Download as pdf or txt
Download as pdf or txt
You are on page 1of 200

GOVERNMENT OF RAJASTHAN

PUBLIC WORKS DEPARTMENT


RAJASTHAN, JAIPUR

BASIC SCHEDULE OF RATES


(FOR ELECTRICAL WORKS)
2022

( Effective From 01-06-2022)


P.W.D. Rajasthan Electrical B.S.R. 2022 Index

PWD RAJASTHAN ELECTRICAL WORKS B.S.R.-2022


INDEX
Chapter No. Chapter Name Page No.

E -01 Electrical Wiring in PVC Conduit Chapter E- 01 Page No 01 - 03

E -02 Electrical Wiring in Steel Conduit Chapter E- 02 Page No 04 - 06

E -03 Electrical wiring in PVC trunking Chapter E- 03 Page No 07 - 08

E -04 Drawing of Wires and Sub mains Chapter E- 04 Page No 09 - 12


G.I. /M. S./ Wooden boxes, Laminates &
E -05 Chapter E- 05 Page No 13 - 16
dismantling
E -06 Distribution Board & it’s accessories Chapter E- 06 Page No 17 - 26

E -07 Electrical Accessories Chapter E- 07 Page No 27 - 33

E -08 LT Panels & Accessories Chapter E- 08 Page No 34 - 44

E -09 Air circuit breakers & MCCB Chapter E- 09 Page No 45 - 49

Switch Fuse Unit & Change over switch &


E -10 Chapter E- 10 Page No 50 - 54
Bus bar Chamber

E -11 LT Cables Chapter E- 11 Page No 55 - 61

E -12 LT Cable Termination & Accessories Chapter E- 12 Page No 62 - 69

E -13 H T Cables & Termination Kits Chapter E- 13 Page No 70 - 72

E -14 Earthing & Lightning arrester Chapter E- 14 Page No 73 - 79

E -15 Fans Chapter E- 15 Page No 80 - 83

E -16 Storage Water Heaters Chapter E- 16 Page No 84 - 86

E -17 Indoor Lighting Chapter E- 17 Page No 87 - 91

Chapter E- 18 Page No 92 - 96 & P


E -18 Outdoor Lighting & pole tables
01 to P 04

E -19 Over Head Lines Chapter E- 19 Page No 97 - 105

E -20 Local area networking Chapter E- 20 Page No 106 - 111

E -21 Electrical Motor Pump sets Chapter E- 21 Page No 112 - 117


P.W.D. Rajasthan Electrical B.S.R. 2022 Index

Chapter No. Chapter Name Page No.

E -22 Air Cooling & Air conditioning Chapter E- 22 Page No 118 - 137

E -23 Transformer & DG Sets Chapter E- 23 Page No 138 - 153

E -24 Fire Protection work Chapter E- 24 Page No 154 - 173


Hire Charges for PA System & Temporary
E -25 Chapter E- 25 Page No 174 - 181
Lighting

Repairing of Fans, Coolers, Pumps, Motors,


E -26 Chapter E- 26 Page No 182 - 188
Fridges & Air conditioners

Annexure "A" Annexure "A" Page 189 to 191


P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-01

Chapter E - 01

Electrical Wiring in PVC Conduit


Code No. Description Unit Complete Rate

1.1 Wiring of light point/ fan point/ exhaust fan point/ call bell point with
1.5 sq. mm nominal size FR PVC insulated unsheathed flexible copper
conductor 1.1 kV grade and 1.5 sq. mm nominal size FR PVC insulated
unsheathed flexible copper earth conductor 1.1 kV grade (IS:694) in
recessed ISI marked MMS ( IS:9537 P - III ) virgin material PVC conduit &
it's ISI marked (IS:3419-1988) accessories, round tiles, 1.2 mm thick Hot
Dipped Galvanized Modular Box with earth terminal, 10A Modular
switch,Modular face plate with grid plate, 3 pin ceiling rose / Holder /3
way connector, screws, making connections, testing etc. as required.
For specification of copper Conductor, Phenolic Laminated sheet's &
Electrical/ Wiring accessories refer Chapter E - 04, E - 05 & E - 07 For
additional technical parameters of product / work refer Annexure 'A'
attached with this BSR

1.1.1 Short point (up to 3 mtr.) P. point 359.00


1.1.2 Medium point (up to 6 mtr.) P. point 578.00
1.1.3 Long point (up to 10 mtr.) P. point 772.00

1.2 Wiring of twin control light point with 1.5 sq. mm nominal size FR PVC
insulated unsheathed flexible copper conductor 1.1 kV grade and 1.5 sq.
mm nominal size FR PVC insulated unsheathed flexible copper earth
conductor 1.1 kV grade (IS:694) in recessed ISI marked MMS ( IS:9537 P
- III ) PVC conduit & it's ISI marked (IS:3419-1988) accessories, round
tiles, 2 Nos Hot Dipped Galvanized M.S Modular box of 1.2 mm thick
with earth terminal,2 Nos10 A two way Modular switch, 3 pin ceiling
rose / holder / 3 way connector ,Modular face plate with grid plate,
screws, making connections, testing etc. as required. For specification
of copper Conductor, Phenolic Laminated sheet's & Electrical/ Wiring
accessories refer Chapter E - 04, E - 05 & E - 07 For additional technical
parameters of product / work refer Annexure 'A' attached with this BSR

1.2.1 Short point (up to 3 mtr.) P. point 772.00


1.2.2 Medium point (up to 6 mtr.) P. point 1137.00
1.2.3 Long point (up to 10 mtr.) P. point 1226.00

Chapter E- 01 Page1
P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-01

Code No. Description Unit Complete Rate


1.3 Wiring of 3/5 pin 6 amp. Light plug point with 1.5 sq. mm nominal size
FR PVC insulated unsheathed flexible copper conductor 1.1 kV grade
and 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible
copper earth conductor 1.1 kV grade(IS:694) in recessed ISI marked
MMS ( IS:9537 P - III ) PVC conduit & it's ISI marked (IS:3419-
1988)accessories, Hot Dipped Galvanized Modular box of 1.2 mm thick
with earth terminal, 10 A modular switch, 3/5 pin 6 A modular socket,
Modular face plate with grid plate, screws, making connections, testing
etc. as required. For specification of copper Conductor, Phenolic
Laminated sheet's & Electrical/ Wiring accessories refer Chapter E - 04, E
- 05 & E - 07 For additional technical parameters of product / work refer
Annexure 'A' attached with this BSR

1.3.1 On board P. point 357.00


1.3.2 Short point (up to 3 mtr.) P. point 507.00
1.3.3 Medium point (up to 6 mtr.) P. point 726.00
1.3.4 Long point (up to 10 mtr..) P. point 920.00

1.4 S&F following sizes (dia.) of ISI marked virgin material MMS ( IS:9537 P -
III ) PVC conduit along with ISI marked (IS:3419-1988) accessories as
required in recess including cutting the wall, covering conduit and
making good the same as required. For additional technical parameters
of product / work refer Annexure 'A' attached with this BSR

1.4.1 20 mm R. mtr. 40.00


1.4.2 25 mm R. mtr. 56.00
1.4.3 32 mm R. mtr. 84.00
1.4.4 40 mm R. mtr. 115.00
1.4.5 50 mm R. mtr. 170.00
1.5 Rewiring of light point/ fan point/ exhaust fan point/ call bell point with
1.5 sq. mm nominal size FR PVC insulated unsheathed flexible copper
conductor 1.1 kV grade and 1.5 sq. mm nominal size FR PVC insulated
unsheathed flexible copper earth conductor 1.1 kV grade (IS:694) in
recessed ISI marked MMS ( IS:9537 P - III ) virgin material PVC conduit &
it's ISI marked (IS:3419-1988) accessories, round tiles, 1.2 mm thick MS
box with earth terminal, 6 A switch, 3 pin ceiling rose/holder / 3 way
connector , 3.0 mm thick ISI marked (IS:2036-1995) phenolic laminated
sheet, Al.alloy / Cadmium plated iron/ brass screws, cup washers,
making connections, testing etc. as required. For specification of copper
Conductor, Phenolic Laminated sheet's & Electrical/ Wiring accessories
refer Chapter E - 04, E - 05 & E - 07 For additional technical parameters
of product / work refer Annexure 'A' attached with this BSR

1.5.1 Short point (up to 3 mtr.) P. point 256.00


1.5.2 Medium point (up to 6 mtr.) P. point 472.00
1.5.3 Long point (up to 10 mtr.) P. point 662.00

Chapter E- 01 Page2
P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-01

Code No. Description Unit Complete Rate

1.6 Rewiring of twin control light / fan / call bell point with 1.5 sq. mm
nominal size FR PVC insulated unsheathed flexible copper conductor 1.1
kV grade and 1.5 sq. mm nominal size FR PVC insulated unsheathed
flexible copper earth conductor 1.1 kV grade (IS:694) in recessed ISI
marked MMS ( IS:9537 P - III ) virgin material PVC conduit & it's ISI
marked (IS:3419-1988) accessories, round tiles, 2 Nos 1.2 mm thick MS
box with earth terminal, 2 Nos 6 A two way switch,3 pin ceiling rose /
holder/ 3 way connector, 3.0 mm thick ISI marked (IS:2036-1995)
phenolic laminated sheet, Al.alloy / Cadmium plated iron/ brass screws,
cup washers, making connections, testing etc. as required. For
specification of copper Conductor, Phenolic Laminated sheet's &
Electrical/ Wiring accessories refer Chapter E - 04, E - 05 & E - 07 For
additional technical parameters of product / work refer Annexure 'A'
attached with this BSR

1.6.1 Short point (up to 3 mtr.) P. point 471.00


1.6.2 Medium point (up to 6 mtr.) P. point 877.00
1.6.3 Long point (up to 10 mtr..) P. point 1231.00
1.7 Rewiring of 3/5 pin 6 amp. Light plug point with 1.5 sq. mm nominal size
FR PVC insulated unsheathed flexible copper conductor 1.1 kV grade
and 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible
copper earth conductor 1.1 kV grade(IS:694) in recessed ISI marked
MMS ( IS:9537 P - III ) virgin material PVC conduit & it's ISI marked
(IS:3419-1988) accessories, 1.2 mm thick MS box with earth terminal of
required size, 6 A switch, 3/5 pin 6 A socket, 3.0 mm thick ISI marked
(IS:2036-1995) phenolic laminated sheet, Al.alloy / Cadmium plated
iron/ brass screws, cup washers, making connections, testing etc. as
required. For specification of copper Conductor, Phenolic Laminated
sheet's & Electrical/ Wiring accessories refer Chapter E - 04, E - 05 & E -
07 For additional technical parameters of product / work refer Annexure
'A' attached with this BSR

1.7.1 On board P. point 136.00


1.7.2 Short point (up to 3 mtr.) P. point 283.00
1.7.3 Medium point (up to 6 mtr.) P. point 499.00
1.7.4 Long point (up to 10 mtr..) P. point 689.00

Chapter E- 01 Page3
P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-02

Chapter E - 02

Electrical Wiring in Steel Conduit

Code Description Unit Complete


No. Rate

2.1 Wiring of light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq. mm
nominal size FR PVC insulated unsheathed flexible copper conductor 1.1 kV
grade and 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible copper
earth conductor 1.1 kV grade (IS:694) in recessed ISI marked ( IS:9537 P - II )
rigid steel conduit & it's ISI marked (IS:14768 P-II 2003) accessories, round
tiles,Hot Dipped Galvanized Modular Box of 1.2 mm thick with earth terminal,
10A Modular switch,3 pin ceiling rose / holder / 3 way connector ,Modular face
plate with grid plate, pvc bushes, check nuts, screws, making connections,
testing etc. as required. For specification of copper Conductor, Phenolic
Laminated sheet's & Electrical/ Wiring accessories refer Chapter E - 04, E - 05 & E
- 07 For additional technical parameters of product / work refer Annexure 'A'
attached with this BSR

2.1.1 Short point (up to 3 mtr.) P. point 476.00


2.1.2 Medium point (up to 6 mtr.) P. point 853.00
2.1.3 Long point (up to 10 mtr..) P. point 1185.00

2.2 Wiring of twin control light / Fan / Call bell point with 1.5 sq. mm nominal size FR
PVC insulated unsheathed flexible copper conductor 1.1 kV grade and 1.5 sq.
mm nominal size FR PVC insulated unsheathed flexible copper earth conductor
1.1 kV grade (IS:694) in recessed/surface ISI marked ( IS:9537 P - II ) rigid steel
conduit & it's ISI marked (IS:14768 P-II 2003) accessories, round tiles, 2 Nos Hot
Dipped Galvanized Modular box of 1.2 mm thick with earth terminal, 2 Nos 10A
two way Modular switch, 3 pin ceiling rose / holder / 3 way connector ,Modular
face plate with grid plate, screws, pvc bushes, check nuts, making connections,
testing etc. as required. For specification of copper Conductor, Phenolic
Laminated sheet's & Electrical/ Wiring accessories refer Chapter E - 04, E - 05 & E
- 07 For additional technical parameters of product / work refer Annexure 'A'
attached with this BSR

2.2.1 Short point (up to 3 mtr.) P. point 918.00


2.2.2 Medium point (up to 6 mtr.) P. point 1585.00
2.2.3 Long point (up to 10 mtr..) P. point 2310.00

Chapter E-02 Page4


P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-02

Code Description Unit Complete


No. Rate

2.3 Wiring of 3/5 pin 6 amp. Light plug point with 1.5 sq. mm nominal size FR PVC
insulated unsheathed flexible copper conductor 1.1 kV grade and 1.5 sq. mm
nominal size FR PVC insulated unsheathed flexible copper earth conductor 1.1 kV
grade(IS:694) in recessed ISI marked ( IS:9537 P - II ) rigid steel conduit & it's
ISI marked (IS:14768 P-II 2003) accessories, Hot Dipped Galvanized Modular box
of 1.2 mm thick with earth terminal, 10A modular switch, 3/5 pin 6 A modular
socket, Modular face plate with grid plate, pvc bushes, check nuts, screws,
making connections, testing etc. as required. For specification of copper
Conductor, Phenolic Laminated sheet's & Electrical/ Wiring accessories refer
Chapter E - 04, E - 05 & E - 07 For additional technical parameters of product /
work refer Annexure 'A' attached with this BSR

2.3.1 On board P. point 357.00


2.3.2 Short point (up to 3 mtr.) P. point 623.00
2.3.3 Medium point (up to 6 mtr.) P. point 1001.00
2.3.4 Long point (up to 10 mtr.) P. point 1333.00
2.4 S&F following sizes (dia.) of ISI marked ( IS:9537 P - II ) rigid steel conduit with
wall thickness according to IS Specified along with ISI marked (IS:14768 P-II
2003) accessories in recessed using saddles, clamps, fasteners, pvc bushes,
check nuts, as required including cutting jhiris in the wall and making good the
same as required. For additional technical parameters of product / work refer
Annexure 'A' attached with this BSR
2.4.1 20 mm R. mtr. 122.00
2.4.2 25 mm R. mtr. 156.00
2.4.3 32 mm R. mtr. 214.00
2.4.4 40 mm R. mtr. 337.00
2.4.5 50 mm R. mtr. 483.00

2.5 Rewiring of light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.
mm nominal size FR PVC insulated unsheathed flexible copper conductor 1.1 kV
grade and 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible copper
earth conductor 1.1 kV grade (IS:694) in recessed ISI marked ( IS:9537 P - II )
rigid steel conduit & it's ISI marked (IS:14768 P-II 2003) marked accessories,
round tiles, 1.2 mm thick MS box with earth terminal, 6 A switch, 3 pin ceiling
rose/holder / 3 pin connector, 3.0 mm thick ISI marked (IS:2036-1995) phenolic
laminated sheet, pvc bushes, check nuts, Al.alloy / Cadmium plated iron/ brass
screws, cup washers, making connections, testing etc. as required. For
specification of copper Conductor, Phenolic Laminated sheet's & Electrical/
Wiring accessories refer Chapter E - 04, E - 05 & E - 07 For additional technical
parameters of product / work refer Annexure 'A' attached with this BSR

2.5.1 Short point (up to 3 mtr.) P. point 370.00


2.5.2 Medium point (up to 6 mtr.) P. point 738.00
2.5.3 Long point (up to 10 mtr.) P. point 1058.00

Chapter E-02 Page5


P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-02

Code Description Unit Complete


No. Rate
2.6 Rewiring of twin control light / Fan / Call bell point with 1.5 sq. mm nominal size
FR PVC insulated unsheathed flexible copper conductor 1.1 kV grade and 1.5 sq.
mm nominal size FR PVC insulated unsheathed flexible copper earth conductor
1.1 kV grade (IS:694) in recessed ISI marked ( IS:9537 P - II ) rigid steel conduit &
it's ISI marked (IS:14768 P-II 2003) accessories, round tles, 2 Nos 1.2 mm thick
MS box with earth terminal, 2 Nos 6 A two way switch, 3 pin ceiling rose /
holder / 3 way connector, 3.0 mm thick ISI marked (IS:2036-1995) phenolic
laminated sheet, pvc bushes, check nuts, Al.alloy / Cadmium plated iron/ brass
screws, cup washers, making connections, testing etc. as required. For
specification of copper Conductor, Phenolic Laminated sheet's & Electrical/
Wiring accessories refer Chapter E - 04, E - 05 & E - 07 For additional technical
parameters of product / work refer Annexure 'A' attached with this BSR

2.6.1 Short point (up to 3 mtr.) P. point 665.00


2.6.2 Medium point (up to 6 mtr.) P. point 1387.00
2.6.3 Long point (up to 10 mtr..) P. point 2014.00

2.7 Rewiring of 3/5 pin 6 amp. Light plug point with 1.5 sq. mm nominal size FR PVC
insulated unsheathed flexible copper conductor 1.1 kV grade and 1.5 sq. mm
nominal size FR PVC insulated unsheathed flexible copper earth conductor 1.1 kV
grade(IS:694) in recessed ISI marked ( IS:9537 P - II ) rigid steel conduit & it's
ISI marked (IS:14768 P-II 2003) accessories, required size 1.2 mm thick , G.I. box
with earth terminal, 6 A switch, 3/5 pin 6 A socket, 3.0 mm thick ISI marked
(IS:2036-1995) phenolic laminated sheet, pvc bushes, check nuts, Al.alloy /
Cadmium plated iron/ brass screws, cup washers, making connections, testing
etc. as required. For specification of copper Conductor, Phenolic Laminated
sheet's & Electrical/ Wiring accessories refer Chapter E - 04, E - 05 & E - 07 For
additional technical parameters of product / work refer Annexure 'A' attached
with this BSR

2.7.1 On board P. point 136.00


2.7.2 Short point (up to 3 mtr.) P. point 397.00
2.7.3 Medium point (up to 6 mtr.) P. point 765.00
2.7.4 Long point (up to 10 mtr..) P. point 1085.00

Chapter E-02 Page6


P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-03

Chapter E - 03

Electrical wiring in PVC trunking

Code No. Description Unit Complete


Rate

3.1 Wiring of light point/ fan point/ exhaust fan point/ call bell point with
1.5 sq. mm nominal size FR PVC insulated unsheathed flexible copper
conductor 1.1 kV grade and 1.5 sq. mm nominal size FR PVC insulated
unsheathed flexible copper earth conductor 1.1 kV grade (IS:694) on
surface ISI marked ( IS:14927 P - II ) virgin material UPVC trunking &
it's accessories, Hot Dipped Galvanized Modular box of 1.2 mm thick
with earth terminal/ Surface Moulded virgin material UPVC Modular
Box , 10 A Modular switch,Modular face plate with grid plate, 3 pin
ceiling rose/holder /3 way Connector, screws, making connections,
testing etc. as required. For specification of copper Conductor,
Phenolic Laminated sheet's & Electrical/ Wiring accessories refer
Chapter E - 04, E - 05 & E - 07 For additional technical parameters of
product / work refer Annexure 'A' attached with this BSR

3.1.1 Short point (up to 3 mtr.) P. point 361.00


3.1.2 Medium point (up to 6 mtr.) P. point 584.00
3.1.3 Long point (up to 10 mtr.) P. point 814.00

3.2 Wiring of twin control light point with 1.5 sq. mm nominal size FR PVC
insulated unsheathed flexible copper conductor 1.1 kV grade and 1.5
sq. mm nominal size FR PVC insulated unsheathed flexible copper earth
conductor 1.1 kV grade (IS:694) of approved make on surface ISI
marked ( IS:14927 P - II ) virgin material UPVC trunking & it's
accessories, Hot Dipped Galvanized Modular box of 1.2 mm thick with
earth terminal/ Surface 2 No. Moulded virgin material UPVC Modular
Box , 2 Nos 10 A two way Modular switch, 3 pin ceiling rose / holder/3
way Connector , Modular face plate with grid plate, screws, making
connections, testing etc. as required. For specification of copper
Conductor, Phenolic Laminated sheet's & Electrical/ Wiring accessories
refer Chapter E - 04, E - 05 & E - 07 For additional technical parameters
of product / work refer Annexure 'A' attached with this BSR

3.2.1 Short point (up to 3 mtr.) P. point 730.00


3.2.2 Medium point (up to 6 mtr.) P. point 1148.00
3.2.3 Long point (up to 10 mtr..) P. point 1516.00

Chapter E- 03 Page7
P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-03

Code No. Description Unit Complete


Rate
3.3 Wiring of 3/5 pin 6 amp. Light plug point with 1.5 sq. mm nominal size
FR PVC insulated unsheathed flexible copper conductor 1.1 kV grade
and 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible
copper earth conductor 1.1 kV grade(IS:694) on surface ISI marked (
IS:14927 P - II ) virgin material UPVC Trunking & it's accessories, Hot
Dipped Galvanized Modular box of 1.2 mm thick with earth terminal/
Surface Moulded virgin material UPVC Modular Box, modular 10A
switch, 3/5 pin 6 A modular socket, Modular face plate with grid plate,
screws, making connections, testing etc. as required. For specification
of copper Conductor, Phenolic Laminated sheet's & Electrical/ Wiring
accessories refer Chapter E - 04, E - 05 & E - 07 For additional technical
parameters of product / work refer Annexure 'A' attached with this BSR

3.3.1 On board P. point 389.00


3.3.2 Short point (up to 3 mtr.) P. point 509.00
3.3.3 Medium point (up to 6 mtr.) P. point 732.00
3.3.4 Long point (up to 10 mtr..) P. point 929.00

3.4 S&F following sizes of ISI marked ( IS:14927 P - II ) virgin material UPVC
trunking along with accessories like coupler, inner, outer, elbow,
square box, tee, end cap etc. on surface with screws, expansion
fasteners as required. For additional technical parameters of product /
work refer Annexure 'A' attached with this BSR

3.4.1 20 mm x 12 mm R. mtr. 41.00


3.4.2 25 mm x 12 mm R. mtr. 50.00
3.4.3 32 mm x 12 mm R. mtr. 64.00
3.4.4 25 mm x 16 mm R. mtr. 61.00
3.4.5 38 mm x 16 mm R. mtr. 88.00
3.4.6 38 mm x 25 mm R. mtr. 98.00
3.4.7 38 mm x 38 mm R. mtr. 126.00
3.4.8 50 mm x 16 mm R. mtr. 139.00
3.4.9 50 mm x 50 mm R. mtr. 224.00
3.4.10 75 mm x 50 mm R. mtr. 525.00
3.4.11 75 mm x 75 mm R. mtr. 674.00
3.4.12 100 mm x 50 mm R. mtr. 844.00
3.4.13 150 mm x 50 mm R. mtr. 1274.00

Chapter E- 03 Page8
P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-04

Chapter E - 04

Drawing of Wires and Submains

Code No. Description Unit Complete Rate


4.1 Supplying and drawing FR PVC insulated & unsheathed flexible copper
conductor as per PWD specification for electrical Works with ISI
marked (IS:694) and as per IS 8130 : 2013 of 1.1 kV grade . Wire should
be made from 99.90 % purity copper, class 5 stranding in acc. to
IS:8130/IEC 60228 for lower watt loss , oxygen free for less chances of
oxidization, insulation PVC type A/C/D , flame retardant as per IS
10810-53, better amperage rating as per IS:3961 part 5, in existing
surface or recessed PVC/ MS conduit/casing capping making
connections with Copper Lugs of suitable size, Ferrules,testing etc. as
required. OEM Must have its own in house NABL lab setup for all
testing facilities for wires. For additional technical parameters of
product / work refer Annexure 'A' attached with this BSR

4.1.1 1 x 1.5 sq.mm Mtr. 22.00


4.1.2 2 x 1.5 sq.mm Mtr. 43.00
4.1.3 3x 1.5 sq.mm Mtr. 63.00
4.1.4 4 x 1.5 sq.mm Mtr. 83.00
4.1.5 1 x 2.5 sq.mm Mtr. 31.00
4.1.6 2 x 2.5 sq.mm Mtr. 61.00
4.1.7 2 x 2.5 sq. mm. + 1x1.5sqmm Mtr. 81.00
4.1.8 3 x 2.5 sq.mm Mtr. 90.00
4.1.9 4 x 2.5 sq.mm Mtr. 119.00
4.1.10 1 x 4.0 sq.mm Mtr. 48.00
4.1.11 2 x 4.0 sq.mm Mtr. 93.00
4.1.12 3 x 4 sq. mm. Mtr. 137.00
4.1.13 4 x 4.0 sq.mm Mtr. 182.00
4.1.14 2 x 4.0 sq. mm. + 1 x 2.5 sq. mm. Mtr. 122.00
4.1.15 1 x 6.0 sq.mm Mtr. 71.00
4.1.16 2 x 6.0 sq.mm Mtr. 140.00
4.1.17 3 x 6.0 sq. mm. Mtr. 208.00
4.1.18 4 x 6.0 sq.mm Mtr. 276.00
4.1.19 2 x 6.0 sq. mm. + 1 x 2.5 sq. mm. Mtr. 170.00
4.1.20 2 x 6.0 sq. mm. + 1 x 4.0 sq. mm. Mtr. 185.00
4.1.21 1 x 10.0 sq.mm Mtr. 136.00
4.1.22 2 x 10.0 sq.mm Mtr. 267.00
4.1.23 4 x 10.0 sq.mm Mtr. 531.00
4.1.24 1 x 16.0 sq.mm Mtr. 221.00
4.1.25 2 x 16.0 sq.mm Mtr. 432.00
4.1.26 4 x 16.0 sq.mm Mtr. 857.00

Chapter E- 04 Page9
P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-04

Code No. Description Unit Complete Rate


4.2 Supplying and drawing coaxial cable 75 ohm impedance with foam PE
insulated solid bare copper inner conductor, and Ist outer conductor of
bonded alum. tape and second outer conductor of alum. alloy braid in
existing surface or recessed conduit/casing capping including making
connections as required. For additional technical parameters of
product / work refer Annexure 'A' attached with this BSR

4.2.1 RG - 6 Mtr. 30.0


4.2.2 RG -11 Mtr. 58.00

4.3 Supplying and drawing PE Insulated & PVC Sheathed unarmoured


telephone cable with 0.5 mm dia. Solid Annealed electrolytic grade
bare Copper Conductor as per IS: 8130/84 &confirming to TEC
specification GR / WIR/06-03 March 2002 in existing surface or
recessed conduit/casing capping. including ferruling on each pair for
Identification etc. as required. For additional technical parameters of
product / work refer Annexure 'A' attached with this BSR

4.3.1 1 pair Mtr. 12.0


4.3.2 2 pair Mtr. 18.00
4.3.3 3 pair Mtr. 26.00
4.3.4 4 pair Mtr. 33.00
4.3.5 5 pair Mtr. 41.00
4.3.6 10 pair Mtr. 83.00
4.3.7 20 pair Mtr. 159.00
4.3.8 50 pair Mtr. 392.00
4.3.9 100 pair Mtr. 822.00
4.3.10 200 pair Mtr. 1554.00

4.4 Supply and Laying of PE Insulated, PVC Inner Sheathed, armoured &
PVC Sheathed Telephone Cable. with 0.5 mm thick Solid Annealed
Bare Copper Conductor as per IS: 8130/84 telephone cable confirming
to TEC specifications GR/WIR 06/03, Mar.-2002 in existing pipe / open
trench / Cable tray / on surface including making necessary
connection, testing etc. as required of size. For additional technical
parameters of product / work refer Annexure 'A' attached with this
BSR
4.4.1 5 pair Mtr. 91.0
4.4.2 10 pair Mtr. 142.00
4.4.3 20 pair Mtr. 231.00
4.4.4 50 pair Mtr. 491.00
4.4.5 100 pair Mtr. 906.00
4.4.6 200 pair Mtr. 1729.00

Chapter E- 04 Page10
P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-04

Code No. Description Unit Complete Rate


4.5 Supply and Laying of PE Insulated jelly filled Armoured Telephone
Cable. with 0.6 mm thick Solid Annealed Bare Copper Conductor and
confirming to TEC specifications confirming. to DOT GR/CUG-
01/Aug.2003 in existing pipe / open trench / Cable tray / on surface
including making necessary connection, testing etc. as required of size.
For additional technical parameters of product / work refer Annexure
'A' attached with this BSR
4.5.1 5 pair Mtr. 113.0
4.5.2 10 pair Mtr. 169.00
4.5.3 20 pair Mtr. 254.00
4.5.4 50 pair Mtr. 529.00
4.5.5 100 pair Mtr. 951.00
4.5.6 200 pair Mtr. 1765.00

4.6 Supply & drawing Wiring for sub mains ISI marked (IS:694) 1100 Volts
grade PVC insulated flat twin core sheathed solid aluminium conductor
with 10 SWG G.I. Support wire duly clipped etc. as required. For
additional technical parameters of product / work refer Annexure 'A'
attached with this BSR
4.6.1 4.0 sq.mm Mtr. 60.0
4.6.2 6.0 sq.mm Mtr. 73.00
4.6.3 10.0 sq.mm Mtr. 98.00

4.7 P/Laying ISI marked P.V.C. insulated submersible cable confirming


to(IS:694) and as per IS 8130 : 2013 of 1.1 kV grade . Wire should be
made from 99.90 % purity copper, stranding in acc. to IS:8130/IEC
60228 for lower watt loss , oxygen free for less chances of oxidization,
insulation PVC type A/C/D , flame retardant as per IS 10810-53, better
amperage rating as per IS:3961 part 5, existing pipe / open trench /
Cable tray / on surface including making connection etc. as required.
For additional technical parameters of product / work refer Annexure
'A' attached with this BSR

4.7.1 1.5 Sq.mm 3 core flat / Round Mtr. 92.0


4.7.2 2.5 Sq.mm 3 core flat / Round Mtr. 146.00
4.7.3 4.0 Sq.mm 3 core flat / Round Mtr. 214.00
4.7.4 6.0 Sq.mm 3 core flat / Round Mtr. 300.00

Chapter E- 04 Page11
P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-04

Code No. Description Unit Complete Rate


4.7.5 10.0 Sq.mm 3 core flat / Round Mtr. 490.00
4.7.6 16.0 Sq.mm 3 core flat / Round Mtr. 743.00

4.8 Supply and laying following size twin parallel type Speaker cables of
IS/ISO 9001 CERTIFIED COMPANY made with multi wire, bright
annealed flexible bare electrolytic grade copper conductor, insulated
with specially formulated transparent grade PVC compound, red strip
for identification in existing conduit etc. as required. For additional
technical parameters of product / work refer Annexure 'A' attached
with this BSR
4.8.1 0.75 sq.mm Rmtr. 36
4.8.2 1.0 Sq. mm Rmtr. 44.00
4.8.3 1.5 Sq.mm Rmtr. 62.00
4.8.4 2.5 Sq.mm Rmtr. 100.00

4.90 Supply and laying speaker cable of IS/ISO 9001 CERTIFIED COMPANY
made following size 2 core twin twisted multi stranded electrolytic
grade copper conductor, overall PVC insulated and armoured cable
(Blue colour) on surface/ above false ceiling including cost of GI
spacers, saddles etc. as required. For additional technical parameters
of product / work refer Annexure 'A' attached with this BSR

4.9.1 0.75 sq.mm Rmtr. 102


4.9.2 1.0 Sq. mm Rmtr. 111.00
4.9.3 1.5 Sq.mm Rmtr. 131.00
4.9.4 2.5 Sq.mm Rmtr. 182.00

4.1 Supply and laying PVC Insulated and PVC Round Sheathed Multi Core
copper conductor (IS:694) and as per IS 8130 : 2013 of 1.1 kV grade .
Wire should be made from 99.90 % purity copper, stranding in acc. to
IS:8130/IEC 60228 for lower watt loss , oxygen free for less chances of
oxidization, insulation PVC type A/C/D , flame retardant as per IS
10810-53, better amperage rating as per IS:3961 part 5, in existing
pipe / open trench / Cable tray / on surface including making
connection etc. as required. For additional technical parameters of
product / work refer Annexure 'A' attached with this BSR

4.10.1 1.5 sq.mm x 3 core Rmtr. 95.00


4.10.2 1.5 sq.mm x 4 core Rmtr. 118.00
4.10.3 1.5 sq.mm x 6 core Rmtr. 185.00
4.10.4 1.5 sq.mm x 8 core Rmtr. 241.00
4.10.5 2.5 sq.mm x 3 core Rmtr. 148.00
4.10.6 2.5 sq.mm x 4 core Rmtr. 195.00
4.10.7 2.5 sq.mm x 6 core Rmtr. 294.00
4.10.8 2.5 sq.mm x 8 core Rmtr. 381.00
4.10.9 4.0 sq.mm x 3 core Rmtr. 222.00
4.10.10 4.0 sq.mm x 4 core Rmtr. 281.00
4.10.11 4.0 sq.mm x 6 core Rmtr. 455.00

Chapter E- 04 Page12
P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-05

Chapter E - 05

G.I. /M. S./ Wooden boxes ,Laminates & dismantling

Description Unit Complete Rate


Code No.
P & F 1.2 mm thick G. I. / M .S. Sheet boxes duly finished with two
coats of red oxide and with earthing terminal of following sizes
5.1 (nominal size) in recessed/surface as required.For additional
technical parameters of product / work refer Annexure 'A' attached
with this BSR
5.1.1 1.2 mm thick M. S. Sheet boxes
5.1.1.1 75mm x 75mm x 60mm Each 45.0
5.1.1.2 100mm x 100mm x 60mm Each 58.0
5.1.1.3 150mm x 75mm x 60mm Each 66.0
5.1.1.4 175mm x 100mm x 60mm Each 83.0
5.1.1.5 150mm x 150mm x 60mm Each 91.0
5.1.1.6 225mm x 100mm x 60mm Each 99.0
5.1.1.7 200mm x 150mm x 60mm Each 112.0
5.1.1.8 200mm x 125mm x 75mm Each 120.0
5.1.1.9 200mm x 250mm x 75mm Each 201.0
5.1.1.10 200mm x 250mm x 100mm Each 223.0
5.1.1.11 250mm x 300mm x 75mm Each 285.0
5.1.1.12 250mm x 300mm x 100mm Each 313.0
5.1.1.13 300mm x 375mm x 75mm Each 401.0
5.1.1.14 300mm x 375mm x 100mm Each 429.0
5.1.1.15 250mm x 100mm x 60mm Each 90.0
5.1.1.16 300mm x 100mm x 60mm Each 129.0
5.1.1.17 300mm x 300mm x 75mm Each 265.0

5.1.2 1.2 mm thick G I boxes


5.1.2.1 75mm x 75mm x 60mm Each 50.0
5.1.2.2 100mm x 100mm x 60mm Each 63.0
5.1.2.3 150mm x 75mm x 60mm Each 73.0
5.1.2.4 175mm x 100mm x 60mm Each 94.0
5.1.2.5 150mm x 150mm x 60mm Each 101.0
5.1.2.6 225mm x 100mm x 60mm Each 112.0
5.1.2.7 200mm x 150mm x 60mm Each 126.0
5.1.2.8 200mm x 125mm x 75mm Each 135.0
5.1.2.9 200mm x 250mm x 75mm Each 197.0
5.1.2.10 200mm x 250mm x 100mm Each 258.0
5.1.2.11 250mm x 300mm x 75mm Each 327.0
5.1.2.12 250mm x 300mm x 100mm Each 355.0
5.1.2.13 300mm x 375mm x 75mm Each 457.0
5.1.2.14 300mm x 375mm x 100mm Each 486.0
5.1.2.15 250mm x 100mm x 60mm Each 104.0
5.1.2.16 300mm x 100mm x 60mm Each 143.0
5.1.2.17 300mm x 300mm x 75mm Each 401.0

Chapter E- 05 Page 13
P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-05

Description Unit Complete Rate


Code No.

P & F in position frame made out of M.S. angle (riveted or welded)


finished with two coats of red oxide and two coats enamel paint
5.2 including cutting, welding, holes etc.of following sizes as required.For
additional technical parameters of product / work refer Annexure 'A'
attached with this BSR
5.2.1 25mm x 25mm x 3mm Mtr. 135.0
5.2.2 25mm x 25mm x 5mm Mtr. 220.0
5.2.3 35mm x 35mm x 5mm Mtr. 318.0
5.2.4 40mm x 40mm x 5mm Mtr. 367.0
5.2.5 50mm x 50mm x 6mm Mtr. 551.0

P & Fixing Powder coated CRCA sheet enclosures on existing angle


iron frame by means of nuts and bolts and making holes , Din rail etc.
5.3
as required.For additional technical parameters of product / work
refer Annexure 'A' attached with this BSR
5.3.1 1.0 mm thick Sqm. 1665.0
5.3.2 1.6 mm thick Sqm. 2327.0
5.3.3 2.0 mm thick Sqm. 2839.0
5.3.4 2.5 mm thick Sqm. 3490.0

P & Fixing M.S. flat on existing angle iron frame and making required
nos. of holes for fixing accessories including one coat of red oxide
5.4 paint and two coats of enamel paint etc. as required.For additional
technical parameters of product / work refer Annexure 'A' attached
with this BSR
5.4.1 25 mm x 3 mm Mtr. 73.0
5.4.2 25 mm x 5 mm Mtr. 122.0
5.4.3 32 mm x 5 mm Mtr. 159.0
5.4.4 40 mm x 6 mm Mtr. 193.0
5.4.5 50 mm x 6 mm Mtr. 293.0
5.4.6 50 mm x 10 mm Mtr. 477.0

P & F paper phenolic resin bonded laminates confirming to IS : 2036 -


1995 for boxes/ frames including making holes for switches etc, with
5.5 brass screws, washers/ zinc plated nut and bolts as required. For
additional technical parameters of product / work refer Annexure 'A'
attached with this BSR
5.5.1 3.0 mm thick Sq.m 1002.0
5.5.2 4.8 mm thick Sq.m 1150.0
5.5.3 6.4 mm thick Sq.m 1291.0
5.5.4 9.0 mm thick Sq.m 1638.0
5.5.5 12.0 mm thick Sq.m 2161.0
5.5.6 19.0 mm thick Sq.m 3359.0
5.5.7 25.0 mm thick Sq.m 6107.0

Chapter E- 05 Page 14
P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-05

Description Unit Complete Rate


Code No.
P & F phenolic laminated sheet 2.0 mm thick of following size .
Including screws, cup washer as required.For additional technical
5.6
parameters of product / work refer Annexure 'A' attached with this
BSR
5.6.1 75 mm dia Each 10.0
5.6.2 100 mm dia. Each 17.0

P & F P.V.C. sheet 2.0 mm thick of following size Including screws,


cup washer as required.For additional technical parameters of
5.7
product / work refer Annexure 'A' attached with this BSR

5.7.1 75 mm dia. Each 6.0


5.7.2 100 mm dia. Each 7.0

P & F Aluminium sheet 1.0 m thick of following size dia. Including


screws, cup washer as required.For additional technical parameters
5.8 of product / work refer Annexure 'A' attached with this BSR

5.8.1 75 mm dia. Each 10.0


5.8.2 100 mm dia. Each 13.0

P & F 1.2mm thick M.S. Recessed fan box, hexagonal/ round of size
130 mm dia, depth 75mm, 12 mm dia rod fan hook with 100 mm
5.9 length extended on each side . All as per pre approved by Engineer in
charge. For additional technical parameters of product / work refer
Annexure 'A' attached with this BSR Each 128.0

P & F 1.00mm thick M.S. Recessed concealed box, round of size 150
mm dia, depth 100 mm complete as required. All as per pre
5.10 approved by Engineer in charge.For additional technical parameters
of product / work refer Annexure 'A' attached with this BSR
Each 94.0

Labour charges for dismantling of surface PVC/ Steel conduit


5.11 including wiring in conduit, conduit fittings and depositing the same
with listing of material in store. R. Mtr. 8.0

Labour charges for dismantling of surface/ recessed switch board of


5.12 any size and depositing the same with listing of material in store.
Each 6.0

Labour charges for dismantling of switch accessories like switch,


5.13 socket, ceiling rose, holder and depositing the same with listing of
material in store. Each 3.0

Chapter E- 05 Page 15
P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-05

Description Unit Complete Rate


Code No.
Labour charges for dismantling of wiring in existing conduit of
5.14 following size and depositing the same with listing of material in
store.
5.14.1 up to 2.5 sq. mm. wire R. Mtr. 2.0
5.14.2 4/ 6 sq. mm. wire R. Mtr. 3.0
5.14.3 10 sq. mm. wire R. Mtr. 4.0

P & F 3.0 mm thick Poly propelene plastic polished concealed fan


box, squre of size (106x106) mm dia, depth 50 mm , 10 mm dia rod
of MS with chrome plated with 55 mm length extended on each side
5.15
. All as per pre approved by Engineer in charge. For additional
technical parameters of products/ work , refer Annexure "A"
attached with this BSR . Each 119.0

Chapter E- 05 Page 16
P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-06

Chapter E - 06

Distribution Board & it's Accessories


Code No. Description Unit Complete Rate

6.1 Providing & Fixing of 240/415 V AC MCB with positive isolation of 10


kA breaking capacity (B/ C/D tripping characteristic as per type of
load and site requirement) 4 KV impulse withstand voltage, ISI
marked IS 8828(1996) / conforming to IEC 60898-1 2002, IEC 60947-
2, low watt losses, trip free mechanisum , energy limiting of class 3
as per IEC, minimum phase termination capacity of 35sq.mm. ,
conductor line load reversibility , IP 20 contact protection and fitted
in existing distribution board/sheets, minimum electrical operation
20,000 upto 20 A rating and 10,000 upto 63 A, 5000 for 80 A &
above rating including making connections, testing etc. as required.
OEM shall have submit NABL / CPRI / ERDA accrediated lab type
test reports & All as per pre approved by Engineer in charge. For
additional technical parameters of product / work refer Annexure
'A' attached with this BSR

6.1.1 Single pole MCB (With B/C curve tripping Characteristics)


6.1.1.1 0.5 A to 5 A rating Each 296.0
6.1.1.2 6 A to 32 A rating Each 187.0
6.1.1.3 40 A rating Each 415.0
6.1.1.4 50/63 A rating Each 415.0
6.1.1.5 80 A rating Each 1541.0
6.1.1.6 100 A rating Each 1722.0
6.1.1.7 125 A rating Each 1851.0

6.1.2 Double pole MCB(With B/C curve tripping Characteristics)


6.1.2.1 0.5 A to 5 A rating Each 784.0
6.1.2.2 6 A to 32 A rating Each 566.0
6.1.2.3 40 A rating Each 900.0
6.1.2.4 50/63 A rating Each 900.0
6.1.2.5 80 A rating Each 3392.0
6.1.2.6 100 A rating Each 3617.0
6.1.2.7 125 A rating Each 2853.0

6.1.3 Triple pole MCB (With B/C curve trippingCharacteristics)


6.1.3.1 0.5A to 5 A rating Each 1152.0
6.1.3.2 6 A to 32 A rating Each 910.0
6.1.3.3 40 A rating Each 1384.0
6.1.3.4 50/63 A rating Each 1384.0
6.1.3.5 80 A rating Each 5346.0
6.1.3.6 100 A rating Each 5697.0
6.1.3.7 125 A rating Each 6318.0

Chapter E- 06 Page17
P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-06

Code No. Description Unit Complete Rate

6.1.4 Four pole MCB (With B/C curve tripping Characteristics)


6.1.4.1 0.5A to 5 A rating Each 1445.0
6.1.4.2 6 A to 32 A rating Each 1223.0
6.1.4.3 40 A rating Each 1738.4
6.1.4.4 50/63 A rating Each 1745.0
6.1.4.5 80 A rating Each 6976.0
6.1.4.6 100 A rating Each 7262.0
6.1.4.7 125 A rating Each 8213.0

6.1.5 Triple pole MCB (With D curve tripping Characteristics)


6.1.5.1 0.5 A to 5 A rating Each 1186.0
6.1.5.2 6 A to 32 A rating Each 947.0
6.1.5.3 40 A rating Each 1452.0
6.1.5.4 50/63 A rating Each 1452.0

6.2 Providing & Fixing of 240/415 V isolator ISI marked IS:13947-


III/conforming to IEC 60947-3, suitable for AC22A utilization
category, 4KV impulse withstand voltage, true contact indication,
Red colour dolly / lever shall have single mould covering over all
poles for operation , two position din rail mounting, minimum
phase termination capacity of 35sq.mm. IP 20 contact protection
and fitted in existing distribution board / sheet including making
connections, testing etc. as required. OEM shall have submit NABL
/ CPRI / ERDA accrediated lab type test reports & All as per pre
approved by Engineer in charge.For additional technical parameters
of product / work refer Annexure 'A' attached with this BSR

6.2.1 Double pole isolator


6.2.1.1 30 A / 40 A rating Each 351.0
6.2.1.2 63 A rating Each 453.0
6.2.1.3 80 A/ 100 A rating Each 589.0

6.2.2 Triple pole Isolator


6.2.2.1 40 A rating Each 334.0
6.2.2.2 63 A rating Each 705.0
6.2.2.3 80 A/ 100 A rating Each 802.0

6.2.3 Four pole Isolator


6.2.3.1 40 A rating Each 780.0
6.2.3.2 63 A rating Each 818.0
6.2.3.3 80 A/ 100 A rating Each 957.0

Chapter E- 06 Page18
P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-06

Code No. Description Unit Complete Rate

6.3 Providing & Fixing of 240/415 V factory fitted RCBO with overload,
short-circuit and earth leakage protection with ISI marked (IS12640-
2)/ conforming to IEC 61009-1, breaking capacity 10 KA, provision
for pad lock, min. Electrical operation 10,000 upto 63 A rating ,
minimum phase termination capacity of 35sq.mm. , IP 20 contact
protection with existing distribution board / sheet including making
connections, testing etc. as required. OEM shall have submit NABL
/ CPRI / ERDA accrediated lab type test reports & All as per pre
approved by Engineer in charge. For additional technical
parameters of product / work refer Annexure 'A' attached with this
BSR

6.3.1 Two pole 30 mA sensitivity


6.3.1.1 6A-32 A rating Each 2942.0
6.3.1.1 40 A rating Each 2942.0
6.3.1.3 63 A rating Each 3703.0

6.3.2 Two pole 100/300mA sensitivity


6.3.2.1 6A-32 A rating Each 3004.0
6.3.2.2 40 A rating Each 3038.0
6.3.2.3 63 A rating Each 3955.0

6.3.3 Four pole 30 mA sensitivity


6.3.3.1 6A-32 A rating Each 3351.0
6.3.3.2 40 A rating Each 3518.0
6.3.3.3 63 A rating Each 4217.0

6.3.4 Four pole 100/300 mA sensitivity


6.3.4.1 6A-32 A rating Each 3801.0
6.3.4.2 40 A rating Each 3829.0
6.3.4.3 63 A rating Each 4296.0

6.4 P&F 240/415 V AC Change Over Miniature circuit breaker with three
positions (I-O-II) which allows supply change over from one source
to second source & vice- versa, conforming to IS/ IEC 60947-3 in
existing board/sheets including making connections, testing etc. as
required. OEM shall have submit NABL / CPRI / ERDA accrediated
lab type test reports & All as per pre approved by Engineer in
charge.For additional technical parameters of product / work refer
Annexure 'A' attached with this BSR

6.4.1 Double Pole


6.4.1.1 25 Amp, 2 Module Each 1012.0
6.4.1.2 40 Amp, 2 Module Each 1544.0
6.4.1.3 63 Amp,3 Module Each 1793.0

6.4.2 FourPole
6.4.2.1 40 Amp, 4 Module Each 2649.0
6.4.2.2 63 Amp, 6 Module Each 3007.0

Chapter E- 06 Page19
P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-06

Code No. Description Unit Complete Rate

6.5 Providing & Fixing of 240/415 V Residual current circuit breaker


(RCCB) conforming to (IS:12640-1)/ IEC 61008 -1 , rated 4 KV
impulse withstand voltage truly current operated and shall operate
on CBCT mechanisum, provision for pad lock, min. operation
10,000 upto 63 A rating and 5000 for 100 A rating and minimum
phase termination capacity of 35 sq.mm. rigid wire , IP 20 contact
protection with existing distribution board / sheet including making
connections, testing etc. as required. OEM shall have submit NABL
/ CPRI / ERDA accrediated lab type test reports & All as per pre
approved by Engineer in charge. For additional technical
parameters of product / work refer Annexure 'A' attached with this
BSR

6.5.1 Two pole 30 mA sensitivity


6.5.1.1 16/25 A rating Each 2001.0
6.5.1.2 32/40 A rating Each 2237.0
6.5.1.3 63A rating Each 2786.0
6.5.1.4 100 A rating Each 4842.0

6.5.2 Two pole 100/300mA sensitivity


6.5.2.1 16/25 A rating Each 2073.0
6.5.2.2 40 A rating Each 2366.0
6.5.2.3 63 A rating Each 2850.0

6.5.3 Four pole 30 mA sensitivity


6.5.3.1 25 A rating Each 2642.0
6.5.3.2 40 A rating Each 2666.0
6.5.3.3 63 A rating Each 3021.0
6.5.3.4 100 A rating Each 5196.0

6.5.4 Four pole 100/300 mA sensitivity


6.5.4.1 25 A rating Each 2717.0
6.5.4.2 40 A rating Each 2762.0
6.5.4.3 63 A rating Each 2225.0
6.5.4.4 100 A rating Each 5288.0
6.6 Providing & Fixing of din rail mounting surge protection device
confirming to IEC 61643-11 for Type 1 + 2 protection and Maximum
discharge current 50 kA with following configuration in existing
distribution board / sheet including making connections, testing
etc. as required. OEM shall have submit NABL / CPRI / ERDA
accrediated lab type test reports & All as per pre approved by
Engineer in charge. For additional technical parameters of product /
work refer Annexure 'A' attached with this BSR

6.6.1 1P + N Each 3437.0


6.6.2 3P + N Each 6315.0

Chapter E- 06 Page20
P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-06

Code No. Description Unit Complete Rate

6.7 Providing & Fixing of din rail mounting contactor and accessories
confirming to IEC 61095 with following description and
configuration in existing distribution board / sheet including
making connections, testing etc. as required.OEM shall have submit
NABL / CPRI / ERDA accrediated lab type test reports & All as per
pre approved by Engineer in charge.For additional technical
parameters of product / work refer Annexure 'A' attached with this
BSR

