Catalogo de Samwha 2010
Catalogo de Samwha 2010
com/fc
SAMWHA
1960 1963.10. Company name changed into Samwha Electrical Industry, Inc.
Began production of High Voltage & Low Voltage Power Capacitor at first in Korea
1964.04. Began Motor Capacitor production at first in Korea
1968.08. Company name changed to Samwha Capacitor
1970 1970.01. Certified KS Mark for Low Voltage Power Capacitor at first in Korea [C4801 No.423]
1976.06. Listed on Stock Market and opened Initial Public Offering
1977.01. Certified KS Mark for High and Extra High Voltage Power Capacitor [C4802 No.1524]
1979.09. Certified KS Mark for Motor Capacitor [C4805 No.1827]
3. EMI Filter
2. Capacitor Bank 19
2-1. Capacitor Bank [Purpose]
① General Capacitor Bank
② Harmonic Filter Capacitor Bank
2-2. Capacitor Bank Type
① Cubicle Capacitor Bank
② Open-rack Capacitor Bank
③ Pole Mounted Capacitor Bank
2-3. Capacitor Bank Protection
① NVS [Neutral Voltage Sensor]
② NCT [Neutral Current Transformer]
3.SVC 26
4.Special Capacitor 28
4-1. A.C Harmonic Filter
4-2. Zero Sequence Filter(ZSF)
4-3. Hybrid Harmonic Filter(HHF)
4-4. L-C Complex Harmonic Filter(LCF)
4-5. Active Power Harmonic Filter(APF)
4-6. Intelligent Var Compensator(IVC)
4-7. Low Frequency Induction Furnace Capacitor
4-8. Water Cooling Capacitor
4-9. Surge Absorbing Capacitor
4-10. Grounding Capacitor
4-11. Pulse Power Capacitor
5. Reactor 47
5-1. Series Reactor
5-2. Discharging Coil
6.Appendix 56
6-1. Capacity Calculation
6-2. Tips for Handling Capacitor
6-3. Maintenance
6-4. Certificate and Test Report
6-5. Order Form
Samwha
1. Capacitor
1. Capacitor
〉 Application
The capacitors are designed for power factor correction and harmonics filtration in power network.
They are all-film dielectric and impregnated with an environmentally friendly, Non-PCB biodegradable
insulating oil.
In addition each capacitor is provided with an internal discharge resistor.
All SAMWHA capacitors comply with most national and international capacitor standards.
Capacitor benefits to • Improve Power Factor
• Reduce Line Losses
• Decrease Voltage Drop
Through that it helps greater Energy Efficiency
〉 Product Scope
• Power Range Single Phase 25kvar to 1000kvar
Three Phase 50kvar to 500kvar
• Voltage Range Single Phase 1000V to 22000V
Three Phase 1000V to 11000V
• Frequency 50Hz / 60Hz
• Applicable Standards IEC, ANSI / IEEE, NEMA
〉 Technical Data
Capacitor Loss 0.2W/kvar or Less with Internal fuse
[Under Stabilized Condition] 0.15W/kvar or Less without Internal fuse
Ambient Temperature -40℃ / A [+40℃], B [+45℃], C [+50℃], D [+55℃]
UN + 10% [up to 8 hours daily]
UN + 15% [up to 30 minutes daily]
Max overvoltage Umax
UN + 20% [up to 5 minutes]
UN + 30% [up to 1 minute]
Max overcurrent IS 1.3 × IN
Painting Color Munsell No. 5Y 7/1
Reference Standard IEC 60871
〉 Bushings Characteristics
Creepage Strike Total 60Hz Withstand Weight
BIL [kV] Distance Distance Height
Dry Test [kV] Wet Test [kV] [kg]
[mm] [mm] [mm]
60 191 109.2 188.1 60 45 0.87
75 191 109.2 188.1 60 45 0.87
95 318 162.6 235.6 70 55 1.23
150 438 193.0 266.8 80 60 1.75
175 635 223.5 287.9 90 70 2.14
200 720 302.4 388.9 100 80 2.79
* The standard terminal sieze is M12, but M16 could be applied according to rated voltage.
* Same Bushing is used on 60 and 75kV BIL of capacitor units.
* Bird Cap and Parallel-groove connector with all bushings is supplied, and it is applicable to Copper or
Aluminum conductor [14~100㎟ 2line]
* Applied bushing could be changed by special requirements
Samwha 4
Samwha
1. Capacitor
Creative TEchnology Provider
5 Samwha
Samwha
1. Capacitor
Samwha 6
Samwha
1. Capacitor
Creative TEchnology Provider
7 Samwha
Samwha
1. Capacitor
Samwha 8
Samwha
1. Capacitor
Creative TEchnology Provider
9 Samwha
Samwha
1. Capacitor
Samwha 10
Samwha
1. Capacitor
Creative TEchnology Provider
11 Samwha
Samwha
1. Capacitor
〉 Product Scope
• Power Range 0.2kvar to 150kvar
• Voltage Range 220V to 1000V
• Frequency 50Hz / 60Hz
• Applicable Standards IEC, AISI / IEEE, NEMA
〉 Technical Data
Location Indoor
Capacitor Loss
0.5W/kvar
[Under stabilized Condition]
Ambient Temperature -25℃ / A [+40℃], B [+45℃], C [+50℃], D [+55℃]
UN + 10% [up to 8 hours daily]
UN + 15% [up to 30 minutes daily]
Max overvoltage Umax
UN + 20% [up to 5 minutes]
UN + 30% [up to 1 minute]
Max overcurrent IS 1.3 × IN
Painting Color Munsell No. 5Y 7/1
Reference Standard IEC 60831-1
Samwha 12
Samwha
1. Capacitor
Creative TEchnology Provider
* Approximate dimensions and weights are given above. Please contact to factory for exact dimensions
of a particular unit before order.
