ENERIA ref. : Project 405715 - Genset nr.

405715A
Customer ref. : 0000001194 - Résidence P00079

N.V. BERGERAT MONNOYEUR S.A. Job nr. : EE98 403

STANDARD DIESEL GENERATOR SET TEST REPORT

Information

GENSET Model DE88EO GENSET kVA: 88


Serial N° GT900663 GENSET Dash (-X) EO

ENGINE model 1104A-44TG2 ALTERNATOR model R1973L4


Serial N° E3M00706 Serial N° LWH00533

Service meter 3.5H Speed Governor model MEC


Voltage Regulator model M61FA655A

Generator set specification TYPE : DE88EO Serial N° : GT900663

Application: Continuous (C), Prime (P), Stand-by (S)


Rated power 80 KVA prime- 88 kVA standby / 64 EkW prime -70 EkW standby
Rated voltage 380 V
Rated frequency 50 Hz

Test report

PRE-RUNNING CHECKS S/U Comments-recommendations


Cooling:
~ Coolant S
~Jacket water heater S
Lubrication:
~Crank case ventilation S
~oil level S
Fuel (vented): S Fuel separator mounted
Air intake: S
Exhaust: S
Mounting: S
Starting:
~Batteries S not filled up/ not charged
~Battery charger S
~Alternator S
~Belts S
Generator:
~Space heaters S
Control panels:
~Monitors S
~Safety S
Circuit Breaker (adjusting) S 160A

s = satisactory u = unsatisfactory

Form. OPE-D-06
OFF-LOAD RUN S/U SAFETY CHECKS Alarm setting S/U
Manual starting S Oil press 200 kPA S
Check for leaks S Water temp. 107 °C S
Manual stopping S Overspeed 1700 RPM S
Auto starting S Emergency stop S
Record specified readings after 5 m. S Overcranking 3 S
Opening Circuit
Auto stopping Cooldown 5 min. S N/A
Breaker
LOAD TEST (PF=1) 15 min 60 min 60 min 60 min
Load 0% 50% 100% 110%
Load kW 0 32 64 70
Min Current 0 49 97 107
Frequency Hz 52.2 51.3 50.6 50.2
Voltage AB V 382 382 385 385
Voltage BC V 382 383 385 385
Voltage AC V 382 382 384 384
Current A A 0 48 97 107
Current B A 0 48 97 107
Current C A 0 49 98 108
Jacket water temp °C 55 78 82 83
Lube oil pressure Bar 458 388 344 333
Exhaust temp °C 63 156 255 311
Ambiant temp °C 2 2 2 2
TRANSIENT RESPONSE Volt dip t (sec) Freq. Dip t (sec)
100% --> 0% Load (clear) 443 3 55,2 1
0% --> 50% Load (32) 362 1,5 50,3 0,5
50% --> 75% Load (48) 373 1,5 50,4 0,5
75% --> 100% Load (64) 364 2,5 50 0,5
100% --> 50% Load (32) 419 2,5 52,9 0,5
50% --> 0% Load (clear) 415 2,5 54,2 0,5
0% --> 75% Load (48) 353 2,5 48,7 0,5
75% --> 0% Load (clear) 422 2,5 54 0,75
FINAL CHECKS S/U
Coolant:- Rust inhibitor 5%
S
- Anti-Freeze -24%
Oil level S
Wiring diagram S
Books:
- Parts
S
- Maintenance and operating
manuels
Comments - recommendations:
- 2000hrs spare parts included in canopy
- binder(s) with operation manuals, parts, lists, schematics
- 2 sets of spare fuses

Eneria repr. Name : L361 Customer repr. Name Date:


23/12/2016
Signature Signature

s = satisactory u = unsatisfactory