6.7.1 Modular contactor 25A - 1NO Each 1535.0


6.7.2 Modular contactor 25A - 2NO Each 1919.0
6.7.3 Modular contactor 40A - 2NO Each 3270.0
6.7.4 Modular contactor 40A - 3NO Each 4676.0
6.7.5 Modular contactor 40A - 4NO Each 5489.0
6.7.6 Modular contactor 63A - 2NO + 2 NC Each 5820.0
6.7.7 Modular contactor 63A - 3NO Each 5963.0
6.7.8 Modular contactor 63A - 4NO Each 6555.0
6.7.9 Auxilary contact, 2 NO Each 1578.0
6.7.10 Auxilary contact, 1 NO + 1 NC Each 819.0
6.7.11 Under voltage Release Each 1903.0
6.7.12 Shunt Trip Release Each 2175.0

6.8 Providing & Fixing of din rail mounting LED Indicating Lights with
following description and configuration in existing distribution
board / sheet including making connections, testing etc. as
required.For additional technical parameters of product / work
refer Annexure 'A' attached with this BSR
6.8.1 Red / Yellow / Blue / Green Each 924.0
6.8.2 Red-yellow-Blue Each 1115.0

6.9 Providing & Fixing of Recessed/surface mounting heavy duty


Enclosure made out from Galvanized steel / CRCA sheet not less
then 1.2 mm thick conforming to IS-8623-1 & 3 / IEC 61439- 1 & 3.
powder painted complete with din rail making internal DB
terminations with copper lugs, detachable gland plate, including
making connections, testing etc. as required.For additional
technical parameters of product / work refer Annexure 'A' attached
with this BSR
6.9.1 Suitable for Two / Three / Four module for MCB Each 660.0
6.9.2 Suitable for Six / Eight module for MCB/ RCCB Each 1099.0

Chapter E- 06 Page21
P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-06

Code No. Description Unit Complete Rate

6.10 Providing & Fixing of Recessed/surface mounting heavy duty


horizontal type Double Door ( Metal / Glazed )Distribution board
with Metal end box made out from Galvanized steel / CRCA sheet
not less then 1.2 mm thick conforming to IS-8623-1 & 3 / IEC
61439- 1 & 3, powder painted complete with reversible door (for
double door DB only )100 amp. insulated copper bus bar/shorting
link , copper neutral link, copper earth link , color coded
interconnecting wire set of suitable rating and din bar,masking
sheet, making internal DB terminations with copper lugs, Ferrules,
detachable gland plate, including making connections, testing etc.
as required. OEM shall have submit NABL / CPRI / ERDA accrediated
lab type test reports & All as per pre approved by Engineer in
charge. For additional technical parameters of product / work refer
Annexure 'A' attached with this BSR

6.10.1 Metal door (single phase) IK-09 and IP-43 with Metal end box

6.10.1.1 4 Way (4+2) Each 1795.0


6.10.1.2 6 Way (6+2) Each 2018.0
6.10.1.3 8 Way (8+2) Each 2184.0
6.10.1.4 12 Way (12+2) Each 2590.0
6.10.1.5 16 Way (16+2) Each 3389.0

6.10.2 Glazed door (single phase) IK-09 and IP-43 with Metal end box
6.10.2.1 4 Way (4+2) Each 2146.0
6.10.2.2 6 Way (6+2) Each 2373.0
6.10.2.3 8 Way (8+2) Each 2581.0
6.10.2.4 12 Way (12+2) Each 2990.0
6.10.2.5 16 Way (16+2) Each 3921.0

6.10.3 Metal door (Three phase) IK-09 and IP-43 with Metal end box

6.10.3.1 4 Way Each 3838.0


6.10.3.2 6 Way Each 4811.0
6.10.3.3 8 Way Each 5980.0
6.10.3.4 12 Way Each 8852.0

6.10.4 Glazed door (Three phase) IK-09 and IP-43 with Metal end box

6.10.4.1 4 Way Each 4806.0


6.10.4.2 6 Way Each 6126.0
6.10.4.3 8 Way Each 7533.0
6.10.4.4 12 Way Each 10660.0

6.10.5 Metal door (Three phase) Per phase isolation, Horizontal IK-09
and IP-43 with Metal end box
6.10.5.1 4Way(Incomer 8,Sub Incomer2+2+2) Each 6320.0
6.10.5.2 6Way(Incomer 8,Sub Incomer2+2+2) Each 7618.0
6.10.5.3 8Way(Incomer 8,Sub Incomer2+2+2) Each 9168.0
6.10.5.4 12 Way(Incomer 8,Sub Incomer2+2+2) Each 12248.0

Chapter E- 06 Page22
P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-06

Code No. Description Unit Complete Rate

6.10.6 Metal door (Three phase) Per phase isolation,Vertical IK-09 and IP-
43 with Metal end box
6.10.6.1 4Way(Incomer 8,Sub Incomer2+2+2) Each 7494.0
6.10.6.2 6Way(Incomer 8,Sub Incomer2+2+2) Each 9153.0
6.10.6.3 8Way(Incomer 8,Sub Incomer2+2+2) Each 9814.0
6.10.6.4 12 Way(Incomer 8,Sub Incomer2+2+2) Each 10655.0

6.11 Providing & Fixing of Recessed/surface mounting heavy duty


horizontal type TPN phase selector Distribution board with Metal
end box made out from Galvanized steel / CRCA sheet not less then
1.2 mm thick conforming to IS-8623-1 & 3 / IEC 61439- 1 & 3.
powder painted with reversible door (for double door DB only )
complete with 100 amp. insulated copper bus bar/ shorting link ,
neutral link, earth link , color coded interconnecting wire set of
suitable rating and din bar,masking sheet provided with 3 nos 63
Amp rotary switches,3 nos rocker switches for phase identifications
etc. making internal DB terminations with copper lugs, ferrules,
detachable gland plate, including making connections, testing etc.
as required. OEM shall have submit NABL / CPRI / ERDA accrediated
lab type test reports & All as per pre approved by Engineer in
charge.For additional technical parameters of product / work refer
Annexure 'A' attached with this BSR

6.11.1 Double door. IK-09 and IP-43 with Metal end box
6.11.1.1 4Way(Incomer 8,Outgoing 4+4+4) Each 11591.0
6.11.1.2 6Way(Incomer 8,Outgoing6+6+6) Each 11856.0
6.11.1.3 8Way(Incomer 8,Outgoing 8+8+8) Each 13215.0
6.11.1.4 12Way(Incomer 8,Outgoing 12+12+12) Each 15016.0

6.12 Providing & Fixing of Recessed/surface mounting heavy duty Flexi /


Row type Distribution board with Metal end box made out from
Galvanized steel / CRCA sheet not less then 1.2 mm thick
conforming to IS-8623-1 & 3 / IEC 61439- 1 & 3. powder painted
with reversible door (metal or Glazed) complete with 100 Amp.
copper shorting link , neutral link, earth link , color coded
interconnecting wire set of suitable rating and din bar,masking
sheet, making internal DB terminations with copper lugs, ferrules
detachable gland plate, including making connections, testing etc.
as required. OEM shall have submit NABL / CPRI / ERDA accrediated
lab type test reports & All as per pre approved by Engineer in
charge.For additional technical parameters of product / work refer
Annexure 'A' attached with this BSR

6.12.1 Metal door IK-09 & IP-43 with Metal end box
6.12.1.1 2 Row 28 Module(14 module per row) Each 4668.0

Chapter E- 06 Page23
P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-06

Code No. Description Unit Complete Rate


6.12.1.2 3 Row 42 Module(14 module per row) Each 5423.0
6.12.1.3 4 Row 56 Module(14 module per row) Each 5951.0
6.12.1.4 4 Row 64 Module(16 module per row) Each 6836.0

6.12.2 Glazed door IK-09 & IP-43 with Metal end box
6.12.2.1 2 Row 28 Module(14 module per row) Each 4994.0
6.12.2.2 3 Row 42 Module(14 module per row) Each 5923.0
6.12.2.3 4 Row 56 Module(14 module per row) Each 6663.0
6.12.2.4 4 Row 64 Module(16 module per row) Each 7360.0

6.13 P&F metal clad / Plastic industrial plug top & socket unit with pin
and sleeve type contact on porcelain/ bakelite base in
Recessed/surface mounting heavy duty Enclosure made out from
Galvanized steel / CRCA sheet not less then 1.2 mm thick
conforming to IS-8623-1 & 3 / IEC 61439- 1 & 3. powder painted
(without MCB) including making connections, testing etc.as
required.For additional technical parameters of product / work
refer Annexure 'A' attached with this BSR
6.13.1 20 amp, 2 pin + scrapping Earth, 1 Module Each 1279.0
6.13.2 20 amp, 2 pin + scrapping Earth, 2 Module Each 1386.0
6.13.3 20 amp, 3 pin + scrapping Earth, 4 Module Each 2052.0
6.13.4 32 amp, 5 pin + scrapping Earth, 8 Module Each 2754.0
6.13.5 63 amp, 5 pin + scrapping Earth, 8 Module Each 9776.0

6.14 P & F of Industrial plug and socket conforming to IEC 60309-1/2


made out of self extinguishing engineering polymer / polyamide,
nickel plated brass sleeve and pins, socket with shutter including
making connection etc as reqd. For additional technical parameters
of product / work refer Annexure 'A' attached with this BSR

6.14.1 IP -67 Panel mounted socket


6.14.1.1 16 A 3 pin(2P+E) Each 791.0
6.14.1.2 32 A 3 pin(2P+E) Each 979.0
6.14.1.3 32 A 5 pin(3P+N+E) Each 1234.0
6.14.1.4 63 A 5 pin(3P+N+E) Each 3532.0

6.14.2 IP -67 Surface/Wall mounted socket


6.14.2.1 16 A 3 pin(2P+E) Each 1046.0
6.14.2.2 32 A 3 pin(2P+E) Each 1222.0
6.14.2.3 32 A 5 pin(3P+N+E) Each 2266.0

Chapter E- 06 Page24
P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-06

Code No. Description Unit Complete Rate


6.14.2.4 63 A 5 pin(3P+N+E) Each 4517.0

6.14.3 IP -67 Surface/Wall mounted Interlocked Switched socket Outlet


Vertical
6.14.3.1 16 A 3 pin(2P+E) Each 7186.0
6.14.3.2 32 A 3 pin(2P+E) Each 8322.0
6.14.3.3 32 A 5 pin(3P+N+E) Each 9762.0

6.14.4 IP - 67 Plug top


6.14.4.1 16 A 3 pin(2P+E) Each 762.0
6.14.4.2 32 A 3 pin(2P+E) Each 1028.0
6.14.4.3 32 A 5 pin(3P+N+E) Each 1142.0
6.14.4.4 63 A 5 pin(3P+N+E) Each 2990.0

6.15 Providing & Fixing of Recessed/surface mounting heavy duty


Vertical TPN Distribution board with Metal end box with provision
of incomer suitable for MCB / RCCB and SP / TP MCB as outgoing
,made out from Galvanized steel / CRCA sheet not less then 1.2 mm
thick conforming to IS-8623-1 & 3 / IEC 61439- 1 & 3. powder
painted with reversible door (for double door DB only ) complete
with insulated 100 A rating copper bus bar, neutral bars with
shrouds, earth bar , color coded interconnecting wire set of
suitable rating and din bar,masking sheet, making internal DB
terminations with copper lugs, ferrules, detachable gland plate,
including making connections, testing etc. as required. OEM shall
have submit NABL / CPRI / ERDA accrediated lab type test reports
& All as per pre approved by Engineer in charge.For additional
technical parameters of product / work refer Annexure 'A' attached
with this BSR

6.15.1 Double door IK-09 & IP-43 with Metal end box
6.15.1.1 4 Way(8+12) Each 8255.0
6.15.1.2 6 Way(8+18) Each 9425.0
6.15.1.3 8 Way(8+24) Each 10580.0
6.15.1.4 12 Way(8+36) Each 13984.0

Chapter E- 06 Page25
P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-06

Code No. Description Unit Complete Rate


6.16 Providing & Fixing of Recessed/surface mounting heavy duty
Vertical TPN Distribution board with Metal end box with provision
of incomer suitable for 3/4 pole MCCB and SP / TP MCB as outgoing
,made out from Galvanized steel / CRCA sheet not less then 1.2 mm
thick conforming to IS-8623-1 & 3 / IEC 61439- 1 & 3. powder
painted with reversible door (for double door DB only ) complete
with insulated 160 (upto 160 A Incomer) / 250 Amp. copper bus
bar, neutral bars with shrouds, earth bar , color coded
interconnecting wire set of suitable rating and din bar,masking
sheet, making internal DB terminations with copper lugs, ferrules,
detachable gland plate, including making connections, testing etc.
as required. OEM shall have submit NABL / CPRI / ERDA
accrediated lab type test reports & All as per pre approved by
Engineer in charge.For additional technical parameters of product /
work refer Annexure 'A' attached with this BSR

6.16.1 Double door IP-43 & IK-09 with Provision of Incomer MCCB 100/
125 A Rating with Metal end box
6.16.1.1 4 Way Each 11538.0
6.16.1.2 6 Way Each 12751.0
6.16.1.3 8 Way Each 13775.0
6.16.1.4 12 Way Each 17813.0

6.16.2 Double door IP-43 & IK-09 with Provision of Incomer MCCB 160 A
Rating with Metal end box
6.16.2.1 4 Way Each 13778.0
6.16.2.2 6 Way Each 15274.0
6.16.2.3 8 Way Each 16589.0
6.16.2.4 12 Way Each 18858.0
6.16.3 Double door IP-43 & IK-09 with Provision of Incomer MCCB 250 A
Rating with Metal end box
6.16.3.1 4 Way Each 15200.0
6.16.3.2 6 Way Each 16831.0
6.16.3.3 8 Way Each 18103.0
6.16.3.4 12 Way Each 20755.0
6.17 P & F Surface mounting IP-65, IK-09 Class-II self extinguishing
insulating material weather proof cabinets confirming to EN60439-
3 with IP-65 Key lock, fully reversible door and cabinet, removable
chasis and face plates, of following size. For additional technical
parameters of product / work refer Annexure 'A' attached with this
BSR
6.17.1 1 row 3/4 module Each 2487.00
6.17.2 1 row 6 module Each 2955.00
6.17.3 1 row 12 module Each 4550.00
6.17.4 1 row 18 module Each 5303.00
6.17.5 2 row x 12 module Each 5991.00
6.17.6 2 row x 18 module Each 8628.00
6.17.7 3 row x 12 module Each 10379.00

Chapter E- 06 Page26
P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-07

Chapter E - 07

Electrical Accessories

Code No. Description Unit Complete Rate

7.1 P & F ISI marked (IS:3854) 6 amp. flush type non modular switch with
CM/L no. printed and made out from industrial grade Polycarbonate or fire
resistant ABS material including cutting hole in tile and making connection
testing etc. as required. All as per pre approved by Engineer in charge. For
additional technical parameters of products/ work , refer Annexure "A"
attached with this BSR . Each 23.0

7.2 P & F ISI marked (IS :3854) 16 amp. flush type non modular switch CM/L
no. printed and made out from industrial grade Polycarbonate or fire
resistant ABS material including cutting hole in tile and making connection
testing etc. as required. All as per pre approved by Engineer in charge. For
additional technical parameters of products/ work , refer Annexure "A"
attached with this BSR . Each 50.0

7.3 Providing & Fixing of 6 amp. Combined flush type non modular socket and
switch set as per PWD specification for electrical Works,made out from
industrial grade Polycarbonate or fire resistant ABS material including
cutting hole in tile and making connection testing etc. as required. All as
per pre approved by Engineer in charge. For additional technical
parameters of products/ work , refer Annexure "A" attached with this
BSR . Each 123.0

7.4 Providing & Fixing of 16 amp. Combined flush type non modular socket
and switch set with indicator and fuse set as per PWD specification for
electrical Works, made out from industrial grade Polycarbonate or fire
resistant ABS material including cutting hole in tile and making connection
testing etc. as required. All as per pre approved by Engineer in charge. For
additional technical parameters of products/ work , refer Annexure "A"
attached with this BSR . Each 180.0

7.5 Providing & Fixing of ISI marked (IS :3854) non modular 6A bell push
surface type CM/L no. printed and made out from industrial grade
Polycarbonate or fire resistant ABS material including making connection
testing etc. as required.All as per pre approved by Engineer in charge. For
additional technical parameters of products/ work , refer Annexure "A"
attached with this BSR . Each 34.0

7.6 Providing & Fixing of ISI marked (IS :3854) twin control non modular 6A
switch surface type as per PWD specification for electrical Works, made
out fromindustrial grade Polycarbonate or fire resistant ABS material, brass
terminal & captive screws including making connection testing etc. as
required. All as per pre approved by Engineer in charge. For additional
technical parameters of products/ work , refer Annexure "A" attached
with this BSR . Each 48.0

Chapter E - 07 Page27
P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-07

Code No. Description Unit Complete Rate


7.7 Providing & Fixing of ISI marked (IS :3854) non modular 6A bell push flush
type CM/L no. printed and made out from industrial grade Polycarbonate
or fire resistant ABS materialincluding cutting hole in tile and making
connection testing etc. as required.All as per pre approved by Engineer in
charge. For additional technical parameters of products/ work , refer
Annexure "A" attached with this BSR . Each 34.0

7.8 Providing & Fixing of ISI marked (IS :3854) twin control non modular 6A
switch flush type as per PWD specification for electrical Works, made out
from industrial grade Polycarbonate or fire resistant ABS material,
including cutting hole in tile and making connection testing etc. as
required. All as per pre approved by Engineer in charge. For additional
technical parameters of products/ work , refer Annexure "A" attached
with this BSR . Each 30.0

7.9 Providing & Fixing of ISI marked non modular 6A hanging bell push/one
way switch made out from industrial grade Polycarbonate or fire resistant
ABS materialincluding making connection testing etc. as required.All as per
pre approved by Engineer in charge. For additional technical parameters of
products/ work , refer Annexure "A" attached with this BSR .
Each 38.0

7.10 Providing & Fixing of of 3/5 pin 6 amp. flush type non modular socket
made out from industrial grade Polycarbonate or fire resistant ABS
material, brass terminal with Porcelain based back cover & captive screws
including cutting hole in tile and making connection testing etc. as
required.All as per pre approved by Engineer in charge. For additional
technical parameters of products/ work , refer Annexure "A" attached
with this BSR . Each 33.0

7.11 Providing & Fixing of 3/6 pin 16 amp flush type non modular socket made
out from Industrial grade Polycarbonate or fire resistant ABS material,
brass terminal with Porcelain based back cover & captive screws including
cutting hole in tile and making connection testing etc. as required.All as per
pre approved by Engineer in charge. For additional technical parameters of
products/ work , refer Annexure "A" attached with this BSR .
Each 78.0

7.12 Providing & Fixing of ISI marked (IS:371) 6 amp surface type 3 pin ceiling
rose with CM/L no. printed and made out from industrial grade
Polycarbonate or fire resistant ABS material, brass terminal & captive
screws including making connection testing etc. as required.All as per pre
approved by Engineer in charge. For additional technical parameters of
products/ work , refer Annexure "A" attached with this BSR .
Each 30.0

7.13 Providing & Fixing of ISI marked (IS:1258) batten/angle lamp holder with
CM/L no. printed and made out from industrial grade Polycarbonate or fire
resistant ABS material, brass terminal & captive screwsincluding making
connection testing etc. as required. All as per pre approved by Engineer in
charge. For additional technical parameters of products/ work , refer
Annexure "A" attached with this BSR .
Each 30.0

Chapter E - 07 Page28
P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-07

Code No. Description Unit Complete Rate


7.14 Providing & Fixing of ISI marked (IS:1293) 6 amp unbreakable 3 pin plug
top having lamp indicator with CM/L no. printed and made out from
industrial grade Polycarbonate or fire resistant ABS material, brass terminal
including making connection testing etc. as required. All as per pre
approved by Engineer in charge. For additional technical parameters of
products/ work , refer Annexure "A" attached with this BSR .
Each 44.0

7.15 Providing & Fixing of ISI marked (IS:1293) 16 amp unbreakable 3 pin plug
top having lamp indicator with CM/L no. printed and made out from
industrial grade Polycarbonate or fire resistant ABS material, brass terminal
including making connection testing etc. as required. All as per pre
approved by Engineer in charge. For additional technical parameters of
products/ work , refer Annexure "A" attached with this BSR .
Each 68.0

7.16 Providing & Fixing of flush type non modular 2 pin telephone socket with
plug top made out from industrial grade Polycarbonate or fire resistant
ABS material, brass terminals including making connection testing etc. as
required.All as per pre approved by Engineer in charge. For additional
technical parameters of products/ work , refer Annexure "A" attached
with this BSR . Each 59.0

7.17 Providing & Fixing of flush type non modular single line telephone jack
made out fromindustrial grade Polycarbonate or fire resistant ABS
material, including making connection testing etc. as required.All as per pre
approved by Engineer in charge. For additional technical parameters of
products/ work , refer Annexure "A" attached with this BSR .
Each 72.0

7.18 Providing & Fixing of flush type non modular double line telephone jack
made out fromindustrial grade Polycarbonate or fire resistant ABS
materialincluding making connection testing etc. as required.All as per pre
approved by Engineer in charge. For additional technical parameters of
products/ work , refer Annexure "A" attached with this BSR .
Each 86.0

7.19 Providing & Fixing of flush type non modular coaxial T.V. socket made out
from industrial grade Polycarbonate or fire resistant ABS material,including
making connection testing etc. as required.All as per pre approved by
Engineer in charge. For additional technical parameters of products/ work
, refer Annexure "A" attached with this BSR .
Each 48.0

7.20 Providing & Fixing of IS 11037:1984 marked non modular socket size flush
type 120 watt rotary minimum 5 step fan regulator with CM/L no. printed
and made out from industrial grade Polycarbonate or fire resistant ABS
material including making connection testing etc. as required.All as per pre
approved by Engineer in charge. For additional technical parameters of
products/ work , refer Annexure "A" attached with this BSR .
Each 199.0

Chapter E - 07 Page29
P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-07

Code No. Description Unit Complete Rate


7.21 Providing & Fixing of IS 11037:1984 marked non modular socket size flush
type 180 watt rotary minimum 5 step fan regulator with CM/L no. printed
and made out from industrial grade Polycarbonate or fire resistant ABS
material including making connection testing etc. as required.All as per pre
approved by Engineer in charge. For additional technical parameters of
products/ work , refer Annexure "A" attached with this BSR .
Each 219.0

7.22 P & F ISI marked 32 A D.P. switch with fuse and indicating lamp including
making connection testing etc. as required.All as per pre approved by
Engineer in charge. For additional technical parameters of products/ work
, refer Annexure "A" attached with this BSR . Each 173.0

7.23 Providing & Fixing of ISI marked (IS:2268-1994) gong bell with CM/L no.
printed including making connection testing etc. as required. All as per pre
approved by Engineer in charge. For additional technical parameters of
products/ work , refer Annexure "A" attached with this BSR .
Each 173.0

7.24 Providing & Fixing of ISI marked surface type buzzer (IS:2268-1994) with
CM/L no. printed including making connection testing etc. as required. All
as per pre approved by Engineer in charge. For additional technical
parameters of products/ work , refer Annexure "A" attached with this
BSR . Each 109.0

7.25 Providing & Fixing of single / multi tone electronic call bell as per PWD
specification for electrical Works, including making connection testing etc.
as required. All as per pre approved by Engineer in charge. For additional
technical parameters of products/ work , refer Annexure "A" attached
with this BSR . Each 492.0

7.26 Providing & Fixing of ding dong/musical chime bell as per PWD
specification for electrical Works, including making connection testing etc.
as required.All as per pre approved by Engineer in charge. For additional
technical parameters of products/ work , refer Annexure "A" attached
with this BSR . Each 328.0

7.27 Providing & Fixing of modular type switch/ bell push duly ISI marked (IS
:3854) with CM/L no. printed and made out of unbreakable and fire
retardant vergin UV Stabilized Polycarbonate with brass terminals and
captive screws & silver alloy contact tip with IP-20 rating ,minimum width
of switch toggle( PUSH PART ) should not less then 20mm, including all as
per pre approved by Engineer in charge,making connections, testing etc. as
required. For additional technical parameters of product / work refer
Annexure 'A' attached with this BSR

7.27.1 10 A one way switch Each 55.0


7.27.2 10 A two way switch Each 79.0
7.27.3 10 A bell push Each 110.0
7.27.4 16 A one way switch With Led Indicator Each 113.0
7.27.5 16 Amp. 2 Module switch With Led Indicator Each 147.0
7.27.6 25 Amp. 2 Module switch With Led Indicator Each 200.0
7.27.7 32 Amp. 2 Module switch With Led Indicator Each 369.0

Chapter E - 07 Page30
P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-07

Code No. Description Unit Complete Rate


7.28 Providing & Fixing of modular type lockable feature socket duly made out
of unbreakable and fire retardant vergin poly carbonate with brass
terminals and captive screws & silver alloy contact tip with IP-20 rating ,
including all as per pre approved by Engineer in charge,making
connections, testing etc. as required. For additional technical parameters
of product / work refer Annexure 'A' attached with this BSR

7.28.1 6 A 3/5 pin shuttered socket Each 107.0


7.28.2 6/16 A shuttered socket Each 176.0
7.28.3 13 A flat pin international socket Each 187.0
7.28.4 25 Amp. 2 Module Socket Each 228.0

7.29 Providing & Fixing of modular type 120 W Step Fan regulator duly ISI
marked (IS 11037:1984 ) with CM/L no. printed made out of unbreakable
and fire retardant vergin poly carbonate with brass terminals and captive
screws & silver alloy contact tip with IP-20 rating , including all as per pre
approved by Engineer in charge,making connections, testing etc. as
required. For additional technical parameters of product / work refer
Annexure 'A' attached with this BSR

7.29.1 5 step fan regulator 2 Module 360 dgree rotating Each 398.0

7.30 Providing & Fixing of following modular accessories as per PWD


specification for electrical Works, made out of unbreakable and fire
retardant vergin poly carbonate with brass terminals and captive screws &
silver alloy contact tip with IP-20 rating , including all as per pre approved
by Engineer in charge,making connections, testing etc. as required. For
additional technical parameters of product / work refer Annexure 'A'
attached with this BSR
7.30.1 RJ-11 telephone jack single line Each 142.0
7.30.2 RJ-11 telephone jack Double line Each 169.0
7.30.3 USB Charger 1 A - 1 M with BIS mark Each 483.0
7.30.4 RJ-45, Cat 6 computer jack with shutter Each 316.0
7.30.5 T.V. coaxial socket Each 159.0
7.30.6 Blanking plate Each 22.0
7.30.7 25 Amp. 2 Module Motor Starter with on / off Push button Each 388.0
7.30.8 LED Skirting /Foot Light 2 Module Each 361.0
7.30.9 Electronic Chime/Buzzer 2M Each 212.0
7.30.10 Modular MCB 6 A to 32 A SP Each 225.0
7.30.11 Modular MCB 6 A to 32 A DP Each 461.0

7.31 Providing & Fixing of following size mounting grid plates with cover plates
made from fire retardent UV established high performance engineering
plastic suitable for all universal metal boxes for front installation & removal
direct fit type complete in all respect.All as per pre approved by Engineer in
charge. For additional technical parameters of products/ work , refer
Annexure "A" attached with this BSR .

7.31.1 1/2 Module Each 65.0


7.31.2 3 Module Each 86.0
7.31.3 4 Module Each 89.0
7.31.4 5 Module Each 105.0
7.31.5 6 Module Each 114.0
7.31.6 8 Module Each 155.0

Chapter E - 07 Page31
P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-07

Code No. Description Unit Complete Rate


7.31.7 10 Module Each 198.0
7.31.8 12 Module Each 214.0
7.31.9 16/18 Module Each 316.0

7.32 Providing & Fixing of Wiring Accessories OEM fabricated following size GI
box of 1.2 mm thick with earthing terminal and adjustable floating clamp in
recess/ surface suitable for modular accessories as required.All as per pre
approved by Engineer in charge. For additional technical parameters of
products/ work , refer Annexure "A" attached with this BSR .

7.32.1 1-2 Module Each 86.0


7.32.2 3 Module Each 120.0
7.32.3 4/5 Module Each 140.0
7.32.4 6 / 8 module Each 204.0
7.32.5 10 / 12 module Each 286.0
7.32.6 16/18 module Each 417.0

7.33 Providing & Fixing of Wiring Accessories OEM fabricated following size
virgin material UPVC modular boxes on surface suitable for modular
accessories as required.All as per pre approved by Engineer in charge. For
additional technical parameters of products/ work , refer Annexure "A"
attached with this BSR .
7.33.1 1-2-3 Module Each 98.0
7.33.2 4-5 Module Each 152.0
7.33.3 6-8 Module Each 216.0
7.33.4 10-12 Module Each 287.0
7.33.5 16/18 Module Each 332.0

7.34 Providing & Fixing of of ISO certified company made Multiple socket with
surge and spikes protection cartridge not less then 5 KV as per PWD
specification for electrical Works with minimum four nos. universal 6 A
sockets, one 6 A switch and 3 pin company fitted plug top and 3 core
multistrand copper lead minimum 1.5 mtr. including making connection
etc as required. All as per pre approved by Engineer in charge. For
additional technical parameters of products/ work , refer Annexure "A"
attached with this BSR . Each 572.0

7.35 Providing & Fixing of ISO certified company made virgin material PVC
trunking system as per PWD specification for electrical Works, with double
lock feature for cable management including finishing accessories like
corners, tees, adjustable angles, junction etc. as required . The trunking
system shall have adaptable system for modular type RJ 45 data socket/
wiring accessories/ power sockets and shall be covered with peal off plastic
cover. OEM shall have submit NABL accrediated /CPET lab test reports
before execution & All as per pre approved by Engineer in charge. For
additional technical parameters of products/ work , refer Annexure "A"
attached with this BSR .

7.35.1 32mm X 20mm Mtr. 228.0


7.35.2 80mm x 50mm Mtr. 997.0
7.35.3 100/105mm x 50mm Mtr. 1181.0
7.35.4 150/160mm x 50mm Mtr. 1994.0
7.35.5 195/200mm x 50mm Mtr. 2544.0

Chapter E - 07 Page32
P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-07

Code No. Description Unit Complete Rate


7.36 Providing and fixing of power plug point with non modular accessories as
per PWD specification for electrical Works with Galvanized box of 1.2 mm
thick with earth terminal with suitable size phenolic laminated sheet (IS :
2036 - 1995) cover including cost of 16 amp. Switch (IS :3854) and 3/6 pin
16 amp. socket outlet making connection , testing , etc. as required. . For
specification of Wiring accessories refer Chapter E - 07 related item & For
additional technical parameters of product / work refer Annexure 'A'
attached with this BSR
Each 303.00

7.37 Supplying and fixing of power plug point with Modular accessories as per
PWD specification for electrical Works, on hot dipped galvanized modular
box of 1.2 mm thick with earthing terminal/connector on surface or in
recessed with suitable size of modular face place with grid plate and cover
plate including cost of ISI marked modular 16 amp. Switch (IS :3854) and
6/16 amp. socket outlet (IS:1293) making connection , testing , etc. as
required. For specification of Wiring accessories refer Chapter E - 07
related item & For additional technical parameters of product / work refer
Annexure 'A' attached with this BSR
Each 580.00

7.38 P & F Krone module with base frame in the recess / surface made out of
1.2 mm thick sheet steel box, front openable, having locking arrangements
duly powder painted,including dressing, ferruling and punching of
telephone cable with krone tool etc. as required. For additional technical
parameters of product / work refer Annexure 'A' attached with this BSR

7.38.1 10 Pairs Each 943.00


7.38.2 20 Pairs Each 1213.00
7.38.3 50 Pairs Each 2561.00
7.38.4 100 Pairs Each 4988.00
7.38.5 200 Pairs Each 8424.00

Chapter E - 07 Page33
P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-08

Chapter E - 08

LT Panels & Accessories

Complete
Code No. Description Unit
Rate

8.1 SITC of IP-42 and general construction confirming to IS:8623 : 1993, wall/ free
standing floor mounted dust and vermin proof compartmentalised cubical panel
as specifications and Other parameters required as per point (a) ,(b), (c),(d), (e),
(f), (g), (h) as below:-
(a)Thickness of CRCA sheet shall be 2.0 mm, cable alley compartments having
concealed hinged type doors with key type lock with / without detachable
extension type structure. Removable 3 mm. thick sheet steel gland plates with
appropriate size of knockouts for cables shall be provided

(b)complete panel shall undergo a process of degreasing, Water rinsing,


Activation, derusting, pickling in acid bath, phosphatising & shall be subjected to
nine tank process and then Powder coated with approved shade of minimum 70
microns on both side of panel. The panel having PE foam/ Neoprene rubber
gasket of not less than 3mm thickness ,required hardware , concealed hinged
door with key type locking arrangement for equipment/switchgear earthed with
2.5 sq.mm braided copper wire.
[c) Interconnection between bus bar and switchgears /cable shall be rigidly
supported and made out by flexible copper wires (up to 63 amp ) and by solid bus
bar (>63 amp ) . control wiring will be carried out with 1.5 Sq.mm, Earth wire with
2.5 Sq.mm and CT with 2.5 sq.mm flexible copper wire only. All joints /
interconnections of copper bus bar shall be dully tinned . Clearance between
main bus bar and risers / metal parts shall be at least 10 mm additional to width
of bus bar Bus bar is insulated by Heat Shrinkable sleeves . Earth and Neutral bus
bar shall be half of the size of phase bus bar. ( Cost of Bus bar / Flexible wire for
Interconnection between Main busbar and Switchgear is to be Paid Extra )

(d)Wiring between components within switchgear and Incoming / outgoing cable


shall be done through the terminal block only. Direct connection shall not be
permitted. Each terminal block shall be one piece moulded, barrier type, 650 volt
grade, complete with washers, heads, studs with two nuts and identification strips
and shall have adequate continuous current rating. For tap-offs, adjacent
terminals with shorting strips shall be used. 10% Spare terminal blocks shall be
provided. Wire identification on marking strip shall correspond to the designation
of the wiring diagrams. All wire terminals on the equipment shall also be marked
with designation corresponding to those of the wiring diagram.

(e)All wiring shall be enclosed in plastic channels and neatly bunched and closed
in metering chamber, Wiring between terminals of various devices shall be ‘point
to point’ (no wire splitting or tee connections) with wires neatly trucked along the
back of the panels, adequately supported to prevent sagging.

(f)Floor mounted panel shall be mounted on Base frame of ISMC channel size 100
x 50 x 5 mm ( to be paid Extra )

Chapter E - 08 Page34
P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-08

Complete
Code No. Description Unit
Rate
(g) Tests: The insulation resistance (with 1000 V Megger) and High voltage Power
frequency test (by applying a voltage of 2.5KV for one minute) shall be measured
between phases, between phase and neutral and between phase and earth. both
before and after high voltage power frequency test. The insulation resistance shall
not be less than three megaohm. CT Secondary current injection test shall also be
carried out.
(h) only outer surface area on all sides shall be measured & panel to be fabricated
only from CPRI approved fabricator only (CPRI Test certificates to be submitted)All
as per pre approved by Engineer in charge. For additional technical parameters of
products/ work , refer Annexure "A" attached with this BSR .
Sq. Mtr 5975.0

8.2 Supplying and fixing of Aluminium (IEC 60105 ISO 209-1,2) / Copper (IEC 60028)
bus bar by means of SMC / DMC type insulator with standard short circuit
withstand capacity , high tensile nuts and bolts spring washers in existing panel
including bending , cutting in required shape and size and colour coding with heat
shrinkable PVC sleeves. All as per pre approved by Engineer in charge. For
additional technical parameters of products/ work , refer Annexure "A" attached
with this BSR .
8.2.1 Electrolytic grade Aluminium bus bar 6010 grade Kg. 542.0
8.2.2 Electrolytic grade (Cu-ETP) Tin Coated annealed copper bus bars IACS 100% Kg. 1301.0
grade

8.3 Providing & Fixing of IS: 13875 & IEC :61326 confirming LED Digital type (up to
500) V range Volt meter / Direct- Ammeter / CT oertated ammeter/ Frequency
meter / KWH meter / Multi Function Meter / Power analyzer of class 1 accuracy
as per IS : 1248 of size 96mm x 96 mm including making connection by PVC
insulated copper conductor with PVC sleeves / channel etc. as required. All as per
pre approved by Engineer in charge. For additional technical parameters of
products/ work , refer Annexure "A" attached with this BSR .

8.3.1 Single Phase Ammeter Each 1172.0


8.3.2 Single Phase Voltmeter Each 1172.0
8.3.3 Three phase Ammeter with Inbuilt Selector Switch Each 1689.0
8.3.4 Three phase Voltmeter with Inbuilt Selector Switch Each 1689.0
8.3.5 Three phase KWH Meter Each 3530.0
8.3.6 Three phase KWH Meter Dual Source Each 3858.0
8.3.7 Frequency Meter Each 1172.0
8.3.8 Three phase AMP+HZ+PF+KW+KVA+KVAR+T.ENERGY+THD-I, THD-V & RUN HRS Each 3252.0
Three phase AMP + HZ + PF + KW + KVA + KVAR + KVARH+KWH+DUAL ENERGY+
8.3.9 Each 5241.0
ENERGY+THD-I, THD-V & RUN HRS
Three phase with universal Auxiliary supply + AMP + HZ + PF + KW + KVA + KVAR +
8.3.10 KVARH + KWH + DUAL ENERGY+ ENERGY+THD-I, THD-V & RUN HRS + MD with Each 6272.0
RS485

Chapter E - 08 Page35
P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-08

Complete
Code No. Description Unit
Rate
8.4 Providing & Fixing of BIS approved Current Transformer as per PWD specification
for electrical Works ,ISI marked as per IS 2705-1992/ conforming to IEC 60044-1,
with secondary terminal of CT shall be brought out suitable to a terminal block
which shall be easier accessible for testing and terminal connection , with all
necessary support in existing panel including connection etc. as required Current
transformer Ring Type Tape Wound/Resin Cast Wound as per IS 16227 with,
Accuracy Cl, CT ratio and burden as specified. ISF<=5, Cu cross section of
secondary wire 1.5sqmm (minimum), including all necessary support in existing
panel including connection etc. as required . All as per pre approved by Engineer
in charge.All as per pre approved by Engineer in charge. For additional technical
parameters of products/ work , refer Annexure "A" attached with this BSR .

8.4.1 Ring type tape wound CT


8.4.1.1 C T Class 1, Ratio upto 150/5, Burden 5 VA Each 614.0
8.4.1.2 C T Class 1, Ratio 200/5 to 300/5, Burden 10 VA Each 788.0
8.4.1.3 C T Class 1, Ratio 400/5 to 1200/5, Burden 15 VA Each 919.0
8.4.1.4 C T Class 1, Ratio 1600/5 to 3000/5, Burden 15 VA Each 1768.0
8.4.1.5 C T Class 1, Ratio 3200/5 to 4000/5, Burden 15 VA Each 2963.0
8.4.2 Resin cast wound type CT
8.4.2.1 C T Class 1, Ratio upto 150/5, Burden 5 VA Each 1214.0
8.4.2.2 C T Class 1, Ratio 200/5 to 300/5, Burden 10 VA Each 1312.0
8.4.2.3 C T Class 1, Ratio 400/5 to 1200/5, Burden 15 VA Each 1574.0
8.4.2.4 C T Class 1, Ratio 1600/5 to 3000/5, Burden 15 VA Each 2586.0
8.4.2.5 C T Class 1, Ratio 3200/5 to 4000/5, Burden 15 VA Each 4360.0

8.5 Providing & Fixing of selector switch of 10 A for voltmeter using high grade
engineering material to international standards with cam assembly insulation of
glass filled polyamide with high tracking index. For reliable and stable electrical
and mechanical endurance double butt contacts with silver bi-metal on copper
should provided . contact assembly is of operating temp range -25 degree C to 55
degree C, frequency upto 10 KHz. switch life under std. op. conditions shall be
mechanically minimum 50000 operations @300 cycles/ hour and electrically
10,000 operations at 100% rated duty for 100 cycles/ hour including making
connection etc. as required . All as per pre approved by Engineer in charge. For
additional technical parameters of products/ work , refer Annexure "A" attached
with this BSR .

8.5.1 Voltage Between Phases with OFF ( 4 Position ) Each 351.0


8.5.2 Voltage Between Phases & Individual Phases to Neutral with OFF ( 7 Position ) Each 692.0

8.6 Providing & Fixing of CT linked selector switch of 10 A for Ampere meter (4
position ) using high grade engineering material to international standards with
cam assembly insulation of glass filled polyamide with high tracking index. For
reliable and stable electrical and mechanical endurance double butt contacts with
silver bi-metal on copper should provided . contact assembly is of operating temp
range -25 degree C to 55 degree C, frequency upto 10 KHz. switch life under std.
Each 384.0
op. conditions shall be mechanically minimum 50000 operations @300 cycles/
hour and electrically 10,000 operations at 100% rated duty for 100 cycles/ hour ,
including making connection etc. as required .All as per pre approved by Engineer
in charge. For additional technical parameters of products/ work , refer
Annexure "A" attached with this BSR .

Chapter E - 08 Page36
P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-08

Complete
Code No. Description Unit
Rate
8.7 Providing & Fixing of Cam operated rotary (Auto/manual) switches on existing
panel with 2 way and off position using high grade engineering material to
international standards with cam assembly insulation of glass filled polyamide
with high tracking index. For reliable and stable electrical and mechanical
endurance double butt contacts with silver bi-metal on copper should provided .
contact assembly is of operating temp range -25 degree C to 55 degree C,
frequency upto 10 KHz. switch life under std. op. conditions shall be mechanically
minimum 50000 operations @300 cycles/ hour and electrically 10,000 operations
at 100% rated duty for 100 cycles/ hour including making connection etc. as
required . All as per pre approved by Engineer in charge. For additional technical
parameters of products/ work , refer Annexure "A" attached with this BSR .

8.7.1 10 AMP Each 363.0


8.7.2 16 Amp Each 428.0
8.7.3 32 AMP Each 504.0
8.7.4 63 AMP Each 880.0

8.8 Providing & Fixing of 110/220 V, unibody LED Indicating lamp IEC 60947 with
integral circuit, IP 65 above panel & IP 20 terminal block, Approx. body dia for
panel not less then 20 mm, length min. 50mm, front LED cover dia min. 29 mm,
contact material phospher bronze for Led, PCB contacts shall be of brass (tin
plated), impulse dielectric tested for 2.5 KV, Rated insulation resistance shall be
100 M ohm at 500VDC including connection etc. as required. All as per pre
approved by Engineer in charge. For additional technical parameters of products/
work , refer Annexure "A" attached with this BSR .

8.8.1 Red/yellow/Green colour Each 170.0


8.8.2 Blue / white Colour Each 260.0

8.9 Providing & Fixing of flush head push button actuators IEC 60947 with integral
circuit, IP 65 above panel & IP 20 terminal block, Approx. body dia for panel not
less then 20 mm, length min. 50mm, front LED cover dia min. 29 mm, contact
material phospher bronze for Led, PCB contacts shall be of brass (tin plated),
impulse dielectric tested for 2.5 KV, including connection etc. as required. All as
per pre approved by Engineer in charge. For additional technical parameters of
products/ work , refer Annexure "A" attached with this BSR .

8.9.1 Non luminous type Each 164.0


8.9.2 Luminous type Red , Yellow, Green, Amber Each 215.0
8.9.3 Luminous type Blue , white Each 344.0

8.10 Providing & Fixing of Electrical insulating rubber matts as per PWD specification
for electrical Works, ISI marked confirming to IS: 15652 / 2006 with one side anti
skid abberation marks and pasting the mat with synthetic rubber adhesive as
required. All as per pre approved by Engineer in charge. For additional technical
parameters of products/ work , refer Annexure "A" attached with this BSR .

3.3 KV, class A 2 mm thick with proof voltage 10 KV AC (rms) and Break Down
8.10.1 SQ.Mtr. 1498.0
Voltage 30 KV AC (rms)
11 KV, Class B 2.5 mm thick with proof voltage 22 KV AC (rms) and Break Down
8.10.2 SQ.Mtr. 2043.0
Voltage 45 KV AC (rms)
33 KV, class C 3 mm thick with proof voltage 36 KV AC (rms) for 3 min. and Break
8.10.3 SQ.Mtr. 2316.0
Down Voltage 65 KV AC (rms)

Chapter E - 08 Page37
P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-08

Complete
Code No. Description Unit
Rate
8.11 Providing & Fixing of self healing IP20 MPP type shunt capacitor (banks)
conforming to IS:13340-41 / IEC :831-1&2 OR IEC : 60831-1& 2 in existing panel
or parallel with load terminals , the capacitor shall be fitted with discharge
resistors, pressure sensitive disconnector ( PSD ) and shall have dissipation factor
less than 0.0025 at 50 Hz, Operating loss less than 0.30 Watt per KVAR. Min over
current capacity 1.8 times rated current & peak inrush current min. 300 times of
rated current, llife expectancy greater than 100000hrs (temp class - 25 D) in 440
V/480 V Capacitor and for 525 V should life expectancy minimum 1,65,000 hrs
(temp class - 25 D) including making connections, testing etc. as required.All as
per pre approved by Engineer in charge. For additional technical parameters of
products/ work , refer Annexure "A" attached with this BSR .

8.11.1 Heavy duty Three phase 440 V, 50 Hz cylindrical type capacitor (Bank) KVAR 374.0
8.11.2 Heavy duty Three phase 480 V, 50 Hz cylindrical type capacitor (Bank) KVAR 415.0
8.11.3 Heavy duty Three phase 525V, 50 Hz cylindrical type capacitor (Bank) KVAR 470.0

8.12 Providing & Fixing of 3-Phase 415/440 V , 7 % / 14 % Detuned Reactors


conforming to IEC 61558-2-20 & IEC 60076-6 Aluminium wound for harmonics
filter with 180% to 200 % Linearity, H - Class Insulation ( 180 degree C), high temp.
Disconnection above 155 deg C., ambient temperature: +60 deg C. with thermal
cut off switch in existing panel with following Capacitor ratings. including making
connections, testing etc. as required. All as per pre approved by Engineer in
charge. For additional technical parameters of products/ work , refer Annexure
"A" attached with this BSR .

8.12.1 7 % (189 Hz) Aluminium wound Reactors


8.12.1.1 For 1 to 5 KVAR capacitor 5295.0
8.12.1.2 10 KVAR 7430.0
8.12.1.3 12.5 KVAR 8133.0
8.12.1.4 15 KVAR 8728.0
8.12.1.5 20 KVAR 10445.0
8.12.1.6 25 KVAR 11098.0
8.12.1.7 50 KVAR 17507.0
8.12.1.8 100 KVAR 35350.0
8.12.2 14 % (133 Hz) Aluminium wound Reactors
8.12.2.1 For 1 to 5 KVAR capacitor 8208.0
8.12.2.2 10 KVAR 10291.0
8.12.2.3 12.5 KVAR 11727.0
8.12.2.4 15 KVAR 12202.0
8.12.2.5 20 KVAR 14930.0
8.12.2.6 25 KVAR 15720.0
8.12.2.7 50 KVAR 25702.0
8.12.2.8 100 KVAR 47811.0

Chapter E - 08 Page38
P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-08

Complete
Code No. Description Unit
Rate
8.13 Providing & Fixing of IP54 microprocessor based 3 CT’s for all 3 phase sensing
compensation power factor correction relay Size 139mm x 139 mm, Operating
Voltage 415/440 V , IEC / EN 61000-6-(2&4) having 3 CT sensing, sensitivity up to
50 milli amp secondary current , self analysing auto c/k setting according to
targeted power factor setting, the relay shall have digit display unit for display of
real power factor, targeted power factor, lag/lead capacitor switching status,
alarm output for under current, over current, insufficient compensation,
communication interface with RS 485, indication of switching on units,
auto/manual status, and shall have over load protection, no volt release , having
multi parameter like KW, KVA, KVAR, RMS Value, step switching time 2 sec to
1800 sec. Lead & Lag parameters, metering facility and 3 no. Class- 0.5 Cast Resin
CT ( refer CT specs in this chapter )for sensing the relay including making
coonection with 1.5 Sq.mm copper wire etc. as required. All as per pre approved
by Engineer in charge. For additional technical parameters of products/ work ,
refer Annexure "A" attached with this BSR .

8.13.1 6 to 8 stage Each 14995.0


8.13.2 12 to 14 stage Each 19624.0

8.14 Providing & Fixing of AC operated heavy duty 230 /440 Volt power contactor as
per PWD specification for electrical Works, ISI marked IS/IEC 60947-4-1 : 2000
having provision of mechanical interlocking, auxilary contacts, Din rail mounting
type including making connections, testing etc. as required. All as per pre
approved by Engineer in charge. For additional technical parameters of products/
work , refer Annexure "A" attached with this BSR .

8.14.1 3 pole Power contactors with following AC 3 Rating


8.14.1.1 Up to 12 Amp Each 1033.0
8.14.1.2 13 to 25 Amp Each 1346.0
8.14.1.3 32 Amp. Each 2784.0
8.14.1.4 40 Amp Each 4019.0
8.14.1.5 50 Amp Each 5450.0
8.14.1.6 70 Amp Each 7618.0
8.14.1.7 80 Amp Each 9405.0
8.14.1.8 95 Amp Each 13429.0
8.14.1.9 140 Amp Each 21906.0
8.14.1.10 185 Amp Each 24680.0
8.14.1.11 250 Amp Each 30614.0
8.14.1.12 300 Amp Each 38637.0
8.14.1.13 400 Amp Each 48984.0
8.14.1.14 550 Amp Each 72214.0
8.14.1.15 630 Amp Each 109755.0

8.14.2 4 pole Power contactors with following AC 1 Rating


8.14.2.1 16 Amp. Each 1134.0
8.14.2.2 25/32 Amp. Each 1188.0
8.14.2.3 40 Amp Each 1700.0
8.14.2.4 50 Amp Each 2135.0
8.14.2.5 63 Amp Each 4045.0
8.14.2.6 100 Amp Each 7849.0
8.14.2.7 160 Amp Each 14656.0
8.14.2.8 200 Amp Each 19935.0
8.14.2.9 250 Amp Each 20752.0
Chapter E - 08 Page39
P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-08

Complete
Code No. Description Unit
Rate
8.14.2.10 325 Amp Each 37908.0
8.14.2.11 400 Amp Each 47811.0
8.14.2.12 500 Amp Each 58857.0
8.14.2.13 600 Amp Each 64027.0
8.14.2.14 700 Amp Each 81130.0
8.14.2.15 800 Amp Each 105899.0

8.15 Providing & Fixing of 440 Volt 3 pole capacitor (AC 6 B ) duty contactor with 3 no.
early make and post break auxiliary contacts in series with quick discharge
damping resistors/ reactors to limit the inrush current as per PWD specification
for electrical Works, IS/IEC 60947-4-1 : 2000, insulation voltage 1000V, impulse
withstand voltage 8 KV,Din rail mounting type including making connections,
testing etc. as required. suitable for following capacity capacitor bank. All as per
pre approved by Engineer in charge. For additional technical parameters of
products/ work , refer Annexure "A" attached with this BSR .