13 Samwha
Samwha
1. Capacitor
Samwha 14
Samwha
1. Capacitor
Creative TEchnology Provider
15 Samwha
Samwha
1. Capacitor
〉 Product Scope
• Power Range 0.2kvar to 50kvar
• Voltage Range 220V to 1000V
• Frequency 50Hz / 60Hz
• Applicable Standards IEC, ANSI / IEEE, NEMA
〉 Technical Data
Location Indoor
Capacitor Loss
1.5W/kvar
[Under Stabilized Condition]
Ambient Temperature -25℃ / A [+40℃], B [+45℃], C [+50℃], D [+55℃]
UN + 10% [up to 8 hours daily]
UN + 15% [up to 30 minutes daily]
Max overvoltage Umax
UN + 20% [up to 5 minutes]
UN + 30% [up to 1 minute]
Max overcurrent IS 1.3 × IN
Reference Standard IEC 60831-1
〉 Disconnector Function
Expansion caused by
overpressure
Samwha 16
Samwha
1. Capacitor
Creative TEchnology Provider
17 Samwha
Samwha
1. Capacitor
Samwha 18
Samwha
Creative TEchnology Provider
2. Capacitor Bank
① General Capacitor Bank
2. Capacitor Bank
〉 Application
Capacitor Bank is an economical method of reducing the reactance of high and extra high voltage lines.
And It controls the level of voltage supplied by reducing or eliminating the voltage drop and increase
power transfer in network.
Capacitor Bank is relatively inexpensive and can be easily installed with all accessories anywhere on the
network.
19 Samwha
Samwha Creative TEchnology Provider
〉 Application
Most type of equipment in electrical systems generate harmonics.
Harmonics are not only found in industrial networks. It can spread into the distribution network and
cause problems for other power users.
Each plant is unique and needs its own special technical solution to prevent it.
Harmonic Filter Bank usually consists of a capacitor which is connected in series with a reactor.
The components are dimensioned to create a series resonance circuit for a required frequency.
We can help you to calculate and design filters which will reduce interference and interruption on your
network.
Samwha 20
Samwha
Creative TEchnology Provider
2. Capacitor Bank
〉 Application & Construction
This is a fixed reactive compensation system for individual motor compensation.
There is a range of metal enclosed capacitor banks for a variety of medium voltage applications.
The product range consists of indoor and outdoor solutions, which can be single step fixed or multi-step
switched.
According to the requirement it is possible to include also inrush current reactors or other protection and
measuring elements
It will automatically compensate the network to maintain a preset level of power factor.
〉 Available options
•Circuit Breaker
•Disconnect Switch
•Earthing Switch
•Inrush or Detuning reactor
•Discharge Coil
•Unbalance Protection
•Automatic Power Factor Controller
<<3.3kV 3P 50Hz 300kvar>> <<10kV 3P 50Hz 700kvar>> <<APFCR with Dry Type Capacitor>>
21 Samwha
Samwha Creative TEchnology Provider
The Samwha Open-rack Capacitor Bank type is the most common capacitor bank and available with
internally fused capacitor units.
Samwha 22
Samwha
Creative TEchnology Provider
2. Capacitor Bank
〉 Application & Construction
The Samwha Pole Mounted Capacitor Bank provide voltage support, reducing system losses, improving
power factor in the network.
The installation is in a distribution network.
〉 Composition equipments
•Cut-off Switch
•Capacitor Switch
•Surge Arrester
•Voltage Transformer
•Controller
•Capacitors
System Dimension
Frequency Capacity Number of
Voltage [mm]
[Hz] [kvar] Capacitor unit
[kV] A B C
1000 334kvar x 3EA 575 1600 990
1500 500kvar x 3EA 575 1600 1100
12
2000 334kvar x 6EA 575 2185 990
2500 417kvar x 6EA 575 2275 990
50 / 60
1000 334kvar x 3EA 575 1600 990
1500 500kvar x 3EA 575 1600 1100
24
2000 334kvar x 6EA 575 2185 990
2500 417kvar x 6EA 575 2275 990
* Approximate Dimensions and Capacities are given above. Please contact factory for your projects.
23 Samwha
Samwha Creative TEchnology Provider
〉 General
Capacitor Bank is needed to set proper protection systems to protect Capactor bank against faults occurring
within the bank including those inside the capacitor units, and to protect Capacitor bank against system
diturbances and faults.
Generally, the method of detecting neutral value[voltage or current] is selected as the protection for
capacitor bank system.
〉 Application
NVS is the protection system using voltage unbalance signals to alarm or shut down the bank
in case of faults that may lead to significant damages.
To measure the unbalance of voltage, the voltage-sensing device[NVS] is used.
Auxiliary resistor
Samwha 24
Samwha
Creative TEchnology Provider
2. Capacitor Bank
〉 Application
NCT is the protection system using current unbalance on neutrals composed in Double Wye Capacitor
Banks signals to alarm or shut down the banks.
To measure the unbalance of current, the current transformer with low current value is used.
The current transformer ration and relay rating is seleted for the desired sensitivity.
NCT protection system is normally used on wide range of level from high to extra voltage capacitor
banks, and can detect faults in all kinds of capacitor units.
Current Transformer with rated current value 1 is manufactured,
therefore it is useful to protect Internal Fuse Type Capacitor Bank which has low fault current value on
neutral.
