N.V. Bergerat Monnoyeur S.A.: Information
N.V. Bergerat Monnoyeur S.A.: Information
405715A
Customer ref. : 0000001194 - Résidence P00079
Information
Test report
s = satisactory u = unsatisfactory
Form. OPE-D-06
OFF-LOAD RUN S/U SAFETY CHECKS Alarm setting S/U
Manual starting S Oil press 200 kPA S
Check for leaks S Water temp. 107 °C S
Manual stopping S Overspeed 1700 RPM S
Auto starting S Emergency stop S
Record specified readings after 5 m. S Overcranking 3 S
Opening Circuit
Auto stopping Cooldown 5 min. S N/A
Breaker
LOAD TEST (PF=1) 15 min 60 min 60 min 60 min
Load 0% 50% 100% 110%
Load kW 0 32 64 70
Min Current 0 49 97 107
Frequency Hz 52.2 51.3 50.6 50.2
Voltage AB V 382 382 385 385
Voltage BC V 382 383 385 385
Voltage AC V 382 382 384 384
Current A A 0 48 97 107
Current B A 0 48 97 107
Current C A 0 49 98 108
Jacket water temp °C 55 78 82 83
Lube oil pressure Bar 458 388 344 333
Exhaust temp °C 63 156 255 311
Ambiant temp °C 2 2 2 2
TRANSIENT RESPONSE Volt dip t (sec) Freq. Dip t (sec)
100% --> 0% Load (clear) 443 3 55,2 1
0% --> 50% Load (32) 362 1,5 50,3 0,5
50% --> 75% Load (48) 373 1,5 50,4 0,5
75% --> 100% Load (64) 364 2,5 50 0,5
100% --> 50% Load (32) 419 2,5 52,9 0,5
50% --> 0% Load (clear) 415 2,5 54,2 0,5
0% --> 75% Load (48) 353 2,5 48,7 0,5
75% --> 0% Load (clear) 422 2,5 54 0,75
FINAL CHECKS S/U
Coolant:- Rust inhibitor 5%
S
- Anti-Freeze -24%
Oil level S
Wiring diagram S
Books:
- Parts
S
- Maintenance and operating
manuels
Comments - recommendations:
- 2000hrs spare parts included in canopy
- binder(s) with operation manuals, parts, lists, schematics
- 2 sets of spare fuses
s = satisactory u = unsatisfactory
Form. OPE-D-06