8.15.1 up to 6 KVAR Each 1813.0


8.15.2 8.5 KVAR Each 2127.0
8.15.3 10 KVAR Each 2277.0
8.15.4 12.5 KVAR Each 2304.0
8.15.5 15.0 KVAR Each 3075.0
8.15.6 20.0 KVAR Each 3518.0
8.15.7 25.0 KVAR Each 3764.0
8.15.8 30.0 KVAR Each 5993.0
8.15.9 40.0 KVAR Each 10535.0
8.15.10 50.0 KVAR Each 10787.0
8.15.11 60.0 KVAR Each 12547.0
8.15.12 75.0 KVAR Each 14047.0
8.15.13 85 KVAR Each 15909.0
8.15.14 100 KVAR Each 17218.0

8.16 P & F of Auxiliary Contactor for AC control standard. 24 V Coil 110, 240 V, 415 V,
50 Hz conforming to IS:13947-4-1/IEC:60947-4-1 with required NO & NC
combination including making connections, testing etc. as required. All as per pre
approved by Engineer in charge. For additional technical parameters of products/
work , refer Annexure "A" attached with this BSR .
Each 1330.0

8.17 P & F of Front / Side mounting Add on Auxiliary Contact Block with required NO
& NC combination including making connections, testing etc. as required. All as
per pre approved by Engineer in charge. For additional technical parameters of
products/ work , refer Annexure "A" attached with this BSR .
Each 629.0

8.18 Providing & Fixing of thermal over load relay with built in single phase protection
and having at least 1NO & 1NC contacts, manual /auto reset facility including
making connection testing etc. as required. All as per pre approved by Engineer
in charge. For additional technical parameters of products/ work , refer
Annexure "A" attached with this BSR .
8.18.1 Up to 14 Amp Each 1158.00
8.18.2 14 to 23 Amp Each 1295.00
Chapter E - 08 Page40
P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-08

Complete
Code No. Description Unit
Rate
8.18.3 20 to 33 Amp Each 1840.00
8.18.4 24 to 40 Amp Each 1977.00
8.18.5 36 to 60 Amp Each 2931.00
8.18.6 45 to 75 Amp Each 3341.00
8.18.7 66 to 110 Amp Each 3750.00

8.19 P & F of 240 / 415 V Electronic ON - OFF Timer 3 -30 Sec / 12 - 120 Sec including
making Connection etc. as required. All as per pre approved by Engineer in
charge. For additional technical parameters of products/ work , refer Annexure
"A" attached with this BSR . Each 1938.0

8.20 Providing & Fixing of mechanical / digital time switch having following day / week
programme and minimum 100 hours reserve and AC1 rating of 16-20 amperes
including making connection, programming conforming to IEC 60730-1 and 60730-
2-7 etc. as required. All as per pre approved by Engineer in charge. For additional
technical parameters of products/ work , refer Annexure "A" attached with this
BSR .
8.20.1 One day reserve (Analog type ) Each 4390.0
8.20.2 One day & week reserve (Analog type ) Each 4690.0
8.20.3 One day & week reserve (digital type ) Each 4100.0

8.21 Providing & Fixing of 110 - 240 V, AC, 1 ph. , 2 W Astronomical time switch with
surge suppressor, memory card, Sunrise / Sunset selectable, software for
programming including making connection, etc. as required. All as per pre
Each 5017.00
approved by Engineer in charge. For additional technical parameters of products/
work , refer Annexure "A" attached with this BSR .

8.22 Providing & Fixing of IP51 direct or CT operated, 1x240 / 3x240 volts , 50 Hz static
watt-hour meter (kwh) as per PWD specification for electrical Works, ISI marked
(IS :13010-2002 ) having resolution 0.1 / 0.01 kwh , accuracy class 1 as per
IS:13779, LED indicators for tamper operation ( Reverse &/or earth connection) ,
pulsating LED indicator for meterology , LCD Display, cover plate for body and
terminal sealing , push button for all standard parameters, including making
connection ,testing etc. as required. All as per pre approved by Engineer in
charge. For additional technical parameters of products/ work , refer Annexure
"A" attached with this BSR .

8.22.1 up to 30 ampere single phase meter Each 1700.0


8.22.2 10 A to 60 ampere Single phase meter Each 1836.0
8.22.3 3ph, 4W KWh CT Operated Base mounting 240 V, /5A Each 5334.0
8.22.4 3ph, 4W KWh Direct Base mounting 240 V 10-40 /5-30 Amp Each 4638.0
8.22.5 3ph, 4W KWh Direct Base mounting 240 V 10-60 Amp Each 5647.0
8.22.6 3ph, 4W Trivector Meter,240 V(L-N) 5A Each 21600.0

Chapter E - 08 Page41
P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-08

Complete
Code No. Description Unit
Rate
8.23 P & F of Automatic Transfer Switch (ATS) confirming to IEC60947-6-1, Utilization
cateogory AC-33B in Existing panel for automatic on load transfer between two
source power supply of 415V through Solenoid/Motorised mechanism and
integrated with three positions realize fast transfer within 100 ms. ATS shall have
three postions (S1-OFF-S2) , Manual / Auto Override feature, The two sources can
be isolated in the off position with a padlock. capability to expand with RS 485
communication module, which can ensure real-time transmission of
communication data. ATS shall have automatic generator start & stop control
function; Auxillary contacts to indicate mechanical positions. Minimum Electrical
operations 6000, of following Current ratings, including making connections etc.
as required. All as per pre approved by Engineer in charge. For additional
technical parameters of products/ work , refer Annexure "A" attached with this
BSR .

8.23.1 63 Amps Each 37750.00


8.23.2 125 Amps Each 71332.00
8.23.3 160 Amps Each 73293.00
8.23.4 200 Amps Each 83667.00
8.23.5 250 Amps Each 105896.00
8.23.6 315 Amps Each 112759.00
8.23.7 400 Amps Each 128055.00
8.23.8 630 Amps Each 156882.00
8.23.9 800 Amps Each 192835.00

8.24 P & F Earth leakage relay for continuous surveillance of the earth leakage current
of Rating 240 VAC at 50/60 Hz, Overload : x2 continuously, x10 for 3 secs as per
BS6253, Voltage Tolerance : : - 25% to +10% Operating temp.: : -10 C to +70 C,
Setting of trip point : : 0.030, 0.10, 0.30, 0.50, 1.0 ,3.0 ,5.0, 10.0,20.0 & 30.0 (
User Selectable) with Alarm Relay Output, Trip Relay Output etc. as required. All
as per pre approved by Engineer in charge. For additional technical parameters of
products/ work , refer Annexure "A" attached with this BSR .

8.24.1 ELR with 35mm CBCT 2172.00


8.24.2 ELR with 70mm CBCT 2389.00
8.24.3 ELR with 120mm CBCT 2656.00
8.24.4 ELR with 210mm CBCT 3664.00

8.25 P & F of Direct on line (DOL) / Star - Delta Starter as per IEC type-2 Co-ordination
chart of OEM in Existing Panel with circuit breaker having inbuilt overload
protection or separate thermal Overload relay , Short circuit, phase loss
protection, suitable Contactors, including wiring between switchgears, Indicating
lamps for R,Y,B,ON,OFF, Push button for ON, OFF, Volt meter, Ammeter, selector
switch for local/remote, auto/manual/OFF operation. Cast resin CT's, provision
for potential free contacts making connection, testing etc. as required. All as per
pre approved by Engineer in charge. For additional technical parameters of
products/ work , refer Annexure "A" attached with this BSR .

8.25.1 Direct on line (DOL) Starter with following Motor rating


8.25.1.1 Motor rating 0.55 KW Set 9990.00
8.25.1.2 Motor rating 0.75 KW Set 11262.00
8.25.1.3 Motor rating 1.5 KW Set 11499.00
8.25.1.4 Motor rating 2.2 KW Set 11533.00
8.25.1.5 Motor rating 4.0 KW Set 12288.00
8.25.1.6 Motor rating 5.5 KW Set 12757.00

Chapter E - 08 Page42
P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-08

Complete
Code No. Description Unit
Rate
8.25.1.7 Motor rating 7.5 KW Set 13075.00
8.25.1.8 Motor rating 9.0 KW Set 16192.00
8.25.1.9 Motor rating 11.0 KW Set 16305.00
8.25.1.10 Motor rating 15.0 KW Set 24383.00
8.25.1.11 Motor rating 18.5 KW Set 27500.00
8.25.1.12 Motor rating 22.0 KW Set 30363.00
8.25.1.13 Motor rating 30.0 KW Set 37668.00
8.25.1.14 Motor rating 37.0 KW Set 44560.00
8.25.1.15 Motor rating 45.0 KW Set 46033.00
8.25.1.16 Motor rating 55.0 KW Set 49920.00
8.25.1.17 Motor rating 75.0 KW Set 69634.00
8.25.1.18 Motor rating 90.0 KW Set 77829.00
8.25.1.19 Motor rating 110.0 KW Set 92373.00
8.25.2 Star - Delta Starter with following Motor rating
8.25.2.1 Motor rating 4.0 KW Set 17785.00
8.25.2.2 Motor rating 5.5 KW Set 18427.00
8.25.2.3 Motor rating 7.5 KW Set 18796.00
8.25.2.4 Motor rating 9.0 KW Set 24116.00
8.25.2.5 Motor rating 11.0 KW Set 24813.00
8.25.2.6 Motor rating 15.0 KW Set 35864.00
8.25.2.7 Motor rating 18.5 KW Set 44893.00
8.25.2.8 Motor rating 22.0 KW Set 46824.00
8.25.2.9 Motor rating 30.0 KW Set 54663.00
8.25.2.10 Motor rating 37.0 KW Set 71611.00
8.25.2.11 Motor rating 45.0 KW Set 77037.00
8.25.2.12 Motor rating 55.0 KW Set 85874.00
8.25.2.13 Motor rating 75.0 KW Set 91754.00
8.25.2.14 Motor rating 90.0 KW Set 123832.00
8.25.2.15 Motor rating 110.0 KW Set 157054.00

8.26 SITC of IP-42 and general construction confirming to IEC 61439-1&2. type tested
assembly (TTA) wall/ free standing floor mounted dust and vermin proof
compartmentalised cubical panel as specifications and Other parameters
required as per point (a) ,(b), (c),(d), (e), (f), (g), (h) as below:-
(a) Panel having short circuit withstand capacity of minimum of 50 kA for 1s (Icw
rating) at 415 V, 50 HZ AC supply, Rated Impulse withstand voltage (Uimp) of
12kV for withstanding against transient Overvoltages, mechanical impact level of
IK10 level and internal arc for 50kA for 0.3 second with aluminum busbar and fully
type tested at an Independent Laboratory, Type test certifacte has to be
submitted for all rating of LV Switchgear to be used in Panel.

(b) All four Horizontal Busbars shall be in same compartment. Certified design of
switchboards shall be proven design from OEM (Switchgear Manufacturer). OEM
name should be mentioned on top of each column of switchboard. Also, OEM
Partnership Certificate shall be furnished by Panel builder. Panel shall be
fabricated with a double door arrangement. Front Door shall be fitted with
transparent Glass to allow maintenance staff to visually access device status,
meter readings, indicating lamp status without opening the door.

Chapter E - 08 Page43
P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-08

Complete
Code No. Description Unit
Rate
© Panels and cubicles shall be fabricated with CRCA Sheet Steel of thickness,
same as as per OEM Design. Sheet Steel having vibration free structure chemically
treated with nine tank process before painting for surface treatment and powder
coated, with suitable electrolytic grade high conductivity Aluminium busbar
extensible type, busbar supports, ( Cost of Bus bar / Flexible wire for
Interconnection between Main busbar and Switchgear is to be Paid Extra )

(d)Wiring between components within switchgear and Incoming / outgoing cable


shall be done through the terminal block only. Direct connection shall not be
permitted. Each terminal block shall be one piece moulded, barrier type, 650 volt
grade, complete with washers, heads, studs with two nuts and identification strips
and shall have adequate continuous current rating. For tap-offs, adjacent
terminals with shorting strips shall be used. 10% Spare terminal blocks shall be
provided. Wire identification on marking strip shall correspond to the designation
of the wiring diagrams. All wire terminals on the equipment shall also be marked
with designation corresponding to those of the wiring diagram.

(e)All wiring shall be enclosed in plastic channels and neatly bunched and closed
in metering chamber, Wiring between terminals of various devices shall be ‘point
to point’ (no wire splitting or tee connections) with wires neatly trucked along the
back of the panels, adequately supported to prevent sagging.

(f)Floor mounted panel shall be mounted on Base frame of ISMC channel size 100
x 50 x 5 mm ( to be paid Extra )
(g) Tests: The insulation resistance (with 1000 V Megger) and High voltage Power
frequency test (by applying a voltage of 2.5KV for one minute) shall be measured
between phases, between phase and neutral and between phase and earth. both
before and after high voltage power frequency test. The insulation resistance shall
not be less than three megaohm. CT Secondary current injection test and Heat
run test(type test) shall also be carried out.

(h) only outer surface area on all sides shall be measured & panel to be fabricated
only from Switchgear OEM approved fabricators only. All as per pre approved by
Engineer in charge. For additional technical parameters of products/ work , refer
Annexure "A" attached with this BSR . Sqm 9864.00

Chapter E - 08 Page44
P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-09

Chapter E 09
Air circuit breakers & MCCB

Code No. Description Unit Complete Rate


9.1 SITC of Draw out type 3/4 pole door interlock Air Circuit Breaker (ACB) as
conforming to IS/IEC 60947 P - 2 :2003 in existing LT panel suitable for LT
installation 440 V, 50 Hz and having adjustable over load short-circuit,
Instantaneous , earth fault (LSIG) with separate LED indication for each type of
fault shall confirm to EMI/ EMC test , LCD/LED display, last 10 trip history,
provision of ZSI, Communication, Power metering module, Thermal memory ,
trip free mechanisum , suitable for ambient 50 degree and utilization catagary B.
In built electrical & mechanical anti pumping feature , 100% rated neutral . ACB
shall have separate indication for service, test, isolation & maintenance position,
Breaking capacity Icu = Ics = Icw ( 1 sec ) , U imp - 12 KV, break time not more
then 25 ms. Provision for electrical & mechanical interlock between ACBs,
Min.electrical operation 10000 upto 2000 A rating and 5,000 for 2500 A to
4000 A. including making connections, testing etc. as required. OEM shall have
submit NABL / CPRI / ERDA accrediated lab type test certificate before
execution. All as per pre approved by Engineer in charge.For additional technical
parameters of product / work refer Annexure 'A' attached with this BSR

9.1.1 Microprocessor based release Draw out type (Manual spring charged) 3
Pole
9.1.1.1 630/800 A Rating , 50 kA Each 136853.00
9.1.1.2 1000 A Rating , 50 kA Each 146321.00
9.1.1.3 1250 A Rating ,50 kA Each 161878.00
9.1.1.4 1600 A Rating ,50 kA Each 177381.00
9.1.1.5 2000 A Rating ,50 kA Each 218379.00
9.1.1.6 2500 A Rating ,50 kA Each 261020.00
9.1.1.7 3200 A Rating ,65 kA Each 333331.00
9.1.1.8 4000 A Rating ,65 kA Each 422228.00
9.1.2 Microprocessor based release Draw out type ( Motorised charging type
) 3Pole
9.1.2.1 630/800 A Rating , 50 kA Each 166488.00
9.1.2.2 1000 A Rating , 50 kA Each 175949.00
9.1.2.3 1250 A Rating ,50 kA Each 186343.00
9.1.2.4 1600 A Rating ,50 kA Each 208833.00
9.1.2.5 2000 A Rating ,50 kA Each 253265.00
9.1.2.6 2500 A Rating ,50 kA Each 289229.00
9.1.2.7 3200 A Rating ,65 kA Each 364180.00
9.1.2.8 4000 A Rating ,65 kA Each 429335.00
9.1.3 Microprocessor based release Draw out type (Manual spring charged) 4
Pole
9.1.3.1 630/800 A Rating , 50 kA Each 171863.00
9.1.3.2 1000 A Rating , 50 kA Each 178861.00
9.1.3.3 1250 A Rating ,50 kA Each 208960.00
9.1.3.4 1600 A Rating ,50 kA Each 226734.00
9.1.3.5 2000 A Rating ,50 kA Each 281011.00
9.1.3.6 2500 A Rating ,50 kA Each 333351.00
9.1.3.7 3200 A Rating ,65 kA Each 406058.00
9.1.3.8 4000 A Rating ,65 kA Each 564113.00

Chapter E - 09 Page45
P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-09

Code No. Description Unit Complete Rate

9.1.4 Microprocessor based release Draw out type ( Motorised charging type
) 4 Pole
9.1.4.1 630/800 A Rating ,50 kA Each 203823.00
9.1.4.2 1000 A Rating , 50 kA Each 214095.00
9.1.4.3 1250 A Rating ,50 kA Each 227825.00
9.1.4.4 1600 A Rating ,50 kA Each 255522.00
9.1.4.5 2000 A Rating ,50 kA Each 304023.00
9.1.4.6 2500 A Rating ,50 kA Each 358982.00
9.1.4.7 3200 A Rating ,65 kA Each 437943.00
9.1.4.8 4000 A Rating ,65 kA Each 538469.00

9.2 Supply and fixing of following accessories for Air circuit breaker (ACB)
compatible with MAin ACB OEM as per PWD specification for electrical
Works, conforming to IS/IEC 60947 P - 2 :2003 including making
connection etc complete in all respect. OEM shall have submit NABL /
CPRI / ERDA accrediated lab type test certificate before execution. All
as per pre approved by Engineer in charge. For additional technical
parameters of products/ work , refer Annexure "A" attached with this
BSR .
9.2.1 Mechanical Interlocking Kit using key & Lock Each 9058.00
9.2.2 Closing Release Each 12304.00
9.2.3 Shunt Trip Release Each 2783.00
9.2.4 Under voltage Release Each 4434.00
9.2.5 External Neutral CT cast resin Each 6630.00
9.2.6 Microswitch for Indication Each 2421.00
9.2.7 Operation Counter Each 8150.00
9.2.8 Door Interlock Each 3301.00
9.2.9 Auxiliary Contact 4 NO + 4 NC Each 5504.00
9.2.10 Breaker Control Switch (TNC) Each 1290.00

9.3 SITC of 3 /4 pole current limiting Moulded case circuit breaker (MCCB)
made of flame retardent & heat resistant material having following
current rating, short circuit breaking capacity at 440/415 V, 50 Hz; O/L &
S/C settings , conforming to IS/IEC 60947 P -2 :2003 with front face and
centralised adjustable, trip free mechanisum, true contact position
indicator, line load interchangeability, designed for both horizontal &
vertical mounting without any adverse effect on electrical performance,
suitable for operation upto 55 degree and without derating upto 40
degree, pollution degree 3, having positive isolation capability, push
(test) to trip, trip time less then 10 ms under s/c condition, Breaking
capacity Ics = 100% Icu. U imp =8 KV, rated insulation voltage 690 V.
provision for UVR , shunt trip , earth fault trip, door interlock, pad lock &
rotary handle , including making connections etc. as required.OEM shall
have submit NABL / CPRI / ERDA accrediated lab type test certificate
before execution All as per pre approved by Engineer in charge. For
additional technical parameters of product / work refer Annexure 'A'
attached with this BSR

9.3.1 3 pole MCCB With Thermal Magnetic release


9.3.1.1 up to 100 Amp , 10 kA, fixed O/L & fixed S/C setting Each 1698.00
9.3.1.2 up to 100 Amp , 25 kA, adjustable O/L & adjustable S/C setting, Each 5170.00

Chapter E - 09 Page46
P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-09

Code No. Description Unit Complete Rate


9.3.1.3 125 Amp , 25 kA, adjustable O/L & adjustable S/C setting, Each 6387.00
9.3.1.4 160 Amp , 25 kA, adjustable O/L & adjustable S/C setting, Each 9961.00
9.3.1.5 200 Amp , 25 kA, adjustable O/L & adjustable S/C setting, Each 13188.00
9.3.1.6 250 Amp , 25 kA, adjustable O/L & adjustable S/C setting, Each 15326.00
9.3.1.7 250 Amp , 35 kA, adjustable O/L & adjustable S/C setting, Each 16117.00
9.3.1.8 400 Amp , 35 kA, adjustable O/L & adjustable S/C setting, Each 19732.00
9.3.1.9 630 Amp , 50 kA, adjustable O/L & adjustable S/C setting, Each 28237.00
9.3.1.10 800 Amp , 50 kA, adjustable O/L & adjustable S/C setting, Each 51440.00

3 pole MCCB With Microprocessor based release with adjustable O/L &
9.3.2 S/C setting with Inbuilt Instantaneous and Ground fault Protection.

9.3.2.1 250 Amp , 25 kA Each 28482.00


9.3.2.2 400 Amp , 35 kA Each 33918.00
9.3.2.3 630 Amp , 50 kA Each 37833.00
9.3.2.4 800 Amp , 50 kA Each 63519.00

9.3.3 4 pole MCCB With Thermal Magnetic release


9.3.3.1 up to 100 Amp , 10 kA, fixed O/L & fixed S/C setting Each 2215.00
9.3.3.2 up to 100 Amp , 25 kA, adjustable O/L & adjustable S/C setting, Each 7112.00
9.3.3.3 125 Amp , 25 kA, adjustable O/L & adjustable S/C setting, Each 8391.00
9.3.3.4 160 Amp , 25 kA, adjustable O/L & adjustable S/C setting, Each 11835.00
9.3.3.5 200 Amp , 25 kA, adjustable O/L & adjustable S/C setting, Each 15348.00
9.3.3.6 250 Amp , 25 kA, adjustable O/L & adjustable S/C setting, Each 17480.00
9.3.3.7 250 Amp , 35 kA, adjustable O/L & adjustable S/C setting, Each 19792.00
9.3.3.8 400 Amp , 35 kA, adjustable O/L & adjustable S/C setting, Each 23846.00
9.3.3.9 630 Amp , 50 kA, adjustable O/L & adjustable S/C setting, Each 34513.00
9.3.3.10 800 Amp , 50 kA, adjustable O/L & adjustable S/C setting, Each 39173.00

4 pole MCCB With Microprocessor based release with adjustable O/L &
9.3.4 S/C setting with Inbuilt Instantaneous and Ground fault Protection.

9.3.4.1 Upto 160 Amp , 50 kA Each 34818.00


9.3.4.2 250 Amp , 50 kA Each 38201.00
9.3.4.3 400 Amp , 50 kA Each 40781.00
9.3.4.4 630 Amp, 50 kA Each 46531.00
9.3.4.5 800 Amp , 50 kA Each 76151.00

9.4 Supply and fixing of following accessories for Moulded case circuit
breaker (MCCB) compatible to main MCCB OEM as per PWD
specification for electrical Works, conforming to IS/IEC 60947 P - 2 :2003
including making connection etc complete in all respect. OEM shall have
submit NABL / CPRI / ERDA accrediated lab type test certificate before
execution. All as per pre approved by Engineer in charge. For additional
technical parameters of products/ work , refer Annexure "A" attached
with this BSR .
9.4.1 Shunt Trip Release Each 1424.00
9.4.2 Under Voltage Release Each 2673.00
9.4.3 Extended Rotary Handle Each 2713.00

Chapter E - 09 Page47
P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-09

Code No. Description Unit Complete Rate


9.4.4 Direct Rotary Handle Each 1651.00
9.4.5 Mechanical Interlocking kit Each 6943.00
9.4.6 Motor mechanism for 250A MCCB (240V, 50Hz) Each 22292.00
9.4.7 Motor mechanism for 400A MCCB (240V, 50Hz) Each 27447.00
9.4.8 Motor mechanism for 630A MCCB (240V, 50Hz) Each 41221.00
9.4.9 Auxiliary contact Each 1345.00
9.4.10 Trip Alarm contact Each 1345.00
9.4.11 Auxiliary + Trip alarm contact Each 1634.00
9.4.12 Spreaders upto 125A, 3 Pole MCCB set 389.00
9.4.13 Spreaders for 160A, 3 Pole MCCB set 1162.00
9.4.14 Spreaders for 160A, 4 Pole MCCB set 1507.00
9.4.15 Spreaders for 250A, 3 Pole MCCB set 1196.00
9.4.16 Spreaders for 250A, 4 Pole MCCB set 1541.00
9.4.17 Spreaders for 400A, 3Pole MCCB set 2204.00
9.4.18 Spreaders for 400A, 4Pole MCCB set 3101.00
9.4.19 Spreaders for 630A, 3Pole MCCB set 2594.00
9.4.20 Spreaders for 630A, 4Pole MCCB Set 3427.00
9.4.21 Spreaders for 800A, 3Pole MCCB Set 5376.00
9.4.22 Spreaders for 800A, 4Pole MCCB Set 6767.00
9.4.23 Phase Barriers up to 630A, 3/4Pole MCCB set 1106.00
9.4.24 External Neutral CT with Adaptor Kit set 4596.00
9.4.25 Current Metering Module set 19125.00

9.5 Providing & Fixing of IK08 and IP-30 Recessed/surface mounting heavy
duty Enclosure suitable for mounting 3 / 4 pole MCCB, Inbuilt neutral
linkmade out from Galvanized steel / CRCA sheet not less then 1.2 mm
thick conforming to IS-8623-1 & 3 / IEC 61439- 1 & 3. powder painted
complete with din rail making internal DB terminations, detachable
gland plate, including making connections, testing etc. as required. All as
per pre approved by Engineer in charge. For additional technical
parameters of products/ work , refer Annexure "A" attached with this
BSR .
9.5.1 Suitable to accommodate up to 70 sqmm 3.5 core Al arm. Cable Each 1830.00
9.5.2 Suitable to accommodate above 70 sqmm 3.5 core Al arm. Cable to 185
Each 3951.00
Sqm , 3.5 core Al Arm. Cable

9.6 SITC of IP-43 surface mounting heavy duty modular Sub main Distribution
board (SMDB) fabricated by switchgear OEM having short circuit
withstand current 35 kA (upto 400 amp.Incomer ) and 50 kA for 630 amp.
Incomer with suitable bottom cabling box, 4 no. corner boxes, 2 no. side
cabling boxes, metering Extension box with provision of incomer
suitable for 3 pole MCCB and 3 pole MCCB as outgoing ,made out from
Galvanized steel / CRCA sheet not less then 1.6 mm thick conforming to
IEC 61439 Part 1 & 2. , U imp 8 KV, form of separation 2b, powder
painted complete with insulated suitable rating tinned copper bus bar,
neutral bars with shrouds, earth bar , din bar, making internal DB
terminations with copper lugs, detachable gland plate, including making
connections, testing etc. as required. (Without MCCB, ammeter,
voltmeter, selector switch , Indicating lamp) OEM shall have submit
NABL / CPRI / ERDA accrediated lab type test certificate before
execution. All as per pre approved by Engineer in charge. For additional
technical parameters of products/ work , refer Annexure "A" attached
with this BSR .

Chapter E - 09 Page48
P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-09

Code No. Description Unit Complete Rate


9.6.1 SMDB with 250 Amp. Incoming and 4 no. 100 Amps Outgoing Set 62558.00
9.6.2 SMDB with 250 Amp. Incoming and 8 no. 100 Amps Outgoing Set 72351.00
9.6.3 SMDB with 250 Amp. Incoming and 12 no. 100 Amps Outgoing Set 86012.00
9.6.4 SMDB with 400 Amp. Incoming and 4 no. 100 Amps Outgoing Set 72482.00
9.6.5 SMDB with 400 Amp. Incoming and 8 no. 100 Amps Outgoing Set 80007.00
9.6.6 SMDB with 400 Amp. Incoming and 12 no. 100 Amps Outgoing Set 94061.00
9.6.7 SMDB with 630 Amp. Incoming and 4 no. 100 Amps Outgoing Set 103968.00
9.6.8 SMDB with 630 Amp. Incoming and 8 no. 100 Amps Outgoing Set 108948.00
9.6.9 SMDB with 630 Amp. Incoming and 12 no. 100 Amps Outgoing Set 135558.00
9.6.10 SMDB with 630 Amp. Incoming and 6 no. 100 Amps + 2 No. 250 amp.
Set 112229.00
Outgoing
9.6.11 SMDB with 630 Amp. Incoming and 10 no. 100 Amps + 2 No. 250 amp.
Set 137142.00
Outgoing

Chapter E - 09 Page49
P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-10

Chapter E - 10

Switch Fuse Unit & Change over switch

Code No. Description Unit Complete Rate

10.1 Providing & Fixing of ISO certified company made TP&N 415 V side handle
operated double break fuse switch unit in sheet steel enclosure as per
PWD specification for electrical Works conforming to IS/lEC 60947-3 : 1999
(W/O HBC fuses) including making connections with suitable lugs, testing
etc. as required. Appropriate type test certificate / OEM test report shall
be submitted . All as per pre approved by Engineer in charge. For
additional technical parameters of products/ work , refer Annexure "A"
attached with this BSR .

10.1.1 63 A rating Each 6610.00


10.1.2 100 A rating Each 8974.00
10.1.3 200 A rating Each 15278.00
10.1.4 300/320 A rating Each 17460.00
10.1.5 400 A rating Each 24949.00
10.1.6 500 A rating Each 34973.00

10.2 Providing & Fixing of ISO certified company made TP&N 415 V AC-23A
front handle operated switch disconnector fuse unit, cubical type, with
metallic enclosure, as per PWD specification for electrical Works
conforming to IS/lEC 60947-3 : 1999 with HBC fuses including making
connections with lugs, testing etc as required. Appropriate type test
certificate / OEM test report shall be submitted . All as per pre approved
by Engineer in charge. For additional technical parameters of products/
work , refer Annexure "A" attached with this BSR .

10.2.1 32 A rating Each 3841.00


10.2.2 63 A rating Each 4537.00
10.2.3 100/125 A rating Each 7344.00
10.2.4 160 A rating Each 9320.00
10.2.5 200 A rating Each 12707.00
10.2.6 250 A rating Each 14596.00
10.2.7 300/320 A rating Each 17038.00
10.2.8 400 A rating Each 19440.00
10.2.9 630 A rating Each 30849.00

10.3 Providing & Fixing of ISO certified company made TP&N 415 V AC-23A
front handle operated switch disconnector fuse unit, cubical type, without
metallic enclosure (For Panel Mounting), as per PWD specification for
electrical Works conforming to IS/lEC 60947-3 : 1999 in existing panel With
HBC fuses including making connections with lugs, testing etc as required.
Appropriate type test certificate / OEM test report shall be submitted . All
as per pre approved by Engineer in charge. For additional technical
parameters of products/ work , refer Annexure "A" attached with this
BSR .
10.3.1 32 A rating Each 1970.00
10.3.2 63 A rating Each 2717.00
10.3.3 100/125 A rating Each 5611.00

Chapter E - 10 Page 50
P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-10

Code No. Description Unit Complete Rate


10.3.4 160 A rating Each 7743.00
10.3.5 200 A rating Each 9711.00
10.3.6 250 A rating Each 11304.00
10.3.7 300/320 A rating Each 13798.00
10.3.8 400 A rating Each 16990.00
10.3.9 630 A rating Each 26682.00

10.4 Providing & Fixing of ISO certified company made bakelite fuse fitting for
HBC fuse links (front/bus bar connections) Conforms To IS 13703/IEC 269
w/o HBC fuses as per PWD specification for electrical Works on existing
board including making connections with lugs, testing etc. as required.
Appropriate type test certificate / OEM test report shall be submitted . All
as per pre approved by Engineer in charge. For additional technical
parameters of products/ work , refer Annexure "A" attached with this
BSR .
10.4.1 20 A rating Each 170.00
10.4.2 32 A rating Each 190.00
10.4.3 63 A rating Each 312.00
10.4.4 100/125 A rating Each 878.00

10.5 Providing & Fixing of ISO certified company made 240/415 V porcelain
kitkat fuse (/HBC type) as per PWD specification for electrical Works
conforming to IS:2086,1983 on existing board/ sheet including making
connections with lugs, testing etc. as required . Appropriate type test
certificate / OEM test report shall be submitted . All as per pre approved
by Engineer in charge. For additional technical parameters of products/
work , refer Annexure "A" attached with this BSR .

10.5.1 16 A ,240 V Each 88.00


10.5.2 16 A ,415 V Each 133.00
10.5.3 32 A ,240 V Each 135.00
10.5.4 32 A ,415 V Each 164.00
10.5.5 63 A , 415 V Each 250.00
10.5.6 100 A ,415 V Each 486.00
10.5.7 200 A , 415 V Each 893.00
10.5.8 320 A , 415 V Each 1363.00

10.6 Providing & Fixing of ISO certified company made bolted type/ Din type
HBC (High breaking capacity) fuse links of 80 KA breaking capacity,as per
PWD specification for electrical Works conforming to IS:13703 in the
existing fuse base, fuse switch unit etc. of the following type and rating.
Appropriate type test certificate / OEM test report shall be submitted . All
as per pre approved by Engineer in charge. For additional technical
parameters of products/ work , refer Annexure "A" attached with this
BSR .

10.6.1 Cylindrical Fuse Link


10.6.1.1 2 A to 32 A Each 90.00
10.6.1.2 40 A Each 99.00
10.6.1.3 50 A Each 210.00
10.6.1.4 63A Each 252.00

10.6.2 Offset tag type

Chapter E - 10 Page 51
P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-10

Code No. Description Unit Complete Rate


10.6.2.1 2 A to 20 A Each 44.00
10.6.2.2 25 A to 32 A Each 75.00
10.6.2.3 35 A to 63 A Each 105.00
10.6.2.4 80 A to 125 A Each 368.00

10.6.3 Central tag type


10.6.3.1 80 A to 125 A Each 293.00
10.6.3.2 160 A to 200 A Each 333.00
10.6.3.3 250 A to 315 A Each 487.00
10.6.3.4 400 A to 500 A Each 1325.00
10.6.3.5 630 A Each 1448.00

10.6.4 Din (knife type) type


10.6.4.1 63 A to 125 A Size 000 Each 357.00
10.6.4.2 63 A to 160 A Size 00 Each 388.00
10.6.4.3 80 A to 200 A Size 0 Each 534.00
10.6.4.4 125 A to 315 A Size 1 Each 639.00
10.6.4.5 200 A to 400 A Size 2 Each 843.00
10.6.4.6 315A to 800 A Size 3 Each 2831.00

10.7 Providing & Fixing of ISO certified company made on load change over
switch, front handle operated, four pole 415 V as per PWD specification
for electrical Works conforming to IS/lEC 60947-3 : 1999 including
connections , testing etc. as required .in the following rating. Appropriate
type test certificate / OEM test report shall be submitted . All as per pre
approved by Engineer in charge. For additional technical parameters of
products/ work , refer Annexure "A" attached with this BSR .

10.7.1 Open execution type


10.7.1.1 63 A Each 4038.00
10.7.1.2 125 A Each 7149.00
10.7.1.3 160 A Each 8750.00
10.7.1.4 200 A Each 11691.00
10.7.1.5 250 A Each 15975.00
10.7.1.6 320 A Each 17693.00
10.7.1.7 400 A Each 26014.00
10.7.1.8 630 A Each 33366.00
10.7.1.9 800 A Each 43651.00
10.7.1.10 1000 A Each 51154.00
10.7.2 With sheet steel enclosure made out from CRCA sheet door 1.2mm &
body 1.6mm thick, powder quoted, door locking system allow opening of
door in OFF position only with 2 nos external earthing points.

10.7.2.1 63 A Each 5321.00


10.7.2.2 125 A Each 9124.00
10.7.2.3 160 A Each 11293.00
10.7.2.4 200 A Each 13064.00
10.7.2.5 250 A Each 17448.00
10.7.2.6 320 A Each 21055.00
10.7.2.7 400 A Each 29271.00
10.7.2.8 630 A Each 34861.00
10.7.2.9 800 A Each 49836.00
10.7.2.10 1000 A Each 57567.00

Chapter E - 10 Page 52
P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-10

Code No. Description Unit Complete Rate


10.8 Providing & Fixing of ISO certified company made off load change over
switch four pole/two pole, 230/ 415 V ,side handle operated conforming to
IS:13947 P-III in sheet steel enclosure complete with connections with
lugs, testing etc. as required in the following rating: All as per pre
approved by Engineer in charge. For additional technical parameters of
products/ work , refer Annexure "A" attached with this BSR .

10.8.1 32 A, Double pole Each 1518.00


10.8.2 32 A, Four pole Each 2593.00
10.8.3 63 A Four pole Each 5081.00
10.8.4 100 A Four pole Each 9806.00
10.8.5 200 A Four pole Each 14789.00
10.8.6 315 A Four pole Each 18995.00
10.8.7 400 A Four pole Each 21870.00

10.9 Providing & Fixing of ISO certified company made Four Pole By pass
Change Over Switch conforming to IS:13947(Part 3) : IEC:60947-3-1 and
IEC:60947-6-1, Open execution type in the following ratings. All as per pre
approved by Engineer in charge. For additional technical parameters of
products/ work , refer Annexure "A" attached with this BSR .

10.9.1 63 A Each 13430.00


10.9.2 100 A Each 15388.00
10.9.3 200 A Each 21040.00
10.9.4 320 A Each 31470.00
10.9.5 400 A Each 46810.00
10.9.6 630 A Each 53363.00
10.9.7 800 A Each 67925.00
10.9.8 1000 A Each 121779.00

10.10 Providing & Fixing of ISO certified company made bus bar chamber housed
in sheet metal box as per PWD specification for electrical Works
Confirming to IEC-60439/IS-8623 & IEC-60529/IS-2147 made out from 1.6
mm thick powder coated CRCA sheet,degree of protection IP-31, front
openable bus bar made out of aluminium or wrought aluminium alloy
suitable for 100 amp. Capacity , bus bar fixed on porcelain/DMC
insulators at approved spacing including making connections etc. as
required. Appropriate type test certificate / OEM test report shall be
submitted . All as per pre approved by Engineer in charge. For additional
technical parameters of products/ work , refer Annexure "A" attached
with this BSR .
10.10.1 300 mm long , 2 strip Each 814.0
10.10.2 300 mm long , 4 strip Each 1012.0
10.10.3 450 mm long , 2 strip Each 1154.0
10.10.4 450 mm long , 4 strip Each 1720.0
10.10.5 600 mm long ,2 strip Each 1495.0
10.10.6 600 mm long , 4 strip Each 1972.0
10.10.7 900 mm long , 2 strip Each 1971.0
10.10.8 900 mm long , 4 strip Each 2789.0

Chapter E - 10 Page 53
P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-10

Code No. Description Unit Complete Rate


10.11 Providing & Fixing of ISO certified company made bus bar chamber housed
in sheet metal box as per PWD specification for electrical Works
Confirming to IEC-60439/ IS-8623 & IEC-60529/ IS-2147 made out from 1.6
mm thick powder coated CRCA sheet,degree of protection IP-31 front
openable bus bar made out of aluminium or wrought aluminium alloy
suitable for 200 amp. Capacity , bus bar fixed on porcelain/DMC
insulators at approved spacing including making connections etc. as
required. Appropriate type test certificate / OEM test report shall be
submitted . All as per pre approved by Engineer in charge. For additional
technical parameters of products/ work , refer Annexure "A" attached
with this BSR .
10.11.1 300 mm long , 4 strip Each 1701.0
10.11.2 450 mm long , 4 strip Each 2654.0
10.11.3 600 mm long , 4 strip Each 2825.0
10.11.4 900 mm long , 4 strip Each 3812.0

10.12 Providing & Fixing of ISO certified company made bus bar chamber housed
in sheet metal box as per PWD specification for electrical Works
Confirming to IEC-60439/IS-8623 & IEC-60529/IS-2147 made out from 1.6
mm thick powder coated CRCA sheet,degree of protection IP-31, front
openable bus bar made out of Copper suitable for 100 amp. Capacity ,
bus bar fixed on porcelain/DMC insulators at approved spacing including
making connections etc. as required. Appropriate type test certificate /
OEM test report shall be submitted . All as per pre approved by Engineer
in charge. For additional technical parameters of products/ work , refer
Annexure "A" attached with this BSR .

10.12.1 300 mm long , 2 strip Each 2110.0


10.12.2 300 mm long , 4 strip Each 4292.0
10.12.3 450 mm long , 2 strip Each 2586.0
10.12.4 450 mm long , 4 strip Each 5041.0
10.12.5 600 mm long ,2 strip Each 3405.0
10.12.6 600 mm long , 4 strip Each 6542.0
10.12.7 900 mm long , 2 strip Each 4699.0
10.12.8 900 mm long , 4 strip Each 8518.0

10.13 Providing & Fixing of ISO certified company made bus bar chamber housed
in sheet metal box as per PWD specification for electrical Works
Confirming to IEC-60439/IS-8623 & IEC-60529/IS-2147 made out from 1.6
mm thick powder coated CRCA sheet,degree of protection IP-31, front
openable bus bar made out of Copper suitable for 200 amp. Capacity ,
bus bar fixed on porcelain/DMC insulators at approved spacing including
making connections etc. as required. Appropriate type test certificate /
OEM test report shall be submitted . All as per pre approved by Engineer in
charge. For additional technical parameters of products/ work , refer
Annexure "A" attached with this BSR .

10.13.1 300 mm long , 4 strip Each 4974.0


10.13.2 450 mm long , 4 strip Each 5723.0
10.13.3 600 mm long , 4 strip Each 8178.0
10.13.4 900 mm long , 4 strip Each 11246

Chapter E - 10 Page 54
P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-11

Chapter E - 11
LT Cables

Code No. Description Complete


Unit Rate
11.1 Providing & Laying P.V.C. / XLPE insulated & P.V.C. sheathed Un-Arrmoured
Aluminium cable confirming to IS:1554 P-I / IS :7098 P - I of 1.1 KV with H4-
Grade electrolytic aluminium conductor confirming to IS 8130 of purity >99.6 %,
Inner / outer sheath confirming to IS:5831 in existing RCC / Hume / Stoneware /
PVC pipe/ open duct/cable trench / Cable tray (with cable tie) including testing
etc. as required of following size. OEM must have it's own in house NABL
accrediated Laboratory for testing procedure as per IS:10810. For additional
technical parameters of product / work refer Annexure 'A' attached with this BSR

11.1.1 4.0 Sq. mm


11.1.1.1 2 core Mtr 61.00
11.1.1.2 3 core Mtr 76.00
11.1.1.3 4 core Mtr 87.00
11.1.2 6.0 Sq. mm
11.1.2.1 2 core Mtr 79.00
11.1.2.2 3 core Mtr 98.00
11.1.2.3 4 core Mtr 114.00
11.1.3 10.0 Sq. mm
11.1.3.1 2 core Mtr 111.00
11.1.3.2 3 core Mtr 132.00
11.1.3.3 4 core Mtr 146.00
11.1.4 16.0 Sq. mm
11.1.4.1 2 core Mtr 120.00
11.1.4.2 3 core Mtr 147.00
11.1.4.3 4 core Mtr 179.00
11.1.5 25.0 Sq. mm
11.1.5.1 2 core Mtr 154.00
11.1.5.2 3 core Mtr 207.00
11.1.5.3 3.5 core Mtr 256.00
11.1.6 35.0 Sq. mm
11.1.6.1 2 core Mtr 210.00
11.1.6.2 3 core Mtr 281.00
11.1.6.3 3.5 core Mtr 312.00
11.1.7 50.0 Sq. mm
11.1.7.1 2 core Mtr 255.00
11.1.7.2 3 core Mtr 354.00
11.1.7.3 3.5 core Mtr 417.00
11.1.8 70.0 Sq. mm
11.1.8.1 2 core Mtr 352.00
11.1.8.2 3 core Mtr 501.00
11.1.8.3 3.5 core Mtr 567.00
11.1.9 95.0 Sq. mm
11.1.9.1 1 core Mtr 251.00
11.1.9.2 3.5 core Mtr 714.00
11.1.10 120.0 Sq. mm
11.1.10.1 1 core Mtr 306.00
11.1.10.2 3.5 core Mtr 904.00
11.1.11 150.0 Sq. mm

Chapter E- 11 Page 55
P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-11

Code No. Description Complete


Unit Rate
11.1.11.1 1 core Mtr 363.00
11.1.11.2 3.5 core Mtr 1061.00
11.1.12 185.0 Sq. mm
11.1.12.1 1 core Mtr 445.00
11.1.12.2 3.5 core Mtr 1327.00
11.1.13 240.0 Sq. mm
11.1.13.1 1 core Mtr 512.00
11.1.13.2 3.5 core Mtr 1596.00
11.1.14 300.0 Sq. mm
11.1.14.1 1 core Mtr 627.00
11.1.14.2 3.5 core Mtr 2026.00
11.1.15 400.0 Sq. mm
11.1.15.1 1 core Mtr 788.00
11.1.15.2 3.5 core Mtr 2568.00
11.1.16 500.0 Sq. mm
11.1.16.1 1 core Mtr 1020.00
11.1.16.2 3.5 core Mtr 3304.00
11.1.17 630.0 Sq. mm
11.1.17.1 1 core Mtr 1263.00
11.1.17.2 3.5 core Mtr 4505.00
11.1.18 800.0 Sq. mm
11.1.18.1 1 core Mtr 1635.00
11.1.19 1000.0 Sq. mm
11.1.19.1 1 core Mtr 2079.00
11.2 Providing & Laying P.V.C. / XLPE insulated & P.V.C. sheathed Arrmoured
Aluminium cable confirming to IS:1554 P-I / IS :7098 P - I of 1.1 KV with H4-
Grade electrolytic aluminium conductor confirming to IS 8130 of purity >99.6 %,
round / flat strip armouring of cables, Inner / outer sheath confirming to IS:5831
in existing RCC / Hume / Stoneware / PVC pipe/ open duct/cable trench / Cable
tray(with cable tie) including testing etc. as required of following size. OEM must
have it's own in house NABL accrediated Laboratory for testing procedure as per
IS:10810.For additional technical parameters of product / work refer Annexure
'A' attached with this BSR

11.2.1 4.0 Sq. mm


11.2.1.1 2 core Mtr 109.00
11.2.1.2 3 core Mtr 123.00
11.2.1.3 4 core Mtr 139.00
11.2.2 6.0 Sq. mm
11.2.2.1 2 core Mtr 128.00
11.2.2.2 3 core Mtr 146.00
11.2.2.3 4 core Mtr 166.00
11.2.3 10.0 Sq. mm
11.2.3.1 2 core Mtr 152.00
11.2.3.2 3 core Mtr 179.00
11.2.3.3 4 core Mtr 192.00
11.2.4 16.0 Sq. mm
11.2.4.1 2 core Mtr 171.00
11.2.4.2 3 core Mtr 193.00
11.2.4.3 4 core Mtr 232.00
11.2.5 25.0 Sq. mm
11.2.5.1 2 core Mtr 200.00
11.2.5.2 3 core Mtr 244.00

Chapter E- 11 Page 56
P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-11

Code No. Description Complete


Unit Rate
11.2.5.3 3.5 core Mtr 285.00
11.2.6 35.0 Sq. mm
11.2.6.1 2 core Mtr 246.00
11.2.6.2 3 core Mtr 318.00
11.2.6.3 3.5 core Mtr 347.00
11.2.7 50.0 Sq. mm
11.2.7.1 2 core Mtr 300.00
11.2.7.2 3 core Mtr 416.00
11.2.7.3 3.5 core Mtr 457.00
11.2.8 70.0 Sq. mm
11.2.8.1 1 core Mtr 255.00
11.2.8.2 2 core Mtr 398.00
11.2.8.3 3 core Mtr 544.00
11.2.8.4 3.5 core Mtr 610.00
11.2.9 95.0 Sq. mm
11.2.9.1 1 core Mtr 287.00
11.2.9.2 3.5 core Mtr 765.00
11.2.10 120.0 Sq. mm
11.2.10.1 1 core Mtr 353.00
11.2.10.2 3.5 core Mtr 945.00
11.2.11 150.0 Sq. mm
11.2.11.1 1 core Mtr 411.00
11.2.11.2 3.5 core Mtr 1096.00
11.2.12 185.0 Sq. mm
11.2.12.1 1 core Mtr 496.00
11.2.12.2 3.5 core Mtr 1415.00
11.2.13 240.0 Sq. mm
11.2.13.1 1 core Mtr 616.00
11.2.13.2 3.5 core Mtr 1733.00
11.2.14 300.0 Sq. mm
11.2.14.1 1 core Mtr 746.00
11.2.14.2 3.5 core Mtr 2112.00
11.2.15 400.0 Sq. mm
11.2.15.1 1 core Mtr 940.00
11.2.15.2 3.5 core Mtr 2706.00
11.2.16 500.0 Sq. mm
11.2.16.1 1 core Mtr 1145.00
11.2.16.2 3.5 core Mtr 3448.00
11.2.17 630.0 Sq. mm
11.2.17.1 1 core Mtr 1394.00
11.2.17.2 3.5 core Mtr 4722.00
11.2.18 800.0 Sq. mm
11.2.18.1 1 core Mtr 1776.00
11.2.19 1000.0 Sq. mm
11.2.19.1 1 core Mtr 2222.00

Chapter E- 11 Page 57
P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-11

Code No. Description Complete


Unit Rate
11.3 Providing & Laying P.V.C. / XLPE insulated & P.V.C. sheathed Un-armoured
Copper cable confirming to IS:1554 P-I / IS :7098 P - I of 1.1 KV with electrolytic
grade Copper made of copper rods confirming to IS 613-1964, of purity >99.7
%, Inner / outer sheath confirming to IS:5831 in existing RCC / Hume /
Stoneware / PVC pipe/ open duct/cable trench / Cable tray (with cable tie)
including testing etc. as required of following size. OEM must have it's own in
house NABL accrediated Laboratory for testing procedure as per IS:10810 For
additional technical parameters of product / work refer Annexure 'A' attached
with this BSR
11.3.1 1.5 Sq. mm
11.3.1.1 2 core Mtr 88.00
11.3.1.2 3 core Mtr 109.00
11.3.1.3 4 core Mtr 135.00
11.3.1.4 6 core Mtr 184.00
11.3.1.5 8 core Mtr 246.00
11.3.1.6 10 core Mtr 302.00
11.3.1.7 12 core Mtr 315.00
11.3.2 2.5 Sq. mm
11.3.2.1 2 core Mtr 120.00
11.3.2.2 3 core Mtr 157.00
11.3.2.3 4 core Mtr 201.00
11.3.2.4 6 core Mtr 275.00
11.3.2.5 8 core Mtr 374.00
11.3.2.6 10 core Mtr 424.00
11.3.2.7 12 core Mtr 518.00
11.3.3 4.0 Sq. mm
11.3.3.1 2 core Mtr 166.00
11.3.3.2 3 core Mtr 227.00
11.3.3.3 4 core Mtr 281.00
11.3.4 6.0 Sq. mm
11.3.4.1 2 core Mtr 232.00
11.3.4.2 3 core Mtr 320.00
11.3.4.3 4 core Mtr 404.00
11.3.4 10.0 Sq. mm
11.3.5.1 2 core Mtr 390.00
11.3.5.2 3 core Mtr 531.00
11.3.5.3 4 core Mtr 624.00
11.3.5 16.0 Sq. mm
11.3.5.1 1 core Mtr 292.00
11.3.5.2 2 core Mtr 486.00
11.3.5.3 3 core Mtr 763.00
11.3.5.4 4 core Mtr 951.00
11.3.6 25.0 Sq. mm
11.3.6.1 1 core Mtr 433.00
11.3.6.2 2 core Mtr 803.00
11.3.6.3 3 core Mtr 1153.00
11.3.6.4 4 core Mtr 1472.00