25 Samwha
Samwha Creative TEchnology Provider
3. SVC
〉 Application
SVC[Static Var Compensator] is an advanced capacitor
3. SVC
〉 SVC benefits to
•Near-instantaneous response to changes in the system voltage
•Maximize power compensation
•Remove Harmonic and reduce distortion of voltage through filter capacitors connected in parallel
•Keep three phased load balance
•Make smooth flicker voltage
•Maximize user’s economic benefits
•SVC for 160ton Ac Consteel Electric Arc Furnace •SVC for 170ton Ac Consteel Electric Arc Furnace
Samwha 26
Samwha
Creative TEchnology Provider
3. SVC
〉 Feature of Samwha SVC
•MOU [Memorandum Of Understanding] with CEPRI [China Electric Power Research Institute]
•Verifying Power supply network, designated SVC system, Harmonic, designated function etc
•Using digital control method, active responding time is fast with precision.
•Extremely speedy responding of Thyristor controler [10 ~ 15ms]
•Thyristor valve was designed horizontal type, so operation is safety and repair is convenience
•Water cooling system perceives total 13 variables, such as perceives temperature, pressure, water
level and resistance rate etc to make sure safety operation.
•Drainage system connected paralled with water conduit makes high reliability of Thyristor valve throgh
well temperature control
•Remote control and automatic system interface
3. SVC
〉 SVC installation
Before installing SVC, 22kV current wave After installing SVC, 22kV current wave
SVC dedicates to Power quality of Electric furnace improvement, Power factor improvement, Safety
operation on transmission line.
27 Samwha
Samwha Creative TEchnology Provider
4. Special Capacitor
〉 Application
Harmonic is commonly generated in electricity system due to devices using Thyristor.
It can causes electricity accidents and interference in the system
Therefore, the application of filter facilities is essential to prevent the effect
of Harmonic in the system and use electricity more efficiently.
〉 What is harmonic
Cyclic distortion wave is expressed as the sum of sine wave [50Hz], the integral number frequency and
major sine wave, integral number [50Hz] frequency.
This integral number frequency is called harmonic wave and according to the change of amplitude and
phase, wave form is changed resulting in synthetic distortion.
4. Special Capacitor
Combined distortion wave is manifested in distorted sine wave form. This form can be analyzed into
one fundamental wave [50Hz] which has random cycle and major sine wave which has integral number
frequency or subharmonic frequency.
If the frequency of it is higher than the fundamental frequency, it is called harmonics and if the
frequency of it is lower, it is called fractional harmonic wave or subharmonic.
For example, an distorted wave form comprising sine wave type [50Hz] and 5th [250Hz] and 7th [350Hz]
wave form is analyzed as following :
= + +
Samwha 28
Samwha
Creative TEchnology Provider
4. Special Capacitor
improvement of economics]
•Absorption and removal of harmonics
•Resolving the problem of resonance between inductive and capacitive in the system.
•Keeping the performance and lifetime of the facility high by keeping normal voltage
Zfn·Zsn In
Vn = ───── · In = ─────
Zfn + Zsn Yfn + Ysn
Zfn Ysn Zsn Ysn
Vn = ───── · In = ───── · In , Ifn = ───── · In = ───── · In
Zfn + Zsn Yfn + Ysn Zfn + Zsn Yfn + Ysn
29 Samwha
Samwha Creative TEchnology Provider
Samwha 30
Samwha
Creative TEchnology Provider
1. General
Increasing use of computer and electric home appliance, the neutral current zero sequence
harmonic in line make variety types of disturbances in system.
ZSF(Zero Sequence Filter) is easy to install with electric accessories and
it can reduce this large neutral current up to 90% depending on the installed position.
3. Application
•Applicable load : Computer, OA appliance, Electronic fluorescent lamp, Single Phase SCR heater and
UPS etc
•Applicable system : Single phase nonlinear loads on Three phase four wire systerm
•Applicable place : Office/Commercial Building, School, Apartment, Department, Factory, Medical center etc.
〉 Features
•Neutral impedence adjuster upon request •Ammeter displaying the neutral current in option
•Easy to Install •Easy to select
4. Special Capacitor
•Increasing power quality
〉 Effects
•Protect heating and loss of line and neutral cable that is effected by zero sequence harmonic current
•Reduce unbalance of line current •Reduce system loss
•Protect overinvestment by increasing capacity
•Reduce K-factor rating of load current at main transformer.
31 Samwha
Samwha Creative TEchnology Provider
1. General
The Hybrid Harmonic Filter(HHF) enable most three phase non-linear load to comply with both the voltage and
current distortion limits of IEEE Std.519-1992 and other international limits such as
AS-2279, EN61000-3-4, and BS G5/4.
Comparing with the classical broad band harmonic filter, the HHF have only 30% of
capacitance with better filtering. Less capacitance can minimize leading current at light
loading condition.
2.Problems of Harmonic
•Resonance at Power •Over voltage trip and malfuction of Drive
•Trip the Relay or cut fuse
3. Application
•Applicable loads : Inverter, UPS, Elevator, AC/DC motor drive, Diode/SCR Rectifier,
Induction heater, DC power supply, HVAC system, Fan and Pumps etc.
•Applicable place : Office/Commercial building, School, Shopping Mall,
Department store, Apartment, Hospital, Factory etc
•Applicable system : Low Voltage 3P nonlinear loads
〉 Features
4. Special Capacitor
Samwha 32
Samwha
Creative TEchnology Provider
1. General
The motor using inverter is causing riffle wave form on voltage, and it causes many problems on the
system like breaking down dielectric.
LCF can convert PWM wave form to sine wave form making more safe operation in the system.
2. Problems of Harmonic
•Destroying dielectric in Motor by spike •Damage on Cable
•Damage on Voltage raising transformer •Decreasing productivity
•Malfuction and reduced life spam of Inverter by inversed voltage.
