according to UL 489
65 kA at 480 V AC 50/60 Hz according to UL 489
Icu : 100 kA at 220...240 V AC 50/60 Hz according to IEC 60947-2
Icu : 65 kA at 380...415 V AC 50/60 Hz according to IEC 60947-2
Icu : 65 kA at 440 V AC 50/60 Hz according to IEC 60947-2
Icu : 25 kA at 500...525 V AC 50/60 Hz according to IEC 60947-2
Icu : 10 kA at 690 V AC 50/60 Hz according to IEC 60947-2
65 kA at 480Y/277 V AC 50/60 Hz according to UL 489
25 kA at 600Y/347 V AC 50/60 Hz according to UL 489
100 kA at 208Y/120 V AC 50/60 Hz according to UL 489
[Ue] rated operational voltage 690 V AC 50/60 Hz according to IEC 60947-2
[Ics] rated service breaking capacity 100 kA : at 220...240 V AC 50/60 Hz according to IEC 60947-2
65 kA : at 380...415 V AC 50/60 Hz according to IEC 60947-2
65 kA : at 440 V AC 50/60 Hz according to IEC 60947-2
25 kA : at 500...525 V AC 50/60 Hz according to IEC 60947-2
Environment
Product certifications UL
CSA
CCC
EAC
NOM
IEC
IP degree of protection IP40 (front cover) according to IEC 60529
IK degree of protection IK07 according to IEC 62262
Pollution degree 3 according to IEC 60947-1
Ambient air temperature for operation -25...70 °C
Ambient air temperature for storage -50...85 °C
Operating altitude 5000 m with derating
2000 m without derating
Offer Sustainability
Sustainable offer status Green Premium product
RoHS (date code: YYWW) Compliant - since 1644 - Schneider Electric declaration of conformity
Schneider Electric declaration of conformity
REACh Reference not containing SVHC above the threshold
Reference not containing SVHC above the threshold
Product environmental profile Available
Product end of life instructions Need no specific recycling operations
3
Product data sheet BJL36090LU
Characteristics PowerPact-circuit breaker-90A 3P AC 65kA at
480/440V(UL/IEC)-TMD-EverLink lug
Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Main
Range PowerPact
Product name PowerPact B
Device short name BJ 090
Product or component type Circuit breaker
Device application Distribution
Complementary
[In] rated current 90 A
Poles description 3P
Protected poles description 3t
Control type Toggle
Mounting mode By screws for plate
Clip-on for 35 mm symmetrical DIN rail
Network type AC
Network frequency 50/60 Hz
Breaking capacity code J
Breaking capacity 100 kA at 240 V AC 50/60 Hz according to UL 489
65 kA at 480 V AC 50/60 Hz according to UL 489
Icu : 100 kA at 220...240 V AC 50/60 Hz according to IEC 60947-2
Icu : 65 kA at 380...415 V AC 50/60 Hz according to IEC 60947-2
Icu : 65 kA at 440 V AC 50/60 Hz according to IEC 60947-2
Icu : 25 kA at 500...525 V AC 50/60 Hz according to IEC 60947-2
Icu : 10 kA at 690 V AC 50/60 Hz according to IEC 60947-2
65 kA at 480Y/277 V AC 50/60 Hz according to UL 489
25 kA at 600Y/347 V AC 50/60 Hz according to UL 489
100 kA at 208Y/120 V AC 50/60 Hz according to UL 489
[Ue] rated operational voltage 690 V AC 50/60 Hz according to IEC 60947-2
[Ics] rated service breaking capacity 100 kA : at 220...240 V AC 50/60 Hz according to IEC 60947-2
65 kA : at 380...415 V AC 50/60 Hz according to IEC 60947-2
65 kA : at 440 V AC 50/60 Hz according to IEC 60947-2
25 kA : at 500...525 V AC 50/60 Hz according to IEC 60947-2
Environment
Product certifications UL
CSA
CCC
EAC
NOM
IEC
IP degree of protection IP40 (front cover) according to IEC 60529
IK degree of protection IK07 according to IEC 62262
Pollution degree 3 according to IEC 60947-1
Ambient air temperature for operation -25...70 °C
Ambient air temperature for storage -50...85 °C
Operating altitude 5000 m with derating
2000 m without derating
Offer Sustainability
Sustainable offer status Green Premium product
RoHS (date code: YYWW) Compliant - since 1644 - Schneider Electric declaration of conformity
