Fuse Calculation
Fuse Calculation
Fuse Calculation
Abstract: This white paper provides a 1.1 Method 1: As an external relay interlocked
comprehensive discussion of the modeling of to operate contactors.
Mersen’s medium voltage controllable fuses 1.2 Method 2: As a medium voltage current
(MVCF) in ETAP. Two simulation techniques limiting fuse.
and their incident energy mitigation benefits are
presented. Some important considerations in
system configuration, protective device co- Either method can be used to simulate normal
ordination, and application are also included. and maintenance mode of operation. Their
advantages/disadvantages are discussed in the
conclusion section later in this paper.
Key Words: Medium Voltage Controllable
Fuse, Mitigation techniques, ETAP, Fuse 2 PRIMARY FUSE PROTECTION ISSUES
protection, MVCF, In this example, before presenting the
implementation of the MVCF device in ETAP, a
few application concepts need to be discussed
1 INTRODUCTION first.
The use of electrical fuses has been used in the
industry to protect electrical system, people and
equipment for over 150 years. Medium voltage
fuses used for transformer primary protection
have successfully fulfilled system protection
concerns by isolating fault current from the
equipment. Arc faults on the transformer or
equipment supplied by the transformer may yield
low current magnitudes (in particular with respect
to the primary side of the transformer). Such low
currents often cause long fuse clearing times.
Some of these clearing times may exceed 2
seconds. The end result of such long clearing
times is a high incident energy value (typically
over 40 cal/cm²). Medium voltage controllable
fuses can overcome some of these problems
since they can be configured to maintain
coordination and still operate in a relatively low
clearing time when compared to conventional E-
type fuses. The typical application of a MVCF
device is to install a secondary current relay
which controls the operation of controllable fuse
actuator module which bypasses the current into
a high speed current limiting fuse. There are two
methods which may be used to model MVCF
devices in ETAP.
Figure 1: Switchgear with no MVCF.
1
cal/cm². The primary transformer protection is an
E-rated fuse selected based on the transformer
protection criteria.
2
3.2 MVCF ETAP Implementation-Method II
3
Figure 8: Method II- MVCF Fuse TCC methods. Both methods yields the same results
but have slightly different application advantages
Similar to method I, to implement maintenance in ETAP.
mode, a second fuse curve can be activated by
means of the ETAP revision tool. The revision Method I advantages are:
tool allows the selection of an infinite number of
TCC curves for the same device. Figure 9 shows ETAP Sequence of Operation (both for short-
the MVCF curve activated in an ETAP revision. circuit and arc flash simulations) can graphically
This is a nice feature which allows the simulation simulate the operation of the bypass switch and
of this device without having to insert a third fuse fuse. This provides rich graphical instructional
into the diagram. simulation of the actual MVCF operation.
4 PERFORMANCE ANALYSIS
6 REFERENCES
Several arc flash simulations were used to The following documents were consulted during
evaluate the performance of the MVCF. This the creation of this white paper:
section presents a quick comparison of the
incident energy mitigation benefits when applying
the MVCF under two configurations (normal and [1] IEEE Standard 242, “IEEE Buff Book, IEEE-
with maintenance mode enabled). Note no 1986”
difference is expected in the results of table 1
when implementing the MVCF device in ETAP [2] Mohla, D.C; Driscoll, T.; Hamer, P.S----
using either method I or II. “Mitigating electric shock and arc flash energy —
a total system approach for personnel and
Table 1: Comparison of Incident Energy Results equipment protection”.
Equipment Configuration I.E. (cal/cm²)
E-RATED FUSE (No MVCF) ~40 +
[3] Mersen Tech topic Arc Flash Note 7 issue 1---
- “Using a Medium Voltage Controllable Fuse to
MVCF – NORMAL (Method I or II) ~14 mitigate arc flash energies on low voltage switch
MVCF – MAINT. (Method I or II) 1~2 gear”
4
7 Authors
Albert Marroquin: Arc Flash product manager at
ETAP. IEEE 1584 member and NFPA 70E
Electrical Branch Member. Over 15 years’
experience in arc flash analysis and simulation
software design.
http://etap.com/quality-
assurance/documentation/MVCFMersen.zip