•Instantaneous Over voltage phenomenon by distorted voltage wave form
•Malfuntion of precision apparatus •Over heat on distribution line
3. Application
•Applicable load : Motor and machines using inverter(Between inverter and motor)
•Applicable system: 220V, 380V, 440V, 1000HP
•Applicable place : Plants, Steel Mills, power plant, sewage disposal plants, Garbage dumps etc
〉 Features
•Make smooth voltage and current wave form •Reduce peak voltage of motor
•Reduce voltage reflection and surge impedance
4. Special Capacitor
〉 Effects 〉 Wave
form with LCF
•Prevent dielectric destruction PWM wave form
•Increase productivity and quality
•Increase system communication quality and life span Voltage
Currint
33 Samwha
Samwha Creative TEchnology Provider
1. General
The proliferation of nonlinear loads such as static power converters and arc furnaces results in variety of
undesirable phenomena in the operation of power systems.
The most important among these are harmonic contamination, increased reactive power demand and
power system voltage fluctuations.
Harmonic currents increase power systems losses, excessive heating in rotating machinery, can create
significant interference with the power line communication.
The harmonic is a growing problem for both electricity suppliers and consumers.
2. Problems of Harmonic
•Malfunction of precision control •Capacitor overloading and failures
•High current in neutral conductors •Excitation of network resonance
•Damage to sensitive equipment •Overheating of transformer, motor and cables
•Frequent tripping of circuit breakers
3. Application
•Applicable load : Welding Machine, Electrolyzer in Chemical Factory, Electrolytic machine of ceramic
plasitc, Arc furnace, Crain etc
•Applicable system : 380V, 440V, 50-300A
•Applicable place : Steel Mills, Chemical Plants, Metal mills, Harbors etc
4. Special Capacitor
〉 Features
•Patent No.0459000 as Three Phase fourwire active power filter control device
•Meet IEEE standard 519-1992 •Solve Power Quality Problems
•Parallel connection allows easy retrofit for large system •Curtailment of maintenance fee
〉 Installation Effect
<Before installing APF> <After installing APF> <Before installing APF> <After installing APF>
Samwha 34
Samwha
Creative TEchnology Provider
1. General
Intelligent Var Compensator(IVC) is the product designed to improve power quality
in the systems with welding, crane and many unspecified loads which is generating reactive power.
2. Application
•Applicable loads : Welding machines, Arc furnace, unspecified loads generating reactive power,
•Applicable system: 380V, 440V, 30~1800kvar
•Applicable place : Steel mills, Chemical plants, Metal mills, Harbors etc.
〉 Features
•Patent No.0459000
•3Phase 4Wire reactive power compensation system with linear response characteristics.
•Prevent the voltage drop and flicker with 5-20ms response speed.
•Control the reactive power using power switching sockets without transient
•Protect senstive electric machines and save energy
•Exact and fast power factor improvement •Long life span of swiching sockets and capacitors
〉 Effects
•Power factor on the secondary side of transformer is improved at 98%
•Average current is decreased to 30% •Allowance capacity of transformer is increased.
4. Special Capacitor
•Prevent voltage flicker phenomenon through resolving reactive power in real-time
35 Samwha
Samwha Creative TEchnology Provider
〉 Product Scope
• Installation Place : Indoor
• Ambient Temperature for use : -20℃ ~ +40℃ [below 35℃ average for 24 hours]
〉 Technical Data
Tolerance -5 ~ +15% [at 20℃]
Withstand Voltage 10 seconds of 2.0 times of rated voltage between mutual terminals
Insulation Level 2UN + 2kV or 3kV, whichever is the higher, for 10s
Max Overvoltage Less than 105% of rated voltage : within 12hours per day
120% of rated capacity [less than 60Hz], 115% of rated capacity [more
Max overcurrent
than 60Hz] or less
Capacitor Loss
0.35% [rated voltage, 20℃] or less
[Under stabilized condition]
〉 Diagram
4. Special Capacitor
Samwha 36
Samwha
Creative TEchnology Provider
4. Special Capacitor
37 Samwha
Samwha Creative TEchnology Provider
Temperature of
Cooling water exit temperature less than 45℃
Cooling Water
Ambient Temperature More than 0℃
Tolerance Within ± 10% of rated capacity
Withstand Voltage 2.15 times of rated voltage, 10 seconds
Flux of Cooling Water More than 5ℓ per minute
Pressure of K : Series Logarithm of Coolling Coil
Less than 10kg/㎠ Notes) Pipe Dia(12Ø 1.0t)
〉 Caution
Since the outer case of capacitor is unilateral electrode, please be sure to use the insulated rack in
installation.
When more than 2 capacitors are connected in paralleled, there should be space at least 35mm.
The flow quantity of cooling water shall be more than 5ℓ/min.
In case when capacitor is kept at subzero temperature, remove the water entirely from copper pipe
Samwha 38
Samwha
Creative TEchnology Provider
Figure 1 Figure 2
4. Special Capacitor
Figure 3 Figure 4
39 Samwha
Samwha Creative TEchnology Provider
〉 Product Scope
• Installation Place : Indoor / Outdoor
• Ambient Temperature : -20℃ ~ +40℃ [below average 35℃ per day, below 25℃ average per year]
〉 Technical Data
Tolerance -5% ~ +15% [at 20℃], less than 108% of unbalanced ratio between phases
Below 110% of rated voltage : within 8 hours per day
Below 115% of rated voltage : within 30 minutes per day
Max overvoltage
Below 120% of rated voltage [less than 2 times of 5 min. per month]
Below 130% of rated voltage [less than 2 times of 1 min. per month]
Max overcurrent Transient current 130% of rated current allowed
Between case and all of terminals
Line voltage Test voltage
3300V 16kVAC [1 min.] 45kVDC [10 sec.]
Withstand Voltage 6600V 22kVAC [1 min.] 60kVDC [10 sec.]