Schneider Electric declaration of conformity
REACh Reference not containing SVHC above the threshold
Reference not containing SVHC above the threshold
Product environmental profile Available
Product end of life instructions Need no specific recycling operations
Product data sheet EJB34090
Characteristics E-Frame Brkr 90A, 3P, 480Y/277V, 65/100kA,
Bolt-on Mnt
Product availability : Stock - Normally stocked in distribution facility
Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Main
Range of product 125 A Frame EDB-EGB-EJB
Product or component type Miniature circuit-breaker
Device short name EJB
Module type E-Frame
Trip unit rating 2300 A
Complementary
Line Rated Current 90 A
System Voltage 480Y/277 V AC
AWG gauge AWG 12...AWG 2/0 aluminium
AWG 14...AWG 2/0 copper
Breaking capacity 65 kA 277 V AC
65 kA 480Y/277 V AC
100 kA 120 V AC
100 kA 120/240 V AC
100 kA 240 V AC
Circuit breaker application HACR rated
Depth 4.05 in
Electrical connection Lugs
Height 5.66 in
Holding current 1000 A
Local signalling Trip indicator
Mounting mode Bolt-on
Number of poles 3
Number of spaces 3
Number of spaces required 3
Product destination Panelboard NF
Environment
Product certifications CULus
Ambient air temperature for operation 104 °F (40 °C)
Offer Sustainability
Sustainable offer status Green Premium product
RoHS (date code: YYWW) Compliant - since 1423 - Schneider Electric declaration of conformity
Schneider Electric declaration of conformity
REACh Reference not containing SVHC above the threshold
Reference not containing SVHC above the threshold
Product environmental profile Available
Product end of life instructions Need no specific recycling operations
Contractual warranty
Warranty period 18 months
Product data sheet LA36400
Characteristics 3P 400A 600V, LA FA/LA MOLDED CASE
CIRCUIT BREAKER
Product availability : Stock - Normally stocked in distribution facility
Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Main
Product or component type Circuit breaker
Range of product I-Line
Trip Unit Type Thermal-magnetic
Rating Code A
Complementary
Line Rated Current 400 A
Number of Poles 3P
Interrupt Rating 25 kA at 600 V AC
42 kA at 240 V AC
30 kA at 480 V AC
System Voltage 250 V DC
600 V AC
Mounting mode I-Line
Electrical connection I-Line connection line
Lugs load
Wire Gauge AWG 1...600 kcmil (aluminium/copper) 1 cable(s)
AWG 1...250 kcmil (aluminium/copper) 2 cable(s)
Terminal Type AL400LA
Magnetic hold current 2000 A
Magnetic tripping current 4000 A
Wiring configuration 3-wire
Phase connection ABC
Height 11 in
Width 6 in
Depth 5.84 in
Offer Sustainability
Sustainable offer status Green Premium product
RoHS (date code: YYWW) Compliant - since 1304 - Schneider Electric declaration of conformity
Schneider Electric declaration of conformity
REACh Reference not containing SVHC above the threshold
Reference not containing SVHC above the threshold
Product environmental profile Available
Product end of life instructions Need no specific recycling operations
Contractual warranty
Warranty period 18 months
CATALOG NUMBERING
A, H, OR c __.J
260R36
I
-
.I
L (•) L (••) (***)
... l4.27
) ~-----1~,
Ratings: BOOVAC/250VDC, 125 - 400 AMPERE ON
LCL (Extra High Interrupting)
Ratings: BOOVAC, 300 - -400 AMPERE 11.00
~ 7'1RIPPE01
9.25
If" II-- lj®
l£E'~··-
---..: ~
l)._ 3r
r l
OFF
Wire Size: (1) f1 BOO kcmil
Terminal Torque: -
=<!:"1
LCL (300 - -400 AMP)
Wire Size: (2) 14/0
Terminal Torque: -
- 500 kcrnn
5.81-
.88
D - 2.00-
1.98 f--
200t[ff
'h ~
.3.~J
Catalog Number: SEE CHART
Ratings: SEE CHART 't { ~
UL File/Guide: E10027 .34- I-
CSA File/Guide: LR7551 - l-1.26
Meets Standards: IEC 157-1
Weight: 8.50 lbs.