Chapter E- 11 Page 58
P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-11

Code No. Description Complete


Unit Rate
11.4 Providing & Laying P.V.C. / XLPE insulated & P.V.C. sheathed Armoured Copper
cable confirming to IS:1554 P-I / IS :7098 P - I of 1.1 KV with electrolytic grade
Copper made of copper rods confirming to IS 613-1964, of purity >99.7 %, round
/ flat strip armouring, Inner / outer sheath confirming to IS:5831 in existing RCC
/ Hume / Stoneware / PVC pipe/ open duct/cable trench / Cable tray(with cable
tie) including testing etc. as required of following size. OEM must have it's own
in house NABL accrediated Laboratory for testing procedure as per IS:10810 For
additional technical parameters of product / work refer Annexure 'A' attached
with this BSR

11.4.1 1.5 Sq. mm


11.4.1.1 2 core Mtr 117.00
11.4.1.2 3 core Mtr 142.00
11.4.1.3 4 core Mtr 167.00
11.4.1.4 6 core Mtr 223.00
11.4.1.5 8 core Mtr 281.00
11.4.1.6 10 core Mtr 336.00
11.4.1.7 12 core Mtr 371.00
11.4.2 2.5 Sq. mm
11.4.2.1 2 core Mtr 155.00
11.4.2.2 3 core Mtr 188.00
11.4.2.3 4 core Mtr 231.00
11.4.2.4 6 core Mtr 321.00
11.4.2.5 8 core Mtr 413.00
11.4.2.6 10 core Mtr 468.00
11.4.2.7 12 core Mtr 545.00
11.4.3 4.0 Sq. mm
11.4.3.1 2 core Mtr 196.00
11.4.3.2 3 core Mtr 254.00
11.4.3.3 4 core Mtr 324.00
11.4.4 6.0 Sq. mm
11.4.4.1 2 core Mtr 263.00
11.4.4.2 3 core Mtr 348.00
11.4.4.3 4 core Mtr 463.00
11.4.5 10.0 Sq. mm
11.4.5.1 2 core Mtr 408.00
11.4.5.2 3 core Mtr 551.00
11.4.5.3 4 core Mtr 690.00
11.4.6 16.0 Sq. mm
11.4.6.1 1 core Mtr 348.00
11.4.6.2 2 core Mtr 532.00
11.4.6.3 3 core Mtr 798.00
11.4.6.4 4 core Mtr 1021.00
11.4.7 25.0 Sq. mm
11.4.7.1 1 core Mtr 498.00
11.4.7.2 2 core Mtr 834.00
11.4.7.3 3 core Mtr 1227.00
11.4.7.4 4 core Mtr 1572.00

Chapter E- 11 Page 59
P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-11

Code No. Description Complete


Unit Rate
11.4.8 35 Sq. mm
11.4.8.1 1 core Mtr 668.00
11.4.8.2 2 core Mtr 1154.00
11.4.8.3 3 core Mtr 1651.00
11.4.8.4 4 core Mtr 2251.00
11.4.9 50 Sq. mm
11.4.9.1 1 core Mtr 938.00
11.4.9.2 2 core Mtr 1570.00
11.4.9.3 3 core Mtr 2281.00
11.4.9.4 4 core Mtr 3013.00

11.5 Add Extra for Laying of one number PVC insulated and PVC sheathed / XLPE
power cable of 1.1 KV grade direct in ground including excavation of trench of
size 75 cm (Depth) x 35 cm(Width) , with procedure as per following points:-
(a) Make a river sand bed of height 125 mm along the trench, (b) Lay the cable
in the middle of the trench, (c) Provide river sand bed of height 125 mm on top
of the cable, (d) Lay the protective Common burnt clay F.P.S. Bricks of Class
designation 75 / Sand stone slabs of 50 mm thickness and 225 mm wide just
above the sand bed vertically across the cable ( Approx. 9 no. Bricks per Mtr.), (e)
Backfill the excavated soil leaving 300 mm from the Ground level, (f)Lay the
Cable warning tape and again back-fill the remaining portion of the trench upto
the ground level and compacting the earth
Mtr 185.00
Add Extra in Item no.11.5 if Excavation done in Hard Rock / CC road / TAR Road
11.6
and making Good the same Mtr 24.00
11.7 Add Extra for Laying of one number additional PVC insulated and PVC sheathed /
XLPE power cable of 1.1 KV grade direct in ground in the same trench in one tier
horizontal formation including excavation of trench of size additional 20 cm in
width, with procedure as per following points :- (a) Make a river sand bed of
height 125 mm along the trench, (b) Lay another cable in middle of trench in
such manner that spacing between another cable is 20 cm., (c) Provide river sand
bed of height 125 mm on top of the cable. (d) Lay the protective Common burnt
clay F.P.S. Bricks of Class designation 75 /Sand stone slabs of 50 mm thickness
and 225 mm wide just above the sand bed vertically across the cable ( Approx. 9
no. Bricks per Mtr.), (e) Backfill the excavated soil leaving 300 mm from the
Ground level, (f)Lay the Cable warning tape and again back-fill the remaining
portion of the trench upto the ground level and compacting the earth
Mtr 127.00

11.8 Add Extra in Item no. 11.7 if Excavation done in Hard Rock / CC road / TAR Road
and making Good the same Mtr 14.00

11.09 Add Extra in item no. 11.1 to 11.4 for Laying and fixing of one number PVC
insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size
on wall surface as required.
11.09.1 Up to 35 Sq.mm fixed with 25 mm x 2 mm thick suitable length red oxide and
enamel painted MS clamp and base, pvc rawl plug and screws of sufficient size
with spacing 0.6 Mtr. Between Clamps. Mtr 39.00

Chapter E- 11 Page 60
P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-11

Code No. Description Complete


Unit Rate
11.09.2 Above 35 sq. mm and upto 95 sq. mm fixed with 40 mm x 3 mm thick suitable
length red oxide and enamel painted MS clamp and base, pvc rawl plug and
screws of sufficient size with spacing 0.6 Mtr. Between Clamps. Mtr 67.00
11.09.3 Above 95 sq. mm and upto 185 sq. mm fixed with 40 mm x 4 mm thick suitable
length red oxide and enamel painted MS clamp and base, pvc rawl plug and
screws of sufficient size with spacing 0.6 Mtr. Between Clamps. Mtr 92.00
11.09.4 Above 185 sq. mm and upto 400 sq. mm fixed with 50 mm x 5 mm thick suitable
length red oxide and enamel painted MS clamp and base, pvc rawl plug and
screws of sufficient size with spacing 0.6 Mtr. Between Clamps. Mtr 141.00

11.10 Add extra in item no. 11.1 to 11.4 for Laying Charges for cable through Manual
Boggi by making pit at regular interval and repairing the pit after laying of cable
with PCC/ Bitumin as required. Mtr 114.00

11.11 Add Extra in item no. 11.1 to 11.4 for Laying Charges for cable through Vermeer
machine by making pit at regular interval and repairing the pit after laying of
cable with PCC/ Bitumin as required. Mtr 267.00

Chapter E- 11 Page 61
P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-12

Chapter E - 12

LT Cable Termination & Accessories

Code No. Description Unit Complete Rate


12.1 Supplying and making one end termination with Nickel plated heavy duty brass
single compression gland (as per IS 12943-1990)) SIBG type consisting of Check
Nut, Gland Body, Metal Washer(3 Nos.), Outer Seal Rubber Ring, Compression
Nut, heavy duty aluminium lugs (as per IS 8309 -1993) duly crimped with
crimping tool, PVC tape as per IS 8337-1976 of following size of PVC insulated
& PVC sheathed/ XLPE aluminium conductor cable of 1100 volt grade as
required.All as per pre approved by Engineer in charge. For additional technical
parameters of products/ work , refer Annexure "A" attached with this BSR .

12.1.1 2 x 4.0 sq.mm Set 106.00


12.1.2 2 x 6.0 sq.mm Set 142.00
12.1.3 2 x 10.0 sq.mm Set 143.00
12.1.4 2 x 16.0 sq.mm Set 145.00
12.1.5 2 x 25.0 sq.mm Set 172.00
12.1.6 2 x 35.0 sq.mm Set 200.00
12.1.7 2 x 50.0 sq.mm Set 218.00
12.1.8 2 x 70.0 sq.mm Set 251.00
12.1.9 3 x 4.0 sq.mm Set 121.00
12.1.10 3 x 6.0 sq.mm Set 157.00
12.1.11 3 x 10.0 sq.mm Set 159.00
12.1.12 3 x 16.0 sq.mm Set 172.00
12.1.13 3 x 25.0 sq.mm Set 216.00
12.1.14 3 x 35.0 sq.mm Set 219.00
12.1.15 3 x 50.0 sq.mm Set 263.00
12.1.16 3 x 70.0 sq.mm Set 282.00
12.1.17 3.5 x 25.0 sq.mm Set 231.00
12.1.18 3.5 x 35.0 sq.mm Set 258.00
12.1.19 3.5 x 50.0 sq.mm Set 286.00
12.1.20 3.5 x 70.0 sq.mm Set 382.00
12.1.21 3.5 x 95.0 sq.mm Set 601.00
12.1.22 3.5 x 120.0 sq.mm Set 708.00
12.1.23 3.5 x 150.0 sq.mm Set 777.00
12.1.24 3.5 x 185.0 sq.mm Set 1072.00
12.1.25 3.5 x 240.0 sq.mm Set 1174.00
12.1.26 3.5 x 300.0 sq.mm Set 1441.00
12.1.27 3.5 x 400.0 sq.mm Set 2070.00
12.1.28 3.5 x 500.0 sq.mm Set 2639.00
12.1.29 3.5 x 630.0 sq.mm Set 3145.00
12.1.30 4 x 4.0 sq.mm Set 136.00
12.1.31 4 x 6.0 sq.mm Set 172.00
12.1.32 4 x 10.0 sq.mm Set 185.00
12.1.33 4 x 16.0 sq.mm Set 189.00

Chapter - E- 12 Page 62
P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-12

Code No. Description Unit Complete Rate


12.1.34 1 x 70.0 sq.mm Set 202.00
12.1.35 1 x 95.0 sq.mm Set 203.00
12.1.36 1 x 120.0 sq.mm Set 234.00
12.1.37 1 x 150.0 sq.mm Set 254.00
12.1.38 1 x 185.0 sq.mm Set 374.00
12.1.39 1 x 240.0 sq.mm Set 350.00
12.1.40 1 x 300.0 sq.mm Set 465.00
12.1.41 1 x 400.0 sq.mm Set 715.00
12.1.42 1 x 500.0 sq.mm Set 860.00
12.1.43 1 x 630.0 sq.mm Set 952.00
12.1.44 1 x 800.0 sq.mm Set 1592.00
12.1.45 1 x 1000.0 sq.mm Set 1840.00

12.2 Supplying and making one end termination with Nickel plated heavy duty brass
single compression gland (as per IS 12943-1990)) SIBG type consisting of Check
Nut, Gland Body, Metal Washer(3 Nos.), Outer Seal Rubber Ring, Compression
Nut, heavy duty Copper lugs (IS 8337- 1976) duly crimped with crimping tool,
PVC tape for following size of PVC insulated & PVC sheathed/ XLPE copper
conductor cable of 1100 volt grade as required.All as per pre approved by
Engineer in charge. For additional technical parameters of products/ work ,
refer Annexure "A" attached with this BSR .

12.2.1 1 x 16.0 sq.mm Set 113.00


12.2.2 1 x 25.0 sq.mm Set 133.00
12.2.3 1 x 35.0 sq.mm Set 140.00
12.2.4 1 x 50.0 sq.mm Set 202.00
12.2.5 1 x 70.0 sq.mm Set 228.00
12.2.6 1 x 95.0 sq.mm Set 278.00
12.2.7 1 x 120.0 sq.mm Set 337.00
12.2.8 2 x 4.0 sq.mm Set 128.0
12.2.9 2 x 6.0 sq.mm Set 131.0
12.2.10 2 x 10.0 sq.mm Set 154.0
12.2.11 2 x 16.0 sq.mm Set 161.0
12.2.12 2 x 25.0 sq.mm Set 197.0
12.2.13 2 x 35.0 sq.mm Set 210.0
12.2.14 2 x 50.0 sq.mm Set 279.0
12.2.15 2 x 70.0 sq.mm Set 351.0
12.2.16 2 x 95.0 sq.mm Set 422.0
12.2.17 2 x 120.0 sq.mm Set 580.0
12.2.18 3 x 1.5 sq.mm Set 130.0
12.2.19 3 x 2.5 sq.mm Set 132.0
12.2.20 3 x 4.0 sq.mm Set 148.0
12.2.21 3 x 6.0 sq.mm Set 174.0
12.2.22 3 x 10.0 sq.mm Set 176.0
12.2.23 3 x 16.0 sq.mm Set 197.0
12.2.24 3 x 25.0 sq.mm Set 255.0
12.2.25 3 x 35.0 sq.mm Set 273.0
12.2.26 3 x 50.0 sq.mm Set 354.0

Chapter - E- 12 Page 63
P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-12

Code No. Description Unit Complete Rate


12.2.27 3 x 70.0 sq.mm Set 432.0
12.2.28 3 x 95.0 sq.mm Set 604.0
12.2.29 3 x 120.0 sq.mm Set 905.0
12.2.30 4 x 1.5 sq.mm Set 135.0
12.2.31 4 x 2.5 sq.mm Set 137.0
12.2.32 4 x 4.0 sq.mm Set 176.0
12.2.33 4 x 6.0 sq.mm Set 181.0
12.2.34 4 x 10.0 sq.mm Set 208.0
12.2.35 4 x 16.0 sq.mm Set 222.0
12.2.36 4 x 25.0 sq.mm Set 286.0
12.2.37 4 x 35.0 sq.mm Set 333.0
12.2.38 4 x 50.0 sq.mm Set 411.0
12.2.39 4 x 70.0 sq.mm Set 588.0
12.2.40 4 x 95.0 sq.mm Set 972.0
12.2.41 4 x 120.0 sq.mm Set 1128.0
12.2.42 6 x 1.5 sq.mm Set 181.0
12.2.43 6 x 2.5 sq.mm Set 183.0
12.2.44 8 x 1.5 sq.mm Set 190.0
12.2.45 8 x 2.5 sq.mm Set 204.0
12.2.46 10 x 1.5 sq.mm Set 224.0
12.2.47 10 x 2.5 sq.mm Set 228.0
12.2.48 12 x 1.5 sq.mm Set 234.0
12.2.49 12 x 2.5 sq.mm Set 265.0
12.3 Supplying and making end termination with heavy aluminium lugs ( Pin / ring
type ) confirming to IS 8309 -1993 & IS 8337-1976 duly crimped with crimping
tool, PVC tape etc of following size.All as per pre approved by Engineer in
charge. For additional technical parameters of products/ work , refer
Annexure "A" attached with this BSR .
12.3.1 1.5 Sq.mm Each 2.0
12.3.2 2.5 Sq.mm Each 2.0
12.3.3 4.0 Sq.mm Each 2.0
12.3.4 6.0 Sq.mm Each 3.0
12.3.5 10.0 Sq.mm Each 4.0
12.3.6 16.0 Sq.mm Each 5.0
12.3.7 25.0 Sq.mm Each 7.0
12.3.8 35.0 Sq.mm Each 9.0
12.3.9 50.0 Sq.mm Each 12.0
12.3.10 70.0 Sq.mm Each 18.0
12.3.11 95.0 Sq.mm Each 19.0
12.3.12 120.0 Sq.mm Each 26.0
12.3.13 150.0 Sq.mm Each 34.0
12.3.14 185.0 Sq.mm Each 44.0
12.3.15 240.0 Sq.mm Each 69.0
12.3.16 300.0 Sq.mm Each 95.0
12.3.17 400.0 Sq.mm Each 135.0
12.3.18 500.0 Sq.mm Each 198.0
12.3.19 630.0 Sq.mm Each 243.0
12.3.20 800.0 Sq.mm Each 399.0

Chapter - E- 12 Page 64
P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-12

Code No. Description Unit Complete Rate


12.3.21 1000.0 Sq.mm Each 554.0

12.4 Supplying and making end termination with heavy duty Copper lugs ( ANY type
) confirming to IS 8337 -1976 duly crimped with crimping tool, PVC tape etc of
following size.All as per pre approved by Engineer in charge. For additional
technical parameters of products/ work , refer Annexure "A" attached with
this BSR .
12.4.1 1.5 Sq.mm Each 6.0
12.4.2 2.5 Sq.mm Each 6.0
12.4.3 4.0 Sq.mm Each 7.0
12.4.4 6.0 Sq.mm Each 8.0
12.4.5 10.0 Sq.mm Each 10.0
12.4.6 16.0 Sq.mm Each 13.0
12.4.7 25.0 Sq.mm Each 20.0
12.4.8 35.0 Sq.mm Each 27.0
12.4.9 50.0 Sq.mm Each 43.0
12.4.10 70.0 Sq.mm Each 67.0
12.4.11 95.0 Sq.mm Each 88.0
12.4.12 120.0 Sq.mm Each 128.0

12.5 Supply, Fabricating & installing following sizes of perforated Hot dipped
Galvanized iron cable tray ( Galvanized thickness not less then 50 microns) with
perforation not more then 17.5% in convenient section including horizontal and
vertical bends, reducers tees,cross members and other accessories as required
and duly suspended from the ceiling with GI suspenders including GI bolts &
nuts , fastners, supports etc. as required.All as per pre approved by Engineer in
charge. For additional technical parameters of products/ work , refer
Annexure "A" attached with this BSR .

12.5.1 100mm x 50mm x 1.6mm Mtr 553.0


12.5.2 150mm x 50mm x 1.6mm Mtr 675.0
12.5.3 225mm x 50mm x 1.6mm Mtr 874.0
12.5.4 300mm x 50mm x 1.6mm Mtr 1053.0
12.5.5 375mm x 50mm x 2.0mm Mtr 1633.0
12.5.6 450mm x 50mm x 2.0mm Mtr 1876.0
12.5.7 600mm x 50mm x 2.0mm Mtr 2376.0
12.5.8 300mm x 62.5mm x 2.0mm Mtr 1471.0
12.5.9 375mm x 62.5mm x 2.0mm Mtr 1728.0
12.5.10 450mm x 62.5mm x 2.0mm Mtr 1971.0
12.5.11 600mm x 62.5mm x 2.0mm Mtr 2470.0
12.5.12 750mm x 62.5mm x 2.0mm Mtr 2997.0
12.5.13 600mm x 75mm x 2.0mm Mtr 2565.0
12.5.14 750mm x 75mm x 2.0mm Mtr 3078.0

Chapter - E- 12 Page 65
P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-12

Code No. Description Unit Complete Rate


12.6 Supply, Fabricating & installing following sizes of perforated Powder coated
MS cable tray with perforation not more then 17.5% in convenient section
including horizontal and vertical bends, reducers tees,cross members and other
accessories as required and duly suspended from the ceiling with GI suspenders
including GI bolts & nuts , fastners, supports etc. as required.All as per pre
approved by Engineer in charge. For additional technical parameters of
products/ work , refer Annexure "A" attached with this BSR .

12.6.1 100mm x 50mm x 1.6mm Mtr 480.0


12.6.2 150mm x 50mm x 1.6mm Mtr 584.0
12.6.3 225mm x 50mm x 1.6mm Mtr 755.0
12.6.4 300mm x 50mm x 1.6mm Mtr 907.0
12.6.5 375mm x 50mm x 2.0mm Mtr 1402.0
12.6.6 450mm x 50mm x 2.0mm Mtr 1609.0
12.6.7 600mm x 50mm x 2.0mm Mtr 2036.0
12.6.8 300mm x 62.5mm x 2.0mm Mtr 1265.0
12.6.9 375mm x 62.5mm x 2.0mm Mtr 1485.0
12.6.10 450mm x 62.5mm x 2.0mm Mtr 1691.0
12.6.11 600mm x 62.5mm x 2.0mm Mtr 2118.0
12.6.12 750mm x 62.5mm x 2.0mm Mtr 2571.0
12.6.13 600mm x 75mm x 2.0mm Mtr 2200.0
12.6.14 750mm x 75mm x 2.0mm Mtr 2640.0

12.7 Supply, Fabricating & installing following sizes of Hot dipped Galvanized iron
cable tray ( Galvanized thickness not less then 50 microns) with rungs at span
of 250mm including horizontal and vertical bends, reducers tees,cross
members and other accessories as required and duly suspended from the
ceiling/wall with M.S. suspenders etc. as required.All as per pre approved by
Engineer in charge. For additional technical parameters of products/ work ,
refer Annexure "A" attached with this BSR .

12.7.1 100mm x 50mm x 1.6mm Mtr 440.0


12.7.2 150mm x 50mm x 1.6mm Mtr 533.0
12.7.3 225mm x 50mm x 1.6mm Mtr 689.0
12.7.4 300mm x 50mm x 1.6mm Mtr 826.0
12.7.5 375mm x 50mm x 2.0mm Mtr 1274.0
12.7.6 450mm x 50mm x 2.0mm Mtr 1460.0
12.7.7 600mm x 50mm x 2.0mm Mtr 1847.0
12.7.8 300mm x 62.5mm x 2.0mm Mtr 1150.0
12.7.9 375mm x 62.5mm x 2.0mm Mtr 1350.00
12.7.10 450mm x 62.5mm x 2.0mm Mtr 1536.00
12.7.11 600mm x 62.5mm x 2.0mm Mtr 1922.00
12.7.12 750mm x 62.5mm x 2.0mm Mtr 2335.0
12.7.13 600mm x 75mm x 2.0mm Mtr 1998.0
12.7.14 750mm x 75mm x 2.0mm Mtr 2397.0

Chapter - E- 12 Page 66
P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-12

Code No. Description Unit Complete Rate


12.8 Supplying and fixing of CE certified and UL listed GI wire mesh cable tray made
from spot welded steel wire hot dipped galvanised between 60 and 80 microns
of zinc as per BS 729 including horizontal and vertical bends, reducers, tees,
cross members and other OEM made accessories like wall clamp, hold down
clamps, Earthing terminal, brackets as required, and duly suspended from the
ceiling with electro-zinc coated TF rods, etc. as required of following sizesAll as
per pre approved by Engineer in charge. For additional technical parameters of
products/ work , refer Annexure "A" attached with this BSR .

12.8.1 100 mm x 50 mm x 6 mm Mtr 533.0


12.8.2 150 mm x 50 mm x 6 mm Mtr 649.0
12.8.3 200 mm x 50 mm x 6 mm Mtr 841.0
12.8.4 300 mm x 50 mm x 6 mm Mtr 1012.0
12.8.5 400 mm x 50 mm x 6 mm Mtr 1569.0
12.8.6 500 mm x 50 mm x 6 mm Mtr 1802.0
12.8.7 100 mm x 100 mm x 6 mm Mtr 779.0
12.8.8 150 mm x 100 mm x 6 mm Mtr 896.0
12.8.9 200 mm x 100 mm x 6 mm Mtr 1025.0
12.8.10 300 mm x 100 mm x 6 mm Mtr 1258.0
12.8.11 400 mm x 100 mm x 6 mm Mtr 1505.0
12.8.12 500 mm x 100 mm x 6 mm Mtr 1738.0

12.9 Supply and fixing following size of Hot dipped Galvanized (275 GSM) floor
raceways / Under floor trunking with/ without partion, including common
cover, joint sleeve, cross over junction Box etc. as required.All as per pre
approved by Engineer in charge. For additional technical parameters of
products/ work , refer Annexure "A" attached with this BSR .

12.9.1 75 mm x 25 mm x 1.5 mm Mtr 1107.0


12.9.2 100 mm x 25 mm x 1.5 mm Mtr 1365.0
12.9.3 150 mm x 25 mm x 1.5 mm Mtr 2022.0
12.9.4 250 mm x 25 mm x 1.5 mm Mtr 3169.0
12.9.5 300 mm x 25 mm x 1.5 mm Mtr 3705.0
12.9.6 75 mm x 38 mm x 1.5 mm Mtr 1491.0
12.9.7 100 mm x 38 mm x 1.5 mm Mtr 1712.0
12.9.8 150 mm x 38 mm x 1.5 mm Mtr 2223.0
12.9.9 250 mm x 38 mm x 1.5 mm Mtr 3189.0
12.9.10 300 mm x 38 mm x 1.5 mm Mtr 3800.0
12.9.11 150 mm x 38 mm x 2.0 mm with 2 Compartment Mtr 3298.0
12.9.12 250 mm x 38 mm x 2.0 mm with 3 Compartment Mtr 4805.0
12.9.13 300 mm x 38 mm x 2.0 mm with 3 Compartment Mtr 5222.0

Supply and fixing following Hot dipped Galvanized (275 GSM) accessories for
floor raceways / Under floor trunking etc. as required.All as per pre approved
12.9.14
by Engineer in charge. For additional technical parameters of products/ work ,
refer Annexure "A" attached with this BSR .
12.9.15 Access Outlet 200 mm x 200 mm x 40-75 mm with Galvanized Lid Mtr 8808.0

Chapter - E- 12 Page 67
P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-12

Code No. Description Unit Complete Rate


12.9.16 Access Outlet 250 mm x 250 mm x 40-75 mm with Galvanized Lid Mtr 11210.0
12.9.17 Access Outlet 300 mm x 300 mm x 40-75 mm with Galvanized Lid Mtr 13911.0
12.9.18 Access Outlet 350 mm x 350 mm x 40-75 mm with Galvanized Lid Mtr 18819.0
12.9.19 Access Outlet 250 mm x 250 mm x 40-75 mm with stainless steel Lid Mtr 14081.0
12.9.20 Access Outlet 300 mm x 300 mm x 40-75 mm with stainless steel Lid Mtr 21737.0
12.9.21 Access Outlet 350 mm x 350 mm x 60-120 mm with stainless steel Lid Mtr 26747.0

12.10 S & Making Heat shrinkable type Tubular sleeve version outdoor straight
through joint for following size of PVC/ XLPE insulated aluminium conductor
cable of 1.1 KV grade as required. All as per pre approved by Engineer in
charge. For additional technical parameters of products/ work , refer
Annexure "A" attached with this BSR .
12.10.1 1 x 25 sq.mm-50 sq.mm Set 1997.0
12.10.2 1 x 70 sq.mm-150 sq.mm Set 3197.0
12.10.3 1 x 185 sq.mm-300 sq.mm Set 4822.0
12.10.4 1 x 400 sq.mm Set 4542.0
12.10.5 1 x 500 sq.mm Set 5148.0
12.10.6 1 x 630 sq.mm Set 5327.0
12.10.7 1 x 800 sq.mm Set 5891.0
12.10.8 1 x 1000 sq.mm Set 7152.0
12.10.9 2 x 1.5 sq.mm-6 sq.mm Set 625.0
12.10.10 2 x 10.0-16.0 sq.mm Set 1545.0
12.10.11 2 x 25.0 sq.mm-50 sq.mm Set 2529.0
12.10.12 2 x 70.0 sq.mm-150 sq.mm Set 4390.0
12.10.13 2 x 185.0 sq.mm-300 sq.mm Set 8302.0
12.10.14 2 x 400 sq.mm Set 8932.0
12.10.15 2 x500 sq.mm Set 9634.0
12.10.16 3/3.5/4 x 1.5 sq.mm-6 sq.mm Set 1016.0
12.10.17 3/3.5/4 x 10.0-16.0 sq.mm Set 1768.0
12.10.18 3/3.5/4 x 25.0 sq.mm-50 sq.mm Set 3231.0
12.10.19 3/3.5/4 x 70.0 sq.mm-150 sq.mm Set 4918.0
12.10.20 3/3.5/4 x 185.0 sq.mm-300 sq.mm Set 9006.0
12.10.21 3/3.5/4 x 400 sq.mm Set 9626.0
12.10.22 3/3.5/4 x500 sq.mm Set 11381.0

12.11 S/F cable route marker with 10cm x 10cm x 5mm thick or 10 cm dia. G.I.plate
with inscription thereon, bolted/welded to 35mm x 35mm x 5mm angle iron,
60cm long and fixing the same in ground in C C ( 1:3:6 ) as required. All as per
pre approved by Engineer in charge. For additional technical parameters of
products/ work , refer Annexure "A" attached with this BSR .
Each 388.0

Chapter - E- 12 Page 68
P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-12

Code No. Description Unit Complete Rate


12.12 P / L of Double wall corrugated HDPE pipe confirming to IS : 16205 P-24,
Stiffness Class 750 N, Externally corrugated and having smooth surface inside
with HDPE Coupler, Elbow, Tee at required Depth below the ground for laying
cable of following Nominal Outer dia. MFR Test report from NABL accrediated
is to be submitted.(Excavation of Earth & Back filling with compaction is to be
Paid Extra)All as per pre approved by Engineer in charge. For additional
technical parameters of products/ work , refer Annexure "A" attached with
this BSR .
12.12.1 50 mm Mtr 85.0
12.12.2 63 mm Mtr 99.0
12.12.3 75 mm Mtr 130.0
12.12.4 90 mm Mtr 176.00
12.12.5 110 mm Mtr 226.0
12.12.6 120 mm Mtr 256.0
12.12.7 160 mm Mtr 366.0
12.12.8 200 mm Dia. Mtr 494.0

12.13 Providing and laying Non Pressure NP-3 class R.C.C. pipes including
collars/spigot jointed with stiff mixture of cement mortar in the proportion of
1:2 (1 cement : 2 fine sand) etc. as required. (Excavation of Earth & Back filling
with compaction is to be Paid Extra). All as per pre approved by Engineer in
charge. For additional technical parameters of products/ work , refer
Annexure "A" attached with this BSR .
12.13.1 200 mm Dia. Mtr 560.00
12.13.2 250 mm dia. Mtr 698.00
12.13.3 300 mm dia Mtr 917.00
12.13.4 450 mm dia. Mtr 1753.00

12.14 labour charges for Excavating trenches of required width for pipes dressing of
sides, ramming of bottoms, depth up to 1.5 Mtr. including taking out the
excavated soil, and then returning the soil as required in layers not exceeding
20cm in depth including consolidating each deposited layer by ramming,
watering etc. and disposal of surplus excavated soil as directed within a lead of
50 Mtr.:
12.14.1 All kind of Soils Cum 213.00
12.14.2 Ordinary Rocks Cum 305

Chapter - E- 12 Page 69
P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-13

Chapter E - 13

H T Cables & Termination Kits


Code No. Description Unit Complete
Rate
13.1 Providing & Laying XLPE insulated three core Armoured Aluminium
cable for working voltage 11 K.V.(E) confirming IS :7098 P - 2 with H4-
Grade electrolytic aluminium conductor confirming to IS: 8130 class-2
of purity >99.6 %, Insulation Screening: Extruded Semiconducting
Compound followed by helically wrapped Copper Tape, round / flat strip
armouring of cables , Inner / outer sheath PVC type ST-2 confirming to
IS:5831 in existing RCC / Hume / Stoneware / PVC pipe/ open
duct/cable trench / Cable tray including testing etc. as required of
following size. OEM must have it's own in house NABL accrediated
Laboratory for testing procedure as per IS:10810 All as per pre approved
by Engineer in charge. For additional technical parameters of products/
work , refer Annexure "A" attached with this BSR .

13.1.1 3 core 95.0 Sq.mm Mtr 1287.0


13.1.2 3 core 120.0 Sq.mm Mtr 1465.0
13.1.3 3 core 150.0 Sq.mm Mtr 1653.0
13.1.4 3 core 185.0 Sq.mm Mtr 1904.0
13.1.5 3 core 240.0 Sq.mm Mtr 2299.0
13.1.6 3 core 300.0 Sq.mm Mtr 2690.0

13.2 Providing & Laying XLPE insulated three core Armoured Aluminium
cable for working voltage 33 K.V.(E) confirming IS :7098 P - 2 with H4-
Grade electrolytic aluminium conductor confirming to IS: 8130 class-2
of purity >99.6 %, Insulation Screening: Extruded Semiconducting
Compound followed by helically wrapped Copper Tape, round / flat strip
armouring of cables , Inner / outer sheath PVC type ST-2 confirming to
IS:5831 in existing RCC / Hume / Stoneware / PVC pipe/ open
duct/cable trench / Cable tray including testing etc. as required of
following size. OEM must have it's own in house NABL accrediated
Laboratory for testing procedure as per IS:10810 All as per pre approved
by Engineer in charge. For additional technical parameters of products/
work , refer Annexure "A" attached with this BSR .

13.2.1 3 core 150.0 Sq.mm Mtr 2780.0


13.2.2 3 core 185.0 Sq.mm Mtr 3068.0
13.2.3 3 core 240.0 Sq.mm Mtr 3536.0
13.2.4 3 core 300.0 Sq.mm Mtr 3959.0

Chapter E - 13 Page 70
P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-13

Code No. Description Unit Complete


Rate
13.3 Add Extra for Laying of one number XLPE power cable of 11/33 KV
(Earthed) voltage grade direct in ground including excavation of trench
of size 120 cm (Depth) x 35 cm(Width) , with procedure as per following
points:- (a) Make a river sand bed of height 125 mm along the trench,
(b) Lay the cable in the middle of the trench, (c) Provide river sand bed
of height 125 mm on top of the cable. (d) Lay the protective Common
burnt clay F.P.S. Bricks of Class designation 75 / Sand stone slabs of 50 Mtr 233.0
mm thickness and 225 mm wide just above the sand bed vertically
across the cable ( Approx. 9 no. Bricks per Mtr.), (e) Backfill the
excavated soil leaving 300 mm from the Ground level, (f)Lay the Cable
warning tape and again back-fill the remaining portion of the trench
upto the ground level and compacting the earth

13.4 Add Extra in Item no. 13.3 if Excavation done in Hard Rock / CC road /
Mtr 39.0
TAR Road and making Good the same
13.5 Add Extra for Laying of one number additional XLPE power cable of
11/33 KV (Earthed) voltage grade direct in ground in the same trench in
one tier horizontal formation including excavation of trench of size
additional 20 cm in width, with procedure as per following points:- (a)
Make a river sand bed of height 125 mm along the trench, (b) Lay
another cable in middle of trench in such manner that spacing between
another cable is 20 cm, (c) Provide sand bed of height 125 mm on top of
Mtr 155.0
the cable. (d) Lay the protective Common burnt clay F.P.S. Bricks of Class
designation 75 / Sand stone slabs of 50 mm thickness and 225 mm wide
just above the sand bed vertically across the cable ( Approx. 9 no. Bricks
per Mtr.) (e) Backfill the excavated soil leaving 300 mm from the Ground
level. (f)Lay the Cable warning tape and again back-fill the remaining
portion of the trench upto the ground level and compacting the earth

13.6 Add Extra in Item no. 13.5 if Excavation done in Hard Rock / CC road /
Mtr 22.0
TAR Road and making Good the same

13.12 Providing & making heat shrinkable type indoor/outdoor/straight


through terminations/ joint kit suitable for 11 KV / 33 KV (Earthed)
cable with required components, prepration of cable ends. Type test
report should be as per IS13573:2011 which covered all sequence for
table 2 for termination kit and table 3 for streight through joint
inclusive thermal & dynamic short circuit test, humidity test, soil fog
test. Cross linking shall be done out side factory with E- beam/ peroxide
technology. Extrusion process shall be in house OEM within same
vicinity. including testing etc. as required of following sizes. All as per
pre approved by Engineer in charge. For additional technical parameters
of products/ work , refer Annexure "A" attached with this BSR .

13.12.1 11 KV End Termination Kit Indoor type


13.12.1.1 3 core up to 35 Sqmm Each 3975.0
13.12.1.2 3 core 50/70/95 Sq.mm Each 4812.0
13.12.1.3 3 core 120/150/185 Sq.mm Each 5862.0
13.12.1.4 3 core 240/300 Sq.mm Each 6845.0

Chapter E - 13 Page 71
P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-13

Code No. Description Unit Complete


Rate
13.12.1.5 3 core 400 Sq.mm Each 7840.0
13.12.2 11 KV End Termination Kit Outdoor type
13.12.2.1 3 core up to 35 Sqmm Each 5987.0
13.12.2.2 3 core 50/70/95 Sq.mm Each 7041.0
13.12.2.3 3 core 120/150/185 Sq.mm Each 8063.0
13.12.2.4 3 core 240/300 Sq.mm Each 9330.0
13.12.2.5 3 core 400 Sq.mm Each 10136.0
13.12.3 11 KV Straight Through Joint Kit
13.12.3.1 3 core up to 35 Sq.mm Each 8282.0
13.12.3.2 3 core 50/70/95 Sq.mm Each 9265.0
13.12.3.3 3 core 120/150/185 Sq.mm Each 12076.0
13.12.3.4 3 core 240/300 Sq.mm Each 14357.0
13.12.3.5 3 core 400 Sq.mm Each 15971.0
13.12.4 33 KV End Termination Kit Indoor type
13.12.4.1 3 core 95 Sq.mm Each 7212.0
13.12.4.2 3 core 120/150/185 Sq.mm Each 8191.0
13.12.4.3 3 core 240/300/400 Sq.mm Each 9886.0
13.12.5 33 KV End Termination Kit Outdoor type
13.12.5.1 3 core 95 Sq.mm Each 7442.0
13.12.5.2 3 core 120/150/185 Sq.mm Each 8948.0
13.12.5.3 3 core 240/300/400 Sq.mm Each 10332.0
13.12.6 33 KV Straight Through Joint Kit
13.12.6.1 3 core 95/120/150 Sq.mm Each 18287.0
13.12.6.2 3 core 185/240/300 Sq.mm Each 21657.0
13.12.6.3 3 core 400 Sq.mm Each 24581.0

Chapter E - 13 Page 72
P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-14

Chapter E 14

Earthing & Lightning Arrester


Code No. Description Unit Complete Rate

14.1 Pipe Earthing as per IS:3043- 1987 with 3.0 Mtr. Long, 40 mm dia. ' B '
class G.I. Pipe IS: 1239 (Part-1) 2004, Equivalent to BS : 1387 with
perforated holes of 12 mm dia ,including all accessories like nut, bolts,
reducer, nipple, wire meshed funnel, and Heavy duty weather proof poly-
propylene earth pit chamber with lockable Jam free lid suitable for safe
working load 5000 Kg or more of size Top Dia. 225 to 260 mm, Bottom
Dia 300 to 350 mm. and Height 250 to 300 mm. and embodying the pipe
complete with alternate layers salt and coke/ charcoal, testing of earth
resistance for value of 5 ohms or less as required & must record by
engineer in charge during site visit and ensure to enter in measurment
book.All as per pre approved by Engineer in charge. For additional
technical parameters of products/ work , refer Annexure "A" attached
with this BSR .
Set 3643.0

14.2 Plate Earthing as per IS:3043 with Hot dipped G.I. Earth plate of size
600mm x 600mm x 6.0mm by embodying 3 to 4 mtr. below the ground
level with 20 mm dia. G.I. 'B' class watering Pipe ,including all accessories
like nut, bolts, reducer, nipple, wire meshed funnel, and Heavy duty
weather proof poly-propylene earth pit chamber with lockable Jam free
lid suitable for safe working load 5000 Kg or more of size Top Dia. 225 to
260 mm, Bottom Dia 300 to 350 mm. and Height 250 to 300 mm. and
embodying the pipe complete with alternate layers salt and coke/
charcoal, testing of earth resistance for value of 5 ohms or less as
required & must record by engineer in charge during site visit and ensure
to enter in measurment book.All as per pre approved by Engineer in
charge. For additional technical parameters of products/ work , refer
Annexure "A" attached with this BSR .
Set 5733.0

14.3 Plate Earthing as per IS:3043 with copper Earth plate of purity >95% of
size 600mm x 600mm x 3.0mm by embodying 3 mtr. below the ground
level with 20 mm dia. G.I. 'B' class watering Pipe ,including all accessories
like nut, bolts, reducer, nipple, wire meshed funnel, and Heavy duty
weather proof poly-propylene earth pit chamber with lockable Jam free
lid suitable for safe working load 5000 Kg or more of size Top Dia. 225 to
260 mm, Bottom Dia 300 to 350 mm. and Height 250 to 300 mm. and
embodying the pipe complete with alternate layers salt and coke/
charcoal, testing of earth resistance for value of 5 ohms or less as
required & must record by engineer in charge during site visit and ensure
to enter in measurment book. All as per pre approved by Engineer in
charge. For additional technical parameters of products/ work , refer
Annexure "A" attached with this BSR .
Set 15144.0

Chapter E - 14 Page 73
P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-14

Code No. Description Unit Complete Rate


14.4 Supply and installation of high tensile low carbon steel rod molecularly
bonded with 99.9 % Copper thickness (250 microns) and confirming to
UL 467, IS/IEC 62561-2 of following size and length and as per point
mentioned (a), (b), [c), (d), (e) below :-
(a) Bore a hole of dia. 100 mm of required length, Place the rod in the
centre of Hole
(b) filled with anti corrosive conductive compounds with the permanent
sealings at both the ends, CPRI/ ERDA tested with RMS capacity of
minimum 30 KA for withstanding 1 second .To ensure the moisture
content and electrical conductivity, 25 kg for 2000 mm & 50 Kgs for
3000mm of resistance lowering earth enhancement material shall be
used as a backfill compound. The compound shall be tested form NABL
acredeated lab for low resistivity ( less than 0.12 Ohm - meter ) & high
conductivity in nature with carbon as a major content as per referance of
IS 3043-1987,IEEE 80-2013 (clause 14.5d) , IEEE 837 & IER 1956 with
latest amendemnts
© Connect the rod with copper Strip/Conductor/Wire with suitable
clamp made from tinned copper and SS 304 Bolt
(d) Place Heavy duty weather proof poly-propylene earth pit chamber
with lockable Jam free lid suitable for safe working load 5000 Kg or more
of size Top Dia. 225 to 260 mm, Bottom Dia 300 to 350 mm. and Height
250 to 300 mm.
(d) Testing of earth resistance for value of 5 ohms or less as required &
must record by engineer in charge during site visit and ensure to enter in
measurment book.
(e) Test certificates for confirming above standards from OEM is
mandatory. All as per pre approved by Engineer in charge. For additional
technical parameters of products/ work , refer Annexure "A" attached
with this BSR .
14.4.1 17.2 mm thick and 3 Mtr. Long Set 7010.00
14.4.1 25 mm thick and 3 Mtr. Long Set 7955.00

14.5 Supply & Laying following size earth strip in horizontal or vertical run in
surface by means of Earth strip DMC Insulator including riveting/
soldering/ welding, Jointing shall be done by overlapping and with 2 set
of Brass (for Cu strip) / GI (for GI Strip) nut bolt & spring washer spaced at
50cm making connection etc. as required.All as per pre approved by
Engineer in charge. For additional technical parameters of products/
work , refer Annexure "A" attached with this BSR .

14.5.1 20mm x 3mm copper strip Mtr. 781.0


14.5.2 25mm x 3mm copper strip Mtr. 1037.0
14.5.3 25mm x 5mm copper strip Mtr. 1551.0
14.5.4 30mm x 5 mm copper strip Mtr. 1940.0
14.5.5 40mm x 6mm copper strip Mtr. 3090.0
14.5.6 50mm x 6mm copper strip Mtr. 4120.0
14.5.7 20mm x 3mm tinned copper strip Mtr. 866.0
14.5.8 25mm x 3mm tinned copper strip Mtr. 1150.0
14.5.9 25mm x 5mm tinned copper strip Mtr. 1720.0
14.5.10 30mm x 5 mm tinned copper strip Mtr. 2152.0
14.5.11 40mm x 6mm tinned copper strip Mtr. 3429.0
14.5.12 50mm x 6mm tinned copper strip Mtr. 4572.0

Chapter E - 14 Page 74
P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-14

Code No. Description Unit Complete Rate


14.5.13 20mm x 3mm G.I. ( Hot Dipped ) Strip Mtr. 88.0
14.5.14 25mm x 3mm G.I. ( Hot Dipped ) Strip Mtr. 105.0
14.5.15 25mm x 6mm G.I. ( Hot Dipped ) Strip Mtr. 196.0
14.5.16 32mm x6mm G.I. ( Hot Dipped ) Strip Mtr. 245.0
14.5.17 50mm x 6mm G.I. ( Hot Dipped ) Strip Mtr. 406.0
14.5.18 20mm x 3mm Alum. Strip Mtr. 110.0
14.5.19 25mm x 3mm Alum. Strip Mtr. 133.0
14.5.20 25mm x 4 mm Alum. Strip Mtr. 177.0
14.5.21 25mm x 5 mm Alum. Strip Mtr. 215.0
14.5.22 30mm x 6mm Alum. Strip Mtr. 304.0
14.5.23 50mm x 5mm Alum. Strip Mtr. 429.0
14.5.24 50mm x 8mm Alum. Strip Mtr. 695.0
14.5.25 100mm x 8mm Alum. Strip Mtr. 1363.0
14.5.26 100mm x 10mm Alum. Strip Mtr. 1690.0
14.5.27 200mm x 20mm Alum. Strip Mtr. 6279.0

14.6 Supply & Laying following size earth wire in horizontal or vertical run in
ground/surface/recess including riveting, soldering, saddles, making
connection with GI/Cu purity purity >95% thimble etc. as required. All as
per pre approved by Engineer in charge. For additional technical
parameters of products/ work , refer Annexure "A" attached with this
BSR .
14.6.1 6 SWG tinned copper Wire Mtr. 232.0
14.6.2 8 SWG tinned copper Wire Mtr. 163.0
14.6.3 10 SWG tinned copper. Wire Mtr. 107.0
14.6.4 6 SWG copper Wire Mtr. 210.0
14.6.5 8 SWG copper Wire Mtr. 148.0
14.6.6 10 SWG copper. Wire Mtr. 97.0
14.6.7 6 SWG G.I. ( Hot Dipped ) Wire Mtr. 27.0
14.6.8 8 SWG G.I. ( Hot Dipped ) Wire Mtr. 20.0
14.6.9 10 SWG G.I. ( Hot Dipped ) Wire Mtr. 14.0
14.6.10 16 Sq.mm Copper coated steel stranded conductor (Wt. 130 Kg/Km Mtr. 48.0
14.6.11 25 Sq.mm Copper coated steel stranded conductor ( Wt. 200Kg/Km Mtr. 74.0

14.7 Supply & Laying following size' B ' class , G.I. Pipe confirming to IS : 1239
P - 1 ( 2004 ) with accessories like bend, socket etc. for laying earth
conductor/ strip / cable in ground/ surface/ recess as required. All as per
pre approved by Engineer in charge. (Earth Excavation will be Paid
Extra)All as per pre approved by Engineer in charge. For additional
technical parameters of products/ work , refer Annex ure "A" attached
with this BSR .
14.7.1 15 mm dia. Mtr. 205.0
14.7.2 20 mm dia. Mtr. 259.0
14.7.3 25 mm dia. Mtr. 358.0
14.7.4 32mm dia Mtr. 448.0
14.7.5 40 mm dia. Mtr. 516.0
14.7.6 50 mm dia. Mtr. 718.0
14.7.7 65 mm dia. Mtr. 915.0
14.7.8 80 mm dia. Mtr. 1155.0
14.7.9 100 mm dia. Mtr. 1657.0
14.7.10 150 mm dia. Mtr. 2575.0

Chapter E - 14 Page 75
P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-14

Code No. Description Unit Complete Rate


14.8 Mesh earthing as per IS:3043 with Hot dipped galvanized earth strip of
size 25 mm x 6 mm to form a mesh of size 1000 mm x 1000 mm in
horizontal formation to create equal sections of 200 mm x 200 mm by
means of welding and embodying 1 mtr. Below the ground level, refilling
the pit by alternative layers of charcoal & salt up to 500 mm with 20 mm
dia. GI 'B' class watering pipe, wire mesh funnel and and Heavy duty
weather proof poly-propylene earth pit chamber with lockable Jam free
lid suitable for safe working load 5000 Kg or more of size Top Dia. 225 to
260 mm, Bottom Dia 300 to 350 mm. and Height 250 to 300 mm testing
of earth resistance for value of 5 ohms or less as required & must record
by engineer in charge during site visit and ensure to enter in measurment
book. All as per pre approved by Engineer in charge. For additional
technical parameters of products/ work , refer Annexure "A" attached
with this BSR .
Each 7235.0

14.10 P & F of Heavy duty weather proof poly-propylene earth pit chamber
with lockable Jam free lid suitable for safe working load 5000 Kg or more
of size Top Dia. 225 to 260 mm, Bottom Dia 300 to 350 mm. and Height
250 to 300 mm. All as per pre approved by Engineer in charge. For
additional technical parameters of products/ work , refer Annexure "A"
attached with this BSR . Each 1012.0

14.11 S & F of Earth Bar with Disconnecting link Made out from 50 mm x 6 mm
copper purity purity >95% /GI strip pre fitted on epoxy powder coated
metal base mounted on hexagonal SMC Insulators of following Size.All as
per pre approved by Engineer in charge. For additional technical
parameters of products/ work , refer Annex ure "A" attached with this
BSR .
14.11.1 400 mm , 6 Way Copper Each 2160.0
14.11.2 600 mm , 10 Way Copper Each 2970.0
14.11.3 400 mm , 6 Way GI Each 809.0
14.11.4 600 mm , 10 Way GI Each 1079.0

14.12 Providing & Making of Exothermic joint in Tee / Square / Straight


through joint in Strip for permanently bonding of copper to copper or
copper to GI including required exothermic jointing kit comprising of
graphite mould, weld powder, tools etc. as required.All as per pre
approved by Engineer in charge. For additional technical parameters of
products/ work , refer Annex ure "A" attached with this BSR .
per Joint 1145.0

14.13 Supply, installation, testing & commissioning of following size & Material
air termination rods confirming to IEC/EN 62561 with suitable OEM
recommended mounting arrangement on parapet wall all as per
standard , complete as required. the test report accredited by third party
accreditation body like VDE/ ILAC/ DAkkS/ UL/ NABL is to be
submitted.All as per pre approved by Engineer in charge. For additional
technical parameters of products/ work , refer Annex ure "A" attached
with this BSR .
14.13.1 700 mm long, 10 mm Dia. Aluminium / AlMgSi Set 1754.0

Chapter E - 14 Page 76
P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-14

Code No. Description Unit Complete Rate


14.13.2 1000 mm long, 10 mm Dia. Aluminium / AlMgSi Set 2430.0
14.13.3 1500 mm long, 10 mm Dia. Aluminium / AlMgSi Set 3374.0
14.13.4 2000 mm long, 16mm rod tapered to 10 mm, AlMgSi Set 8502.0
14.13.5 3000 mm long, 16mm rod tapered to 10 mm, AlMgSi Set 12817.0

14.14 Supply & Laying of Aluminum / SS / AlMgSi Round Conductor confirming


to IEC/EN 62561 etc. as required. the test report accredited by third party
accreditation body like VDE/ILAC/ DAkkS/ UL/ NABL is to be submitted. (
Supporting Clamps to be paid Extra )All as per pre approved by Engineer
in charge. For additional technical parameters of products/ work , refer
Annex ure "A" attached with this BSR .