4. Special Capacitor
〉 Diagram
Figure 1 Figure 2
Samwha 40
Samwha
Creative TEchnology Provider
Figure 1 Figure 2
4. Special Capacitor
* Approximate Ratings and Dimensions are given above. Please contact factory before order.
41 Samwha
Samwha Creative TEchnology Provider
dVc 1 1
Ip = C ── + ─ Vc = ─ [2Vo - Vo]
dt R Z
d
To rearrange the expression ── = P, Vo = EoH[t]
dt
R+Z 2Eo
( (
PVc = ── Vc = ── H[t]
CRZ CZ
R+Z
( CRZ
── ( = α
2Eo 1 2Eo
Vc = ── × ── H[t] = ── [1-e-αt] H[t]
CZ P+α αCZ
When Z and R is constant and C is changed, the terminal voltage of the rotator Vc is as in the figure B.
From this, it can be seen that the wave height value is reduced
according to the value of C or R. When R = ∞ and C = 0.3㎌, the terminal voltage of the rotator is
reduced to 1/2 of invasion wave, which shows the effects of surge absorbing capcitor.
4. Special Capacitor
Figure A
Voltage
Figure B
Time(㎲)
Samwha 42
Samwha
Creative TEchnology Provider
〉 Product Scope
•Installation Place : Indoor / Outdoor
•Ambient Temperature : -20℃ ~ +40℃[below 35℃ average per day, below 25℃ average per year]
〉 Technical Data
Tolerance -5% ~ +15% [at 20℃], less than 108% of unbalanced ratio between phases
Below 110% of rated voltage : within 12 hours per day
Below 115% of rated voltage : within 30 minutes per day
Max overvoltage Below 120% of rated voltage : within 5 minutes
Below 130% of rated voltage : within 1 minute
Below 182% of rated voltage : within 2 seconds
Max overcurrent Transient current 130% of rated current allowed
Between case and all of terminals
Line voltage Test voltage
Withstand Voltage 3300V 10kVAC [1 min.] 30kVDC [10 sec.]
6600V 16kVAC [1 min.] 45kVDC [10 sec.]
Capacitor Loss Less than 0.35% [at rated voltage, 20℃]
4. Special Capacitor
Painting Color Munsell no. 5Y 7/1
Reference Standard JEM1362 [1999]
〉 Diagram
43 Samwha
Samwha Creative TEchnology Provider
〉 Operation Principle
In 3 phase circuit, for 1 line grounding current is calculated from the following formula.
lg = 3jωCEa = j√
3E×2πfC
Ig : Grounding Current [A] E : Line Voltage [V]
Ea : Phase Voltage [V] C : Equivalent Ground Capacitance [C = C1+C2]
IC1 [Ground fault current Ig in figure A - charged current after zero phase current transformer [ZCT]]
passes the zero phase current transformer. Therefore, ground fault current Ig1 passing ZCT can be
calculated from the following formula.
√
Ig1 = 3E×2π×f×C1
When the distance between transformer and ZCT is small, ground capacity in line is small and
penetration ground fault current Ig1 is not enough to move circuit breaker. Therefore, use capacitor for
earthing to improve ground capacity in line.
For example, when E = 3300V, C1 = 0.5㎌, and f = 50Hz in figure B, ZCT penetration ground fault current
4. Special Capacitor
is as following :
√
Ig1 = 3×3300×2π×60×0.5×10-6 = 1.08A
Since detecting current of grounding breaker is selected to be 0.1 ~ 0.8A, it is good to select the value
of C1 to be more than this value
[C1 is equivalent to 1 phase and in case of C1 = 0.5㎌, capacitor for grounding of 0.5㎌×3 is to be
selected]
Grounding Transformer
Grounding Capacitor
Grounding Transformer
Grounding Accident
Samwha 44
Samwha
Creative TEchnology Provider
45 Samwha
Samwha Creative TEchnology Provider
Samwha 46
Samwha
Creative TEchnology Provider
5. Reactor
〉 Application
Reactor is used in conjuction with capacitor banks in series.
Its main function is to compensative or produce reactive power.
According to the purpose of use, reactor helps to limit inrush or short circuit current, filter out harmonics.
•Product scope
Installation Place : Indoor / Outdoor
Ambient Temperature for Use : -20℃ ~ +40℃[below 35℃ average per day]
Technical Data
Max overcurrent Less than rated current 120% of effective value of resultant
Oil type : winding 55℃[resistance method], impregnant 50℃[thermometer
Temperature Rise
method]
Insulation resistance More than 500MΩ [1000VDC : Oil type]
Reference standard IEC 289
47 Samwha
Samwha Creative TEchnology Provider
Figure 1 Figure 2
240 4000 100.8 HSR20KA-240 1720 1250 1120 320 700 650 580 1450
300 5000 126.0 HSR20KA-300 1800 1350 1220 350 800 650 700 2100 2
360 6000 151.2 HSR20KA-360 1800 1350 1220 350 800 650 780 2200
450 7500 189.0 HSR20KA-450 1900 1500 1550 400 800 750 850 2500
540 9000 226.9 HSR20KA-540 2000 1600 1600 400 1000 750 900 2600
720 12000 302.5 HSR20KA-720 2100 1600 1700 400 1000 750 1200 3500
900 15000 378.1 HSR20KA-900 2100 1600 1800 400 1000 750 1850 4300
1200 20000 504.2 HSR20KA-1200 2200 1650 2000 400 1000 800 2200 5100
* Approximate Ratings and Dimensions are given above. Please contact factory before order.