Wire Size: SEE CHART
Terminal torque:
Mounting Hwd.:
-
8-32 SCREWS
Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Main
Product or component type Circuit breaker
Range of product PowerPact M
Breaking capacity code J
Trip unit technology Electronic basic ET 1.0 LI
Complementary
Current sensor rating range 400 A
Line Rated Current 400 A
System Voltage 600 V AC
Mounting mode Unit mount
Poles description 3P
Breaking capacity 100 kA 240 V AC
65 kA 480 V AC
25 kA 600 V AC
Continuous current rating 80 %
Electrical connection Lugs load
Lugs line
AWG gauge AWG 3/0...500 kcmil aluminium/copper 3(cables(s))
Environment
Product certifications CSA
IEC
UL listed
Offer Sustainability
Sustainable offer status Green Premium product
RoHS (date code: YYWW) Compliant - since 1323 - Schneider Electric declaration of conformity
Schneider Electric declaration of conformity
REACh Reference not containing SVHC above the threshold
Reference not containing SVHC above the threshold
Product environmental profile Available
Product end of life instructions Available
California proposition 65 WARNING: This product can expose you to chemicals including:
- - - - - - - Substance 1 DINP, which is known to the State of California to cause cancer, and
- - - - - - - Substance 2 DIDP, which is known to the State of California to cause Birth Defects or other reproductive harm.
- - - - - - - More information For more information go to www.p65warnings.ca.gov
Contractual warranty
Warranty period 18 months
Product data sheet MJA36600
Characteristics PowerPact M Molded CASE CIRCUIT BREAKER
600V 600A 3P
Product availability : Stock - Normally stocked in distribution facility
Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Main
Product or component type Circuit breaker
Range of product PowerPact M
Breaking capacity code J
Trip unit technology Electronic basic ET 1.0 LI
Complementary
Current sensor rating range 600 A
Line Rated Current 600 A
System Voltage 600 V AC
Mounting mode Plug-in
Poles description 3P
Breaking capacity 100 kA 240 V AC
65 kA 480 V AC
25 kA 600 V AC
Continuous current rating 80 %
Electrical connection I-Line connection line
Lugs load
AWG gauge AWG 3/0...500 kcmil aluminium/copper 3(cables(s))
Magnetic tripping current 1200...6000 A
Environment
Product certifications CSA
IEC
UL listed
Offer Sustainability
Sustainable offer status Green Premium product
RoHS (date code: YYWW) Compliant - since 1323 - Schneider Electric declaration of conformity
Schneider Electric declaration of conformity
REACh Reference not containing SVHC above the threshold
Reference not containing SVHC above the threshold
Product environmental profile Available
Product end of life instructions Available
California proposition 65 WARNING: This product can expose you to chemicals including:
- - - - - - - Substance 1 DINP, which is known to the State of California to cause cancer, and
- - - - - - - Substance 2 DIDP, which is known to the State of California to cause Birth Defects or other reproductive harm.
- - - - - - - More information For more information go to www.p65warnings.ca.gov
Contractual warranty
Warranty period 18 months
Product data sheet MJL36800
Characteristics PowerPact M Molded CASE CIRCUIT BREAKER
600V 800A 3P
Product availability : Stock - Normally stocked in distribution facility
Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Main
Product or component type Circuit breaker
Range of product PowerPact M
Breaking capacity code J
Trip unit technology Electronic basic ET 1.0 LI
Complementary
Current sensor rating range 800 A
Line Rated Current 800 A
System Voltage 600 V AC
Mounting mode Unit mount
Poles description 3P
Breaking capacity 100 kA 240 V AC
65 kA 480 V AC
25 kA 600 V AC
Continuous current rating 80 %
Electrical connection Lugs load
Lugs line
AWG gauge AWG 3/0...500 kcmil aluminium/copper 3(cables(s))
Environment
Product certifications CSA
IEC
UL listed
Offer Sustainability
Sustainable offer status Green Premium product
RoHS (date code: YYWW) Compliant - since 1323 - Schneider Electric declaration of conformity
Schneider Electric declaration of conformity
REACh Reference not containing SVHC above the threshold
Reference not containing SVHC above the threshold
Product environmental profile Available
Product end of life instructions Available
Contractual warranty
Warranty period 18 months
7.87
-
[200,0] f.22
- [5,5]
~ 1/-
' •
0 0
r---1 h
~ li:
•• c 3.92
[9~,5~
~
....~
.,-
~
~
~-
==---
r-
......,
r--
r-··-
~
~
.83
[199,0]
0
•
Cl
•
- c
ID
:i '" 1111
aD I'(
~
•~
!;=;
.