14.14.1 8 mm Dia. Aluminium conductor Mtr 263.0


14.14.2 8 mm Dia. AlMgSi conductor Mtr 286.0

14.15 Supply & Fixing Air-termination rod clamps for connecting air-termination
rods with one or two conductors. Material of clamp Al, with clamping
range of air-termination rod 10 / 16 mm and Clamping range of
conductor Rd 2x 8-10 mm, & Complied as per Standard EN 62561-1,
tested to carry from 100KA (10/350μs) lightning current the test report
accredited by third party accreditation body like VDE/ILAC/ DAkkS/ UL/
NABL is to be submitted. All as per pre approved by Engineer in charge.
For additional technical parameters of products/ work , refer Annex ure
"A" attached with this BSR .
Set 513.0

14.16 Supply and Fixing of stainless steel clamp for holding 8 mm dia.
conductor on Parapet Wall / Side Fl 20 mm, Height- 20 mm & Complied
as per Standard EN 62561-4. With accessories SS Screw and Gitty etc. as
required. the test report accredited by third party accreditation body like
VDE/ILAC/ DAkkS/ UL/ NABL is to be submitted. All as per pre approved
by Engineer in charge. For additional technical parameters of products/
work , refer Annex ure "A" attached with this BSR . Set 144.0

14.17 Supply and Fixing Polyamide Roof conductor Holder for Roof with
Concrete Block with 8 mm conductor Holder including adhesive material
to paste with roof where drilling not allowed.All as per pre approved by
Engineer in charge. For additional technical parameters of products/
work , refer Annex ure "A" attached with this BSR .
Set 391.0

14.18 Supply and Fixing of Test Joint (Folding Clamp) made of SS,suitable to
connect 8mm round conductor with 25 mm x 6 mm GI strip etc. as
required. the test report accredited by third party accreditation body
likeVDE/ILAC/ DAkkS/ UL/ NABL is to be submitted. All as per pre
approved by Engineer in charge. For additional technical parameters of
products/ work , refer Annex ure "A" attached with this BSR .
Set 1444.0

Chapter E - 14 Page 77
P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-14

Code No. Description Unit Complete Rate


14.19 Supply and Fixing GI flat (25x6mm) Strip. Having width- 25mm, Thickness-
6mm, Material- Hot dipped Galvanized Iron, Coating thickness- Avg. 70
microns. & Complied as per IEC 62561-2 GI strip holder of material- Dow
moulded compound, at spacing of 0.5 Mtr. having height- 19mm, Slot
Size- 25x6 mm Etc. as required.All as per pre approved by Engineer in
charge. For additional technical parameters of products/ work , refer
Annex ure "A" attached with this BSR . Mtr. 364.0

14. 20 Clamps to connect reinforcing steel mesh or reinforcement at every 2


meters with round and flat conductors. of material- St/bare, having
clamping range- Rd / Rd 6-22 / 6-10 mm, Clamping range- Rd / Fl 6-22 /
40 mm & Complied as per Standard EN 62561-1 the test report
accredited by third party accreditation body like VDE/ILAC/ DAkkS/ UL/
NABL is to be submitted. All as per pre approved by Engineer in charge.
For additional technical parameters of products/ work , refer Annex ure
"A" attached with this BSR .
Each 540.0

14.21 P & F cross universal connector: For T and cross / parallel connection, to
route vertical down conductor /mesh formation made of hot dipped
galvanised iron with necessary screws etc as required. Installed with 4
hexagonal bolts M8*25 with M8 hexagonal nuts Complied as per
Standard EN 62561-1.,the test report accredited by third party
accreditation body like VDE/ILAC/ DAkkS/ UL/ NABL is to be submitted.
All as per pre approved by Engineer in charge. For additional technical
parameters of products/ work , refer Annex ure "A" attached with this
BSR . Each 648.0

14.22 P & F Universal clamp made of SS to connect rod with flat conductor
Complied as per Standard EN 62561-1.,the test report accredited by third
party accreditation body like VDE/ILAC/ DAkkS/ UL/ NABL is to be
submitted.All as per pre approved by Engineer in charge. For additional
technical parameters of products/ work , refer Annex ure "A" attached
with this BSR . Each 1256.0

14.23 P & F Lightning counter - To count no of lightning strike & it can record
the date and time of the lightning incident also tested as per IEC 62561-6.
the test report accredited by third party accreditation body like
VDE/ILAC/ DAkkS/ UL/ NABL is to be submitted.All as per pre approved by
Engineer in charge. For additional technical parameters of products/
work , refer Annex ure "A" attached with this BSR .
Each 9046.00

14.24 Providing & Fixing of ISO Certified company made lightning conductor
finial as per PWD specification for electrical Works as per IS 2309-1989
made out of 25 mm dia.,300 mm long copper solid rod having single
prong at top with 85 mm dia., 3 mm thick copper base plate including
holes etc. complete as required. All as per pre approved by Engineer in
charge. All as per pre approved by Engineer in charge. For additional
technical parameters of products/ work , refer Annex ure "A" attached
with this BSR . Each 3102.00

Chapter E - 14 Page 78
P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-14

Code No. Description Unit Complete Rate

14.25 Providing & Fixing of ISO Certified company made lightning conductor
finial as per PWD specification for electrical Works as per IS 2309-1989
made out of 25 mm dia.,300 mm long G.I. solid Rod having single prong
at top with 85 mm dia., 3 m thick G.I. base plate including holes etc.
complete as required. All as per pre approved by Engineer in charge. All
as per pre approved by Engineer in charge. For additional technical
parameters of products/ work , refer Annex ure "A" attached with this
BSR . Each 1752.00

14.26 Providing & Fixing of testing joint, made out of 20mm x 3mm copper
Strip, 125 mm long, with 4 no. tinned brass bolts, nuts, checknuts, spring
washer etc. complete as required. All as per pre approved by Engineer in
charge.All as per pre approved by Engineer in charge. For additional
technical parameters of products/ work , refer Annex ure "A" attached
with this BSR . Each 1012.00

14.27 Providing & Fixing of testing joint, made out of 20mm x 3mm G.I. Strip,
125 mm long, with 4 no.G.I. bolts, nuts, checknuts, spring washer etc.
complete as required. All as per pre approved by Engineer in charge. All
as per pre approved by Engineer in charge. For additional technical
parameters of products/ work , refer Annex ure "A" attached with this
BSR . Each 606.00

Chapter E - 14 Page 79
P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-15

Chapter E -15

Fans
Code No. Description Unit Complete Rate

15.1 Making of hole in wall (brick/stone) of required and placing NP-2 RCC
pipe ring of required size for housing exhaust fan and making good the
same, with cement plaster required of following size. All as per pre
approved by Engineer in charge. For additional technical parameters of
products/ work , refer Annexure "A" attached with this BSR .

15.1.1 Up to 457 mm size Each 348.00


15.1.2 more than 457 mm & up to 610 mm Each 488.00

15.2 Supply & Fixing of phenolic laminated board of 6.4 mm thick for fresh air
fan/exhaust fan up to size of 300 mm on existing window frame
including cost of board, cutting of hole , Nut bolts etc. as required.All as
per pre approved by Engineer in charge. For additional technical
parameters of products/ work , refer Annexure "A" attached with this
BSR . Sqm 1369.00

15.3 Installation , testing and Commissioning of ceiling fan (any size) including
wiring the down rod up to 30 cm with 3 x 1.5 sq.mm pvc insulated flexible
copper conductor making connection testing etc. as required. All as per
pre approved by Engineer in charge. For additional technical parameters
of products/ work , refer Annexure "A" attached with this BSR .

15.3.1 With regulator Each 100.00


15.3.2 Without regulator Each 87.00

15.4 Providing & Fixing of 1200 mm sweep BLDC technology power saving
ceiling fan which can withstand on votage fluctuations from 140 volts to
240 volts ,power factor not less then 0.9 , service value (CMM/W)
minimun 6.85 , air delivery minimun 220 CMM, speed minimum 330 RPM
( tolerance as per IS:374 2019 ) THD less then 10% and complete with
down rod of 15 mm dia . ERW (Electrical resistance welded ) of 1.6mm
nominal thick medium duty steel pipe up to 80 cm , cotter pin with 3 x
1.5 sq.mm pvc insulated flexible copper conductor making connection
testing etc. as required. All as per pre approved by Engineer in charge.
For additional technical parameters of products/ work , refer Annexure
"A" attached with this BSR .

15.4.1 Without Remote Each 3378.00


15.4.2 With Remote Each 3568.00

15.5 Providing & Fixing of of BLDC Technology ventilating fans , single phase
with PVC impeller, ABS body, Double Ball bearing, automatic back lower
shutter including making connection, testing etc. as required. All as per
pre approved by Engineer in charge. For additional technical parameters
of products/ work , refer Annexure "A" attached with this BSR .

15.5.1 150 mm sweep with Min. Air delivery 350 cmh, 2000 RPM Each 2417.00
15.5.2 200 mm sweep with Min. Air delivery 800 cmh, 1600 RPM Each 2538.00
15.5.3 250 mm sweep with Min. Air delivery 1150 cmh, 1300 RPM Each 2741.00

Chapter E - 15 Page 80
P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-15

Code No. Description Unit Complete Rate


15.6 Providing & Fixing of 400 mm Sweep BLDC technology Oscillating type
Wall mounting / Pedestal type fans with Three speed, ON and OFF
position, Double Wall bearing with front and back 120 or more ribs
guard; Three no. blades, noise level should be <= 75 dB, including fixing
with anchor bolts, making connection testing etc. as required. ( With
Remote ) All as per pre approved by Engineer in charge. For additional
technical parameters of products/ work , refer Annexure "A" attached
with this BSR .
15.6.1 Wall mounting type with Service value 2.0 CMM /W, Min. Air Delivery 71 Each 4699.00
CMM
15.6.2 Pedestal Type having Adjustable Height with Service value 2.6 CMM /W, Each 6023.00
Min. Air Delivery 85 CMM

15.7 Providing & Fixing of BEE Star rated copper wounded double ball
bearing capacitor start, aluminium body & Metallic blade ceiling fan
Conforming to all the performance requirements laid down in IS
374:2019 including all amendments, as applicable ; & Carry BIS licensing
(i.e. ISI marking) with down rod up to 80 cm with secondary support
safety cable ( steel rope) , cotter pin with 3 x 1.5 sq.mm pvc insulated
flexible copper conductor making connection testing etc. as required. All
as per pre approved by Engineer in charge. For additional technical
parameters of products/ work , refer Annexure "A" attached with this
BSR .
15.7.1 1200 mm Sweep BEE 1 Star rated (service value >=4.0 to < 4.5 ) Each 1890.00
15.7.2 1200 mm Sweep BEE 2 Star rated (service value >=4.5 to < 5 ) Each 2025.00
15.7.3 1200 mm Sweep BEE 3 Star rated (service value >=5.0 to< 5.5 ) Each 2190.00
15.7.4 1400 mm Sweep BEE 2 Star rated (service value >=4.5 to < 5 ) Each 2430.00
15.7.5 1400 mm Sweep BEE 3 Star rated (service value >=5.0 to< 5.5 ) Each 2565.00

15.8 Providing & Fixing of shackle (iron hook) made from 2mm nominal thick
CRCA sheet and bolts (2nos) of 6mm with spring washer nut, checknut &
split pin as required. All as per pre approved by Engineer in charge. For
additional technical parameters of products/ work , refer Annexure "A"
attached with this BSR .
Each 135.00

15.9 Providing & Fixing of of M.S. J- hook of standard design made out of 16
mm dia. M.S. round bar and fixed with cement concrete mortar with
required support as required. All as per pre approved by Engineer in
charge. For additional technical parameters of products/ work , refer
Annexure "A" attached with this BSR . Each 179.00
15.10 P & F 1.2mm thick M.S. Recessed fan box, hexagonal/ round of size 130
mm dia, depth 75mm, 12 mm dia rod fan hook with 100 mm length
extended on each side . All as per pre approved by Engineer in charge.
For additional technical parameters of product / work refer Annexure 'A'
attached with this BSR Each 128.00
15.11 Providing & Fixing of of Double ball bearing, copper wounded capacitor
start single phase metallic blade fresh air fan, in existing opening
including cost of hardware , flexible 3 core copper conductor ,making
connections, testing etc. as required. All as per pre approved by Engineer
in charge. For additional technical parameters of products/ work , refer
Annexure "A" attached with this BSR .

15.11.1 225 mm sweep Each 1687.00


15.11.2 300 mm sweep Each 1822.00

Chapter E - 15 Page 81
P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-15

Code No. Description Unit Complete Rate


15.12 Providing & Fixing of Heavy duty capacitor start, copper wound Double
ball bearing 900/1400 RPM single phase Exhaust fan conforming to
IS:2312 ISI marked in existing opening including making connections
testing etc. as required. All as per pre approved by Engineer in charge.
For additional technical parameters of products/ work , refer Annexure
"A" attached with this BSR .

15.12.1 300 mm sweep(900/1400 RPM) Each 3175.00


15.12.2 380 mm sweep(900/1400 RPM) Each 4255.00
15.12.3 450 mm sweep(900/1400 RPM) Each 5883.00
15.12.4 600 mm sweep(700 / 900 RPM) Each 10559.00

15.13 Providing & Fixing of of ventilating fans Capacitor start, copper wounded,
single phase with PVC impeller, ABS body, automatic openable louver
shutter in existing opening including making connection, testing etc. as
required. All as per pre approved by Engineer in charge. For additional
technical parameters of products/ work , refer Annexure "A" attached
with this BSR .
15.13.1 150 mm sweep Each 1579.00
15.13.2 200 mm sweep Each 1687.00
15.13.3 250 mm sweep Each 1957.00

15.14 Providing & Fixing of Wall mounting / Pedestal type Heavy duty Air
Circulator , Double ball bearing and with metal sturdy mesh guard;
Aluminium alloy one piece blade and conforming to IS:2997, including
fixing with anchor bolts, making connection testing etc. as required. All
as per pre approved by Engineer in charge. For additional technical
parameters of products/ work , refer Annexure "A" attached with this
BSR .
15.14.1 450 mm sweep Wall mounting and three speed regulator with Minimum Each 7265.00
Air Delivery 150 Cum. / Minute
15.14.2 450 mm sweep Pedestal type and three speed regulator with Minimum Each 7961.00
Air Delivery 150 Cum. / Minute
15.14.3 600 mm sweep Wall mounting with Minimum Air Delivery 270 Cum. / Each 9459.00
Minute
15.14.4 600 mm sweep Pedestal type with Minimum Air Delivery 270 Cum. / Each 9830.00
Minute
15.14.5 750 mm sweep Wall mounting with Minimum Air Delivery 400 Cum. / Each 11522.00
Minute
15.14.6 750 mm sweep Pedestal type with Minimum Air Delivery 400 Cum. / Each 11927.00
Minute

15.15 Providing & Fixing of 450 mm Sweep Oscillating type Wall mounting /
Pedestal type fans with Three speed, ON and OFF position, Sintered Iron
bush oil impregnated, with metal front and back 120 or more ribs guard;
Three no. Aluminium blades, minimum Air delivery 100 Cum. / Minute ,
Minimum Service Value 1.11 Cum./min/watt, noise level should be <= 75
dB, power consumption <= 120 watts, motor protection through thermal
overload protection device, including fixing with anchor bolts, making
connection testing etc. as required. All as per pre approved by Engineer
in charge. For additional technical parameters of products/ work , refer
Annexure "A" attached with this BSR .

15.15.1 Wall mounting type with Adjustable Vertical Angle Each 4969.00
15.15.2 Pedestal Type with Adjustable Height Each 5294.00

Chapter E - 15 Page 82
P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-15

Code No. Description Unit Complete Rate

15.16 Providing & Fixing of extra down rod of 15 mm dia . ERW (Electrical
resistance welded ) of 1.6mm nominal thick medium duty steel pipe
including cutting, threading, drilling, fixing quarter pin etc as reqd. All as
per pre approved by Engineer in charge. For additional technical
parameters of products/ work , refer Annexure "A" attached with this
BSR . Mtr. 212.00

15.17 Numbering of ceiling fans/ fixtures with approved enamel paint etc as
reqd. All as per pre approved by Engineer in charge. For additional
technical parameters of products/ work , refer Annexure "A" attached
with this BSR . Each 27.00

15.18 P & F of Gravity Louver shutter of superior quality made out of frame of
18 swg M.S. sheet & Louvers made from 24 swg MS Sheet with enamel
paint including cost of nuts, bolts, etc as reqd. All as per pre approved by
Engineer in charge. For additional technical parameters of products/
work , refer Annexure "A" attached with this BSR .

15.18.1 Up to 380 mm size Each 287.00


15.18.2 above 380 mm size Each 361.00

15.19 P & F of Wall cowl with Bird Screen Suitable for Outside Wall of Exhaust
Fan Opening of following size and made out from 24 SWG GI sheet as per
instructions of Engineer in charge including fixing with suitable fasteners
etc. as required. All as per pre approved by Engineer in charge. For
additional technical parameters of products/ work , refer Annexure "A"
attached with this BSR .
15.19.1 Suitable for 300 mm sweep Exhaust Fan Each 1090.00
15.19.2 Suitable for 380 mm sweep Exhaust Fan Each 1524.00
15.19.3 Suitable for 450 mm sweep Exhaust Fan Each 2033.00

15.20 S & F Extruded Aluminium Fresh Air / External Weather Louvre, Small
Format type with 38 mm Flange width & 50 mm depth. Finish - Powder
coated Off white with Alum. Mesh of required Size. All as per pre
approved by Engineer in charge. For additional technical parameters of
products/ work , refer Annexure "A" attached with this BSR .
Sqm 8759.00

Chapter E - 15 Page 83
P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-16

Chapter E - 16

Storage Water Heaters

Code No. Description Unit Complete


Rate
16.1 Providing & Fixing of Vertical(BEE 5 star rated) / Horizontal( BEE 3 star
rated) storage water heater with outer casing made of Engineering
Plastic sheet (Upto 25 Ltr) / Metal rust proof Body (35 & 50 Ltr), Glass -
line / Titanium Enamel coated Pressure Pump Compatible 8 bar pressure
Inner tank, Glass Line Coated , mineral filled heating element, stem type,
snap action adjustable thermostat , Dual indicating lamps Injected PUF
insulation, Multi Function Valve etc. as required held in position with
2/4 no. 10/12 mm anchor Fastener, duly wired with 3 core 2.5/4.0
Sqmm PVC insulated & sheathed copper conductor and 16 A/25A three
pin plug top with Portable Residual Current Device ( PRCD ) , including
making inlet, outlet Flexible alloy connection, testing etc. as required.
All as per pre approved by Engineer in charge. For additional technical
parameters of products/ work , refer Annexure "A" attached with this
BSR .

16.1.1 6 Ltr. Each 8511.00


16.1.2 10 Ltr. Each 9189.00
16.1.3 15 Ltr. Each 10304.00
16.1.4 25 Ltr. Each 11568.00
16.1.5 35 Ltr. Each 13970.00
16.1.6 50 Ltr. Each 16565.00

16.2 Providing & Fixing of stem type ISI marked (IS 3017 / 85) snap action
adjustable thermostat storage water heater including making
connection testing etc. complete in all respect. All as per pre approved
by Engineer in charge. For additional technical parameters of products/
work , refer Annexure "A" attached with this BSR .
Each 602.00

16.3 Providing & Fixing of stem type ISI marked (IS 3017 / 85) , snap action
bipolar adjustable thermostat with built in auto thermal cut out of
storage water heater including making connection testing etc. complete
in all respect. All as per pre approved by Engineer in charge. For
additional technical parameters of products/ work , refer Annexure "A"
attached with this BSR . Each 883.00

Chapter E - 16 Page 84
P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-16

Code No. Description Unit Complete


Rate
16.4 Providing & Fixing 2 / 3 KW nickle plated, mineral filled heating element
including making connection testing etc complete in all respect. All as
per pre approved by Engineer in charge. For additional technical
parameters of products/ work , refer Annexure "A" attached with this
BSR . Each 1043.00

16.5 Providing & Fixing of Glass Line Coated , mineral filled heating
element including making connection testing etc complete in all respect.
All as per pre approved by Engineer in charge. For additional technical
parameters of products/ work , refer Annexure "A" attached with this
BSR . Each 1805.00

16.6 Providing & Fixing of Multi safety valve of 8.5 bar capacity with built in
drain, NRV, Vacuum release, Pressure release etc. as required complete
in all respect. All as per pre approved by Engineer in charge. For
additional technical parameters of products/ work , refer Annexure "A"
attached with this BSR .l technical parameters of products/ work , refer
Annex ure "A" attached with this BSR .
Each 441.00

16.7 Providing & Fixing of Twin neon indicating lamp of superior quality for
storage water heater complete in all respect. All as per pre approved by
Engineer in charge. For additional technical parameters of products/
work , refer Annexure "A" attached with this BSR .
Each 120.00

16.8 Providing & Fixing of 13 mm Brass with C.P. finished ISI marked angle
valve for storage water heater as required complete in all respect. All as
per pre approved by Engineer in charge. For additional technical
parameters of products/ work , refer Annexure "A" attached with this
BSR . Each 433.00

16.9 Providing & Fixing of heavy duty flexible alloy pipe for storage water
heater for inlet and outlet of suitable length including the cost of nuts,
washers etc complete in all respect. All as per pre approved by Engineer
in charge. For additional technical parameters of products/ work , refer
Annexure "A" attached with this BSR .

16.9.1 450 mm Set 562.00


16.9.2 600 mm Set 642.00

Chapter E - 16 Page 85
P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-16

Code No. Description Unit Complete


Rate

16.10 Charges for descaling of storage water heater including replacement of


Multi Function Valve as required. P.Job 720.00

16.11 Charges for Fixing of storage water heater including 10/12 mm Anchor
fasteners of suitable size, testing, carrying from store to site,etc. as
required. P.Job 313.00

16.12 Providing & Fixing of 2.0 KW twin ceremic cartridge, Withstands


temperatures up to 1000 C long lasting even in hard water including
making connection testing etc complete in all respect. All as per pre
approved by Engineer in charge. For additional technical parameters of
products/ work , refer Annexure "A" attached with this BSR .
Each 1043.00

16.13 SITC of MNRE approved & confirming to IS:12933 P-1,2,3 & 5 Flat Plate
Collector type solar hot water system having collector with Zincalum
sheet outer body , Glass - line / Titanium Enamel coated Inner tank with
Metal rust proof PUF insulated Body including electrical back up,
Thermostat, Powder coated / Hot dipped galvanized MS stand for
Collector & Tank etc. as required. of following capacity complete in all
respect. All as per pre approved by Engineer in charge. For additional
technical parameters of products/ work , refer Annexure "A" attached
with this BSR .

16.13.1 100 litre/ day Set 31470.00


16.13.2 200 litre/ day Set 59122.00
16.13.3 250 litre/ day set 73393.00
16.13.4 300 litre/ day Set 90075.00
16.13.5 500 litre/ day Set 159698.00

Chapter E - 16 Page 86
P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-17

Chapter E - 17

Indoor Lighting

Complete
Code No. Description Unit
Rate
17.1 Providing & Fixing of IP20 SMD Mid Power LED batten type integrated light fixture made
from Powder coated Extruded aluminium housing with in built driver , System lumen
efficacy ≥ 110 lm/Watt output, internal surge protection of 2.5 KV with Short & Open circuit
protection ,THD < 10% , P. F.≥0.95, CRI >80 , life time of minimum 50000 Burning Hours
with , 70% of intial Lumen maintaned till life ends , CCT 3000°K / 4000°K / 5700°K
/6000°K/6500°K (As per ANSI Bin) , Maximum power consumption should not more than
the specified rating and Fixture shall be of BIS standard and trade mark certificate ( T.C.).
Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing. OEM
must have its own in house NABL lab setup for all testing facilities for LED fixtures. (LM79 &
LM80) certificate / Report from OEM shall be submitted. All as per pre approved by
Engineer in charge. For additional technical parameters of products/ work , refer
Annexure "A" attached with this BSR .
17.1.1 1170mm(+/-10%) LED batten with min. lumen output 2200 lm Each 492.0
17.1.2 570mm (+/-10%) batten with min. lumen output 1000 lm Each 405.0

17.2 Providing & Fixing of energy efficient direct fit (Retrofit) Polycarbonate/ Glass housing
SMD Mid Power LED tube rod (with integral driver & alumn. heat sink ), on existing fixture.
system lumen efficacy ≥ 100 lm/Watt output, internal surge protection of 2.5 KV ,THD <
20% ,p.f.≥0.95,CRI >80 , life time of minimum 35000 Burning Hours with , 70% of intial
Lumen maintaned till life ends , CCT 3000°K / 4000°K / 5700°K /6000°K/6500°K (As per
ANSI Bin) , maximum power consumption should not more than the specified rating and
Fixture shall be of BIS standard and trade mark certificate ( T.C.). Manufactures Word
Mark/ Name Engraved/ Embossing/ Screen printing on housing. OEM must have its own in
house NABL lab setup for all testing facilities for LED fixtures. (LM79 & LM80)certificate /
Report from OEM shall be submitted. All as per pre approved by Engineer in charge. For
additional technical parameters of products/ work , refer Annexure "A" attached with this
BSR .
17.2.1 600mm , Min. Lumens output 1800 lm LED Tube rod with Polycarbonate Housing Each 202.0
17.2.2 1200mm , Min. Lumens output 2000 lm LED Tube rod with Polycarbonate Housing Each 270.0
17.2.3 1200mm, Min. Lumens output 2000 lm LED Tube rod with Glass Housing Each 250.0

17.3 Providing & Fixing of IP-20 LED Recessed / Surface Mounted, Round / Sqaure SMD Mid
Power LED Downlight with power coated die-cast aluminum housing with UV Stabilized
non yellowish Diffuser with BIS complience 2.5 KV surge protected Isolated driver, with
Short & Open circuit protection, having efficiency > 85% . System Lumen efficacy of ≥ 110
lm / watt, THD < 10 % , Pf.≥0.95, CRI >80, life time of minimum 50000 Burning Hours with ,
70% of intial Lumen maintaned till life ends , CCT 3000°K / 4000°K/ 5700°K
/6000°K/6500°K (As per ANSI Bin) , maximum power consumption should not more than
the specified rating and Fixture shall be of BIS standard and trade mark certificate ( T.C.).
Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing.

OEM must have its own in house NABL lab setup for all testing facilities for LED fixtures.
(LM79 & LM80) certificate / Report from OEM shall be submitted. All as per pre approved
by Engineer in charge. For additional technical parameters of products/ work , refer
Annexure "A" attached with this BSR .

Chapter E - 17 Page 87
P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-17

Complete
Code No. Description Unit
Rate
17.3.1 Recessed Mounting
17.3.1.1 Minimum lumen output 330 lm Each 506.0
17.3.1.2 Minimum lumen output 650 lm Each 675.0
17.3.1.3 Minimum lumen output 1300 lm Each 1046.0
17.3.1.4 Minimum lumen output 1600 lm Each 1161.0
17.3.1.5 Minimum lumen output 1950 lm Each 1451.0
17.3.1.6 Minimum lumen output 2400 lm Each 1850.0
17.3.2 Surface Mounting (with extruded alumn. Housing )
17.3.2.1 Minimum lumen output 650 lm Each 810.0
17.3.2.2 Minimum lumen output 1300 lm Each 1181.0
17.3.2.3 Minimum lumen output 1950 lm Each 1620.0
17.3.2.4 Minimum lumen output 2400 lm Each 2059.0

17.4 Providing & Fixing of IP20, 2'x2' LED Surface/ Recessed mounting Mid power SMD type LED Light
fixture not less than 50mm housing depth made from CRCA sheet steel housing, high purity /
transmisivity UV stabilized Non -yellowish diffuser for uniform light distribution. High efficiency with
4 KV internal/external surge protection BIS certified isolated driver having efficiency > 85% , with
Short & Open circuit protection (Integral with light fixture). System lumen efficacy of ≥ 120 lm/Watt
,THD < 10 % , p.f.≥0.95,CRI >80 , life time of minimum 50000 Burning Hours with , 70% of intial
Lumen maintaned till life ends , CCT 3000°K / 4000°K / 5700°K /6000°K/6500°K (As per ANSI Bin) ,
maximum power consumption should not more than the specified rating and Fixture shall be of BIS
standard and trade mark certificate ( T.C.). Manufactures Word Mark/ Name Engraved/ Embossing/
Screen printing on housing.

OEM must have its own in house NABL lab setup for all testing facilities for LED fixtures. (LM79 &
LM80) certificate / Report from OEM shall be submitted. All as per pre approved by Engineer in
charge. All as per pre approved by Engineer in charge. For additional technical parameters of
products/ work , refer Annexure "A" attached with this BSR .

17.4.1 Recessed Mounting


17.4.1.1 Minimum lumen output 3000 lm Each 2288.0
17.4.1.2 Minimum lumen output 3600 lm Each 2558.0
17.4.1.3 Minimum lumen output 4200 lm Each 2984.0
17.4.2 Surface Moutning
17.4.2.1 Minimum lumen output 3000 lm Each 2491.0
17.4.2.2 Minimum lumen output 3600 lm Each 2862.0
17.4.2.3 Minimum lumen output 4200 lm Each 3308.0

Chapter E - 17 Page 88
P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-17

Complete
Code No. Description Unit
Rate

17.5 Providing & Fixing of IP20, 1100-1200 mm x 50-60 mm x 70-85 mm size Suspended mounting Mid
power SMD type LED linear Light fixture made from Extruded Aluminium housing, PMMI diffuser for
uniform light distribution. High efficiency with 4 KV internal/external surge protection BIS certified
isolated driver having efficiency > 85% , with Short & Open circuit protection (Integral with light
fixture). System lumen efficacy of ≥ 100 lm/Watt ,THD < 10 % , p.f.≥0.95,CRI >80 , life time of
minimum 50000 Burning Hours with , 70% of intial Lumen maintaned till life ends , CCT 3000°K /
4000°K / 5700°K /6000°K/6500°K (As per ANSI Bin) , maximum power consumption should not more
than the specified rating and Fixture shall be of BIS standard and trade mark certificate ( T.C.).
Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing.

OEM must have its own in house NABL lab setup for all testing facilities for LED fixtures. (LM79 &
LM80) certificate / Report from OEM shall be submitted. All as per pre approved by Engineer in
charge. For additional technical parameters of products/ work , refer Annexure "A" attached with
this BSR .

17.5.1 Minimum lumen output 2000 lm Each 4466.0


17.5.2 Minimum lumen output 3000 lm Each 5422.0

17.6 Providing & Fixing of IP65 IK08 rated Integrated SMD Mid power LED bulk head type light
fixture made from Pressure Die Cast AL housing suitable with integral driver, system lumen
efficacy ≥100 lm/Watt output , THD < 10% ,p.f.≥0.95,CRI >80 , life time of minimum 50000
Burning Hours with , 70% of intial Lumen maintaned till life ends , CCT 3000°K / 4000°K /
5700°K /6000°K/6500°K (As per ANSI Bin) , maximum power consumption should not more
than the specified rating and Fixture shall be of BIS standard and trade mark certificate (
T.C.). Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing.
surge protection 4 KV. OEM must have its own in house NABL lab setup for all testing
facilities for LED fixtures. (LM79 & LM80) certificate / Report from OEM shall be submitted.
All as per pre approved by Engineer in charge. For additional technical parameters of
products/ work , refer Annexure "A" attached with this BSR .

17.6.1 Minimum lumen output 1000 lm Each 1647.0

17.7 Providing & Fixing of IP65 IK08 rated Integrated High power LED ( each LED between 3 to 5 watt
power with secondary lencs on each LED) Highbay light fixture made from Pressure Die Cast
Aluminium housing, toughned glass diffuser, potted driver, Eye bolt for mounting, system lumen
efficacy ≥140 lm/Watt output , THD < 10% ,p.f.≥0.95,CRI >80 , life time of minimum 50000 Burning
Hours with , 70% of intial Lumen maintaned till life ends , CCT 3000°K / 4000°K / 5700°K
/6000°K/6500°K (As per ANSI Bin) , maximum power consumption should not more than the
specified rating and Fixture shall be of BIS standard and trade mark certificate ( T.C.). Manufactures
Word Mark/ Name Engraved/ Embossing/ Screen printing on housing. surge protection 4 KV inbuilt
& 10 KV external inside fixture.

OEM must have its own in house NABL lab setup for all testing facilities for LED fixtures. (LM79 &
LM80) certificate / Report from OEM shall be submitted. All as per pre approved by Engineer in
charge. For additional technical parameters of products/ work , refer Annexure "A" attached with
this BSR .
17.7.1 Minimum lumen output 10000 lm Each 6683.0
17.7.2 Minimum lumen output 14000 lm Each 7764.0
17.7.3 Minimum lumen output 16500 lm Each 9790.0

Chapter E - 17 Page 89
P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-17

Complete
Code No. Description Unit
Rate

17.8 Providing & Fixing of Suspended mounting IP66 IK08 rated Integrated High power LED
Wellglass light fixture made from Pressure Die Cast Aluminium housing, potted driver, Eye
bolt for mounting, PC clear / Opal Diffuser, system lumen efficacy ≥120 lm/Watt output ,
THD < 10% ,p.f.≥0.95,CRI >70 , life time of minimum 50000 Burning Hours with , 70% of
intial Lumen maintaned till life ends , CCT 3000°K / 4000°K / 5700°K /6000°K/6500°K (As
per ANSI Bin) , maximum power consumption should not more than the specified rating and
Fixture shall be of BIS standard and trade mark certificate ( T.C.). Manufactures Word
Mark/ Name Engraved/ Embossing/ Screen printing on housing. surge protection 4 KV .
OEM must have its own in house NABL lab setup for all testing facilities for LED fixtures.
(LM79 & LM80)certificate / Report from OEM shall be submitted. All as per pre approved
by Engineer in charge. For additional technical parameters of products/ work , refer
Annexure "A" attached with this BSR .
17.8.1 Minimum lumen output 3500 lm Each 2429.0
17.8.2 Minimum lumen output 4800 lm Each 3239.0

17.9 Providing & Fixing of energy efficient /energy saving IP 20 LED direct retrofit Bulb in
existing holder or fixture as required with system lumen efficacy ≥100 lm/Watt output ,pf
0.95 , CRI >70, minimum life time of minimum 25000 Burning Hours with , 70% of intial
Lumen maintaned till life ends , CCT 3000°K / 4000°K / 5700°K /6000°K/6500°K (As per
ANSI Bin) , maximum power consumption should not more than the specified rating and
Fixture shall be of BIS standard and trade mark certificate ( T.C.). Manufactures Word
Mark/ Name Engraved/ Embossing/ Screen printing on housing. OEM must have its own in
house NABL lab setup for all testing facilities for LED fixtures. (LM79/LM80) certificate /
Report from OEM shall be submitted. All as per pre approved by engineer in charge . for
additional technical parameters of product/ work, refer Annexure "A" attacheded with this
BSR.
17.9.1 2/3 Watt Each 81.0
17.9.2 6/7 Watt Each 94.0
17.9.3 9 Watt Each 115.0
17.9.4 15 Watt Each 135.0
17.9.5 18/20 Watt Each 162.0

17.10 Providing & Fixing of IP20 SMD Mid Power LED batten with integrated box
(min.1200mmx40mmx60mm including reflector) with replacable driver fixture made from Powder
coated Extruded aluminium housing ,Min. lumen output 4400 lm, System lumen efficacy ≥ 110
lm/Watt output, internal surge protection of 4.0 KV with Short & Open circuit protection,THD < 10%
, P. F.≥0.95, CRI >80 , life time of minimum 50000 Burning Hours with , 70% of intial Lumen
maintaned till life ends , CCT 3000°K / 4000°K / 5700°K /6000°K/6500°K (As per ANSI Bin) , Maximum
power consumption should not more than the specified rating and Fixture shall be of BIS standard
and trade mark certificate ( T.C.). Manufactures Word Mark/ Name Engraved/ Embossing/ Screen
printing on housing.

OEM must have its own in house NABL lab setup for all testing facilities for LED fixtures. (LM79 &
LM80) certificate / Report from OEM shall be submitted. All as per pre approved by Engineer in
charge. For additional technical parameters of products/ work , refer Annexure "A" attached with
this BSR .
Each 1620.0

Chapter E - 17 Page 90
P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-17

Complete
Code No. Description Unit
Rate

17.11 Providing & Fixing of IP 20 box made out from 1.2mm thick CRCA sheet steel with depth of
minimun 30 mm and finished with powder coating and suitable for mounting LED tube
including side covers, holders , internal wiring to illuminate the single sided connection LED
tube. ( Without tube). All as per pre approved by Engineer in charge. For additional
technical parameters of products/ work , refer Annexure "A" attached with this BSR .

17.11.1 Suitable for 2' LED Tube shape fixture for single rod Each 151.00
17.11.2 Suitable for 4' LED Tube shape fixture for single rod Each 227.00
17.11.3 Suitable for 4' LED Tube shape fixture for double rod Each 358.00

Chapter E - 17 Page 91
P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-18

Chapter E - 18

Outdoor Lighting

Code No. Description Unit Complete Rate

18.1 Supply and erection of Galvanized Iron pole with galvanizing done in single dipping (Average coating
thickness Minimum 65 Microns) continuously tapered poles having Octagonal / Circular cross-sections
designed to withstand the maximum wind speed as per IS 875, The pole shaft shall be made from sheet
steel (HT Steel Conforming to grade S355JO) and confirming to BSEN 10025 and shall be continuously
tapered with single longitudinal welding. There shall not be any circumferential welding. The welding of
pole shaft shall be done by Submerged Arc Welding (SAW) process. pole shafts shall be provided with the
rigid flange plate of suitable thickness (Fe 410 conforming to IS 226 / IS 2062) with provision for fixing 4
no. foundation bolts, This base plate shall be fillet welded to the pole shaft at two locations i.e. from
inside and outside.The octagonal Poles shall have lockable door of approximate 500 mm length at the
elevation of 500 mm from the Base plate with bakelite sheet having 6A SP MCB and 16 sqmm stud type
connector ( 4 nos) inside the pole at door opening for cable connection of following length and dimension
as per table P-01 with base plate and foundation bolt on the Existing cement concrete foundation.All as
per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer
Annexure "A" attached with this BSR .

18.1.1 Poles with Octagonal Cross Section


18.1.1.1 3 Mtr. Each 6361.0
18.1.1.2 4 Mtr. Each 7806.0
18.1.1.3 5 Mtr. Each 9588.0
18.1.1.4 6 Mtr. Each 11164.0
18.1.1.5 7 Mtr. Each 13152.0
18.1.1.6 8 Mtr. Each 15141.0
18.1.1.7 9 Mtr. Each 18981.0
18.1.1.8 10 Mtr. Each 22823.0
18.1.1.9 11 Mtr. Each 30725.0
18.1.1.10 12 Mtr. Each 35453.0

18.2 Supply and Fixing of Pole OEM fabricated hot dipped galvanised M.S. Overhang (48.3 X 3.25 mm) with
cap (400 x 88.9 / 114.3 x 3.25 mm) over the existing poles. All as per pre approved by Engineer in charge.
For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .

18.2.1 Single arm overhang Mtr. 1889.0


18.2.2 Double arm overhang Mtr. 3314.0

18.3 Supply and erection of Galvanized Iron pole with galvanizing done in single dipping (Average coating
thickness Minimum 65 Microns) Swaged tubular pole conforming to IS: 2713-1980 (part I to II) with
galvanised base plate, The pole shall be made from steel tube & Pipe (IS:1141, Fe 410) including
excavation of the pit and filling the same with C.C. of M-20 grade (1:1.5:3) from base plate to 50 cm
above ground level, with the help of steel frame not less than 40 cm dia up to 114.3mm outer dia and 50
cm beyond 114.3mm outer dia around the pole. Duly finished with cement plaster, earthing terminals,
cable entry with 32 mm dia. 'B' class GI cable sleeves complete as required. of following height &
designation. ( See Table P - 02 for specs. ) All as per pre approved by Engineer in charge. For additional
technical parameters of products/ work , refer Annexure "A" attached with this BSR .
18.3.1 7.5 Mtr. ( 410 SP - 5 ) Each 15419.0
18.3.2 8.5 Mtr. ( 410 SP - 17 ) Each 17098.0
18.3.3 9.0 Mtr. ( 410 SP - 28 ) Each 20938.0
18.3.4 10 Mtr. ( 410 SP - 42 ) Each 26675.0
18.3.5 11 Mtr. ( 410 SP - 51 ) Each 29898.0
18.3.6 12 Mtr. ( 410 SP - 60 ) Each 36827.0

18.4 Add for supply and fixing of Pole OEM fabricated Galvanized Overhang of following size over the existing
poles. All as per pre approved by Engineer in charge. For additional technical parameters of products/
work , refer Annexure "A" attached with this BSR .
18.4.1 76.1 mm OD x 3.25 mm thickness Mtr. 1748.0
18.4.2 88.9 mm OD x 3.25 mm thickness Mtr. 2275.0
18.4.3 114.3 mm OD x 3.65 mm thickness Mtr. 3167.0

Chapter E - 18 Page 92
P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-18

Code No. Description Unit Complete Rate

18.5 Supply and erection of Mild steel Swaged tubular pole conforming to IS: 2713-1980 (part I to II) with
base plate, The pole shall be made from steel tube & Pipe (IS:1141, Fe 410) including excavation of the pit
and filling the same with C.C. of M-20 grade (1:1.5:3) from base plate to 50 cm above ground level, with
the help of steel frame not less than 40 cm dia up to 114.3mm outer dia and 50 cm beyond 114.3mm
outer dia around the pole. Duly finished with cement plaster, earthing terminals, cable entry with 32 mm
dia. 'B' class GI cable sleeves. After eraction pole shall be painted with two coat of red oxide primer and
two quote of enamel paint of silver colour as per the direction of Engineer incharge complete as required
of following height & designation. ( See Table P - 02 for specs. ) All as per pre approved by Engineer in
charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this
BSR .
18.5.1 7.5 Mtr. ( 410 SP - 5 ) Each 13102.0
18.5.2 8.5 Mtr. ( 410 SP - 17 ) Each 14499.0
18.5.3 9.0 Mtr. ( 410 SP - 28 ) Each 17666.0
18.5.4 10 Mtr. ( 410 SP - 42 ) Each 22384.0
18.5.5 11 Mtr. ( 410 SP - 51 ) Each 25045.0
18.5.6 12 Mtr. ( 410 SP - 60 ) Each 30739.0

18.6 Add for supply and fixing of Pole OEM fabricated Mild steel Overhang of following size over the existing
poles, Overhang shall be painted with two coat of red oxide primer and two quote of enamel paint of
silver colour as per the direction of Engineer incharge. All as per pre approved by Engineer in charge. For
additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .

18.6.1 76.1 mm OD x 3.25 mm thickness Mtr. 1490.0


18.6.2 88.9 mm OD x 3.25 mm thickness Mtr. 2014.0
18.6.3 114.3 mm OD x 3.65 mm thickness Mtr. 2813.0

18.7 Supply installation testing & Commissioning of high mast lighting system (as per PLG 07 of ILP UK
techinical report no 7 of ILE UK /IS:875 Part-1 – 2015//BSEN10025/and IS:2062 )consisting of totally hot
dip galvanised by piecewise single dipped method high mast, lantern carriage suitable for up to 12 nos
luminaries with welded arm (excluding luminares), mast head frame assembly with full cover, including 1
No. LED 15 Watts aviation obstruction lights, double drum type self sustaining winch, integral power tool
accesible from door with padlocking arrangement (winch motor with control circuit) hot dipped
galvanised heavy duty pipe lightening finial, Stainless steel 6 mm dia. wire ropes (AISI 316, 7 / 19
costruction 3 no. rope for lantern carrage & 2 no. rope for winch assembly ) foundation bolt, torque
limiter,EPR insulated PCP sheathed 5 core x 2.5 Sq.mm trailing cable, including outdoor type control
panel for auto on / off, reverse / forward motor operation. The mast is constructed from mild steel plates
(as per IS 5986 Gr. 510 ) cut and folded to form a polygonal section, telescopic jointed and welding as per
BS 5135.etc. as required on Existing Foundation. ( See table P - 03 for specs.) OEM Must have Type test
certificate for wind tunnel test . All as per pre approved by Engineer in charge. All as per pre approved by
Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A"
attached with this BSR .
12.5 Mtr HM (in 2 section) suitable for 6 No. Luminaries 2 no. rope for lantern carrage & 2 no. rope for
18.7.1 Each 225679.0
winch assembly
18.7.2 16.0 Mtr HM (in 2 section) suitable for 9 No. Luminaries Each 287292.0
18.7.3 20.0 Mtr Hm (in 2 section) suitable for 12 No. Luminaries Each 330476.0
18.7.4 25.0 Mtr HM (in 3 section) suitable for 12 No. Luminaries Each 483603.0
18.7.5 30.0 Mtr HM (in 3 section) suitable for 12 No. Luminaries Each 555287.0

18.8 Providing and Laying RCC Foundation for Octagonal / Conical Street Light poles, High mast Poles as per
Drawing attach at Table P-4 with Following Procedure & All as per pre approved by Engineer in charge.
For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .

A) Excavation of Pit for Foundation Size upto required depth from Ground level
B) Dressing of Pit and Dry stone pitching 200 mm thick including supply of stones and preparing surface
complete.
C) Providing and laying in position cement concrete of M-10 grade of 75 mm thickness
D) Reinforcement for R.C.C. work with TMT bars including straightening, cutting, bending, placing in
position and binding all complete.
E) Centring and shuttering including strutting , propping etc. and removal of form work for Footing and
Pedestal
F) Providing & Fixing of 2 no. Required Size PLB HDPE Pipe & Foundation Bolt with template as per OEM
Recommendations.
G) Providing and Laying Reinforce cement Concrete of M-25 grade in Footing and Pedestal including
Curing the foundation for 7 days.
H) Providing and Fixing Nosing Angle 40 mm x 40 mm x 6mm with 2 no. 100 mm long, 10 mm dia. Lugs on
each face.
18.8.1 Pole Foundation for Octagonal pole from 3 Mtr. To 6 Mtr. 5827.0
18.8.2 Pole Foundation for Octagonal pole from 7 Mtr. To 9 Mtr. 7943.0
18.8.3 Pole Foundation for Octagonal pole from 10 Mtr. To 12 Mtr. 11921.0

Chapter E - 18 Page 93
P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-18

Code No. Description Unit Complete Rate

18.9 Providing & Fixing of IP-65 Protected LED aviation obstruction light luminaire comprising of die cast
aluminium alloy housingwith Polycarbonate enclosure having more than 200 No's Low Power LED's
having minimum power consumption 15 watts complete in all respect. All as per pre approved by
Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A"
attached with this BSR .
18.9.1 aviation obstruction LED light luminaire Min. 15 Watts Each 5494.0

18.10 Providing & Fixing of IK08 IP65 protected Top/Bottom mounted LED Post top Luminarie made of single
piece construction powder coated die cast alluminium housing with UV stabalized Clear / frosted
Polycarbonate diffuser and Aluminium anodised with sand blast reflector. The System level Luminous
efficacy ≥ 100 Lumen/W. SMD LEDs is to be used, System CRI>70, CCT: 3000/4000/6500 K. The integral
electronic driver must be potted & has a unique BIS R number must be potted & has a unique BIS R
number constant current and Internal/external surge protection device of min. 4KV(L-N) and efficiency >
85%, PF>0.9, THD<10% and input Voltage range of 140-270V AC at 50Hz. System life of 50000 Burning
hours with 70% of Initial Lumens maintained . Driver current <750mA. Fixture must be in compliance
with BIS Standards and Trade mark Certificate complete in all respect.OEM Must have its own in house
NABL lab setup for all testing facilities for LED fixtures. (LM79/LM80) Certificate/ report with liable
warranty of product/accessories from OEM shall be submitted. All as per pre approved by Engineer in
charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this
BSR .
18.10.1 Minimum lumen output 2500 lm Post top Luminarie Each 5075.0
18.10.2 Minimum lumen output 3000 lm Post top Luminarie Each 5703.0
18.10.3 Minimum lumen output 4000 lm Post top Luminarie Each 6575.0
18.10.4 Minimum lumen output 4500 lm Post top Luminarie Each 8195.0

18.11 Providing & Fixing of IK08 IP-66 protected high power LED flood light system with single piece Pressure
diecast aluminium housing, toughened glass diffuser with suitable lenses on LED to achieve various beam
angles, of high power LED of 3 to 5 watt each . Integrated potted driver as a unique BIS R number having
efficiency more than 85 % and in compliance to BIS certified and Trade mark certificate. The System level
Luminaire efficacy >=125 lm/ wt. LED driver Input Voltage AC 120 to 270 V AC with High voltage Cutoff
@>=300 V AC and Auto resetting Safety .Power Factor >0.95 , THD(I) <10% , driver current <=750mA.
driver should be Phase to phase protection of 440 V for 4 Hrs. Electrical Connector , Surge Protection Min
>=4KV internal and 10KV external but inside driver compartment, System life of 50000 Burning hours
with 70% of Initial Lumens maintained, CRI>70 and CCT 5700K ±355K. Manufactures Word Mark/Name
Engraved/Embossing/Screen printing on die cast housing to allow traceability/authenticity. Fixture shall
be IS 10322 Complianced.OEM Must have its own in house NABL lab setup for all testing facilities for LED
fixtures. (LM79/LM80) Certificate/ report with liable warranty of product/accessories from OEM shall
be submitted. All as per pre approved by Engineer in charge. For additional technical parameters of
products/ work , refer Annexure "A" attached with this BSR .
18.11.1 High Power LED Flood Light Minimum lumen output 3700 lm Each 2659.00
18.11.2 High Power LED Flood Light Minimum lumen output 6200 lm Each 3213.00
18.11.3 High Power LED Flood Light Minimum lumen output 8700 lm Each 3739.00
18.11.4 High Power LED Flood Light Minimum lumen output 10000 lm Each 4820.00
18.11.5 High Power LED Flood Light Minimum lumen output 12400 lm Each 5900.00
18.11.6 High Power LED Flood Light Minimum lumen output 14800 lm Each 8872.00
18.11.7 High Power LED Flood Light Minimum lumen output 18650 lm Each 10857.00
18.11.8 High Power LED Flood Light Minimum lumen output 22400 lm Each 13300.00
18.11.9 High Power LED Flood Light Minimum lumen output 25000 lm Each 15583.00
18.11.10 High Power LED Flood Light Minimum lumen output 30000 lm Each 18797.00
18.11.11 High Power LED Flood Light Minimum lumen output 37500 lm Each 21457.00
18.11.12 High Power LED Flood Light Minimum lumen output 43750 lm Each 27237.00

18.12 Providing & Fixing of IK08, IP 66 protected LED Street Light Luminaire on existing bracket/pole. Fixture
made of powder coated single piece pressure die cast aluminum material with heat dissipation fins on
housing with UV stabilized PC (UV stablization report submitted for UV cover ) /Toughened Glass cover
and secondary lens on each LED & should be SMD type of 3 to 5 watt each . The System efficacy >=125
lm/ wt and potted driver & has a unique BIS R number with Input Voltage AC 120 to 270 V AC with High
voltage Cutoff @>=300 V AC and Auto resetting Safety , Power Factor >0.95 driver Efficiency >85%
,THD(I) <10% Humidity 10% to 90% RH Working Temp -5C to 45C . driver current <750mA. The luminaire
shall be BIS certified and Trade mark certified. Life Expectancy Equal or more than 50000 burning hrs
with Minimum 70% lumen maintened , CRI >70 and CCT 5700K +355K. Surge protection shall be min ≥ 4
KV internal and min 10 KV external inside driver compartment. driver should be Phase to phase
protection of 440 V for 4 Hrs. Manufactures Word Mark/Name Engraved/Embossing on die cast housing
to allow traceability/authenticity. Fixture shall be AS PER IS 10322 Complianced.OEM Must have its own
in house NABL lab setup for all testing facilities for LED fixtures. (LM79/LM80) Certificate/ report with
liable warranty of product/accessories from OEM shall be submitted. All as per pre approved by Engineer
in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with
this BSR .
18.12.1 LED Street Light fixture with Minimum lumen output 2450 lm Each 2554.0

Chapter E - 18 Page 94
P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-18

Code No. Description Unit Complete Rate

18.12.2 LED Street Light fixture with Minimum lumen output 3700 lm Each 3370.0
18.12.3 LED Street Light fixture with Minimum lumen output 5600 lm Each 4145.0
18.12.4 LED Street Light fixture with Minimum lumen output 7500 lm Each 4942.0
18.12.5 LED Street Light fixture with Minimum lumen output 8700 lm Each 5847.0
18.12.6 LED Street Light fixture with Minimum lumen output 11225 lm Each 6765.0
18.12.7 LED Street Light fixture with Minimum lumen output 12500 lm Each 7670.0
18.12.8 LED Street Light fixture with Minimum lumen output 15000 lm Each 8723.0
18.12.9 LED Street Light fixture with Minimum lumen output 17500 lm Each 10532.0
18.12.10 LED Street Light fixture with Minimum lumen output 18750 lm Each 11464.0
18.12.11 LED Street Light fixture with Minimum lumen output 22500 lm Each 12963.0
18.12.12 LED Street Light fixture with Minimum lumen output 25000 lm Each 14529.0

18.13 Providing & Fixing of IK10 IP65 protected 600 mm height LED Bollard Luminarie with base plate made of
powder coated die cast alluminium housing with UV stabalized PC diffuser. The System level Luminous
efficacy ≥ 90 Lumen/W. SMD LEDs is to be used, System CRI>70, CCT: 3000/4000/6500 K. The integral
electronic driver must be potted & has a unique BIS R number must be potted & has a unique BIS R
number constant current and Internal/external surge protection device of min. 4KV(L-N) and efficiency >
85%, PF>0.9, THD<20% and input Voltage range of 90-270V AC at 50Hz. System life of 30000 Burning
hours with 70% of Initial Lumens maintained Light output in Cool white or Warm White Colour as per
engineers choice. driver current <750mA. Fixture must be in compliance with BIS Standards and Trade
mark Certificate complete in all respect.OEM Must have its own in house NABL lab setup for all testing
facilities for LED fixtures. (LM79/LM80) Certificate/ report with liable warranty of product/accessories
from OEM shall be submitted. All as per pre approved by Engineer in charge. For additional technical
parameters of products/ work , refer Annexure "A" attached with this BSR .
18.13.1 Minimum lumen output 800 lm Bollard Each 9546.0
18.13.2 Minimum lumen output 980 lm Bollard Each 11241.0

18.14 Providing & Fixing of IK10 IP66 / IP67 protected Rectangular shape LED Step Luminarie made of powder
coated die cast alluminium housing with UV stabalized PC diffuser. The System level Luminous efficacy ≥
90 Lumen/W. SMD LEDs is to be used, System CRI>70, CCT: 3000/4000/6500 K. The integral electronic
driver must be potted & has a unique BIS R number constant current and Internal/external surge
protection device of min. 4KV(L-N) and efficiency > 85%, PF>0.9, THD<10% and input Voltage range of
140-270V AC at 50Hz. System life of 50000 Burning hours with 70% of Initial Lumens maintained . driver
current <750mA . Fixture must be in compliance with BIS Standards and Trade mak Certificate complete
in all respect.OEM Must have its own in house NABL lab setup for all testing facilities for LED fixtures.
(LM79/LM80) Certificate/ report with liable warranty of product/accessories from OEM shall be
submitted. All as per pre approved by Engineer in charge. For additional technical parameters of
products/ work , refer Annexure "A" attached with this BSR .
18.14.1 Minimum lumen output 450 lm Step light Each 3698.0
18.14.2 Minimum lumen output 630 lm Step light Each 4508.0
18.14.3 Minimum lumen output 800 lm Step light Each 4886.0

18.15 Providing & Fixing of IK10 IP65 / IP66 protected LED Up - Down Luminarie Wall / Surface mounting made
of powder coated die cast alluminium housing with UV stabalized PC diffuser. The System level Luminous
efficacy ≥ 90 Lumen/W. COB LEDs is to be used, System CRI>70, CCT: 3000/4000/6500 K. The integral
electronic driver must be potted & has a unique BIS R number constant current and Internal/external
surge protection device of min. 4KV(L-N) and efficiency > 85%, PF>0.9, THD<10% and input Voltage
range of 140-270V AC at 50Hz. System life of 50000 Burning hours with 70% of Initial Lumens maintained
Light output in Cool white or Warm White Colour as per engineers choice. driver current <750mA.
Fixture must be in compliance with BIS Standards and Trade mark Certificate complete in all respect.OEM
Must have its own in house NABL lab setup for all testing facilities for LED fixtures. (LM79/LM80)
Certificate/ report with liable warranty of product/accessories from OEM shall be submitted. All as per
pre approved by Engineer in charge. For additional technical parameters of products/ work , refer
Annexure "A" attached with this BSR .
18.15.1 Minimum lumen output 800 lm Up-Down Luminary Each 6426.0
18.15.2 Minimum lumen output 1300 lm Up-Down Luminary Each 8074.0
18.15.3 Minimum lumen output 2150 lm Up-Down Luminary Each 9519.0

18.16 Providing and fixing of fuse box size 250(H) x 200(W) x 150(D) mm fabricated of 1.6mm MS sheet with
hinged cover, dust and vermin proof, rubber gasket, locking arrangement, duly holded with 2 nos pole
clamps of 20 mm x 3 mm flat with nut and bolts, complete with anticorrosive treatment, finished with
two coat of approved enamel paint. The box shall be provided with 2 / 4 nos copper bus bar 125 x 20 x 3
mm with brass screws suitable supports,earth terminal, inter connection, knock outs for 20 / 25 mm
cable gland, 1 no. 6 Amp MCB complete in all respect. All as per pre approved by Engineer in charge. For
additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .
Each 2274.0

Chapter E - 18 Page 95
P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-18

Code No. Description Unit Complete Rate

18.17 Providing and fixing of IP 65 protected Polycarbonate / Polysterene fuse box moulded with inside knock
outs of following size with hinged cover, transparent window, PU gasket, locking arrangement, duly
holded with 2 nos. pole clamps of 20 mm x 3 mm flat with nut and bolts, The box shall be provided with
Din rail, 4 / 8 way 10.0 / 16.0 sq.mm heavy duty connector, earth terminal, complete in all respect. All as
per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer
Annexure "A" attached with this BSR .
18.17.1 125 mm X 200 mm X 122 mm Each 1827.0
18.17.2 160 mm X 225 mm X 100 mm Each 2185.0
18.17.3 200 mm X 200 mm X 122 mm Each 2854.0
18.17.4 225 mm X 225 mm X 100 mm Each 3550.0

18.18 Providing & Fixing of Street light bracket made out from following size of ' B ' class , Medium class G.I.
Pipe confirming to IS : 1239 P - 1 ( 2004 ) with heavy duty pole clamp, Saddles suitable fastners etc. as
required. All as per pre approved by Engineer in charge. For additional technical parameters of products/
work , refer Annexure "A" attached with this BSR .
18.18.1 20 mm Dia. Mtr. 405.0
18.18.2 25 mm Dia. Mtr. 540.0
18.18.3 32 mm Dia. Mtr. 742.0
18.18.4 40 mm Dia. Mtr. 958.0

18.19 Providing & Fixing of IP - 65 protected impact resistant polycarbonate / Polysterene enclosures with
knock out for cable entry/out including fixing with nut, bolt, fatner etc as required complete in all respect
of following sizes.All as per pre approved by Engineer in charge. For additional technical parameters of
products/ work , refer Annexure "A" attached with this BSR .

18.19.1 180 x 180 x 91 mm Each 1498.0


18.19.2 250 x 200 x 115 mm Each 2174.0
18.19.3 300 x 450 x 132 mm Each 3450.0
18.19.4 320 x 440 x 179 mm Each 4982.0
18.19.5 320 x 640 x 179 mm Each 6616.0
18.20 Supply and erection of PU coated , 6 to 7 mm thick Glass / Fibre Reinforced Pole (GRP /FRP) made by
CNC filament winding machine using thermoset resin polyester/epoxy resin system) having minimum
62% glass content. designed to withstand the maximum wind speed as per IS 875, and Tested for
deflection not more than 15% length of pole as per ASTM D 4923, The pole should be in one piece and
tapered round in shape, pole shafts shall be provided with FRP Anchor with suitable MS cated Base with
provision for fixing 4 no. foundation bolts( Including cost of Foundation Bolt), The Pole shall have
lockable door of approximate 500 mm length at the elevation of 500 mm from the Base plate with
bakelite sheet having 6A SP MCB and 16 sqmm stud type connector ( 4 nos) inside the pole at door
opening for cable connection of following length and dimension on Existing cement concrete foundation.
All as per pre approved by Engineer in charge. For additional technical parameters of products/ work ,
refer Annexure "A" attached with this BSR .
18.20.1 3 Mtr. Long, Top/ Bottom OD Dia 89/126mm ± 2mm approx. With Base 250X250 X 10mm Each 16910.00
18.20.2 4 Mtr. Long, Top/ Bottom OD Dia 89/131mm ± 2mm approx. With Base 250X250 X 10mm Each 20672.00
18.20.3 5 Mtr. Long, Top/ Bottom OD Dia 89/141mm ± 2mm approx. With Base 250X250 X 10mm Each 22091.00
18.20.4 6 Mtr. Long, Top/ Bottom OD Dia 89/152mm ± 2mm approx. With Base 250X250 X 10mm Each 23796.00
18.20.5 7 Mtr. Long, Top/ Bottom OD Dia 89/157mm ± 2mm approx. With Base 300X300 X 12mm Each 29036.00
18.20.6 8 Mtr. Long, Top/ Bottom OD Dia 89/157mm ± 2mm approx. With Base 300X300 X 12mm Each 31280.00
18.20.7 9 Mtr. Long, Top/ Bottom OD Dia 89/183mm ± 2mm approx. With Base 300X300 X 12mm Each 33160.00
18.20.8 10 Mtr. Long, Top/ Bottom OD Dia 89/207mm ± 2mm approx. With Base 350X350 X 15mm Each 42052.00
18.20.9 11 Mtr. Long, Top/ Bottom OD Dia 89/217mm ± 2mm approx. With Base 350X350 X 15mm Each 44246.00
18.20.10 12 Mtr. Long, Top/ Bottom OD Dia 89/226mm ± 2mm approx. With Base 400X400 X 20mm Each 53300.00

18.21 Supply, Erection and Fixing of GRP Overhang with cap over the existing poles. All as per pre approved by
Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A"
attached with this BSR .
18.21.1 Single arm overhang Mtr. 4318.00
18.21.2 Double arm overhang Mtr. 6168.00

Chapter E - 18 Page 96
Table P- 01
GI octagonal pole Standard Dimensions
Pole Height (Mtrs.) 3 Mtrs. 4 Mtrs. 5 Mtrs. 6 Mtrs. 7 Mtrs. 8 Mtrs. 9 Mtrs. 10 Mtrs. 11 Mtrs. 12 Mtrs.

Material of Construction BS EN 10025 BS EN 10025 BS EN 10025 BS EN 10025 BS EN 10025 BS EN 10025 BS EN 10025 BS EN 10025 BS EN 10025 BS EN 10025
Metal Protection
Galvanized Galvanized Galvanized Galvanized Galvanized Galvanized Galvanized Galvanized Galvanized Galvanized
Treatment
Avg. Thickness of
65 Microns 65 Microns 65 Microns 65 Microns 65 Microns 65 Microns 65 Microns 65 Microns 65 Microns 65 Microns
Galvanization

Thickness of Sheet 3 mm 3 mm 3 mm 3 mm 3 mm 3 mm 3 mm 3 mm 3 mm 3 mm

Thickness of Base Plate 12 mm 12 mm 12 mm 12 mm 16 mm 16 mm 20 mm 20 mm 20 mm 25 mm

Bottom Diameter 130 mm 130 mm 130 mm 135 mm 135 mm 135 mm 155 mm 200 mm 200 mm 240 mm

Top Diameter 65 mm 65 mm 70 mm 70 mm 70 mm 70 mm 70 mm 90 mm 100 mm 110 mm


Number of Foundation
4 x 450 mm 4 x 450 mm 4 x 450 mm 4 x 450 mm 4 x 600 mm 4 x 750 mm 4 x 750 mm 4 x 750 mm 4 x 750 mm 4 x 850 mm
Bolts X Length

PCD of Foundation Bolt 200 mm 200 mm 200 mm 200 mm 220 mm 225 mm 240 mm 310 mm 320 mm 340 mm

Bolt Diameter 16 mm 16 mm 16 mm 16 mm 20 mm 20 mm 20 mm 25 mm 25 mm 25 mm
Single & Single & Single & Single & Single & Single & Single & Single & Single & Single &
Bracket
Double Arm Double Arm Double Arm Double Arm Double Arm Double Arm Double Arm Double Arm Double Arm Double Arm
Table P - 02

Swaged Tubular pole as per IS : 2713 P - I, II 1980


S.No. Pole Over all Base Plate Size Planting Length of sections Outside dia. & thickness of sections Approx. Wt. of
Designation length Depth Pole ( Including
( Mtr. ) ( Mtr. ) Base Plate)

Bottom Middle Top


h1 h2 h3

1 410 SP - 5 7.5 300 x 300 x 5 mm 1.25 4.5 1.50 1.50 114.3 x 4.5 88.9 x 4.05 76.1 x 3.25 3.52 Kg + 79 Kg

2 410 SP - 17 8.5 300 x 300 x 5 mm 1.50 5.0 1.75 1.75 114.3 x 4.5 88.9 x 4.05 76.1 x 3.25 3.52 Kg + 89 Kg

3 410 SP - 28 9.0 300 x 300 x 5 mm 1.50 5.0 2.0 2.0 139.7 x 4.5 114.3 x 3.65 88.9 x 3.25 3.52 Kg + 113 Kg

4 410 SP - 42 10.0 400 x 400 x 7 mm 1.8 5.2 2.4 2.4 139.7 x 5.4 114.3 x 4.5 88.9 x 3.25 8.8 Kg + 144 Kg

5 410 SP - 51 11 400 x 400 x 7 mm 1.8 5.6 2.7 2.7 139.7 x 5.4 114.3 x 5.4 88.9 x 3.25 8.8 Kg + 164 Kg

6 410 SP - 60 12 400 x 400 x 7 mm 2 5.8 3.1 3.1 165.1 x 5.4 139.7 x 4.5 114.3 x 3.65 8.8 Kg + 208 Kg
Table P - 03
High mast suitable for 2 / 3 point suspension system of lantern carriage for wind speed up to 180 Km / Hour

Height of Mast Unit 30 Mtr. 25 Mtr. 20 Mtr. 16 Mtr. 12.5 Mtr.


IS 2062 grade E350 / BS IS 2062 grade E350 / BS IS 2062 grade E350 / BS IS 2062 grade E350 / BS IS 2062 grade E350 / BS
EN 10025 or Equivalent EN 10025 or Equivalent EN 10025 or Equivalent EN 10025 or Equivalent EN 10025 or Equivalent
having minimum yield having minimum yield having minimum yield having minimum yield having minimum yield
Material Cunstruction
strength of 350 N/Sq. strength of 350 N/Sq. strength of 350 N/Sq. strength of 350 N/Sq. mm strength of 350 N/Sq. mm
mm mm mm

No. of Longitude Welds No. Single Single Single Single Single

Top/ Bottom (diameter of High Mast) mm. 150/540 150/540 150/410 150/410 150/360
Cross section of Mast polygone (
No. 20 Sides 20 Sides 20 Sides 20 Sides 20 Sides
No. of Sides)
Nos. of Section of Mast No. 3 3 2 2 2
Thickness of Section MM 3-4-5 3-4-5 3-4 3-4 3-3
As per BSEN ISO 1461 As per BSEN ISO 1461 As per BSEN ISO 1461 As per BSEN ISO 1461 (For As per BSEN ISO 1461 (For
(For Steel ≤ 3 mm- 55 (For Steel ≤ 3 mm- 55 (For Steel ≤ 3 mm - 55 Steel ≤ 3 mm - 55 Steel ≤ 3 mm - 55
Thickness of Galvanisations (Min.) Micron Microns & For Steel > Microns & For Steel > Microns) Microns) Microns)
3mm to ≤ 6 mm - 70 3mm to ≤ 6 mm - 70
Microns) Microns)

Size of Base Plate (Min.) MM 730 730 590 570 520


Thickness of Base Plate (Min.) MM 30 30 25 25 20
Foundation Bolts
Nos of Bolts No. 12 12 8 8 6
PCD of Foundation MM 635 635 500 490 445
30X1200/ EN 8 Grade 30X1200/ EN 8 Grade 30X850/ EN 8 Grade 24X850/ EN 8 Grade 24X850/ EN 8 Grade
Bolt Diameter/Grade/Tensile Strength MM Minimum tensile Minimum tensile Minimum tensile Minimum tensile Minimum tensile
strength 600 N/mm2 strength 600 N/mm2 strength 600 N/mm2 strength 600 N/mm2 strength 600 N/mm2
Lantern Carriage (No. of Half) No. 2 2 2 2 2
Material of construction of LC/Lantern 50 NB ERW Class A - M. S. 50 NB ERW Class A - M. 50 NB ERW Class A - M. 50 NB ERW Class A - M. S. 40 NB ERW Class A - M. S.
carrigae finish Pipe S. Pipe S. Pipe Pipe Pipe
Lantern Carriage ( No of Arms) No. 9 9 6 6 6
Table P - 03
High mast suitable for 2 / 3 point suspension system of lantern carriage for wind speed up to 180 Km / Hour

Height of Mast Unit 30 Mtr. 25 Mtr. 20 Mtr. 16 Mtr. 12.5 Mtr.


Lantern Carriage Minimum Inner Dia mm 711 535 535 535 450
Lantern Carriage Minimum Length of mm 600 600 600 600 500
Arms
Hardwares Less than 10 mm stainless Less than 10 mm Less than 10 mm Less than 10 mm stainless Less than 10 mm stainless
steel AISI 304 & 12 mm stainless steel AISI 304 & stainless steel AISI 304 & steel AISI 304 & 12 mm steel AISI 304 & 12 mm
above hot dip galvanized 12 mm above hot dip 12 mm above hot dip above hot dip galvanized above hot dip galvanized
galvanized galvanized
Nos of fittings LED 400W No. 12 12 9 8 6
Winch
Nos. of Drum Drum/Winch 2 2 2 2 2
Capacity (Min.) Kg. SWL 750 SWL 750 SWL 500 SWL 350 SWL 250
Wire Rope (Nos./Thickness) Nos. (MM) 3/6mm, AISI 316 3/6mm, AISI 316 3/6mm, AISI 316 3/6mm, AISI 304 2/6mm, AISI 304
Input Supply/Power tool /Torque Limitor 415V , 3 Phase/ 415V , 3 Phase/ 415V , 3 Phase/ 415V , 3 Phase/ 415V , 3 Phase/
(Reversible with Plate (Reversible with Plate (Reversible with Plate (Reversible with Plate (Reversible with Plate
arrangement for arrangement for arrangement for arrangement for adjusting arrangement for adjusting
adjusting the tension in adjusting the tension in adjusting the tension in the tension in the the tension in the
the coupling chain the coupling chain the coupling chain coupling chain between coupling chain between
between motor & between motor & between motor & motor & motor &
winch/Mechanical winch/Mechanical winch/Mechanical winch/Mechanical winch/Mechanical

Cable Connectors (Plug & Socket) 6 Pin Male/Female 6 Pin Male/Female 6 Pin Male/Female 5 Pin Male/Female 5 Pin Male/Female
Connectors Connectors Connectors Connectors Connectors
Motor HP 1.5 HP 1.5 HP 1.0 HP 1.0 HP 1.0 HP
Trailing Cable ( Condcutor/Type/Size) Copper/EPR insulated Copper/EPR insulated Copper/EPR insulated Copper/EPR insulated PCP Copper/EPR insulated PCP
PCP scheathed cotton PCP scheathed cotton PCP scheathed cotton scheathed cotton scheathed cotton
braided/5CX4.0 sqmm braided/5CX4.0 sqmm braided/5CX4.0 sqmm braided/5CX4.0 sqmm braided/5CX2.5 sqmm
Table P- 04
P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-19

Chapter E - 19

Over Head Lines


Code No. Description Unit Complete Rate

19.1 Supply and erection of P.C.C. pole as per REC manual no 15/1979
(ammended upto date) and as per latest Discom specifications
with factor of safety 2.5 including excavation of pit upto pole
planting depth 1/6th of pole length. and back filling with stone
aggregate/boulders and soil by ramming and watering etc
complete as required. All as per pre approved by Engineer in
charge.For additional technical parameters of product / work
refer Annexure 'A' attached with this BSR

19.1.1 8.0 Mtr long PCC pole of 200 Kg Working Load Each 3343.0
19.1.2 9.0 Mtr long PCC pole of 200 Kg Working Load Each 5037.0
19.1.3 9.0 Mtr long PCC pole of 400 Kg Working Load Each 5918.0
19.1.4 11.0 Mtr long PCC pole of 400 Kg Working Load Each 7177.0

19.2 Supply and erection of GI stay set confirming to pattern-1 of


BS:16/1974 and as per latest Discom Specifications complete
with stay rod with anchor plate fitted with cast iron cross head
and steel bow, in cement concrete 1:3:6 including excavation of
pit-re-filling etc complete as reqd. All as per pre approved by
Engineer in charge.For additional technical parameters of
product / work refer Annexure 'A' attached with this BSR

Stay set of dia 20mm, 2.4m long stay rod and anchor plate 380 x
19.2.1 Each 1358.0
380 x 4.0 mm
Stay set of dia 16mm, 1.8m long stay rod and anchor plate 300 x
19.2.2 Each 836.0
300 x 4.0 mm

19.3 Supply and fixing of following LT Supporting accessories with nut


bolt & Clamps made out as per standard Discom's specifications
with two coats of Red oxide and two coats of Aluminium paint
etc. as required. All as per pre approved by Engineer in
charge.For additional technical parameters of product / work
refer Annexure 'A' attached with this BSR
19.3.1 LT cross arm 600 mm long with clamp Each 460.0
19.3.2 LT cross arm 1200 mm long with clamp Each 787.0
19.3.3 Suspension clamp with eye hook & Pole clamp Each 527.0
19.3.4 Dead end clamp with eye hook & Pole clamp Each 612.0
19.3.5 Type A LT connector for Aerial bunched cable Each 71.0
19.3.6 Type B LT connector for Aerial bunched cable Each 55.0

Chapter E - 19 Page 97
P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-19

Code No. Description Unit Complete Rate


19.4 Supply and fixing of LT porcelain pin insulator as per IS 1445-
1997 and as per Discom's standard specifications,suitable for
working voltage 1100 volts including all accessories like MS
Forged GI LT Pin confirming to IS:7935/1975 (latest amended)
Nut, Bolt etc. as required. All as per pre approved by Engineer in
charge.For additional technical parameters of product / work
refer Annexure 'A' attached with this BSR
19.4.1 100 mm x 70 mm Each 107.0

19.5 Supply and fixing of LT porcelain shackle insulator as per IS:1443


1979 and as per Discom's standard specifications, suitable for
working voltage 1100 volts including all accessories like GI
Hardware fittings confirming to IS:7935/1975 (latest amended)
Nut, Bolt etc. as required. All as per pre approved by Engineer in
charge.For additional technical parameters of product / work
refer Annexure 'A' attached with this BSR

19.5.1 75mm x 90mm Each 109.0


19.5.2 100mm x 110mm Each 119.0

19.6 Supplying and drawing overhead steel core Aluminium conductor


(ACSR) ISI marked(IS 398 part II-1996) on existing cross arms
through insulator with all necessary T&P required including
binding and twisting etc. complete in all respect as required. All
as per pre approved by Engineer in charge.For additional
technical parameters of product / work refer Annexure 'A'
attached with this BSR
19.6.1 30 Sqmm of (6+1) 2.59mm (Weasel) Mtr. 40.0
19.6.2 50 Sqmm of (6+1) 3.35 mm (Rabbit) Mtr. 60.0
19.6.3 50 Sqmm of (6+1) 3.35 mm (Insulated Rabbit) for LT Mtr. 92.0
19.6.4 80 Sqmm of (6+1) 4.09 mm (Raccon) Mtr. 96.0
19.6.5 100 sqmm of (6/4.72 mm+1/1.57 mm) (Dog) Mtr. 117.0
19.6.6 ACSR Panther Aluminium 30/3 MM Mtr. 218.0
19.6.7 AAA Conductor (Equivelent size Weasel) Mtr. 38.0

19.7 Supply and fixing of 'V' type cross arms with top hamper and 1417.0
clamps as per latest Discom specifications made of MS angle on
the existing poles complete including all necessary nut and bolt,
clamps with two coats of Red oxide and two coats of Aluminium
paint etc. as required. All as per pre approved by Engineer in
charge.For additional technical parameters of product / work
refer Annexure 'A' attached with this BSR

19.8 Supply and fixing of top hamper on the existing pole as per latest
Discom specifications complete including nut bolts with two
coats of Red oxide and two coats of Aluminium paint etc as
required. All as per pre approved by Engineer in charge.For
additional technical parameters of product / work refer
Annexure 'A' attached with this BSR
19.8.1 Vertical type
19.8.1.1 11 kV (.7m long) (65 x 65 x6mm angle) Each 275.0

Chapter E - 19 Page 98
P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-19

Code No. Description Unit Complete Rate


19.8.1.2 11 kV(50 x 6 mm flat) Each 194.0
19.8.2 Horizontal type
19.8.2.1 11 kV (65 x 65 x6mm angle) Each 222.0
19.8.2.2 11 kV with double top hamper (65 x 65 x 6mm angle) Each 285.0

19.9 Supply and fixing of MS. Channel Bracket with clamp as per
Discom Specifications including Nut, Bolt with two coats of Red
oxide and two coats of Aluminium paint etc. as Required. All as
per pre approved by Engineer in charge.For additional technical
parameters of product / work refer Annexure 'A' attached with
this BSR
19.9.1 1.8 Mtr. Long Each 1929.0
19.9.2 1.4 Mtr. Long Each 1676.0

19.10 Supply and fixing of 11 kV pin insulator confirming to IS:731:1971


with latest ammendment on existing bracket including all
accessories like MS forged hot dipped GI Pin confirming to IS
2486(Part-I)/1993 & IS:2486 (Part-II)/1989 with latest
amendment, and as per latest Discom specs. etc. as required. All
as per pre approved by Engineer in charge.For additional
technical parameters of product / work refer Annexure 'A'
attached with this BSR Each 175.0

19.11 Supply and fixing of 11kV Disc insulator and Hot dipped
galvanized Hardware confirming to IS:731:1971 with latest
ammendment and as per latest Discom Specs. on existing
bracket including all accessories etc. as required. All as per pre
approved by Engineer in charge.For additional technical
parameters of product / work refer Annexure 'A' attached with
this BSR
19.11.1 B & S type hardware 45 KN Each 640.0
19.11.2 T & C type hardware 45 KN Each 204.0
19.11.3 B & S disc insulator 45 KN Each 374.0
19.11.4 T & C disc insulator 45 KN Each 350.0

19.12 Supply and fixing of PG / T clamps on overhead lines/jumpers,


made of aluminium alloy 4600 of IS 617-1994 (with latest
amendment if any) with steel nut and bolts conforming to IS
1363-1992 & IS 1367/1979-80 (with latest amendments if any)
all ferrous metal parts intended for outdoor use except those
made of stainless steel shall be protected by hotdip galvanising
in accordance with IS 2633-1986 complete in all respect as
required. All as per pre approved by Engineer in charge.For
additional technical parameters of product / work refer
Annexure 'A' attached with this BSR

19.12.1 PG Clamp for Panther Conductor Each 373.5


19.12.2 PG Clamp for Dog Conductor Type - A Each 294.9
19.12.3 PG Clamp for Weasel Conductor Each 94.8
19.12.4 PG Clamp for Rabbit Conductor Each 83.6
19.12.5 T Clamp for Panther Conductor Each 420.6

Chapter E - 19 Page 99
P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-19

Code No. Description Unit Complete Rate


19.13 Supplying and laying of Hot dip galvanized steel stay wire of 550-
900 N/mm Quality confirming to IS-2141/2000 in all respect
Including chemical composition (Heavily coated Hard quality) of
dia 7/3.15 mm(7/10 SWG) and as per latest Discom specs. etc. as
required. All as per pre approved by Engineer in charge.For
additional technical parameters of product / work refer
Annexure 'A' attached with this BSR Mtr 114.7

19.14 Supply and fixing of 11 / 33. KV Stay insulator as per


IS:5300/1969 and as per Discom's standard specifications etc. as
required. All as per pre approved by Engineer in charge.For
additional technical parameters of product / work refer
Annexure 'A' attached with this BSR
19.14.1 110 x 75 x 22mm 11 KV Stay Insulator Set 44.5
19.14.2 140 x 85 x 25mm 33 KV Stay Insulator Set 69.5

19.15 Supply and fixing of LT Distribution Kiosk confirming to


IS:13947/1993/ IEC 60947 Pt.3 amended up-to-date and as per
DISCOM specifications made of 2 mm thick powder coated CRCA
sheet of 415 volts 3 phase 4 wire triple pole and neutral type,
complete in all respect as required. Including Incoming Switch
Disconnector Fuse unit, Aluminium Busbar with copper one piece
U contacts base, brass studs and nuts, copper busbar for main
and interconnection, MS Channel frame of 75 mm x 40 mm
grouted with C.C. of M-10 grade to achieve the height of 1.5 feet
above the road level suitable for required no. outgoing. All as
per pre approved by Engineer in charge.For additional technical
parameters of product / work refer Annexure 'A' attached with
this BSR

19.15.1 200 Amp. LT Distribution Kiosk for 63/100 KVA Transformer Each 37639.0
19.15.2 400 Amp. LT Distribution Kiosk for 250/315 KVA Transformer Each 64700.0
19.15.3 100 Amp. Distribution Kiosk suitable for Underground cable of
23390.0
Size 500mm x 550 mm x 700 mm Each

19.16 Supply and fixing of 11 KV Outdoor 4 way feeder pillar Box


confirming to Discom specifications and made of 3.15 mm thick
powder coated CRCA sheet enclosure confirming to IS 14772/IEC
60670 (1989) of Size 1000 mm x 1000 mm x 1500 mm, Both
front and rear doors should have 3 heavy duty M.S. hinges with
Brass pin inserted inside and locking arrangements.The bottom
foundation frame stand should be made from 65x65x6mm MS
Angle with four legs of 200mm height provided with
150x150x6mm flats grouted with C.C. of M-10 grade to achieve
the height of 2.0 feet above the road level suitable for four
outgoing. All as per pre approved by Engineer in charge. For
additional technical parameters of products/ work , refer
Annexure "A" attached with this BSR .
Each 60098.0

Chapter E - 19 Page 100


P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-19

Code No. Description Unit Complete Rate


19.17 Supply and fixing of 100 Amp, 11kV Horn gap fuse set IS 9385 on
existing DP structure with 6 nos 24kV/22kV post insulator
(IS:5350 part III), hot dipped hard ware,fuse wire of required size
etc. complete in all respect as per Discom specification etc. as
required.All as per pre approved by Engineer in charge. For
additional technical parameters of products/ work , refer
Annexure "A" attached with this BSR .
Each 9071.0

19.18 Supply and fixing of 11kV, 400 Amp 3 pole, central pot rotating
double break type isolator (IS:9921 part I toV) without earth
blade operating mechanism with GI spring loaded reverse loop
type fixed contact, solid hard drawn electolytic copper tubular
moving contact with silver/ nickel plated at end points, 9 nos
post insulator of 12 kV (IS:2554 & IS 5350 part III), hot dipped
galvanising hard ware, nut, bolts etc complete in all respect as
per Discom specification etc. as required. All as per pre approved
by Engineer in charge. For additional technical parameters of
products/ work , refer Annexure "A" attached with this BSR .
Each 22632.0

19.19 Supply and fixing of distribution type Lightening arrestor ( Set of


3 Nos.) 9 kV, 10 kA (IS:3070) with mounting breaking to be
installed on existing DP structure etc. as required.All as per pre
approved by Engineer in charge. For additional technical
parameters of products/ work , refer Annexure "A" attached
with this BSR . Set 5583.0

19.20 Supply and fixing Substation structure for mounting 11/0.4 Kv


Transformer on Double pole as per DISCOM specification
complete in all respect as required including nuts and bolts etc
(excluding the cost of poles) made of MS channel of 4 nos 100 x
50 x 6mm and 4 nos 75 x 40 x 6mm and MS flat 50 x 6mm etc. as
required. All as per pre approved by Engineer in charge. For
additional technical parameters of products/ work , refer
Annexure "A" attached with this BSR .
Each 18245.0

19.21 Supply and fixing of 1.6 mm thick MS 11 kV Danger plates as per


IS :2551-1982 & specification of Discom on the existing poles
complete in all respectas as required. All as per pre approved by
Engineer in charge.For additional technical parameters of
product / work refer Annexure 'A' attached with this BSR
Each 308.0

Chapter E - 19 Page 101


P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-19

Code No. Description Unit Complete Rate


19.22 Providing and fixing of single pole mounted substation structure
set for isolator / single phase transformer as per DISCOM
specification complete in all respect with nuts and bolts as
required MS flat 50 x 6mm, MS angle 65 x 65 x6mm, MS channel
100 x 50 x 6mm. ( Excluding cost of pole ). Etc. as required. All as
per pre approved by Engineer in charge. For additional technical
parameters of products/ work , refer Annexure "A" attached
with this BSR . Each 3539.0

19.23 Supply and erection of RS joist of 116 x 100 mm, 11 Meter long
with the welded/ bolted top hamper 65 x 65 x 6mm (0.7 Mtr
long) making necessary arrangement for fixing 11 kV 'V' cross
arm, LT bracket and guard wire bracket, grouted in ground 1/6 th
of its length and fixed with cement, coarse and grit in 1:3:6 ratio
in 1/5th of its length (40cm dia) from the bottom including two
coats of aluminium paint over the complete length of joist etc.
as required. (Excavation of pit PCC and CC foundation as per
Discom specs. to be Paid Extra) All as per pre approved by
Engineer in charge. For additional technical parameters of
products/ work , refer Annexure "A" attached with this BSR .
Each 24427.0

19.24 Supplying and drawing of XLPE insulated LT Aerial bunched


Aluminium conductor cable confirming to IS 14255/1995 and IS
398 (Pt-4)/ 1994 and as per Discom Specs. on existing cross arms
through I hook with all necessary T&P required including binding
and twisting etc. complete in all respect as required. All as per
pre approved by Engineer in charge. For additional technical
parameters of products/ work , refer Annexure "A" attached
with this BSR .
19.24.1 1 X 25 sq. mm. + 1X25 sq. mm. (Bared) Mtr 58.0
19.24.2 1 X 25 sq. mm. + 1X25 sq. mm. (insulated) Mtr 63.0
19.24.3 3 X 16 sq. mm. + 1X25 sq. mm. (Bared) Mtr 82.0
19.24.4 3 X 16 sq. mm. + 1X25 sq. mm. (insulated) Mtr 89.0
19.24.5 3 X 25 sq. mm. + 1X25 sq. mm. (Bared) Mtr 113.0
19.24.6 3 X 25 sq. mm. + 1X25 sq. mm. (insulated) Mtr 123.0
19.24.7 3 X 50 sq. mm. + 1X35 sq. mm. (Bared) Mtr 190.0

19.25 Supply & Erection of M S lattice structure of height 12.8 mtr as


per DISCOMs approved design & details in alignment, including
painting of tower of approved make two coat of red oxide paint
and one coat of aluminium paint before installation and one coat
of Aluminium paint after erection work completed as per
technical specifications & drawing of DISCOM. (Excavation of pit
PCC and CC foundation as per Discom specs. to be Paid Extra). All
as per pre approved by Engineer in charge. For additional
technical parameters of products/ work , refer Annexure "A"
attached with this BSR .
Each 57638.0

Chapter E - 19 Page 102


P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-19

Code No. Description Unit Complete Rate


19.26 Supply & Erection of M S lattice structure of height 11.0 mtr as
per DISCOMs approved design & details in alignment, including
painting of tower of approved make two coat of red oxide paint
and one coat of aluminium paint before installation and one coat
of Aluminium paint after erection work completed as per
technical specifications & drawing of DISCOM. (Excavation of pit
PCC and CC foundation as per Discom specs. to be Paid Extra) All
as per pre approved by Engineer in charge. For additional
technical parameters of products/ work , refer Annexure "A"
attached with this BSR .
Each 46560.0

19.27 Supply of Fabricated 33 KV of 'V' type cross arms as per Discom


specifications made of MS channel 100x50 ISMC (9.5Kg. Per
Mtr.) on the existing poles complete including all necessary nut
and bolt etc with clamps including two coats of Red oxide and
two coats of Aluminium paint etc. as Required. All as per pre
approved by Engineer in charge. For additional technical
parameters of products/ work , refer Annexure "A" attached
with this BSR . Each 2340.0

19.28 Supply and fixing of top hamper as per Discom specifications on


the existing pole complete including nut bolts etc as required.
Vertical type 33 kV. 0.75mtr. IS 75x75x6mm as per tech specs. Of
DISCOM (Steel weight 6.5Kg. Approx. per top hamper). All as per
pre approved by Engineer in charge. For additional technical
parameters of products/ work , refer Annexure "A" attached
with this BSR .
Each 405.0

19.29 Supply & Erection of special stud structure for 33KV lattice
structure as per Discom specifications made of M.S. angle,
channer, flats complete in all respects with bracings including
painting of tower of approved make two coat of red oxide paint
and one coat of aluminium paint before installation and one coat
of Aluminium paint after erection work completed as per
technical specifications & drawing of DISCOM. (Excavation of pit
PCC and CC foundation as per Discom specs. to be Paid Extra). All
as per pre approved by Engineer in charge. For additional
technical parameters of products/ work , refer Annexure "A"
attached with this BSR .
Each 25434.0

19.30 Supply and fixing of 33 kV pin insulator confirming to IS:731:1971


with latest ammendment on existing bracket including all
accessories like MS forged hot dipped GI Pin confirming to IS
2486(Part-I)/1993 & IS:2486 (Part-II)/1989 with latest
amendment, and as per latest Discom specs. etc. as required. All
as per pre approved by Engineer in charge. For additional
technical parameters of products/ work , refer Annexure "A"
attached with this BSR . Each 510.0

Chapter E - 19 Page 103


P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-19

Code No. Description Unit Complete Rate


19.31 Supply and fixing of 33kV Disc insulator and Hot dipped
galvanized Hardware confirming to IS:731:1971 with latest
ammendment and as per latest Discom Specs. on existing
bracket including all accessories etc. as required.All as per pre
approved by Engineer in charge. For additional technical
parameters of products/ work , refer Annexure "A" attached
with this BSR .
19.31.1 B & S type hardware 120KN Each 984.0
19.31.2 B & S disc insulator 120KN Each 1139.0

19.32 Supply and fixing of guard bracket 2.2 mtr. long made from
(75x40) ISMC 7.14Kg. Per Mtr. M.S. channel including necessary
clamp and botls etc. as per technical specification & drawing of
DISCOM. All as per pre approved by Engineer in charge. For
additional technical parameters of products/ work , refer
Annexure "A" attached with this BSR .
Each 1456.0

19.33 Supply and fixing M.S. channel (cut point) 100x50mm ISMC
(9.5Kg. Per Mtr.) 2x1.8mtr. long with pilot patti 50x6mm thick
necessary nuts and bolts etc. as per technical specification &
drawing of DISCOM. All as per pre approved by Engineer in
charge. For additional technical parameters of products/ work ,
refer Annexure "A" attached with this BSR .
Each 3644.0

19.34 Supply and installation of spike of M.S. rod 20mm dia 3.0mtr.
long for earthing of (tower/pole) drive into earth by mechanical
means sturcture connection the spike with cross arm top hamper
PCC pole, lattics tower to earth etc. complete as per technical
specification of DISCOM. Each 1819.0

19.35 Labour charges for Dismentling the structure with pole mounted
transformer different capacity along with distribution boards and
re- erecting the transformer in the structure to be newly erected
along with distribution boards and erecting testing, testing and
commissioning (as well as cabling)
Job 3183.0

19.36 Labour charges for Dismantling of existing electric poles (PCC


poles, MS channel, Lattic tower 12.6mtr. , 11 mtr. along with the
ACSR Conductors, 11KV/33KV/LT line etc. 11KV insulator LT
insulator guard wires, staywires and other electric items of the
pole coming along the alignment of the road and removal and re-
rolling PCC pole, MS channel different sizes as well as handing
over the same to DISCOM store including transportation from
site to store and stacking of dismantling material in store and as
per the direction of Engineer Incharge and clean the site good as
per the requirement and submit the receipt from DISCOM/
concering authority, including all complete works.
job 1203.0

Chapter E - 19 Page 104


P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-19

Code No. Description Unit Complete Rate


19.37 Labour charges for Dismantling of following existing street light
electric poles with street light fixtures, underground cable, MS
box and other electric items of the pole coming along the
alignment of the road and removal and re- rolling MS poles/PCC
poles of different sizes as well as handing over the same to
DISCOM/UIT/MC store and as per the direction of Engineer
Incharge and clean the site good as per the requirement and
submit the receipt from concering authority, all complete works.
Job 528.0

Chapter E - 19 Page 105


P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-20

Chapter E - 20

Local Area Networking


Code No. Description Unit Complete
Rate

20.1 Supply, Drawing and Testing of 4 pair, 23 AWG Solid Bare Copper wire insulated with PVC,
UTP (Unshielded Twisted Pair), Category 6, Class E, 100 Ohm Impedance, Indoor Cable as
per latest ammendments of ANSI/TIA/EIA-568 , The copper conductors should be balanced
twisted in pairs, seperated by a cross-member fluted pair divider & protected by PVC
Jacket. Certified performance in a 4-connector configuration upto 100 Mtrs channel
requirements & transmission frequencies up to 250 Mhz. in existing MS/PVC
Conduits/casing capping including making connections to Information outlets and Patch
Panels with jack & ferruling at both ends for identification with necessary tools for
punching, stripping, crimping and testing etc as required complete in all respect. All as per
pre approved by Engineer in charge. For additional technical parameters of products/ work
, refer Annexure "A" attached with this BSR . Mtr. 49.00
20.2 Supply, Drawing and Testing of 4 pair, 23 AWG Solid Bare Copper wire insulated with HDPE,
U/UTP (Unscreened/Unshielded Twisted Pair), Category 6, Class E, 100 Ohm Impedance,
Outdoor Cable as per latest ammendments of ANSI/TIA/EIA-568 C.2 & ISO/IEC 11801 2nd
Ed, The copper conductors should be balanced twisted in pairs, seperated by a cross divider
& protected by LSZH PVC outer jacket of UV resistant. Certified performance in a 4-
connector configuration upto 100 Mtrs channel requirements & transmission frequencies
up to 250 Mhz. Should meet IEEE 802.3af & IEEE 802.3at for POE applications. Cable Should
support Ethernet 10GBASE-T according to the standards. in existing MS/PVC
Conduits/casing capping including making connections to Information outlets and Patch
Panels with jack & ferruling at both ends for identification with necessary tools for
punching, stripping, crimping and testing etc as required. All as per pre approved by
Engineer in charge. For additional technical parameters of products/ work , refer
Annexure "A" attached with this BSR . Mtr. 83.00

20.3 Supply, Drawing and Testing of 4 pair, 23 AWG Solid Bare Copper wire insulated with HDPE,
Category 6A/Class Ea, U/FTP (Unscreened/Foiled Twisted Pair), 100 Ohm Impedance,
Indoor Cable as per latest ammendments of ANSI/TIA/EIA-568 C.2 & ISO/IEC 11801 2nd Ed,
The copper conductors should be balanced twisted in pairs, Unscreened and Aluminum Foil
Sheilding of Individual pairs protected by a Low Smoke Zero Halogen (LSZH)(IEC 60332-1)
Jacket. Certified performance in a 4-connector configuration upto 100 Mtrs channel
requirements & transmission frequencies up to 500 Mhz. Should meet IEEE 802.3af & IEEE
802.3at for POE applications. Cable Should support Ethernet 10GBASE-T according to the
standards. in existing MS/PVC Conduits/casing capping including making connections to
Information outlets and Patch Panels with jack & ferruling at both ends for identification
with necessary tools for punching, stripping, crimping and testing etc as required.All as per
pre approved by Engineer in charge. For additional technical parameters of products/ work
, refer Annexure "A" attached with this BSR . Mtr. 95.00

20.4 Supply and Installation of unsheilded/360 degree sheilded Information outlets made of high
impact plastic body with ABS, FR Grade halogen free material with provision for protection
against dust in jack, suitable for Cat 6/6A application complying to latest ammendments,
According. to Cat. 6/6A channel, It should support channel as well as components
requirements of Cat.6/6A standards at frequencies of up to 250 to 500 Mhz. Cat 6/6A
unshielded/shielded Jack should be suitable to terminate 4 pair, 23/24 AWG solid/stranded
wire diameters, using 100 Ohm unshielded/shielded balance twisted pair cable, the jack
should have tooless/impact termination on reliable copper tin plated Insulation
displacement contact, with easy lock mechanism, It supports IEC 60603-7-4 and complied
with ANSI/TIA/EIA 568 C.2 standard. jack should be RJ11,RJ12 & RJ45 compatible. Should
support Ethernet 1.2 Gb/s ATM,Digital video and broadband/baseband analog video, Voice
over internet protocal (VOIP) Specifications in existing modular/MS Boxes along with
necessory connections as required.All as per pre approved by Engineer in charge. For
additional technical parameters of products/ work , refer Annexure "A" attached with this
BSR .

chapter E - 20 Page 106


P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-20

Code No. Description Unit Complete


Rate
20.4.1 Cat 6, Un-sheilded Information Outlet Each 398.00
20.4.2 Cat 6A, Sheilded Information Outlet Each 580.00

20.5 Supply & fixing of square Faceplate for Flush / Surface Mount Information Outlets
Single/Dual or Quad Aperture , material should be PC+ABS body, Suitable for RJ45
unshielded/shielded connection modules. Should match with I. O. OEM. Dimensions should
be 86mm X 86mm as required complete in all respect. All as per pre approved by Engineer
in charge. For additional technical parameters of products/ work , refer Annexure "A"
attached with this BSR .
20.5.1 Single Aperture Each 81.00
20.5.2 Dual Aperture Each 101.00
20.5.3 Quad Aperture Each 121.00

20.6 Supply, Installation, Testing and Comissioning of Rack mounted 19" 1U, Cat6 24 Port
loaded, 1.5-1.6 MM CRS chasis, powder coated, sheet steel, made of plastic (ABS), Modular
Patch Panels with Rear Cable management system and mounting hardware to mount the
patch panel. Should have port identification numbers printed/engraved on front of the
panel. Etc. as required.All as per pre approved by Engineer in charge. For additional
technical parameters of products/ work , refer Annexure "A" attached with this BSR .

20.6.1 Modular Patch Panel Loaded with Cat -6 I/O Each 8765.00
20.6.2 Modular Patch Panel Loaded with Cat -6A I/O Each 12817.00

20.7 Supply , Installation and Testing of 4 pair, 100 Ohm impedance, Cat 6/6A /Class E/Ea patch
cords should be constructed of minimum 23/24 AWG, stranded bare Copper cable with
FRPVC/LSZH Jacket, with an enhanced performance by factory moulded RJ45 connectors
with strain relief boots as per ANSI/TIA/EIA 568-C.2 suitable for Cat 6/6A application
complying to latest ammendments Category 6/6A Standards, According. to TIA568C.2,
ISO/IEC 11801, EN 50173, IEC 60603-7-51, EN 60603-7, IEEE 802.3an minimum requirement
for 1G BASE-T to 10G BASE-T performance. Patch cords shall be straight thru cable
compatible with both T568-A and T568-B wiring schemes, should support IEEE 802.3af /
IEEE 802.3at for POE applications, Minimum 750 to 1000 mating cycles in plug contacts for
long durability, Should support Ethernet 10GBASE-T, 1.2 Gb/s ATM, Token ring 4/16, Digital
video and broadband/baseband analog video, Voice over internet protocal (VOIP).All as per
pre approved by Engineer in charge. For additional technical parameters of products/ work
, refer Annexure "A" attached with this BSR .
20.7.1 Cat 6, U/UTP (Unscreened/Un-sheilded Twisted Pair) Patch Cord
20.7.1.1 0.50 Mtr Each 148.00
20.7.1.2 1 Mtr Each 223.00
20.7.1.3 2 Mtr Each 290.00
20.7.1.4 3 Mtr Each 358.00
20.7.2 Cat 6A, U/FTP (Unscreened/Foiled Twisted Pair) Patch Cord
20.7.2.1 0.50 Mtr Each 283.00
20.7.2.2 1 Mtr Each 425.00
20.7.2.3 2 Mtr Each 560.00
20.7.2.4 3 Mtr Each 695.00
20.8 Supply, Drawing and Testing, of stranded Multi mode (50/125 µm) glass optic fiber cable, as
per latest ammendments of TIA/EIA 568/ISO/IEC 11801:2011/ IEC 60794-1-2 E1, E3,E11, F1/
EN 50173-1/ EN 187 000/ IEC 60974-2, 2-20, 2-21/ ITU G.652D, construction of LSZH outer
sheath cable, cable should be used for LAN and WAN back bones, . With its LSZH sheathing
these cables should be ideal for indoor/outdoor installations in existing MS/PVC /HDPE
Conduits/ slotted channels with ferruling at both ends for identification complete in all
respect. All as per pre approved by Engineer in charge. For additional technical parameters
of products/ work , refer Annexure "A" attached with this BSR .
20.8.1 6 fiber mtr 142.00
20.8.2 12 Fiber mtr 182.00
20.8.3 24 Fiber mtr 236.00

chapter E - 20 Page 107


P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-20

Code No. Description Unit Complete


Rate
20.9 Supply, Installation, OTDR Testing & Fusion Splicing of Fiber Multimode Pigtail (50/125 µm)
made of glass fiber optic, should be fitted at one end with any one type of single ST/E-
2000/SC/LC/MT-RJ/PC type connector in acc., as per latest ammendments of TIA/EIA 569
Standard Specification as per requirments complete in all respect. All as per pre approved
by Engineer in charge. For additional technical parameters of products/ work , refer
Annexure "A" attached with this BSR .
Each 1212.00

20.10 Supply, Installation, & Testing of Indoor duplex Multimode patch cord (50/125 µm made of
glass fiber optic with LSZH jacket, F8 2.0x4.1 mm, Multimode G652.D Mounted on both
sides with ST/E-2000/SC/LC/MT-RJ/PC type Duplex connectors in acc. with IEC 61754-20.
Zirconia (ceramic) ferrule with a PC polished endface geometry, connectors should be tuned
in accordance with IEC 61755-3-1 and qualified in acc. with IEC 61753-1 for category U
(uncontrolled environment, duplex clip and white plastic dust cover, should comply to delta
IL < 0.2 dB after 500 mating cycles, there should be an optional Visual coding, mechanical
coding and lock protection on the patch cords which can be added on later stage. patch
cords's performance should be acc. to IEC 61753-1 (Table A.12) as per latest ammendments
of TIA/EIA 569B.3, as per requirements.All as per pre approved by Engineer in charge. For
additional technical parameters of products/ work , refer Annexure "A" attached with this
BSR .
20.10.1 1 Mtr Each 1688.00
20.10.2 2 Mtr Each 1958.00
20.10.3 3 Mtr Each 2228.00
20.10.4 5 Mtr Each 2498.00

20.11 Supply, Installation, & Testing of 19" 1U Rack Mounted/ surface mounted aluminum/ CRCA
1.2mm powder coated, multimode glass Fiber Optic Cable Patch panel/LIU loaded with
flangless/screwable adapters for ST/E-2000/SC/LC/MT-RJ/PC type, It should have easy
removable Top plate with push buttons, there should be a splice tray installed in the Patch
panel/LIU which can handle the fiber cores, splice tray should be PC+ABS material, it should
include accessories like mounting hardware, gormetts, heat shrink tubes/sleevs, screws,
nuts to install the panel for rack/wallmount applications as per requirement complete in all
respect. All as per pre approved by Engineer in charge. For additional technical parameters
of products/ work , refer Annexure "A" attached with this BSR .
20.11.1 Multi Mode LIU 6 Ports Each 6402.00
20.11.2 Multi Mode LIU 12 Ports Each 8691.00
20.11.3 Multi Mode LIU 24 Ports Each 11453.00

20.12 Supply, Drawing and Testing, of stranded Single mode (9/125 µm) glass optic fiber cable, as
per latest ammendments of TIA/EIA 568/ISO/IEC, construction of LSZH outer sheath cable,
cable should be used for LAN and WAN back bones, . With its LSZH sheathing these cables
should be ideal for indoor/outdoor installations in existing MS/PVC /HDPE Conduits/ slotted
channels with ferruling at both ends for identification complete in all respect.All as per pre
approved by Engineer in charge. For additional technical parameters of products/ work ,
refer Annexure "A" attached with this BSR .