Samwha 48
Samwha
Creative TEchnology Provider
Figure 1 Figure 2
6600 30 500 HSR-60A-30 43.70 87.50 1200 680 640 200 400 400 180 370
36 600 HSR-60A-36 52.40 104.80 1200 730 680 220 400 400 190 390
& 229 114
42 700 HSR-60A-42 61.20 122.40 1200 730 730 220 400 400 210 420
3300 45 750 HSR-60A-45 65.30 131.20 1200 730 730 220 400 400 210 430
48 800 HSR-60A-48 70.00 140.00 1280 730 770 220 400 450 210 440
54 900 HSR-60A-54 78.70 157.40 1280 730 770 220 400 450 260 450
60 1000 HSR-60A-60 87.50 175.00 1280 760 770 220 400 450 260 550 2
72 1200 HSR-60A-72 105.00 210.00 1280 760 770 220 400 450 340 600
90 1500 HSR-60A-90 131.00 262.00 1350 1050 800 250 560 525 500 650
120 2000 HSR-60A-120 175.00 349.00 1500 1050 880 300 560 525 550 1100
150 2500 HSR-60A-150 219.00 437.00 1550 1150 950 300 660 525 560 1200
180 3000 HSR-60A-180 262.00 535.00 1550 1150 1000 300 660 525 600 1400
240 4000 HSR-60A-240 350.00 700.00 1700 1200 1100 300 660 600 700 1600
* Approximate Ratings and Dimensions are given above. Please contact factory before order.
49 Samwha
Samwha Creative TEchnology Provider
Figure 1 Figure 2
18 300 HSR-60B-18 26.20 52.50 500 550 370 150 260 225 160 735
6600 21 350 HSR-60B-21 60.60 61.20 510 550 370 150 260 225 170 770
& 24 400 HSR-60B-24 229 114 35.00 70.00 550 600 380 170 360 250 180 770 1 or 2
3300 30 500 HSR-60B-30 43.70 87.50 550 600 380 170 360 250 220 780
36 600 HSR-60B-36 52.40 104.80 570 600 380 170 360 250 240 800
42 700 HSR-60B-42 61.20 122.40 590 650 400 180 400 300 280 800
45 750 HSR-60B-45 65.60 131.20 590 650 400 180 400 300 300 800
48 800 HSR-60B-48 70.00 140.00 590 650 430 180 400 300 320 800
54 900 HSR-60B-54 78.70 157.50 570 700 430 200 400 300 350 720
60 1000 HSR-60B-60 87.50 175.00 570 700 430 200 400 300 400 720
72 1200 HSR-60B-72 105.00 210.00 730 800 470 250 460 300 420 880
90 1500 HSR-60B-90 131.20 262.40 770 850 880 250 460 300 550 920
* Approximate Ratings and Dimensions are given above. Please contact factory before order.
Samwha 50
Samwha
Creative TEchnology Provider
Figure 1 Figure 2
18 300 HSR-04A-18 393.60 787.30 950 630 530 180 300 375 110 230 2
24 400 HSR-04A-24 524.80 1049.70 1050 650 550 200 360 375 130 280
30 500 HSR-04A-30 656.00 1312.20 1220 680 640 200 400 400 150 350
* Approximate Ratings and Dimensions are given above. Please contact factory before order.
51 Samwha
Samwha Creative TEchnology Provider
Figure 1 Figure 2
& 4.5 75 HSR-04B-4.5 15.2 7.62 98.40 196.80 370 350 220 100 320 150 50 470 260 1 or 2
220 6 100 HSR-04B-6 131.20 262.40 370 380 220 120 340 150 65 470 260
9 150 HSR-04B-9 196.80 393.60 385 400 220 120 360 150 80 485 270
12 200 HSR-04B-12 262.40 524.80 430 450 220 130 400 175 100 500 280
15 250 HSR-04B-15 328.00 656.00 400 450 300 130 400 175 115 530 280
18 300 HSR-04B-18 393.60 767.30 500 500 300 150 460 175 125 560 280
24 400 HSR-04B-24 524.80 1049.70 550 550 300 180 500 200 160 610 450
30 500 HSR-04B-30 656.00 1312.20 550 600 300 180 500 200 200 600 450
* Approximate Ratings and Dimensions are given above. Please contact factory before order.
Samwha 52
Samwha
Creative TEchnology Provider
〉 Product Scope
• Installation Place : Indoor[Dry type] or Outdoor[Oil type]
• Technical Data
Altitude Up to 1000m
Ambient Temperature -20℃ ~ +40℃ [Not exceed average 35℃]
Discharge Voltage 50V or Lesser in 5seconds
Max overvoltage 110% rated voltage or Less
〉 Connection
SC : Shunt Capacitor
SR : Shunt Reactor
DC : Discharge Coil
53 Samwha
Samwha Creative TEchnology Provider
Figure 1 Figure 2
Samwha 54
Samwha
Creative TEchnology Provider
55 Samwha
Samwha Creative TEchnology Provider
6. Appendix
< Capacity Table >
* Use this table to calculate necessary capacity according load quantity and present power factor.