1-4------- 8.27
.30 [210,0]
[7,51.49
[12,5] ~--7.40
[188,0]
2.56
[64,9]
l
~---.26
[6,5]
1-4------ .43
6] [11 ,0]
5.78
[146,8]
3.84
[97,6]
t
~-5.00
[126,9]
~---12.86
t-----8.27
[326,6] [210,0]
_ _N_u_M_BE_R_:
t-CA:_:r_M.OG
DESCRIPTION:
-----------------------t~
C4RUUIEC 3P SODA ~
E3 THIRD
ANGLE
"THE SQUARE D COMPANY HAS PROPRIETARY RIGHTS TO THE INFORMATION
CONTAINED HEREON. THIS INFORMATION REMAINS THE PROPERTY OF
BA'IARE D
SQUARED COMPANY AND MAY BE USED ONLY IN CONFORMANCE WITH DRAWN BY: wre DATE: 25MAR2004
DO NOT SCALE DRAWING Schneider Electric
INSTRUCTlONS ISSUED BY SQUARE D CO.
USER SHOULD VERIFY DRAWINGS ARE TO THE LATEST/CURRENT CHECKED BY: DATE: UNLESS OTHERWISE SPECIFIED
REVISION PRIOR TO INCORPORATlNG IN A DESIGN FILE: DIMENSIONS ARE
DRAWING FILE: 48096-445-01 .DRW _Hi_ DRAWING NUMBER -4 _ REVISION
ECN: K026 mm 48096 45 0 1
Product data sheet HLL36060LV
Characteristics PowerPact H Circuit
Breaker,ThermMagn,60A,3P,600V,50kA,Control
Wire
Product availability : Non-Stock - Not normally stocked in distribution facility
Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Main
Product or component type Circuit breaker
Range of product PowerPact H
Trip Unit Type Thermal-magnetic
Breaking capacity code L
Options Control wire at OFF end
Complementary
Line Rated Current 60 A
Number of Poles 3P
Interrupt Rating 125 kA at 240 V AC
100 kA at 480 V AC
50 kA at 600 V AC
20 kA at 250 V DC
50 kA at 500 V DC
System Voltage 250 V DC
500 V DC
600 V AC
Continuous current rating 80 %
Mounting mode Unit mount
Electrical connection Lugs load
Lugs line
Wire Gauge AWG 14...AWG 3/0 (aluminium/copper)
Magnetic hold current 800 A
Magnetic tripping current 1450 A
Height 6.4 in
Width 4.12 in
Depth 4.36 in
Sep 20, 2018
Environment
Product certifications CCC
CE
CSA
IEC
UL listed
Ambient air temperature for operation 104 °F (40 °C)
Offer Sustainability
Sustainable offer status Green Premium product
RoHS (date code: YYWW) Compliant - since 0832 - Schneider Electric declaration of conformity
Schneider Electric declaration of conformity
REACh Reference not containing SVHC above the threshold
Reference not containing SVHC above the threshold
Product environmental profile Available
Product end of life instructions Need no specific recycling operations
California proposition 65 WARNING: This product can expose you to chemicals including:
- - - - - - - Substance 1 DINP, which is known to the State of California to cause cancer, and
- - - - - - - Substance 2 DIDP, which is known to the State of California to cause Birth Defects or other reproductive harm.
- - - - - - - More information For more information go to www.p65warnings.ca.gov
Contractual warranty
Warranty period 18 months