20.12.1 6 fiber Mtr 94.00


20.12.2 12 Fiber Mtr 121.00
20.12.3 24 Fiber Mtr 162.00

20.13 Supply, Installation, OTDR Testing & Fusion Splicing of Fiber Singlemode Pigtail (9/125 µm
(OS1/OS2) made of glass fiber optic, with semi-tight buffer PA/PBT, Ø 0.9 mm, yellow,
singlemode G652.D (9/125 µm (OS1, OS2), should have length of min 1.5m, should be fitted
at one end with any one type of single ST/E-2000/SC/LC/MT-RJ/PC type connector in acc.
with IEC 61754-20, Should be delta IL < 0.2 dB after 500 mating cycles, It should be Zirconia
(ceramic) ferrule with a PC polished endface geometry connector qualified in acc. with IEC
61753-1 for category U (uncontrolled environment). and qualified in acc. with IEC 61753-1,
Performance acc. to IEC 61753-1 (Table A.12) as per latest ammendments of TIA/EIA
569B.3, Standard Specification as per requirments.All as per pre approved by Engineer in
charge. For additional technical parameters of products/ work , refer Annexure "A"
attached with this BSR . Each 1212.00

chapter E - 20 Page 108


P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-20

Code No. Description Unit Complete


Rate
20.14 Supply, Installation, & Testing of Indoor duplex Singlemode patch cord (9/125 µm
(OS1/OS2) made of glass fiber optic with LSZH jacket, F8 2.0x4.1 mm, yellow, singlemode
G652.D (9/125 µm (OS1, OS2) Mounted on both sides with ST/E-2000/SC/LC/MT-RJ/PC
type Duplex connectors in acc. with IEC 61754-20. Zirconia (ceramic) ferrule with a PC
polished endface geometry, connectors should be tuned in accordance with IEC 61755-3-1
and qualified in acc. with IEC 61753-1 for category U (uncontrolled environment, duplex clip
and white plastic dust cover, should comply to delta IL < 0.2 dB after 500 mating cycles,
there should be an optional Visual coding, mechanical coding and lock protection on the
patch cords which can be added on later stage. patch cords's performance should be acc. to
IEC 61753-1 (Table A.12) as per latest ammendments of TIA/EIA 569B.3, as per
requirements.All as per pre approved by Engineer in charge. For additional technical
parameters of products/ work , refer Annexure "A" attached with this BSR .

20.14.1 Single Mode Patch Cord 1 Mtr. Each 1417.00


20.14.2 Single Mode Patch Cord 2 Mtr. Each 1688.00
20.14.3 Single Mode Patch Cord 3 Mtr. Each 1823.00
20.14.4 Single Mode Patch Cord 5 Mtr. Each 2039.00

20.15 Supply, Installation, & Testing of 19" 1U Rack Mounted/ surface mounted aluminum/ CRCA
1.2mm powder coated, Singlemode glass Fiber Optic Cable Patch panel/LIU loaded with
flangless/screwable duplex adapters for ST/E-2000/SC/LC/MT-RJ/PC type, It should have
easy removable Top plate with push buttons, there should be a splice tray installed in the
Patch panel/LIU which can handle the fiber cores, splice tray should be PC+ABS material, it
should include accessories like mounting hardware, gormetts, heat shrink tubes/sleevs,
screws, nuts to install the panel for rack/wallmount applications as per requirment
complete in all respect. All as per pre approved by Engineer in charge. For additional
technical parameters of products/ work , refer Annexure "A" attached with this BSR .
20.15.1 6 Ports Each 6739.00
20.15.2 12 Ports Each 8759.00
20.15.3 24 Ports Each 10778.00

20.16 Supply & Installation of IP-20 & IK-08 , UL Listed Wall mounted Double Section
Communication enclosure (Rack) made from powder coated (60 to 80 Micron) CRCA sheet,
front sturdy sheet steel frame folded from one piece and welded with minimum 5mm
toughened glass door,Vertical Mounting Rail 1.6 MM with 'U'Marking , with All round
protective channel on the door aperture, lock integrated on front door, top and bottom
cover with cable entry provision with gland plates, integrated side walls, 2 pair of 19" angles
with wall mounting provision on wall. Accessories like: 1 No of 19" 1U Horizontal Cable
manager, 1 No of 90 cfm 230V AC Fan with 1 mts long cable, mounting hardware , 1 No of
19" 1U, mountable socket strips with 5 nos of 5A universal sockets with 2 mts long power
chord for supplying power to switches, fans etc along with earth continuity kit, indicator,
moulded power supply cable. fixing on wall with Suitable Anchor fastner etc as required.All
as per pre approved by Engineer in charge. For additional technical parameters of
products/ work , refer Annexure "A" attached with this BSR .
20.16.1 6 U Rack with Width 600 mm & Depth 400 mm + 100 mm Each 9173.00
20.16.2 9 U Rack with Width 600 mm & Depth 400 mm + 100 mm Each 12142.00
20.16.3 12 U Rack with Width 600 mm & Depth 400 mm + 100 mm Each 15244.00
20.16.4 15 U Rack with Width 600 mm & Depth 400 mm + 100 mm Each 18213.00

chapter E - 20 Page 109


P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-20

Code No. Description Unit Complete


Rate
20.17 Supply & Installation of IP-20 & IK-08 , UL Listed Communication enclosure (Rack) made
from powder coated (60 to 80 Micron) CRCA sheet,Vertical Mounting Rail 1.6 MM with
'U'Marking, front sturdy sheet steel frame folded from one piece and welded with 5mm
toughened glass door, with All round protective channel on the door aperture, lock
integrated on front door, top and bottom cover with cable entry provision with gland plates,
integrated side walls, Set of 75 mm height 4 castors, 2 of which have brakes, Accessories
like: 5 Nos of 19" 1U Horizontal Cable manager, 2 Nos of vertical cable managers, 1 no.
Keyboard Tray, 4 Nos of 90 cfm 230V AC Fan with 1 mts long cable, mounting hardware , 2
No of 19" 1U, mountable socket strips with 6 nos of 5A universal sockets with 2 mts long
power chord for supplying power to switches, fans etc along with earth continuity kit,
indicator, moulded power supply cable complete in all respect. All as per pre approved by
Engineer in charge. For additional technical parameters of products/ work , refer
Annexure "A" attached with this BSR .
20.17.1 17 U Rack with Width 600 mm & Depth 800 mm Each 28616.00
20.17.2 22 U Rack with Width 600 mm & Depth 800 mm Each 33069.00
20.17.3 27 U Rack with Width 600 mm & Depth 800 mm Each 41841.00
20.17.4 36 U Rack with Width 600 mm & Depth 800 mm Each 46227.00
20.17.5 42 U Rack with Width 600 mm & Depth 800 mm Each 58716.00
20.17.6
42 U Rack with Width 800 mm & Depth 1000 mm with 3 no. Heavy Duty Sliduing Drawer Each 93136.00

20.18 Supply , Installation, Testing and Comissioning of Unmanaged Switch Plug-and-play - easy
setup with no configuration or no software needed, following Port fast ethernet - 8 port
10/100 MBPS auto-negotiation RJ45 ports, IEEE 802.3x flow control ,supports auto-
MDI/MDIX, eliminating the need for crossover cables including making connection etc as
required complete in all respect. All as per pre approved by Engineer in charge. For
additional technical parameters of products/ work , refer Annexure "A" attached with this
BSR .
20.18.1 8 Port Each 2969.00
20.18.2 24 Port Each 6841.00

20.19 Supply , Installation, Testing and Comissioning of Managed Layer-2 Intelligent 10/100
Ethernet Switch providing 24 x 10/100/1000 MBPS Giga Ethernet ports / with min 2 SFP
Giga Ports (provision for Fiber Giga connectivity) with related LAN Base Software including
making connections etc as required.All as per pre approved by Engineer in charge. For
additional technical parameters of products/ work , refer Annexure "A" attached with this
BSR . Each 36783.00

20.20 Supply , Installation, Testing and Comissioning of Managed Layer-2 Intelligent Giga Ethernet
Switch providing 24 x 10/100/1000 MBPS Giga Ethernet ports and with min 4 SFP Giga
Ports (provision for Fiber Giga connectivity) all switches & related Fiber modules should be
of same make & category for seamless integration with each other of Enterprise class
Catalyst Series including making connections etc as required. All as per pre approved by
Engineer in charge. For additional technical parameters of products/ work , refer
Annexure "A" attached with this BSR . Each 101259.00

20.21 Supply , Installation, Testing and Comissioning of Managed Layer-2 Intelligent PoE Giga
Ethernet Switch providing 24 x 10/100/1000 MBPS PoE Giga Ethernet ports and with min 4
SFP Giga Ports (provision for Fiber Giga connectivity) with provision of minimum Stacking of
06 Switches with minimum 370 Watt PoE Power Budget with related LAN Base Software
including making connections etc as required. All as per pre approved by Engineer in charge.
For additional technical parameters of products/ work , refer Annexure "A" attached with
this BSR . Each 149428.00

20.22 Supply , Installation, Testing and Comissioning of Hot pluggable Small Form Factor
Pluggable (SFP Module), 1000BASE-SX, 1.25/2.125G Fiber Channel, LC Type Duplex
Connector, 850nm laser transmitter, Should support distance upto 500m on 50/125um of
data rate upto 2.125 Gb/s on bi-directional data links. Should also support industrial
temperature, should have metal enclosure for lower EMI. The transceiver should be ROHS
Compliant. (For Each MM Fiber) all switches & related Fiber modules should be of same
make & category for seamless integration with each other of Enterprise class, complete in
all respect.All as per pre approved by Engineer in charge. For additional technical
parameters of products/ work , refer Annexure "A" attached with this BSR .
Each 13850.00

chapter E - 20 Page 110


P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-20

Code No. Description Unit Complete


Rate

20.23 Supply , Installation, Testing and Comissioning of Hot pluggable Small Form Factor
Pluggable (SFP Module), 1000BASE-LX, 1G Fiber Channel, LC Type Duplex Connector, 1310
nm laser transmitter, Should support distance upto 10 km on 9/125 um of data rate upto
1.25 Gb/s on bi-directional data links. Should also support industrial temperature, should
have metal enclosure for lower EMI. The transceiver should be ROHS Compliant. (For Each
SM Fiber) all switches & related Fiber modules should be of same make & category for
seamless integration with each other of Enterprise class. All as per pre approved by
Engineer in charge. For additional technical parameters of products/ work , refer
Annexure "A" attached with this BSR .
Each 25499.00

20.24 Supply, installation, Testing and Commissioning of 1000 base-LX/LH single mode/Multi
mode fibre to 1000 base-T copper giga bit , Media Convertor complete as required
complete in all respect. All as per pre approved by Engineer in charge. For additional
technical parameters of products/ work , refer Annexure "A" attached with this BSR .
Each 9447.00

20.25 Fiber Fusion Splicing with OTDR Testing of Fiber Single/ Multi mode (per splice) of glass Fiber
Optic Cable including cleaning the cable and making splice as per standard practice
complete in all respect. All as per pre approved by Engineer in charge. For additional
technical parameters of products/ work , refer Annexure "A" attached with this BSR .
Each 802.00

20.26 System Certification & Documentation by OEM for 20 Years as required Per Node 154.00

chapter E - 20 Page 111


P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-21

Chapter E - 21

Electrical Driven Pumpsets

Code No. Description Unit Complete


Rate

21.1 Labour charges for installation of submersible motor pump set


including lowering/ delowering of pipes, cables, accessories etc. in
tube-well/ open well complete including T&P, transportation of
tripod, chain pulley block & any other material required for this
purpose complete in all respect.
21.1.1 Lowering only Each 4012.0
21.1.2 Delowering only Each 3343.0
21.1.3 Delowering and Lowering Each 6686.0
21.2 Supply & fixing of PVC threaded casing pipes for Tube well (IS
12818:1992) of 3mtr. Each for depth up to 1200 ft. Plain and
strainer Casing CS for Depth upto 400ft. All as per pre approved by
Engineer in charge. For additional technical parameters of
products/ work , refer Annexure "A" attached with this BSR .

21.2.1 Up to 400 ft Depth


21.2.1.1 150 mm dia Mtr. 669.0
21.2.1.2 175mm dia Mtr. 861.0
21.2.1.3 200 mm dia Mtr. 1163.0
21.2.1.4 250 mm dia Mtr. 1730.0
21.2.2 more than 400 ft to 1200 ft. Depth
21.2.2.1 40mm dia Mtr. 140.0
21.2.2.2 50 mm dia Mtr. 197.0
21.2.2.3 80mm dia Mtr. 273.0
21.2.2.4 100 mm dia Mtr. 354.0
21.2.2.5 125 mm dia Mtr. 552.0
21.2.2.6 150 mm dia Mtr. 755.0
21.2.2.7 175 mm dia Mtr. 973.0
21.2.2.8 200 mm dia Mtr. 1314.0
21.2.2.9 250 mm dia Mtr. 1961.0

21.3 Providing & Laying of Polypropylene rope Confirming to IS:5175 for


submersible pump of following sizes. complete in all respect. All as
per pre approved by Engineer in charge. For additional technical
parameters of products/ work , refer Annexure "A" attached with
this BSR .
21.3.1 12mm (suitable up to 50 mm OD pipe) Mtr. 43.0
21.3.2 16mm (suitable above 50mm & up to 75mm OD pipe) Mtr. 54.0
21.3.3 20mm (suitable for 90 mm OD pipe) Mtr. 61.0

Chapter E- 21 Page 112


P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-21

Code No. Description Unit Complete


Rate
21.4 Providing & Fixing of HDPE pipe Confirming to IS:4984:2021 for
water supply suitable for submersible & jet pump with required
fittings ie socket, elbows, tee etc. complete in all respect. All as per
pre approved by Engineer in charge. For additional technical
parameters of products/ work , refer Annexure "A" attached with
this BSR .
21.4.1 for vertical installation
21.4.1.1 40 mm OD 6 kg / cm2 Mtr. 94.0
21.4.1.2 50 mm OD 6 kg / cm2 Mtr. 115.0
21.4.1.3 63 mm OD 6 kg / cm2 Mtr. 148.0
21.4.1.4 75 mm OD 6 kg / cm2 Mtr. 196.0
21.4.1.5 90 mm OD 10 kg / cm2 Mtr. 337.0
21.4.2 for Horizontal installation
21.4.2.1 40 mm OD 4kg/ cm2 Mtr. 81.0
21.4.2.2 50 mm OD 4 kg/ cm2 Mtr. 101.0
21.4.2.3 63 mm OD 4 kg/ cm2 Mtr. 142.0
21.4.2.4 75 mm OD 4 kg/ cm2 Mtr. 182.0
21.4.2.5 90 mm OD 6 kg/ cm2 Mtr. 283.0

21.5 SITC of Single Stage, water cooled, High Speed (2880 RPM),
Horizontal, Centrifugal, Openwell Submersible pumps set pre filled
with coolent water and fitted with mechanical seal - T/C Vs T/C,
Thrust bearing shall be of carbon + S.S.The stator body of single
phase pump shall be of SS and rest of all shall be of cast iron. All
casting parts should be cathod electro deposition (CED) coated and
other construction material should be confirming to IS : 14220:
2018 . The overall performance of pump shall confirm to BEE
energy efficiency level of 3 star. Valid BEE certificate from OEM
must be submitted for the same. Motor should be IE2 class as per
IEC 60034-2-1: 2007, IEC 60034-30: 2008, & IS12615:2011,
including making connection etc as required complete in all
respect. OEM shall have submit NABL / CPRI / ERDA accrediated
lab type test certificate before execution. All as per pre approved
by Engineer in charge. For additional technical parameters of
products/ work , refer Annexure "A" attached with this BSR .

21.5.1 0.5 HP, 1-Ø, (7 -15) Mtr, (130 - 72) LPM Each 12527.0
21.5.2 1.0 HP, 1-Ø, (7 -12) Mtr, (405- 240) LPM Each 16052.0
21.5.3 1.5 HP, 1-Ø, (18 -26) Mtr, (126 - 78) LPM Each 21249.0
21.5.4 2.0 HP, 1-Ø, (12 -25) Mtr, (350 - 115) LPM Each 22937.0
21.5.5 3.0 HP, 3-Ø, (17 -27) Mtr, (680 - 300) LPM Each 25922.0
21.5.6 5.0 HP, 3-Ø, (14 -28) Mtr, (995-500) LPM Each 28389.0
21.5.7 7.5 HP, 3-Ø, (12 -32) Mtr, (1240-475) LPM Each 36999.0

Chapter E- 21 Page 113


P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-21

Code No. Description Unit Complete


Rate
21.5.8 10.0 HP, 3-Ø, (22 -36) Mtr, (1860 - 1020) LPM Each 47946.0
21.5.9 12.5 HP, 3-Ø, (19.5 -33) Mtr, (2150-1300) LPM Each 66415.0
21.5.10 15.0 HP, 3-Ø, (16 -32) Mtr, (2300-1250) LPM Each 75794.0

21.6 SITC of Radial / mixed flow ISI marked water and anti-corrosive liquid
filled submersible motor pump sets suitable for 100/150mm dia
borewell. The size of adopter fixed on top of the motor should exceed
the top of coupler , for safegaurd the coupler. The construction material
of motor and pump should match IS: 8034 : 2018 and IS: 9283 guideline.
The radial flow pumpset should operate at 5 star energy efficiency level of
BEE and mixed flow pump set should operate at 3 star energy level of
BEE, accompained by valid BEE certificate. Motor should be IE2 class as
per IEC 60034-2-1: 2007, IEC 60034-30: 2008, & IS12615:2011 with
required accessories including making connection suitable for Bore well.
The job includes labour part of lowering of riser pipe G.I./ H.D.P.E. with
rope, cables & pump, installation of complete fitting and accessories,
jointing of electrical cables up to Starter. All labour for testing of
submersible pumps set and supply of water to water mains, complete in
all respect. OEM shall have submit NABL / CPRI / ERDA accrediated lab
type test certificate before execution. All as per pre approved by
Engineer in charge. For additional technical parameters of products/
work , refer Annexure "A" attached with this BSR .

21.6.1 100 mm diameter Submersible pump shall have following HP


Rating, phase, Head range, Discharge range respectively.
21.6.1.1 1.0 HP, 1-Ø, (10 - 83)Mtr, (40- 10) LPM Each 21866.0
21.6.1.2 1.5HP, 1-Ø, (11 - 94)Mtr, (40 - 10) LPM Each 23500.0
21.6.1.3 2.0 HP, 1-Ø, (7- 95)Mtr, (55-22) LPM Each 25202.0
21.6.1.4 3.0 HP, 1-Ø, (40 -170)Mtr, (60- 20) LPM Copper Wound Each 42469.0
21.6.1.5 5.0 HP, 1-Ø, (56 - 236)Mtr, (90 - 25) LPM Copper wound Each 49445.0

21.6.2 150 mm diameter Submersible pump shall have following HP


Rating, phase, Head range, Discharge range respectively.
21.6.2.1 3.0 HP, 3-Ø, (54 -95)Mtr, (250-50) LPM Each 45400.0
21.6.2.2 5.0 HP, 3-Ø, (68 - 102)Mtr, (225-85) LPM Each 53024.0
21.6.2.3 7.5 HP, 3-Ø, (76 - 96)Mtr, (285-180) LPM Each 56583.0
21.6.2.4 10.0 HP, 3-Ø, (91 - 115)Mtr, (285-180) LPM Each 71959.0
21.6.2.5 12.5 HP, 3-Ø, (78 - 126)Mtr, (395-245) LPM Each 78975.0
21.6.2.6 15.0 HP, 3-Ø, (80 - 123)Mtr, (465-305) LPM Each 86343.0

Chapter E- 21 Page 114


P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-21

Code No. Description Unit Complete


Rate
21.7 SITC of Monoblock motor pump set ISI marked (IS:9079-2002) with
TEFC motor, motor should be IE2 class as per IEC 60034-2-1: 2007,
IEC 60034-30: 2008, & IS12615:2011. with Stainless steel Impellor,
Stainless steel shaft, Mechanical seal, Single/Three phase ( 240 -
440 V ) permanent split capacitor type (PSC), fitted with thermal
overload protection, Including cost of hardware etc on existing
platform complete. Pump shall have following HP Rating, phase,
Head, minimum Discharge respectively complete in all respect.
OEM shall have submit NABL / CPRI / ERDA accrediated lab type
test certificate before execution. All as per pre approved by
Engineer in charge. For additional technical parameters of
products/ work , refer Annexure "A" attached with this BSR .

21.7.1 0.5 HP, 1-Ø, (3 - 18)Mtr, (100-26) LPM Each 10730.0


21.7.2 1.0 HP, 1-Ø, (10-120)Mtr, (30-12) LPM Each 13877.0
21.7.3 1.5 HP, 1-Ø, (6-24)Mtr, (400-80) LPM Each 17291.0
21.7.4 2.0 HP, 3-Ø, (6-27)Mtr, (425-100) LPM Each 27943.0
21.7.5 3.0 HP, 3-Ø, (14 - 26)Mtr, (760-600) LPM Each 35287.0
21.7.6 5.0 HP, 3-Ø, (24-44)Mtr, (680-370) LPM Each 41929.0
21.7.7 7.5 HP, 3-Ø, (20-32)Mtr, (1060-900) LPM Each 50515.0
21.7.8 10.0 HP, 3-Ø, 32- 48)Mtr, (830-450) LPM Each 63963.0

21.8 SITC of Dewatering Submersible Motor Pump set, motor should be


IE2 class as per IEC 60034-2-1: 2007, IEC 60034-30: 2008, &
IS12615:2011. with SS Impellor, body, shaft, mechanical seal etc.
as required. Pump shall have following HP Rating, phase, Head,
minimum Discharge respectively complete in all respect. OEM shall
have submit NABL / CPRI / ERDA accrediated lab type test
certificate before execution. All as per pre approved by Engineer
in charge. For additional technical parameters of products/ work ,
refer Annexure "A" attached with this BSR .

21.8.1 1.0 HP, 3-Ø, (5 - 12)Mtr, (333 - 95) LPM each 27896.0
21.8.2 2.0 HP, 3-Ø, (5 - 18)Mtr, (480 - 66) LPM each 43033.0
21.8.3 3.0 HP, 3-Ø, (5 - 20)Mtr, (810 - 126) LPM each 46149.0
21.8.4 5.0 HP, 3-Ø, (5 - 24)Mtr, (1170 - 174) LPM each 85323.0

Chapter E- 21 Page 115


P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-21

Code No. Description Unit Complete


Rate
21.9 SITC of Drain Sewage pump Non-clog fully floodable submersible
pump suitable to handle raw sewage suitable for up to 40 mm
solid with Cast iron CED coated Impellor, CI body & housing, SS
shaft, Mechanical seal etc. as required. Pump shall have following
HP Rating, phase, Head, minimum Discharge respectively complete
in all respect. Appropriate type test certificate / OEM test report
shall be submitted.All as per pre approved by Engineer in charge.
For additional technical parameters of products/ work , refer
Annexure "A" attached with this BSR .

21.9.1 1.0 HP, 3-Ø, (6 - 12)Mtr, (333 - 45) LPM Each 24938.0
21.9.2 2.0 HP, 3-Ø, (8 - 16)Mtr, (375 - 120) LPM Each 47935.0
21.9.3 3.0 HP, 3-Ø, (8 - 20)Mtr, (590 - 220) LPM Each 51322.0

21.1 SITC of Pressure boosting pump with 24 Ltr. MS Tank, pressure


switch, pressure gauge, and all standard fittings fully automatic ON
/ OFF system, 2900 RPM with stainless steel casing, & impellor
suitable for following capacity complete in all respect. Appropriate
type test certificate / OEM shall have submit NABL / CPRI / ERDA
accrediated lab type test certificate before execution. All as per
pre approved by Engineer in charge. For additional technical
parameters of products/ work , refer Annexure "A" attached with
this BSR .

21.10.1 0.5 HP ( 15 - 10 ) Mtr, (24 - 40 ) LPM Each 25654.0


21.10.2 0.75 HP ( 30 - 10 ) Mtr, (09 - 40 ) LPM Each 27717.0
21.10.3 1.0 HP ( 25 - 15 ) Mtr, (30 - 48 ) LPM Each 35723.0
21.10.4 1.5 HP ( 37 - 20 ) Mtr, (24 - 48 ) LPM Each 45565.0

21.11 Providing & Fixing of CI foot valve complete in all respect. All as
per pre approved by Engineer in charge. For additional technical
parameters of products/ work , refer Annexure "A" attached with
this BSR .
21.11.1 Rocket type (for bore well) 50/ 60 mm Each 1321.0
21.11.2 Handi type (for open well) 80/ 100 mm Each 2088.0

21.12 Supply & fixing of GI pipes confirming to IS : 1239 P - 1 ( 2004 )


with flanges duly screwed & welded including rubber washer, nuts
& bolts of 8mm dia complete in all respect.All as per pre approved
by Engineer in charge. For additional technical parameters of
products/ work , refer Annexure "A" attached with this BSR .

21.12.1 B class 32mm dia P mtr 513.0


21.12.2 B class 40mm dia P mtr 608.0

Chapter E- 21 Page 116


P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-21

Code No. Description Unit Complete


Rate
21.12.3 B class 50mm dia P mtr 848.0
21.12.4 B class 65mm dia P mtr 1080.0
21.12.5 B class 80mm dia P mtr 1340.0
21.12.6 B class 100mm dia P mtr 1848.0

21.13 SITC of Contactor OEM Fabricated DOL/Star-Delta Starter panel


with switchgear selection as per Type-2 Cordinatiom Chart and
made out from 1.6 mm thick powder coated CRCA sheet,
enclosure comprising of over load protection relay, short circuit &
single phasing protection, Illuminated ON / OFF push buttons,
ammeter, voltmeter, indicating lamps etc. suitable for following
rating motors complete in all respect. All as per pre approved by
Engineer in charge. For additional technical parameters of
products/ work , refer Annexure "A" attached with this BSR .

21.13.1 For single phase Submersible / Monoblock pump


21.13.1.1 0.5 HP to 1.5 HP (DOL starter) Each 4923.0
21.13.1.2 2.0 HP to 3.0 HP (DOL starter) Each 5406.0

21.13.2 For Three phase Submersible / Mono block pump


21.13.2.1 Upto 3.0 HP ( DOL starter ) Each 7246.0
21.13.2.2 3.0 HP to 5.0 HP ( DOL starter ) Each 10173.0
21.13.2.3 7.5 HP to 10.0 HP ( DOL starter ) Each 13318.0
21.13.2.4 3.0 HP to 5.0 HP ( Star / Delta starter ) Each 14370.0
21.13.2.5 7.5 HP to 10.0 HP ( Star / Delta starter ) Each 18932.0
21.13.2.6 12.5 HP to 15.0 HP ( Star / Delta starter ) Each 21711.00

Chapter E- 21 Page 117


P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-22

Chapter E 22

Air Cooling & Airconditioning

Code No. Description Unit Complete


Rate
22.1 Supply , Installation, Testing and Comissioning of factory assembeled
double skin central evaporative cooling plant having specifications as
per A, B, C, D, E
A. Air washer comprising of 2nos Pre-Filters. First filter shall be 50mm
thick Aluminium wiremesh filter & second filter shall be 50 mm thick
MERV-8 synthetic media filter with efficiency 90 % down to 10 microns.
Both filters to be placed over the common frame.

B. Humidification section comprising of Wet pads 200 mm thick


impregnated cellulose paper media ( Celdec pads ) with 2 bend PVC
eliminator. The End plates of Pad & Eliminator shall be in SS 304
construction. Also, the inner blank offs of Wet section shall be in SS304
construction.
C. Fan Section comprising of belt driven, DIDW Backward curved AMCA
certified centrifugal fan with maximum air outlet velocity of 10m/s
suitable for required cfm at 50 mm static pressure (Total static of the
unit shall be verified by the OEM before the design & supply of the
units). Fan & Motor should be mounted over Aluminium channel of
suitable thickness and should be isolated from the unit's bottom panel
by means of Spring isolators.
D. TEFC High efficiecny IE-3 class motors as required with pulley, belt ,
Guard
E. The unit shall be fabricated with frame work hollow extruded
aluminium profile with 0.80 mm preplasticised GSS on outside and
0.80mm 275gsm plain GSS on inside complete with 25 mm thick CFC free
PUF insulation of minimum 40 kg/cum density sandwiched in between
inner and outer skins. Unit should have MS powder coated legs to give
height to unit's base channel from the floor surface. SS-304 ( 18 g )
Sump, UPVC Internal piping, make up, drain & quick fill and drain
connection, Butterfly/Gate valves for pumps, make up, drain & quick fill
and drain connections of sump, 2 no. Vertical Pumps of suitable capacity
to be placed inside the unit's housing (external pumps are not
acceptable) ,Y strainers and necessary fittings, Concrete Blocks / M S
stand, anti vibration pads etc.as required. All as per pre approved by
Engineer in charge. For additional technical parameters of products/
work , refer Annexure "A" attached with this BSR .

22.1.1 Upto 7500 cfm per cfm 28.0


22.1.2 more than 7500 cfm to 15000 cfm per cfm 26.0

Chapter E -22
Page 118
P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-22

Code No. Description Unit Complete


Rate
22.1.3 more than 15000 cfm to 25000 cfm per cfm 23.0
22.1.4 more than 25000 cfm to 35000 cfm per cfm 20.0
22.2 SITC of Wall mounting cubical type Starter panel made out of 1.6 mm
thick sheet steel powder coated enclosure designed as per Switchgear
OEM type -2 coordination chart and suitable for operation of following
cfm range Air Washer's Blower motor, pump comprising of over load
protection relay, short circuit & single phasing protection, ON / OFF
push buttons, ammeter, voltmeter, indicating lamps, MCB etc. complete
in all respect. All as per pre approved by Engineer in charge. For
additional technical parameters of products/ work , refer Annexure "A"
attached with this BSR .

22.2.1 Upto 7500 cfm Set 14843.0


22.2.2 more than 7500 cfm to 15000 cfm Set 23281.0
22.2.3 more than 15000 cfm to 25000 cfm Set 32394.0
22.2.4 more than 25000 cfm to 35000 cfm Set 39282.0

22.3 Supply , Installation, Testing and Comissioning of wall mounted remote


ON/OFF Push Button station for AHU/Air washers made out from
powder quoted CRCA sheet of 16 SWG , illuminated ON/OFF push
button including making connections etc as required complete in all
respect. All as per pre approved by Engineer in charge. For additional
technical parameters of products/ work , refer Annexure "A" attached
with this BSR . Set 6412.0

22.4 P & F of Fire retardent flexible canvass connection made of fibreglass


weave having silver grey silicon rubber coating, of height 200 mm with
sufficient fold to avoid transmission of vibration with GI frame ,Gasket
Nut Bolts for air cooling Plants/AHU/FCU etc as required. All as per pre
approved by Engineer in charge. For additional technical parameters of
products/ work , refer Annexure "A" attached with this BSR .
Sq Mtr 2023.0

Chapter E -22
Page 119
P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-22

Code No. Description Unit Complete


Rate
22.5 SITC of VFD OEM fabricated VFD cum Bypass starter panel Confirming to
IEC60721-3-3, IEC60068-2-60 & IEC60068-2 for variable torque
applications, 3C3 avg., 200% torque producing capability at min freq of
0.5 Hz, integrated with 3 to 5% of input reactor or built in DC reactor,
Max output frequency 400Hz, built in braking chopper till 30KW, built in
RS485 Modbus RTU, Min 7DI, 2DO, 2AI, 1AO, onboard control supply of
24V -150 mA for external operations, RJ45 port, Monitoring parameters
– V, I, Torque, Freq, RPM, Watt Hour, DC bus voltage, Analog input V or
mA, I/O Status, PID loop monitoring, Torque speed, speed limit, Cooling
fan, Protection functions – Ground fault, Over current, Overload, UV/OV,
Under/over torque, I/P & O/P phase loss, DBR O/L, inverter over hit
alarm, DC bus charge LED indication, heatsink thermistor open
detection, stall prevention, fault history of min 4 last faults. Bypass
starter shall be provided as per type 2 coordination etc. as required. All
as per pre approved by Engineer in charge. For additional technical
parameters of products/ work , refer Annexure "A" attached with this
BSR .

22.5.1 1.5 KW Each 70760.0


22.5.2 2.2 KW Each 73311.0
22.5.3 3.7 KW Each 79317.0
22.5.4 5.5 KW Each 92954.0
22.5.5 7.5 KW Each 100959.0
22.5.6 11.0 KW Each 105997.0
22.5.7 15.0 KW Each 122604.0
22.5.8 18.5 KW Each 140750.0

22.6 Supply , Installation, Testing and Comissioning of site fabricated ducting


made from GI sheet metal conforming to IS:277 with a zinc coating
grade not less than 120 GSM (both side inclusive) & fabricated as per
IS:655 and as per approved drawings & designs including the cost of
hangers, supports, angle, expansion fasteners , closed cell neoprene
gasket T&P etc. as required of following thickness. Test Certificate for
Galavanizing with lot no. to be submitted. All as per pre approved by
Engineer in charge. For additional technical parameters of products/
work , refer Annexure "A" attached with this BSR .

22.6.1 0.60 mm Sqm 970.0


22.6.2 0.80mm Sqm 1155.0
22.6.3 1.00mm Sqm. 1386.0
22.6.4 1.25mm Sqm. 1663.0

Chapter E -22
Page 120
P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-22

Code No. Description Unit Complete


Rate
22.7 Supply , Installation, Testing and Comissioning of site fabricated ducting
made from aluminium sheet conforming to IS:737, Grade 31000
fabricated as per IS:655 and as per approved drawings & designs
including the cost of hangers, supports , angle , expansion fasteners ,
closed cell neoprene gasket T&P etc. as required of following thickness.
All as per pre approved by Engineer in charge. For additional technical
parameters of products/ work , refer Annexure "A" attached with this
BSR .
22.7.1 0.60 mm Sq Mtr 1236.0
22.7.2 0.80mm Sq Mtr 1540.0
22.7.3 1.00mm Sq Mtr 1872.0
22.7.4 1.20mm Sq Mtr 2189.0

22.8 Supply , Installation, Testing and Comissioning of factory fabricated


SMACNA standard ducting made from GI sheet metal conforming to
IS:277 with a zinc coating grade of 120GSM (both side inclusive) &
fabricated as per IS:655 and as per approved drawings & designs
including the cost of hangers, supports, angle, expansion fasteners ,
closed cell neoprene gasket T&P etc. as required of following thickness.
All as per pre approved by Engineer in charge. For additional technical
parameters of products/ work , refer Annexure "A" attached with this
BSR .
22.8.1 0.60mm Sqm 1295.0
22.8.2 0.80mm Sqm 1552.0
22.8.3 1.00mm Sqm. 1903.0
22.8.4 1.25mm Sqm. 2301.0

22.9 Supplying, installing, testing and balancing of extruded Aluminium


Powder coated supply/return Grilles with fixed bars at front having 0 /
15 / 30 / 45 degrees deflection as required. with Flange size 20 mm with
rounded edges including fixing with steel screws etc. complete in all
respect. All as per pre approved by Engineer in charge. For additional
technical parameters of products/ work , refer Annexure "A" attached
with this BSR . Sq.m 6345.0

22.10 Supplying, installing, testing and balancing of double louvered of


extruded Aluminium Powder coated supply/return air grills of various
sizes, Each grill shall be with fixed aerofoil shaped horizontal front bar at
0 deflection and back adjustable vertical louvers, air distribution grid for
straightening the air flow through the collar and register including fixing
with steel screws etc. complete in all respect. All as per pre approved by
Engineer in charge. For additional technical parameters of products/
work , refer Annexure "A" attached with this BSR .

Chapter E -22
Page 121
P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-22

Code No. Description Unit Complete


Rate
22.10.1 Supply air grill with key operated volume control damper Sqm. 10530.0
22.10.2 Return air grill without volume control damper Sqm. 8438.0

22.11 Supplying, installing, testing and balancing of extruded Aluminium


powder coated Air Diffuser and complete with Flush, 20mm flanges with
PVC/neoprene gasket, anti – smudge frame and removable inner core to
facilitate the adjustable of air control damper, square/round/
rectangular as required.including fixing with steel screws etc. complete
in all respect. All as per pre approved by Engineer in charge. For
additional technical parameters of products/ work , refer Annexure "A"
attached with this BSR .

22.11.1 Supply Air Diffuser with Volume Control damper Sqm. 12219.0
22.11.2 Return Air Diffuser without Volume Control damper Sqm. 9855.0

22.12 Supplying, installing and balancing of extruded Aluminium powder


coated fresh air inlet louvers with bird screen & volume control damper
fixing with steel screws etc. complete in all respect. All as per pre
approved by Engineer in charge. For additional technical parameters of
products/ work , refer Annexure "A" attached with this BSR .
Sqm. 8371.0

22.13 Supply , installation, testing & balancing of 20 Gauge G I Damper with


brass bushes and 6" pitch multiblade box type galvanised sheet steel
construction volume control damper for Ducting and air washers to be
provided with suitable links and quadrants for control of volume of air as
per specifications complete as required. All as per pre approved by
Engineer in charge. For additional technical parameters of products/
work , refer Annexure "A" attached with this BSR . Sq Mtr 5128.0

22.14 Supply and fixing of acoustic lining of ducts with chemically cross link
Oxide accetate foam open cell structure Acoustic Insulation with density
30 Kg / Sqm, UV protected and Class O Fire propperty Water Vapour
absorption 0.002 gm / Sqcm, including cost of adhesive etc. complete in
all respect. All as per pre approved by Engineer in charge. All as per pre
approved by Engineer in charge. For additional technical parameters of
products/ work , refer Annexure "A" attached with this BSR .

22.14.1 10 mm thick Sqm 755.0


22.14.2 15 mm thick Sqm. 978.0
22.14.3 25 mm thick Sqm. 1423.0

Chapter E -22
Page 122
P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-22

Code No. Description Unit Complete


Rate
22.15 Supply and fixing duct insulation with 50 mm thick Expanded
Polystyrene Thermocol (ESP) sheet of density 24 kg/cu.m after applying
two coats of cold setting adhesive (CPRX Compound) and binding sheet
with chicken wire mesh and applying cement mortar plaster (1:4)
including primer & painting (suitable for outdoor aplication) matching
with building colour or as per direction of Engineer incharge as required.
All as per pre approved by Engineer in charge. For additional technical
parameters of products/ work , refer Annexure "A" attached with this
BSR .
Sqm. 985.0

22.16 Supply and fixing aluminium foil faced 50 mm thick Rock wool insulation
of density 36 kg/cu.m after applying two coats of cold setting adhesive
(CPRX Compound) sealing all joints with self adhesive tape & finished
with 26 G Aluminium cladding. complete in all respect. (For Outdoor
applications-air conditioning ducts) All as per pre approved by Engineer
in charge. For additional technical parameters of products/ work , refer
Annexure "A" attached with this BSR .
Sqm. 1126.0

22.17 Supply & fixing of external thermal closed-cell Nitrile rubber Insulation
material FM/UL approved with high water vapor diffusion resistance and
low thermal conductivity should be certified 'Class O' in Fire Propagation
as per BS 476 Part 6 in form of sheet on duct including cost of adhesive
(CPRX Compound) complete as required. All as per pre approved by
Engineer in charge.

22.17.1 9mm thick for indoor Application Sqm 718.0


22.17.2 13mm thick for indoor Application Sqm 926.0
22.17.3 13mm thick for Outdoor Application with 26 SWG Aluminium Cladding
Sqm 1148.0
22.17.4 19mm thick for Outdoor Application with 26 SWG Aluminium Cladding
Sqm 1460.0

22.18 Supplying, installing of external thermal closed cell cross linked


polyethelene (XLPE) foam insulation made out from non-fibrous, fire
retardant (FR), closed cell, tri-dimensional chemically crosslinked
polyethylene foam. should be certified 'Class O' in Fire Propagation and
'Class 1' in Surface Spread of Flame as per BS 476 Part 6 & Part 7
respectively in the form of sheet on ducts including cost of adhesive,
tape complete as required. All as per pre approved by Engineer in
charge. For additional technical parameters of products/ work , refer
Annexure "A" attached with this BSR .

Chapter E -22
Page 123
P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-22

Code No. Description Unit Complete


Rate
22.18.1 9mm thick Sqm 680.0
22.18.2 13mm thick Sqm 814.0
22.18.3 25 mm thick 1096.0
22.19 Supply and fixing duct insulation with 50 mm thick Expanded
Polystyrene Thermocol (ESP) sheet of density 24 kg/cu.m after applying
two coats of cold setting adhesive (CPRX Compound) and binding sheet
with chicken wire mesh and applying 26 G aluminium cladding complete
as required. All as per pre approved by Engineer in charge. For
additional technical parameters of products/ work , refer Annexure "A"
attached with this BSR . Sq Mtr 1086.0

22.20 Supply , Installation, Testing and Comissioning of expanded polysterene


over deck insulation having thickness of 50 mm and density of 36 Kg /
m3 including binding of fibre cloth and applying of two coats of UV paint
suitable for exposed atmosphere complete as required. All as per pre
approved by Engineer in charge. For additional technical parameters of
products/ work , refer Annexure "A" attached with this BSR . Sq Mtr 1197.0

22.21 Supplying and fixing of thermal insulation on exposed roof (underdeck)


with 25 mm thick Cross Linked Closed Cell Polyethylene FR-XPE
insulation of density 33 Kg/m³ with adhesive etc. as required & finally
fixed with the help of rawl plug, dash fasteners & adhesive in ceiling of
pieces in size of 900x900 mm or 1200x1200 mm. etc. as required. All as
per pre approved by Engineer in charge. For additional technical
parameters of products/ work , refer Annexure "A" attached with this
BSR . Sq Mtr 1171.0

22.22 Supplying, fixing acoustic lining on wall and ceiling of AHU rooms with
50mm thick, density 32 kg/cu.m resin bonded glass fiber insulation
friction fixed in 610mm x 610 mm frame work made of 25X50X50X50X25
mm made out of 0.6mm thick GI sheet U shaped channel and covered
with reinforced fiber glass tissue and finished with 0.80 mm perforated
aluminium sheet etc. complete as required. All as per pre approved by
Engineer in charge. For additional technical parameters of products/
work , refer Annexure "A" attached with this BSR . Sq Mtr 1092.0

Chapter E -22
Page 124
P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-22

Code No. Description Unit Complete


Rate
22.23 Supply , Installation, Testing and Comissioning of Window type Air
conditioners as per BEE star rating complete with copper power cable
upto 3 Mtr, wireless Remote, suitable for working between 230 V +/-
10% with low & high voltage cutoff and 50 Hz ,1 phase AC supply
capable of performing, cooling, dehumidification, air circulation R-32/R-
410 Green Refrigerant with Scroll / rotary compressor complete with
fixing including T&P & labour etc as required complete in all respect as
specified of following capacity. All as per pre approved by Engineer in
charge. For additional technical parameters of products/ work , refer
Annexure "A" attached with this BSR .

22.23.1 1.5 TR ISEER not less then 3.0 Each 32340.0


22.23.2 1.8 TR Each 35338.0
22.24 Supply , Installation, Testing and Comissioning of Inverter type Air
Cooled Hi Wall split type Air conditioners with latest star rating system
as per BEE amended upto date complete with Indoor unit(IDU), Out door
unit (ODU), surface / concealed copper Refrigerant piping with insulation
(closed cell elastomeric nitrile rubber tubular pipe section) upto 3 Mtr
(IDU to ODU), copper power cable upto 3.5 Mtr (IDU to ODU), R-32/R-
410 Green Refrigerant, wireless Remote control, suitable for working
between 230V +/- 10% with low & high voltage cutoff and 50 hz , single
phase AC supply capable of performing cooling, dehumidification, air
circulation of following capacity with Scroll / rotary compressor. All as
per pre approved by Engineer in charge. For additional technical
parameters of products/ work , refer Annexure "A" attached with this
BSR .

22.24.1 1.0 TR ISEER not less then 3.8 Each 40096.0


22.24.2 1.0 TR ISEER not less then 4.6 Each 50225.0
22.24.3 1.5 TR ISEER not less then 3.8 Each 48875.0
22.24.4 1.5 TR ISEER not less then 4.6 Each 58329.0
22.24.5 1.8 TR ISEER not less then 3.8 Each 62380.0
22.24.6 1.8 TR ISEER not less then 4.6 Each 66432.0
22.24.7 2.0 TR ISEER not less then 3.8 Each 63731.0
22.24.8 2.0 TR ISEER not less then 4.6 Each 67783.0

Chapter E -22
Page 125
P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-22

Code No. Description Unit Complete


Rate
22.25 Supply , Installation, Testing and Comissioning of Air Cooled Floor
standing Tower type split Air conditioners complete with Indoor
unit(IDU), Out door unit (ODU), surface / concealed copper Refrigerant
piping with insulation (closed cell elastomeric nitrile rubber tubular pipe
section) upto 3 Mtr (IDU to ODU), copper power cable upto 3.5 Mtr (IDU
to ODU), R-32/R-410 Green Refrigerant, wireless Remote control,
suitable for working between 415 V +/- 10% ,3 phase 50 Hz AC Supply
with low & high voltage cutoff and capable of performing cooling,
dehumidification, air circulation of following capacity with Scroll / rotary
compressor. All as per pre approved by Engineer in charge. For
additional technical parameters of products/ work , refer Annexure "A"
attached with this BSR .

22.25.1 3.0/3.3 TR Each 132985.0


22.25.2 3.6 TR Each 146490.0
22.25.3 4.0 TR Each 153243.0
22.25.4 4.6 TR Each 159996.0
22.26 SITC of air cooled ducted split type air conditioning machine with each
having a capacity and details as mentioned below suitable for operation
on factory charged R-32/R-410A Green refrigerant comprising of Scroll
/rotary type compressor hermatically sealed complete with automatic
capacity, safety switches, lubrication system, Suitable capacity squirrel
cage induction motor with class 'B' insulation suitable for operation on
sigle / three phase supply, 50 Hz, A.C. supply for Blower motor,
Necessary drive arrangement for blower motor, Matching Air cooled
condenser with necessary fittings for refrigerant piping connections,
necessary structural support for mounting condensers, Microprocessor
based control panel complete with accessories, machine isolation /
disconnect switch, valves and accessories to inter connect compressor
and condender including pressure testing, vacuum. Necessary starters
suitable for Indoor & outdoor unit complete with O/L , U/V, phase
reversal protection, single phase preventors etc complete as required.
All as per pre approved by Engineer in charge. For additional technical
parameters of products/ work , refer Annexure "A" attached with this
BSR .

22.26.1 3.0 TR Each 78962.0


22.26.2 4 TR Each 101908.0
22.26.3 5.5 TR Each 162002.0
22.26.4 8.5 TR Each 226789.0
22.26.5 11 TR Each 289571.0
22.26.6 16.5 TR Each 445488.0

Chapter E -22
Page 126
P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-22

Code No. Description Unit Complete


Rate
22.27 Supply , Installation, Testing and Comissioning of Air Cooled Cassette
type Air conditioners complete with Indoor unit(IDU), Out door unit
(ODU), R-32/R410A Green Refrigerant, wireless Remote, inbuilt drain
pump, suitable for 400/230V, +/- 10% 50 Hz ,1 /3 phase AC supply,
apable of performing cooling, dehumidification, Air circulation,
filteration & ventilation of following capacity with Scroll /rotary/twin
rotary compressor. All as per pre approved by Engineer in charge. For
additional technical parameters of products/ work , refer Annexure "A"
attached with this BSR .