Power Factor After Imporovemet = cosθ2
1.00 0.99 0.98 0.97 0.96 0.95 0.94 0.93 0.92 0.91 0.90 0.89 0.88 0.87 0.86 0.85 0.84 0.83 0.82 0.81 0.80
0.50 173 159 153 148 144 140 137 134 131 128 125 122 119 117 114 111 109 106 103 101 98
0.51 169 154 148 144 140 136 132 129 126 123 120 118 115 112 109 107 104 102 99 96 94
0.52 164 150 144 139 135 131 128 125 122 119 116 113 110 108 105 102 100 97 95 92 89
0.53 160 146 140 135 131 127 124 121 117 114 112 109 106 103 101 98 95 93 90 88 85
0.54 156 142 136 131 127 123 120 116 113 110 108 105 102 99 97 94 91 89 86 84 81
0.55 152 138 132 127 123 119 116 112 109 106 104 101 98 95 93 90 87 85 82 80 77
0.56 148 134 128 123 119 115 112 109 105 102 100 97 94 91 89 86 83 81 78 76 73
0.57 144 130 124 119 115 111 108 105 102 99 96 93 90 88 85 82 80 77 74 72 69
0.58 141 126 120 115 111 108 104 101 98 95 92 89 87 84 81 79 76 73 71 68 66
0.59 137 123 117 112 108 104 101 97 94 91 89 96 83 80 78 75 72 70 67 65 62
0.60 133 119 113 108 104 100 97 94 91 88 85 82 79 77 74 71 69 66 64 61 58
0.61 130 116 110 105 101 97 94 90 87 84 82 79 76 73 71 68 65 63 60 58 55
0.62 127 112 106 102 97 94 90 87 84 81 78 75 73 70 67 65 62 59 57 54 52
0.63 123 109 103 98 94 90 87 84 81 78 75 72 69 67 64 61 59 56 54 51 48
0.64 120 106 100 95 91 87 84 81 78 75 72 69 66 63 61 58 56 53 50 48 45
0.65 117 103 97 92 88 84 81 77 74 71 69 66 63 60 58 55 52 50 47 45 42
0.66 114 100 94 89 85 81 78 74 71 68 65 63 60 57 55 52 49 47 44 41 39
0.67 111 97 91 86 82 78 75 71 68 65 62 60 57 54 52 49 46 44 41 38 36
Power Factor Before Imporovement = cosθ1
0.68 108 94 88 83 79 75 72 68 65 62 59 57 54 51 49 46 43 41 38 35 33
0.69 105 91 85 80 76 72 69 65 62 59 57 54 51 48 46 43 40 38 35 33 30
0.70 102 88 82 77 73 69 66 63 59 56 54 51 48 45 43 40 38 35 32 30 27
0.71 99 85 79 74 70 66 63 60 57 54 51 48 45 43 40 37 35 32 29 27 24
0.72 96 82 76 71 67 64 60 57 54 51 48 45 42 40 37 34 32 29 27 24 21
0.73 94 79 73 69 64 61 57 54 51 48 45 42 40 37 34 32 29 26 24 21 19
0.74 91 77 71 66 62 58 55 51 48 45 43 40 37 34 32 29 26 24 21 19 16
0.75 88 74 68 63 59 55 52 49 46 43 40 37 34 32 29 26 24 21 18 16 13
0.76 86 71 65 60 56 53 49 46 43 40 37 34 32 29 26 24 21 18 16 13 11
0.77 83 69 63 58 54 50 47 43 40 37 35 32 29 26 24 21 18 16 13 11 8
0.78 80 66 60 55 51 47 44 41 38 35 32 29 26 24 21 18 16 13 10 8 5
0.79 78 63 57 53 48 45 41 38 35 32 29 26 24 21 18 16 13 10 8 5 2.6
0.80 75 61 55 50 46 42 39 36 32 29 27 24 21 18 16 13 10 8 5 2.6
0.81 72 58 52 47 43 40 36 33 30 27 24 21 18 16 13 10 8 5 2.6
0.82 70 56 50 45 41 37 34 30 27 24 21 19 16 13 11 8 5 2.6
0.83 67 53 47 42 38 34 31 28 25 22 19 16 13 11 8 5 2.6
0.84 65 50 44 40 35 32 28 25 22 19 16 13 11 8 5 2.6
6. Appendix
0.85 62 48 42 37 33 29 26 23 19 16 14 11 8 5 2.7
0.86 59 45 39 24 30 26 23 20 17 14 11 8 5 2.6
0.87 57 42 36 32 28 24 20 17 14 11 8 6 2.7
0.88 54 40 34 29 25 21 18 15 11 8 6 2.8
0.89 51 37 31 26 22 18 15 12 9 6 2.8
0.90 48 34 28 23 19 16 12 9 6 2.8
0.91 46 31 25 21 16 13 9 6 3
0.92 43 28 22 18 13 10 6 3.1
0.93 40 25 19 14 10 7 3.2
0.94 36 22 16 11 7 3.4
0.95 33 19 13 8 3.7
0.96 29 15 9 4.1
0.97 25 11 4.8
0.98 20 6
0.99 14
Samwha 56
Samwha
Creative TEchnology Provider
1 − cos 2 θ1 1 − cos 2 θ2
Qc = P × 1
− 2
cosθ11 cos θ 22
2. The units to express capacity are ‘kvar’ or ‘㎌’. Following formula is for conversion of those two units ;
Qc = 2 × π × f × C × V2 × 10-9[kvar]
57 Samwha
Samwha Creative TEchnology Provider
Samwha 58
Samwha
Creative TEchnology Provider
6-3 Maintenance
< Attentions for Installed Place >
1] Ambient temperature shall not exceed -25℃ ~ +45℃ [average temperature per day shall be less than
35℃]
2] Installation place shall be dry and well ventilated. Avoid the place such as where corrosive gases or
dust are much or agaitation occurs. Capacitor rack shall be installed on the base of concerete and
tightened with bolts
3] When it is used as a part of group, the space between capacitors shall be more than 30mm for 220V
10 ~ 500㎌, 40mm for 600 ~ 1000㎌, 30mm for 380 ~ 480V 10kVA, 40mm for 15 ~ 25kVA and
60mm for 50kVA considering the rise of temperature for air circulation.
The cubicle shall not sealed tightly and ambient temperature of the Capacitor shall be less than 40℃ in
summer.
4] Use the brackets attached to the body for transpotation and be sure not to grasp the bushing.
5] Use twisted wire for connecting to capacitor.The square of wire shall be more than 1.35 times of rated
current of capacitor.
6] Earth of capacitor shall be grounded with No.1 type grounding construction [less than 10Ω]
7] Capacitor has been produced with built in discharge resistance so that when it is opened from the
circuit, the residual voltage can be reduced to less than 75V within 3 min. If the switch is turn on again
when the residual voltage is not discharged enough, DC voltage becomes double and can be the cause
of damage to capacitor.
When it turns on/off within short time [within 5 seconds], discharging coil is desirable.
8] If the capacitor is connected in series to induction motor as in the picture below, select the capacity to
be the same with non load excitng current when capacitor current ≤ IM.[to prevent voltage rise against
magnetic excitation.]
59 Samwha
Samwha Creative TEchnology Provider
6-3 Maintenance
< Maintenance points to Prevent Accidents >
To contact capacitor terminal for examination, open the switch on the side of power supply and leave it
for 5 minutes as it is until the residual voltage goes below 50V. Then, use earth stick to discharge the
residual voltage entirely and check the charging part.
1] The maximum permissible voltage of capacitor is less than 110% of rated voltage [within 12 hours per
day]. Confirm that each phase is in equilibrium. Especially at night or afternoon, be careful to check the
rise of circuit voltage. When over voltage is applied to capacitor, kvar is increased relatively 2 square of
the voltage rise resulting in excessive increase of temperature of capacitor, leading to shorten life span.
Therefore, it is desirable to separate the capacitor from the circuit in slight load.
2] The maximum temperature of capacitor case is designed to be 40℃ to 60℃. If this limit is exceeded,
forced wind cooling shall be employed to reduce the ambient temperature.
3] Capacitor expands or contracts according to the change of temperature and the bend of case surface
absorbs this expansion or contraction. In operation, case expands about 15mm on the side by the
inner insulation oil. If the expansion is below 15mm, it is normal. If the case expands about 15mm and
abnormal function is suspicious, should check the current.
The current of each phase is within permissible limit of rated current and in 3 phase equilibrium, then
capacitor is normal.
4] Always check the current of capacitor.
5] Check the contact part of breaker or switch used in capacitor circuit once per year. If the contact
is bad, capacitor would be operated in single phase or abnormal noise may be heard due to bad
connection. High frequency agitation voltage is applied to capacitor leading to notable shortening of life
span.
Samwha 60
Samwha
Creative TEchnology Provider
GB 11024-1 FGH Type Test IEH Type Test CESI Type Test
61 Samwha
Samwha Creative TEchnology Provider
〉 Specification
Type □ Capacitor Unit □ Capacitor Bank
Line Voltage[V]
Rated Voltage[V]
Rated Capacity[Kvar]
Frequency[Hz] □ 50Hz □ 60Hz
Number of Phase □ One Phase □ Three Phase □ Special requirements[ ]
Quantity □ EA[Capacitor Unit] □ Bank[Capacitor Bank]
Dimension[mm] W : D: H:
Color □ Munsell No 5Y 7/1 □ Special requirements : Munsell No
〉 Installation Condition
Installation Place □ Indoor □ Outdoor
Installation Method □ Cubicle □ Open Rack □ Pole mounted
Installation Area [ ]mm x [ ]mm
Ambient
□ A [Max +40℃] □ B [Max +45℃] □ C [Max+50℃] □ D [Max +55℃]
Temperature
〉 Protection Methods
Protection Methods □ NVS □ NCS
Special requirements
〉 Attached Facilities
□ %L=6% □ %L=8% □ %L=13%
Series Reactor
□ Oil Type □ Dry Type □ with Discharge Coil
Discharge Device □ Coil □ Resistance □ Others
APFC Step
* Please contact SAMWHA Capacitor, if you have any questions about us and products.
6. Appendix
Samwha 62
Samwha
Creative TEchnology Provider
Memo
63 Samwha
Samwha Creative TEchnology Provider
Memo
Samwha 64
Head Office SAMWHA Hongkong P.T SAMCON
124, Buk-Ri, Namsa-Myun, Cheoin-Gu, Yongin-Si, Unit 3 to 9, 5th Floor, Hi-Tech Center, Jl.raya Subang Cikumapay Campaka
Kyoungki-Do,Korea 9choi Yuen Road Sheungshui, New Territories Purwakatra Jawa-Barat Indonesia
Tel.+82-31-330-5812~7 / Fax.+82-31-339-0413 Hongkong Tel.+62-264-216-881~3 / Fax.+62-264-216-901
[email protected] / [email protected] Tel.+852-2668-2460 / Fax.+852-2668-2420 [email protected]
SAMWHA USA (San Diego Office) [email protected]
SAMWHA Thailand
2555 Melksee street, San Diego, Ca92154, USA Tianjin Samwha Intl Trading 66MOO 4T. Takai A.Mung Chachoengsao 24000.
Tel.+1-619-671-0870 / Fax.+1-619-671-0874 No.22 Xinghua Street Xiqing Economic Thailand
[email protected] Development Zone, Tianjin China Tel.+66-38-847571~3 / Fax.+66-38-847575,847616
SAMWHA USA (Chicago Office) Tel.+86-22-238-8501 / Fax.+86-22-2388-8505
[email protected]
[email protected]
Inc.200 Fairway Drive,
Suite 170 Vernon Hills, IL 60061 SAMWHA Europe SAMWHA India
Tel.+1-847-294-0081 / Fax.+1-847-294-0082 703, 7th floor, Kailash Building, Kasturba Gandhi Marg, New Delhi 110001
Gmbh Lyoner Str. 30 D-60528
[email protected] TEL) 91-11-4355-3460~1 / FAX) 91-11-4355-3462
Frankfurt am Main
Tel.+49-69-963-765-0 [email protected]
(as representative number in 6lines)
Fax.+49-69-963-765-65
[email protected]
2009. 9