22.27.1 Inverter Type


22.27.1.1 1.5 TR with ISEER not less then 3.5 (compact 2x2) Each 92481.0
22.27.1.2 1.8 ISEER not less then 3.5 (compact 2x2) Each 107337.0
22.27.1.3 1.5 TR ISEER not less then 3.5 Each 91130.0
22.27.1.4 1.8 TR ISEER not less then 3.5 Each 104636.0
22.27.1.5 2.0 TR ISEER not less then 3.5 Each 106662.0
22.27.1.6 3.0 TR Each 111389.0
22.27.1.7 3.8 / 4.0 TR Each 124894.0
22.27.2 Non Inverter
22.27.2.1 1.5 TR with ISEER not less then 3.0 (compact 2x2) Each 84377.0
22.27.2.2 1.8 ISEER not less then 3.0 (compact 2x2) Each 92481.0
22.27.2.3 1.5 TR ISEER not less then 3.0 Each 91130.0
22.27.2.4 1.8 TR ISEER not less then 3.0 Each 100584.0
22.27.2.5 2.0 TR ISEER not less then 3.0 Each 103285.0
22.27.2.6 3.0 TR Each 108688.0
22.27.2.7 3.8 / 4.0 TR Each 120843.0

Chapter E -22
Page 127
P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-22

Code No. Description Unit Complete


Rate
22.28 Supply, Installation, Testing & Commissioning of modular type
Variable Refrigerant Flow/Variable Refrigerant Volume air cooled
Outdoor units suitable for cooling and heating, having 100%
hermetically sealed inverter type Scroll Compressor(s) with and
minimum two compressors along with two Condensing fan, above
14/18 HP modules, microprocessor based Controller, Side / top
discharge type condensing unit(s), with R-410 A Refrigerant,
vibration isolators, with suitable foundation etc. complete as
required. The unit shall deliver the rated capacity at AHRI
Conditions and work even at 50°C ambient temperature without
tripping. The unit shall be suitable to work on 400V +/- 10%, 3 Phase,
50Hz AC power supply. The unit shall be filled with first charge of
the refrigerant and ready for use as required. The EER at 100% load with
AHRI conditions shall not be less than 3.5 and Including OEM supplied
Piping connection Kit etc. as required. All as per pre approved by
Engineer in charge. For additional technical parameters of products/
work , refer Annexure "A" attached with this BSR .

per HP 24270.0

22.29 Supply, installation, testing and commissioning of following


minimum capacity 4-way flow VRV/VRF Cassette Type Indoor ceiling
mounted unit equipped with synthetic washable media pre-filter, fan
section with low noise fan/dynamically balanced blower, multispeed
motor, coil section with DX Copper coil, electronic expansion valve,
outer cabinet, drain pump, grill, necessary supports, vibration
isolation, Corded remote control etc., suitable for operation on
single phase 230 V ± 10%, 50Hz AC supply, complete, as required. The
unit shall have automatic force shut down valve in case of fire on
receiving signal from BMS System. The cooling capacity of indoor
unit will be at air inlet conditions of 27 Degree C DB and 19 Degree C WB
temperature. (Make will be same as of Outdoor). All as per pre approved
by Engineer in charge. For additional technical parameters of products/
work , refer Annexure "A" attached with this BSR .

22.29.1 0.8 TR Each 51234.0


22.29.2 1 TR Each 52720.0
22.29.3 1.2 TR Each 55691.0
22.29.4 1.6 TR Each 56785.0
22.29.5 2 TR Each 58230.0
22.29.6 2.4 TR Each 64943.0
22.29.7 3.2 TR Each 66172.0
22.29.8 4 TR Each 69278.0

Chapter E -22
Page 128
P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-22

Code No. Description Unit Complete


Rate
22.29.9 4.6 TR Each 71588.0

22.30 Supply, installation, testing and commissioning of following


minimum capacity 4-way flow compact VRV/VRF Cassette ( 2' x 2' ) Type
Indoor ceiling mounted unit equipped with synthetic washable media
pre-filter, fan section with low noise fan/dynamically balanced blower,
multispeed motor, coil section with DX Copper coil, electronic
expansion valve, outer cabinet, drain pump, grill, necessary
supports, vibration isolation, Corded remote control etc., suitable
for operation on single phase 230 V ± 10%, 50Hz AC supply, complete,
as required. The unit shall have automatic force shut down valve in case
of fire on receiving signal from BMS System. The cooling capacity of
indoor unit will be at air inlet conditions of 27 Degree C DB and 19
Degree C WB temperature. (Make will be same as of Outdoor) All as per
pre approved by Engineer in charge. For additional technical parameters
of products/ work , refer Annexure "A" attached with this BSR .

22.30.1 0.6 TR Each 57879.0


22.30.2 0.8 TR Each 61418.0
22.30.3 1 TR Each 62093.0
22.30.4 1.2 TR Each 66550.0
22.30.5 1.6 TR Each 67495.0
22.31 Add Extra for OEM make Wireless remote in place of Wired remote
including receiver as required. Each 5396.0
22.32 Supply, installation, testing and commissioning of following
minimum capacity VRV/VRF High wall type Indoor unit equipped
with and comfort washable synthetic media pre-filter, fan section with
low noise fan/dynamically balanced blower, multispeed motor, coil
section with DX copper coil, electronic expansion valve, outer cabinet,
cord less remote control, drain pan, necessary accessories etc.,
suitable for operation on 230 V ± 10%, 50 Hz, single phase AC
supply, complete as required. The unit shall have automatic force shut
down valve in case of fire on receiving signal from BMS System.
The cooling capacity of indoor unit will be at air inlet conditions of
27 Degree C DB and 19 Degree C WB temperature. (Make will be same
as of Outdoor) All as per pre approved by Engineer in charge. For
additional technical parameters of products/ work , refer Annexure "A"
attached with this BSR .

22.32.1 0.6 TR Each 34478.0


22.32.2 0.8 TR Each 34896.0
22.32.3 1.0 TR Each 35572.0

Chapter E -22
Page 129
P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-22

Code No. Description Unit Complete


Rate
22.32.4 1.2 TR Each 36787.0
22.32.5 1.65 TR Each 37867.0
22.32.6 2 TR Each 38948.0
22.33 Supply, installation, testing and commissioning of following
minimum capacity and external static pressure VRF/VRV ceiling
mounted ductable type Indoor unit equipped with washable
synthetic media pre-filter, fan section with low noise
fan/dynamically balanced blower, multispeed motor, coil section
with DX copper coil, electronic expansion valve, corded remote
control, outer cabinet, vibration isolators, drain pan, drain pump, other
necessary supports etc., suitable for operation on single phase AC supply
230 V ± 10%, 50 Hz complete as required. The unit shall have
automatic force shut down valve in case of fire on receiveing signal
from BMS System. The cooling capacity of indoor unit will be at air inlet
conditions of 27 Degree C DB and 19 Degree C WB temperature. All as
per pre approved by Engineer in charge. For additional technical
parameters of products/ work , refer Annexure "A" attached with this
BSR .

22.33.1 Low static ductable units (19 to 30 pascal external static pressure)

22.33.1.1 0.8 TR Each 46413.0


22.33.1.2 1 TR Each 46899.0
22.33.1.3 1.2 TR Each 48182.0
22.33.1.4 1.6 TR Each 49803.0
22.33.1.5 2 TR Each 52909.0
22.33.1.6 2.4 TR Each 58446.0
22.33.2 Mid Static Ductable units ( 35 to 77 pascal external static pressure)

22.33.2.1 3.2 TR Each 67887.0


22.33.2.2 4 TR Each 76517.0
22.33.2.3 4.6 TR Each 88672.0
22.33.3 High Static Ductable units ( 78 pascal or above external static pressure)

22.33.3.1 5.5 TR 128778.0


22.33.3.2 6.6 TR Each 138353.0
22.33.3.3 8.0 TR Each 148476.0
22.33.3.4 13.0 TR Each 205842.0
22.33.3.5 16.0 TR Each 239566.0

Chapter E -22
Page 130
P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-22

Code No. Description Unit Complete


Rate
22.34 Supply, installation, testing & commissioning of Group controller for
monitoring the status and working condition of all indoor and outdoor
units, The controller shall act as an advanced air conditioning
management system to given complete control of VRV/VRF air
conditioning equipment with Starting/stopping of air-conditioning as a
zone or group of individual units. Temperature setting for each Indoor
units of zone, Switching between temperature control modes, switching
Each 43192.0
of the fan speed and direction of airflow, enabling/disabling of individual
remote controller operation, Alarm code display in case of any problem.
It shall be able to control up to 64 (max. 512 if required) number of
Indoor units. All as per pre approved by Engineer in charge. For
additional technical parameters of products/ work , refer Annexure "A"
attached with this BSR .

22.34.1 Add Extra for extenders/adaptors compatible with central controller to


Each 17517.0
enable the controller to work with 128 IDU's
22.34.2 Add Extra for extenders/adaptors compatible with central controller to
Each 32360.0
enable the controller to work with 256 IDU's
22.34.3 Add Extra for extenders/adaptors compatible with central controller to
Each 79563.0
enable the controller to work with 512 IDU's
22.35 Supply, installation, Testing & commissioning of VRV/VRF compatible
OEM make AHU KIT' including expansion valve and controller for Each 59358.0
connecting AHU with VRF.
22.36 Supplying and installation of high-pressure grade required size OEM
make copper connection Y or T Joints / refnet for liquid and suction line
complete erected on wall/ceiling with supports/raceways, Nitrile rubber
insulation, painting etc. with brazing and testing for leakages confirming
Each 6881.0
the normal operation of the VRV / VRF air conditioning system. All as per
pre approved by Engineer in charge. For additional technical parameters
of products/ work , refer Annexure "A" attached with this BSR .

22.37 Gas charging of VRF/VRV system with R410A refrigerant gas. Before gas
charging system shall be flushed with high purity Nitrogen Gas to
remove carbon content, dirt particles to make sure that there is no
chance of mixing any impurity with Refrigerant Gas. Thereafter System
shall be tested with Nitrogen Gas at 1.5 Times of working pressure of
R410 Refrigerant Gas to ensure leakproof system. Whole system shall be
Kg 1821.0
Vacuumed up to 500-micron level which ensures the zero-moisture
content level in piping to ensure better cooling efficiency and long life of
the system. All as per pre approved by Engineer in charge. For additional
technical parameters of products/ work , refer Annexure "A" attached
with this BSR .

Chapter E -22
Page 131
P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-22

Code No. Description Unit Complete


Rate
22.38 Supplying and drawing flexible / stranded bare copper conductor, PVC /
XLPE insulated, overall aluminium mylar tape shielded ATC drain wire
and outer PVC sheathed industrial Instrumentation (shielded)cables
voltage grade 300/500 V as per BS /EN 50288-7 in existing surface or
recessed PVC/ MS conduit/casing capping / Cable tray / Open Duct
making connections, testing etc. as required. OEM Must have its own in
house NABL lab setup for all testing facilities for cables. All as per pre
approved by Engineer in charge. For additional technical parameters of
products/ work , refer Annexure "A" attached with this BSR .

22.38.1 Un Armoured
22.38.1.1 2 core x 1.0 Sq.mm Mtr. 75.0
22.38.1.2 2 core x 1.5 Sq.mm Mtr. 94.0
22.38.1.3 2 core x 2.5 Sq.mm Mtr. 135.0
22.38.1.4 4 core x 2.5 Sq.mm Mtr. 232.0
22.38.2 Armoured
22.38.2.1 2 core x 1.0 Sq.mm Mtr. 135.0
22.38.2.2 2 core x 1.5 Sq.mm Mtr. 158.0
22.38.2.3 2 core x 2.5 Sq.mm Mtr. 204.0
22.38.2.4 4 core x 2.5 Sq.mm Mtr. 329.0
22.39 Supply, installation, testing and comissioning of interconnecting copper
refrigerant piping of DHE Grade C12200- ASTM B68, B75, chemical
composition of copper %- 99.0 Min and Phosphorus %- 0.015 to 0.040 .
For Annealed copper tube :- Tensile strength = 210 Mpa wih elongation
% = 40 Min . Ink Mark Brand Printing on Hard Tubes should be present.
duly insulated with tubular elastomeric nitrile rubber FM/UL approved
with high water vapor diffusion resistance and low thermal conductivity
should be certified 'Class O' in Fire Propagation as per BS 476 Part 6
including chase cutting andfilling with mortar, Slotted channel supports
mounted on 10 mm threaded rod at suitable spacing the exposed piping
shall be wrapped with glass woven cloth and lag coating for vapour
barrier and weather protection. Joints shall be covered with nitrile
rubber tape of 3 mm thick complete as required of following sizes. All as
per pre approved by Engineer in charge. For additional technical
parameters of products/ work , refer Annexure "A" attached with this
BSR .

22.39.1 41.1 mm O.D., wall thinkness ≥ 1.4mm (insulation – 19 mm thick) Mtr. 4316.0
22.39.2 38 mm O.D., wall thinkness ≥ 1.4mm (insulation – 19 mm thick) Mtr. 4019.0
22.39.3 34.9 mm O.D., wall thinkness ≥ 1.4mm (insulation – 19 mm thick) Mtr. 3399.0
22.39.4 28.6 mm O.D., wall thinkness ≥ 1.2mm (insulation – 19 mm thick) Mtr. 2563.0
22.39.5 25 mm O.D., wall thinkness ≥ 1.2mm (insulation – 19 mm thick) Mtr. 2124.0
22.39.6 22.2 mm O.D., wall thinkness ≥ 1.0mm (insulation – 19 mm thick) Mtr. 1821.0

Chapter E -22
Page 132
P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-22

Code No. Description Unit Complete


Rate
22.39.7 19.1 mm O.D., wall thinkness ≥ 1.0mm (insulation – 13 mm thick) Mtr. 1295.0
22.39.8 15.9 mm O.D., wall thinkness ≥ 0.8mm (insulation – 13 mm thick) Mtr. 1066.0
22.39.9 12.7 mm O.D., wall thinkness ≥ 0.8mm (insulation – 13 mm thick) Mtr. 728.0
22.39.10 9.5 mm O.D., wall thinkness ≥ 0.8mm (insulation – 13 mm thick) Mtr. 553.0
22.39.11 6.4 mm O.D., wall thinkness ≥ 0.8mm (insulation – 13 mm thick) Mtr. 383.0

22.40 Providing & Fixing of IS : 4985 - 2000 Class -4 (10 Kgf / Sqcm) UPVC drain
water piping with fittings (IS:7834 & 10Kgf/sqcm) like elbow, socket,
Tee, solvent cement jointing, support with MS hanger on ceiling or
recessed in wall with chasing & plastering with 6 mm thick closed cell
elastomeric nitrile rubber insulation including leakage testing etc. as
required of following Nominal sizes. All as per pre approved by Engineer
in charge. For additional technical parameters of products/ work , refer
Annexure "A" attached with this BSR .

22.40.1 20 mm Mtr. 189.0


22.40.2 25 mm Mtr. 229.0
22.40.3 32 mm Mtr. 296.0
22.40.4 40 mm Mtr. 350.0
22.40.5 50 mm Mtr. 431.0
22.40.6 63 mm Mtr. 526.0

22.41 Supply, Fixing and testing of following capacity ISO certified company
made wall mounted stabilizer having output voltage variation from 200
V to 250 V(+/-5%) with input voltage variation from 170 V to 260 V, time
delay facility from 2 to 4 minute and high cutoff at 270 V with providing
of 16 Amp /20 Amp Industrial plug top making connection etc complete
in all respect. All as per pre approved by Engineer in charge. For
additional technical parameters of products/ work , refer Annexure "A"
attached with this BSR .

22.41.1 3 kVA Each 2970.0


22.41.2 4 kVA Each 3375.0
22.41.3 5 kVA Each 4185.0

22.42 Making hole in stone masonary/ RCC wall/ RCC slab with core cutter for
accomodating refrigerant pipe/ drain pipe/ MS pipe/ cables etc of
following dia
22.42.1 50 mm dia per running inch length
per inch 80.0
22.42.2 100 mm dia per running inch length
per inch 160.0
22.42.3 150 mm dia per running inch length
per inch 241.0

Chapter E -22
Page 133
P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-22

Code No. Description Unit Complete


Rate
22.42.4 200 mm dia per running inch length
per inch 334.0

22.43 Providing and making wall openings in existing stone / Brick masonary
partition wall complete with all requited T & P , Scafolding and providing
Cu. Ft. 738.0
lintel of required size and strength, repairing ,plastering and cleaning
the site debrises as required.

22.45 Supply & fixing MS powder coated stand suitable for 1.0/1.5/ 2.0 Tr
outdoor type of Split AC. All as per pre approved by Engineer in charge.
Each 580.0
For additional technical parameters of products/ work , refer Annexure
"A" attached with this BSR .

22.46 Supply & fixing MS powder coated stand suitable for 2.5/3.0/4.0 Tr
outdoor type of Split/Ductable/Tower AC. All as per pre approved by
Engineer in charge. For additional technical parameters of products/ Each 1349.0
work , refer Annexure "A" attached with this BSR .

22.47 P & F of trap door for AHU / FCU's in existing false ceiling duly made
from 12 mm thick laminated board, hinged with wooden frame of cheed
wood size 50mm x 80mm, Frame suspended with MS strip 25 x 3 mm
with ancor fastner min 8 supports from ceiling, Hinges, Locking
arrangement etc as required. All as per pre approved by Engineer in
charge. For additional technical parameters of products/ work , refer
Annexure "A" attached with this BSR .
Sq Mtr 5055.0

22.48 SITC of Condensate water Drain pump suitable to Install with Existing
Split type AC Indoor unit , single phase, 230V, including all acessories of
pump like discharge tube, filter, reservoir etc. as required. All as per pre
approved by Engineer in charge. For additional technical parameters of
products/ work , refer Annexure "A" attached with this BSR .
Each 6746.0
22.49 SITC of VRF OEM manufactured treated fresh air unit (TFA) equipped
with pre-filter, fan section with low noise fan, multispeed motor, coil
section with DX coil, outer cabinet, insulated drain pan, pipe connections
etc. of following Nominal capacities with Tolerance +/- 5%. All as per pre
approved by Engineer in charge. For additional technical parameters of
products/ work , refer Annexure "A" attached with this BSR .

22.49.1 4.12 TR/635 CFM Each 70176.0


22.49.2 6.6 TR/988 CFM Each 107952.0
22.49.3 8.25 TR/1230 CFM Each 126833.0

Chapter E -22
Page 134
P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-22

Code No. Description Unit Complete


Rate
22.49.4 10 TR/1750 CFM Each 191621.0
22.49.5 13.2 TR/2050 CFM Each 263161.0
22.49.6 16.5 TR/2150 CFM Each 330623.0

22.51 Supply , Installation, Testing and Comissioning of IS:1475 marked self


contained drinking water cooler with hermetically sealed
compressor,non CFC refrigerent suitable for operation on
230V/1pH/50Hz AC supply,Full stainless steel (SS304)body (0.8 mm
thick) and tank (0.5 mm thick) , stainless steel water tray,minimum two
nos Brass Chrome plated faucets and suitable drainage system complete
in all respect with required height MS fabricated and Painted Angle iron
frame ( Cost of frame to be paid Extra )complete in all respect of the
following capacity. All as per pre approved by Engineer in charge. For
additional technical parameters of products/ work , refer Annexure "A"
attached with this BSR .

22.51.1 cooling capacity 150 Ltr./Hr. and storage capacity 150 Ltrs Each 75878.0
22.51.2 cooling capacity 60 Ltr./Hr. and storage capacity 120 Ltrs Each 64428.0
22.51.3 cooling capacity 40 Ltr./Hr. and storage capacity 80 Ltrs Each 57859.0

22.52 Supply and Installation of Box type EU13 Hepa Filter of 99.997%
efficiency down to 0.3 micron particle size installed in zero leakage
Aluminium frame as per ISO 14644-1 clean room including sealing and
packing material cost like silicon and hardware cost and Labour cost for
the dismantling of existing worn out filters & shifting the same to the
store as required as under. All as per pre approved by Engineer in
charge. For additional technical parameters of products/ work , refer
Annexure "A" attached with this BSR .

22.52.1 305 mm Thick Sq Mtr 40259.0


22.52.2 150 mm thick Sq Mtr 29078.0

22.53 Supply and Installation of Box type EU13 Hepa Filter of 99.997%
efficiency down to 0.3 micron particle size installed in zero leakage
Aluminium frame as per ISO 14644-1 clean room including sealing and
packing material cost like silicon and hardware cost and Labour cost.
NABL accredeated / appropriated lab testing reports with OEM
certificate must submitted to engineer in charge. All as per pre approved
by Engineer in charge. For additional technical parameters of products/
work , refer Annexure "A" attached with this BSR .

22.53.1 305 mm Thick Sq Mtr 37858.0


22.53.2 150 mm thick Sq Mtr 26700.0

Chapter E -22
Page 135
P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-22

Code No. Description Unit Complete


Rate

22.54 Providing & Fixing of ISO certified company made submersible pump of
rating 18 W to 24 Watts ,minimum water discharge capacity 2800 LPH
and suitable for central/large size desert cooler complete with making
connections, testing etc as required. NABL accredeated / appropriated
each 1139.0
lab testing reports with OEM certificate must submitted to engineer in
charge. All as per pre approved by Engineer in charge. For additional
technical parameters of products/ work , refer Annexure "A" attached
with this BSR .

22.55 Dismentling of split air conditioner of any capacity/any type including


existing indoor unit & outdoor unit , refrigerant piping , connecting
Job 936.0
cables , drain pipe etc. including shifting of dismentaled material to
store complete as required

22.56 Providing & Fixing of 26 SWG thick Aluminium sheet cladding on existing
refrigerant copper pipe /insulated chiller pipe or any other surface with
nut & bolts complete as required. All as per pre approved by Engineer in
Sq Mtr 617.0
charge. All as per pre approved by Engineer in charge. For additional
technical parameters of products/ work , refer Annexure "A" attached
with this BSR .

22.57 Providing & Fixing of BIS certified Oil filled radiator having following fins
with temperature control setting sound free operation with minimum 1
year warranty & temperature setting, Rated Voltage:-230 V, Rated
Wattage:-2400 W made out from CRCA sheet with powder coating,
tubular type element castor wheel, 1.5 mtr PVC power cord along with
16 Amp plug top. net weight should not be less then 12 Kg and minimum
dimensions are 520 X 165 X 710mm complete in all respect. NABL
accredeated / appropriated lab testing reports with OEM certificate
must submitted to engineer in charge. All as per pre approved by
Engineer in charge. For additional technical parameters of products/
work , refer Annexure "A" attached with this BSR .

22.57.1 9 Fins Each 15799.0


22.57.2 11 Fins Each 18365.0
22.57.3 13 Fins Each 20121.0

Chapter E -22
Page 136
P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-22

Code No. Description Unit Complete


Rate
22.58 Supply & fixing of evaporative cooling Celdec pads of 200mm Thick
made out from impregnated cellulose paper media of imported origin
including fixing in Air washer complete in all respect. All as per pre
Sq.ft
approved by Engineer in charge. For additional technical parameters of
products/ work , refer Annexure "A" attached with this BSR .
742.00

22.59 SITC of Interconnecting refrigerant copper pipe for split/Ductable/


Casseette AC of DHE Grade C12200- ASTM B68, B75, chemical
composition of copper %- 99.0 Min and Phosphorus %- 0.015 to 0.040 .
For Annealed copper tube :- Tensile strength = 210 Mpa wih elongation
% = 40 Min . Ink Mark Brand Printing on Hard Tubes should be present.
Piping between each set of indoor & outdoor units of different sizes as
Kg 1987.00
per OEM requirement & specifications including class 'O' Nitrile rubber
sleeves, chase cutting, supports, making good the same with sand
cement plaster etc. as required. All as per pre approved by Engineer in
charge. For additional technical parameters of products/ work , refer
Annexure "A" attached with this BSR .

Chapter E -22
Page 137
P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-23

Chapter E - 23
Substation Equipments
Code No. Description Complete
Unit Rate
23.1 Supply installation testing & Commissioning of Copper wound distribution
Transformer of following rating and % Impedance, 11/0.433KV Delta-Star
Connected, Vector Group Dyn 11, ONAN Cooled losses as per IS 1180 part I
2014 (Fourth Revision) Level-1, with boltless core design including standard
accessories like conservator with prismatic oil level gauge , silica gel breather,
Bucholz relay, pressed steel radiator fins, Radiator Valve(above 800 Kva)
Suitable size HT cable box, LT cable box with Busbar connection for outgoing
cables, Off -LTC (+/- 2.5%, +/- 5% to - 7.5% ), temperature rise of 40 degree C in
oil / 45 degree C in winding , drain valve, Air release device, Dial type Oil &
Winding Temperature gauge with alarm & trip contacts, first filling of
transformer oil as per IS :335-1953 , Epoxy primer and PU based paint as Top
coat, Unidirectional rollers for rating upto 800 kva & bi- directionalabove 800
Kva rollers with locking arrangement etc. as required. The Transformer shall be
subjected to routine factory tests (as per IS:2026 and IS:1180) including
Temperature rise test in OEM's own lab shall be witnessed by Department
engineer Physically.
Transformer shall be tested from CTL of discom before charging of transformer
& complete installaion must be certified from Electrical Inspectorate office as
per Indian Electricity rule, (CTL testing charges and Electrical Inspection charges
shall be reimbursed by the department to the contractor)Following tests shall
be carried out on each transformer at site by OEM enginer in presence of
department authorised representative:- a) Ratio test on each tapping.b)
Resistance of windings at principal and all tapings.c) Insulation resistance of the
winding between HV to earth / HV to LV / LV to earth.d) Vector group test.e)
Magnetic Balance test. All as per pre approved by Engineer in charge. For
additional technical parameters of products/ work , refer Annexure "A"
attached with this BSR .
23.1.1 500 KVA with % Impedance 4.5 Each 1665580.0
23.1.2 630 KVA with % Impedance 4.5 Each 1918965.0
23.1.3 800 KVA with % Impedance 4.5 Each 2169269.0
23.1.4 1000 KVA with % Impedance 5.0 Each 2583252.0
23.1.5 1250 KVA with % Impedance 5.0 Each 2910231.0
23.1.6 1600 KVA with % Impedance 6.25 Each 3161324.0
23.1.7 2000 KVA with % Impedance 6.25 Each 3619014.0
23.1.8 2500 KVA with % Impedance 6.25 Each 4116435.0

23.2 S I T C of star rated Aluminium wound distribution Transformer of following


rating 11/0.433KV Delta-Star Connected, Vector Group Dyn 11,ONAN Cooled &
as per BEE star - 1 & BIS approved as per IS 2026- 1977 & losses as defined as
per 2014 (Fourth Revision) Level-1 . including standard accessories like
conservator, silica gel breather, radiator, fins, HT cable box & LT cable boxes,
temperature rise in winding/oil 35-40 degree C upto 200 KVA & 40-45 degree C
for above 200 KVA, ISI marked drain valve, Dial type Temperature gauge, first
filling of transformer oil as per IS :335-1953, Epoxy based paint, including
carrying of pre-commission Testing & Charging of Transformer complete in all
respect .

Chapter E -23
page 138
P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-23

Code No. Description Complete


Unit Rate
The Transformer shall be subjected to routine factory tests (as per IS:2026 and
IS:1180) including testing from CTL of discom before charging of transformer &
complete installaion must be certified from Electrical Inspectorate office as per
Indian Electricity rule, (CTL testing charges and Electrical Inspection charges
shall be reimbursed by the department to the contractor). All as per pre
approved by Engineer in charge. For additional technical parameters of
products/ work , refer Annexure "A" attached with this BSR .

23.2.1 63 KVA Each 197732.0


23.2.2 100 KVA Each 255138.0
23.2.3 160KVA Each 318922.0
23.2.4 200 KVA Each 401842.0
23.2.5 250 KVA with Off -LTC (+5% to - 10% @ 2.5%) Each 427356.0
23.2.6 315 KVA with Off -LTC (+5% to - 10% @ 2.5%) Each 619551.0
23.2.7 400 KVA with Off -LTC (+5% to - 10% @ 2.5%) Each 744713.0
23.2.8 500 KVA with Off -LTC (+5% to - 10% @ 2.5%) Each 872656.0

23.3 SITC of Marshalling box fabricated out of 2.0 mm thick sheet steel, provided
with water tight hinged doors with padlock arrangement, neoprene gasket all
around door to make enclosure water and dust proof (IP-55). Space Heater,
Illumination lamp, 5A switch & Socket, MCB, Viewing window, detachable gland
plate completely wired, ready for external connections at the terminal blocks.
All wirings shall be carried out with 1100 V grade PVC insulated stranded
conductors. Power circuits if any shall be wired with stranded copper
conductors of adequate sizes to suit the rated current. The minimum size shall
be 2.5 sq.mm. Control, alarm and indication circuits, shall be wired with
stranded copper conductor of sizes not smaller than 1.5 sq. mm. CT circuits shall
be wired with stranded copper conductor of size not smaller than 4 sq.mm.
including 150 mm dia. Winding temperature indicator with A&T contacts, 150
mm dia. Oil temperature indicator with A&T contacts , 150 mm dia. Magnetic
Oil level Gauge ( MOG) with alarm contact, double float type Buchholz relay
with isolating valves on both sides and as per IS: 3637 with A&T Contacts etc. as
required.
Each 107158.00
All as per pre approved by Engineer in charge. For additional technical
parameters of products/ work , refer Annexure "A" attached with this BSR .

23.4 Supply & Installation of D.P. Structure With AIR BREAK SWITCH having following
specifications A, B, C, D, E. All as per pre approved by Engineer in charge. For
additional technical parameters of products/ work , refer Annexure "A"
attached with this BSR .
A) Double pole structure on 2 no ISMB ( I beam ) of size 150 x 75 mm, 10 mtr
length using 7 no MS channel each of size 100 mm x 50 mm x 2500 mm
complete in all respect with nuts, springs washers, clamps as required.

B) Off load type gang operated 3-pole vertical flute type switch suitable for
11KV ; 400A ,3-ø, central post rotating double break isolator complete with MS
hardware , copper moving & fixed contact ,assembly of 9 nos pin insulator ,GI
pipe of suitable length for operation.
C) 3nos Vertical / Horizontal mounted 11kv horn gap fuse set /drop out 11kv
barrel fuses mounted on 6no pin insulators

Chapter E -23
page 139
P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-23

Code No. Description Complete


Unit Rate
D) 3 piece non linear resistor type. lighting arrestor of approved make suitable
for 3 wire, 11kv Overhead line with rated voltage of 9kv rms & nominal
discharge current rating of 5 ka & complete with galvanized clamping
arrangement GI bolts, nuts, washer etc as required.
E) 3 no 11kv ACSR conductors mounted on pin type insularors as required.
6.GENERAL:The go shall be operated by hand operated liver properly earthed 102164.0
with provision for locking mounted at 3’ Set

23.5 SITC of 11kV 630 Amps 21KA for 3 Sec. SF6 insulated, outdoor duty (IP54) ,
Extensible / Non extensible type Ring main unit (RMU) manually operated in
combination of VCB modules and Load Break switch consisting of Copper
busbar in SF6 insulated 304 (Non-Ferrite Non-Magnetic Grade) stainless steel
enclosure of thickness 2.5mm with manometer. The HV switchgear and control
gear should be confirming to IEC-62271-100, IEC-62271-200-2003 & IEC-60694-
1996. The RMU should be internal arc tested for 21KA for 1Second with IAC-AFL
classification for gas tank. Vacum Interrupter of VCB should be RMU
Manufacturer’s own make. Each feeder of RMU should have voltage presence
indicator. . and compring of followings:- 1 no. microprocessor based Self
powered numerical relay with over Current/ earth fault & short circuit
protection with each VCB feeder. - 3 Nos. Protection CT shall be of Burden
2.5VA, ratio 50/1A, Class of Accuracy class 5P10 for O/C and E/F protection for
each VCB.- 1 No. Manometer for each tank,- 1 nos. Fault Passage indicator,-
Right angle boots for all the feeder Modules All the type test certificates as per
IEC from Third party NABL / CPRI / ERDA accrediated lab to be submitted. (Cost
of RCC Foundation / Steel Structure to be paid Extra) All as per pre approved by
Engineer in charge. For additional technical parameters of products/ work ,
refer Annexure "A" attached with this BSR

23.5.1 Non Extensible 3 way RMU with 1 no. VCB & 2 No. Load Break Switch Each 438067.0
23.5.2 Extensible 3 way RMU with 1 no. VCB & 2 No. Load Break Switch Each 465880.0
23.5.3 Extensible 2 way RMU with 1 no. VCB & 1 No. Load Break Switch Each 382439.0
23.5.4 Non Extensible 1 way RMU with 1 no. VCB & Direct Cable Entry Each 340718.0

23.6 SITC of Indoor Type Floor mounted metal clad 11 KV, 630 Amps 3 phase, 50 Hz
Vacuum Circuit Breaker (VCB) Panel Fabricated in VCB Manufacturer's own
Factory as per IEC 62271-1,100,200 Standard made from Powder painted pre-
fabricated, CRCA sheet steel /High quality Aluminium-Zinc (Aluzinc) coated
sheet steel. Fabrication shall be done through CNC turret press and CNC
bending machine having a rupturing capacity of 500 MVA, 26.3 KA breaking
capacity for 3 sec, Internal arc type tested for 26.3KA for 1 sec with AFLR
clasification totally enclosed with Aluminium bus bar of 630 Amps for each
phase, flush front, Horizontal isolation, Horizontal drawout type with Electrical
and Mechanical interlock and automatic safety shutter gear including
padlocking arrangement, isolation plugs, assambly of 3 vaccum interrupters
(VCB manufacturer's own make) , with each pole individually encapsulated by
epoxy insulations to make it dust proof and self - aligning finger type isolating
contacts, truck having integral racking with necessary interlocks (for insertion
and removing of VCB), manual and automatic motor charged independent
closing/ tripping spring , trip free operating mechanism with closing and
tripping push buttons and mechanical breaker.

Chapter E -23
page 140
P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-23

Code No. Description Complete


Unit Rate
interconnected with HT sleeve bus bar of 630 Amps , Basic Insulation level (BIL)
: 28KV (RMS) / 75KV (Peak) and Altiude less than 1000 meters, including all
protection, indication, Operation, monitoring and control and accessories etc.
as required. .Factory Tests of VCB panel as per OEM's QAP in it's own
Manufacturing facility shall be witnessed by department Engineer virtually /
Physically. (Cost of RCC Foundation / Steel Structure to be paid Extra) All as per
pre approved by Engineer in charge. For additional technical parameters of
products/ work , refer Annexure "A" attached with this BSR .

23.6.1 Incoming Cum Outgoing Panel comprising of Side cable box & Transformer
Auxiliary protection and comprising of following.
- VCB 630 Amps . VI of VCB should be sealed for 30000 operation. VCB
operationg mechanism should be of M2 duty for minimum 10000 mechanical
operation.
- Closing & tripping coil of VCB should be of continious rating to achive minimal
failure.
- Resin Cast type CT having Ratio : 400-200A/ 1-1 A, Core1: 5P20, 5 VA; Core 2:
0.5, 5 VA (How ever CT Ratio shall be decided as per load requirement)
- VT Ratio: 11KV/1.732/110V/1.732/110V/1.732, -Core 1: 0.5, 20VA should be
floor mounted and to be connected from the back side of the panel.
- Numerical relay (should be VCB manufacturer's own make) having protections
of 50,51, 50N,51N,TCS. The relay shall have programable 4 digital Input ,
programable 6 Digital Output and programable 4 nos. LED at HMI.
- Ammeter with Selectorswitch and Volt meter with Selector switch
- Multifunction Meter of Acc Class 0.5, having facility to monitor KW, KVA,
KVAR, PF, KWH, KVARH, KVAH, A,V etc.
- Trip circuit supervision relay (feature of numerical relay)
- LR, TNC switch, indication lamp - CB ON/OFF, spring charge, Auto trip, TCS
healthy etc., Space heaters
- Power Pack (230V AC- 110V DC) and 8/12 window Annunciator.

Each 869180.0

Chapter E -23
page 141
P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-23

Code No. Description Complete


Unit Rate
23.6.2 Incoming Panel comprising of following:
- VCB 630 Amps . VI of VCB should be sealed for 30000 operation. VCB
operationg mechanism should be of M2 duty for minimum 10000 mechanical
operation.
- Closing & tripping coil of VCB should be of continious rating to achive minimal
failure.
- Resin Cast type CT having Ratio : 400-200A/ 1-1 A, Core1: 5P20, 5 VA; Core 2:
0.5, 5 VA (How ever CT Ratio shall be decided as per load requirement)
- VT Ratio: 11KV/1.732/110V/1.732/110V/1.732, -Core 1: 0.5, 20VA should be
floor mounted and to be connected from the back side of the panel.
- Numerical relay (should be VCB manufacturer's own make) having protections
of 50,51, 50N,51N,TCS. The relay shall have programable 4 digital Input ,
programable 6 Digital Output and programable 4 nos. LED at HMI.
- Ammeter with Selectorswitch and Volt meter with Selector switch
- Multifunction Meter of Acc Class 0.5, having facility to monitor KW, KVA,
KVAR, PF, KWH, KVARH, KVAH, A,V etc.
- Trip circuit supervision relay (feature of numerical relay)
- LR, TNC switch, indication lamp - CB ON/OFF, spring charge, Auto trip, TCS
healthy etc., Space heaters
- Power Pack (230V AC- 110V DC) and 8/12 window Annunciator.

Each 848319.0
23.6.3 Outgoing Panel comprising of following:
- VCB 630 Amps . VI of VCB should be sealed for 30000 operation. VCB
operationg mechanism should be of M2 duty for minimum 10000 mechanical
operation.
- Closing & tripping coil of VCB should be of continious rating to achive minimal
failure.
- Resin Cast type CT having Ratio : 400-200A/ 1-1 A, Core1: 5P20, 5 VA; Core 2:
0.5, 5 VA (How ever CT Ratio shall be decided as per load requirement)
- Numerical relay (should be VCB manufacturer's own make) having protections
of 50,51, 50N,51N,TCS. The relay shall have programable 4 digital Input ,
programable 6 Digital Output and programable 4 nos. LED at HMI.
- Ammeter with Selectorswitch and Volt meter with Selector switch
- Multifunction Meter of Acc Class 0.5, having facility to monitor KW, KVA,
KVAR, PF, KWH, KVARH, KVAH, A,V etc.
- Trip circuit supervision relay (feature of numerical relay)
- LR, TNC switch, indication lamp - CB ON/OFF, spring charge, Auto trip, TCS
healthy etc., Space heaters
- Power Pack (230V AC- 110V DC)

Each 813552.0
23.6.4 Bus Coupler Panel comprising of following:
-VCB 630 Amps . VI of VCB should be sealed for 30000 operation. VCB
operationg mechanism should be of M2 duty for minimum 10000 mechanical
operation.
- Closing & tripping coil of VCB should be of continious rating to achive minimal
failure.
- LR, TNC switch, indication lamp - CB ON/OFF, spring charge, Space heaters
- Power Pack (230V AC- 110V DC)
Each 764878.0

Chapter E -23
page 142
P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-23

Code No. Description Complete


Unit Rate
23.7 SITC of Indoor Type Floor mounted metal clad 11 KV, 630 Amps 3 phase, 50 Hz
Vacuum Circuit Breaker (VCB) Panel Fabricated by System Integrator of VCB
Manufacturer as per IEC 62271-1,100,200 Standard made from Powder
painted pre-fabricated, CRCA sheet steel /High quality Aluminium-Zinc (Aluzinc)
coated sheet steel. Fabrication shall be done through CNC turret press and CNC
bending machine having a rupturing capacity of 500 MVA, 26.3 KA breaking
capacity for 3 sec, Internal arc type tested for 26.3KA for 1 sec with AFLR
clasification totally enclosed with Aluminium bus bar of 630 Amps for each
phase, flush front, Horizontal isolation, Horizontal drawout type with Electrical
and Mechanical interlock and automatic safety shutter gear including
padlocking arrangement, isolation plugs, assambly of 3 vaccum interrupters
(VCB manufacturer's own make) , with each pole individually encapsulated by
epoxy insulations to make it dust proof and self - aligning finger type isolating
contacts, truck having integral racking with necessary interlocks (for insertion
and removing of VCB), manual and automatic motor charged independent
closing/ tripping spring , trip free operating mechanism with closing and
tripping push buttons and mechanical breaker.

interconnected with HT sleeve bus bar of 630 Amps , Basic Insulation level (BIL)
: 28KV (RMS) / 75KV (Peak) and Altiude less than 1000 meters, including all
protection, indication, Operation, monitoring and control and accessories etc.
as required. Factory Tests of VCB panel as per System Integrator's QAP in it's
own Manufacturing facility shall be witnessed by department Engineer virtually
/ Physically. (Cost of RCC Foundation / Steel Structure to be paid Extra). All as
per pre approved by Engineer in charge. For additional technical parameters of
products/ work , refer Annexure "A" attached with this BSR .

23.7.1 Incoming Cum Outgoing Panel comprising of Side cable box & Transformer
Auxiliary protection and comprising of following.
- VCB 630 Amps . VI of VCB should be sealed for 30000 operation. VCB
operationg mechanism should be of M2 duty for minimum 10000 mechanical
operation.
- Closing & tripping coil of VCB should be of continious rating to achive minimal
failure.
- Resin Cast type CT having Ratio : 400-200A/ 1-1 A, Core1: 5P20, 5 VA; Core 2:
0.5, 5 VA (How ever CT Ratio shall be decided as per load requirement)
- VT Ratio: 11KV/1.732/110V/1.732/110V/1.732, -Core 1: 0.5, 20VA should be
floor mounted and to be connected from the back side of the panel.
- Numerical relay (should be VCB manufacturer's own make) having protections
of 50,51, 50N,51N,TCS. The relay shall have programable 4 digital Input ,
programable 6 Digital Output and programable 4 nos. LED at HMI.
- Ammeter with Selectorswitch and Volt meter with Selector switch
- Multifunction Meter of Acc Class 0.5, having facility to monitor KW, KVA,
KVAR, PF, KWH, KVARH, KVAH, A,V etc.
- Trip circuit supervision relay (feature of numerical relay)
- LR, TNC switch, indication lamp - CB ON/OFF, spring charge, Auto trip, TCS
healthy etc., Space heaters
- Power Pack (230V AC- 110V DC) and 8/12 window Annunciator.

Each 625809.0

Chapter E -23
page 143
P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-23

Code No. Description Complete


Unit Rate
23.7.2 Incoming Panel comprising of following:
- VCB 630 Amps . VI of VCB should be sealed for 30000 operation. VCB
operationg mechanism should be of M2 duty for minimum 10000 mechanical
operation.
- Closing & tripping coil of VCB should be of continious rating to achive minimal
failure.
- Resin Cast type CT having Ratio : 400-200A/ 1-1 A, Core1: 5P20, 5 VA; Core 2:
0.5, 5 VA (How ever CT Ratio shall be decided as per load requirement)
- VT Ratio: 11KV/1.732/110V/1.732/110V/1.732, -Core 1: 0.5, 20VA should be
floor mounted and to be connected from the back side of the panel.
- Numerical relay (should be VCB manufacturer's own make) having protections
of 50,51, 50N,51N,TCS. The relay shall have programable 4 digital Input ,
programable 6 Digital Output and programable 4 nos. LED at HMI.
- Ammeter with Selectorswitch and Volt meter with Selector switch
- Multifunction Meter of Acc Class 0.5, having facility to monitor KW, KVA,
KVAR, PF, KWH, KVARH, KVAH, A,V etc.
- Trip circuit supervision relay (feature of numerical relay)
- LR, TNC switch, indication lamp - CB ON/OFF, spring charge, Auto trip, TCS
healthy etc., Space heaters
- Power Pack (230V AC- 110V DC) and 8/12 window Annunciator.

Each 604949.0
23.7.3 Outgoing Panel comprising of following:
- VCB 630 Amps . VI of VCB should be sealed for 30000 operation. VCB
operationg mechanism should be of M2 duty for minimum 10000 mechanical
operation.
- Closing & tripping coil of VCB should be of continious rating to achive minimal
failure.
- Resin Cast type CT having Ratio : 400-200A/ 1-1 A, Core1: 5P20, 5 VA; Core 2:
0.5, 5 VA (How ever CT Ratio shall be decided as per load requirement)
- Numerical relay (should be VCB manufacturer's own make) having protections
of 50,51, 50N,51N,TCS. The relay shall have programable 4 digital Input ,
programable 6 Digital Output and programable 4 nos. LED at HMI.
- Ammeter with Selectorswitch and Volt meter with Selector switch
- Multifunction Meter of Acc Class 0.5, having facility to monitor KW, KVA,
KVAR, PF, KWH, KVARH, KVAH, A,V etc.
- Trip circuit supervision relay (feature of numerical relay)
- LR, TNC switch, indication lamp - CB ON/OFF, spring charge, Auto trip, TCS
healthy etc., Space heaters
- Power Pack (230V AC- 110V DC)
Each 584089.0
23.7.4 Bus Coupler Panel comprising of following:
-VCB 630 Amps . VI of VCB should be sealed for 30000 operation. VCB
operationg mechanism should be of M2 duty for minimum 10000 mechanical
operation.
- Closing & tripping coil of VCB should be of continious rating to achive minimal
failure.
- LR, TNC switch, indication lamp - CB ON/OFF, spring charge, Space heaters
- Power Pack (230V AC- 110V DC)
Each 549322.0

Chapter E -23
page 144
P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-23

Code No. Description Complete


Unit Rate
23.8 SITC of 11 kV Outdoor Package Sub-Station Factory Assembled and Factory
fitted by RMU & LT Switchgear OEM of Following Transformer & ACB Rating
and consisting of A, B, C, D & E (Cost of RCC Foundation / Steel Structure to be
paid Extra). All as per pre approved by Engineer in charge. For additional
technical parameters of products/ work , refer Annexure "A" attached with
this BSR .
A) HT Compartment: Ring Main Unit 11kV 630 Amps 21KA for 3 Sec. SF6
insulated, non-extensible, Ring main unit consisting of 2 nos. manually operated
Load Break Switch and 1 Nos. 630 Amp Vacuum Circuit Breaker (manually
operated) with Copper busbar in SF6 insulated stainless steel enclosure of
thickness 2.5mm Non ferrite nonmagnetic type 304 grade. Interconnection
between HT switchgear and transformer by Suitable Sized Aluminium un-
armoured HT XLPE Cable. The HV switchgear and control gear should be
confirming to IEC-62271-100, IEC-62271-200-2003 & IEC-60694-1996. The Gas
tank of the RMU should be internal arc tested for 20KA for 1Second. VI should
be RMU Manufacturer’s own make.
- 1 no. microprocessor based Self powered numerical relay with over Current/
earth fault & short circuit protection with each VCB feeder.
- 3 Nos. Protection CT shall be of Burden 2.5VA, ratio 50/1A, Class of Accuracy
class 5P10 for O/C and E/F protection for each VCB feeder
-1 No. Manometer
- 1 No. Fault Passage Indicator for each Load Break switch.
B) Transformer: 11kV/433V, 3phase,50 HZ, Copper wound Dry Type outdoor
type step down transformer having delta connection on primary side and star
connection on secondary side complete with all modern fitting as given in the
specification , off load tap changer (-10% +5% in the step of 2.5%) etc. as
required as per compete with losses as latest ECBC Standards , Class H with 115
Deg temperature rise allowed .
-One No. Winding Temperature Indicator with Alarm and trip Contc
C) LV Compartment: Incoming cum Outgoing with One number Fixed type 4
pole 415V ACB with molded case construction having breaking capacity 50KA
with Ics = Icu = Icw (1 sec) = 50KA with microprocessor release for over current,
earth fault & short circuit protections. Interconnection between Transformer &
LT switchgear using Aluminum Bus bars of ACB Current rating with heat
shrinkable colored sleeves.
D) The Outdoor enclosure shall be made of 1.5 mm mm thickness Galvanized
Sheet Steel tropicalised to meet Indian weather conditions including all the
partition Sheets & doors. The enclosure base shall be of 4.0 mm thickness Hot
Dip Galvanized Sheet Steel. The entire Package Substation shall be Factory
Assemble & Factory Fitted. The enclosure shall have IP54 degree of protection
for HT & LT switchgear compartment IP-23 degree of protection for
Transformer compartment. The Enclosure should be type tested for Internal Arc
fault test to the tune of at least 21 KA for 1 second adhering to as per latest IEC
62271- 202. The offered enclosure should be type tested for K10 class
temparature raise. TTR to be submitted. The enclosure exterior shall be powder
coated. The compartment illumination lamp with door operated switch shall be
provided for MV & LV compartment. Internal earthing connections by using
50x6mm GI Strips. Vacuum Interrupter, RMU, Transformer,LV switchgear,
Outdoor enclosure should be of same make for better life cycle optimization.

Chapter E -23
page 145
P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-23

Code No. Description Complete


Unit Rate
E) All the Type test certificates of RMU, Transformer & LT Switchgear will be
provided by Manufacturer and factory Tests of Package Substation as per OEM's
QAP in it's own Manufacturing facility shall be witnessed by department
Engineer virtually / Physically

23.8.1 Transformer Capacity 250 KVA, ACB Rating 630 Amps. Each 3268116.0
23.8.2 Transformer Capacity 500 KVA, ACB Rating 1000 Amps. Each 4081668.0
23.8.3 Transformer Capacity 630 KVA, ACB Rating 1250 Amps. Each 4603176.0
23.8.4 Transformer Capacity 750 KVA, ACB Rating 1600 Amps. Each 5041242.0
23.8.5 Transformer Capacity 1000 KVA, ACB Rating 2000 Amps. Each 5632285.0

23.9 SITC of battery bank of min 150 AH capacity comprising SMF/VRLA batteries,
FCBC ( Float cum boost charger)suitable for 415V +/-10%, 50 Hz , 1-ǿ / 3 -ǿ
Input & 24/ 48 /110 V DC Output Natural Cooled, free standing in Sheet Steel
enclosure,SCR controlled , regulation +/-1% , Efficiency > 75% on FLAC/ DC
Instruments, Selector Switch ,Built in DC Distribution Board (6 No MCB),
indication , control as required. All as per pre approved by Engineer in charge.
For additional technical parameters of products/ work , refer Annexure "A"
attached with this BSR .
Each 134656.0

23.10 SITC of following capacity IK10 Sandwich Type Rising Mains / Bus Duct
Confirming to IEC 61439 part 1 & part 6 standard & IS 8623 P-II and
Manufactured in India for use on 3 phase 4 wire , 50% internal earth , 415 volts,
50Hz A.C. supply , class F insulation, rated insulation voltage 1000V, impulse
withstand voltage 12 KV, min. seismic zone 4 as per IS1892, with IP-54 / IP-66
(With Canopy) enclosure made of 1.6mm thick sheet steel duly powder coated
in convenient sections complete with 4 Nos aluminium (with 6101 or 63401
grade) bus bars, necessary joints & expansion joints, fire barrier at each floor,
provision of tapping at every metre, continuous earthing with 2 Nos aluminium
strip of suitable size (one on each side) including, G.I. clamping brackets, angle
iron bracket, steel fasteners, connecting to earthing system including making
opening in RCC / Brick Masonary and repairing the same etc. as required. Type
Tests reports like (i) Short Circuit Test (ii) Degree of Protection (iii) Temperature
rise test of Rising main in CPRI / UL / ASTA accrediated lab will be submitted by
OEM.
Routine test as per OEM's QAP in It's own Manufacturing facility in India shall
be witnessed by department Engineer virtually / Physically. Complete
Installation of Rising Mains shall be Vetted by Manufacturer before
Comissioning. All as per pre approved by Engineer in charge. For additional
technical parameters of products/ work , refer Annexure "A" attached with
this BSR .
23.10.1 Sandwich Type Bus Rising Main
23.10.1.1 400 amps 25 KA SC for 1 sec Mtr 17683.0
23.10.1.2 500 amps 30 KA SC for 1 sec Mtr 19389.0
23.10.1.3 630 amps 40 KA SC for 1 sec Mtr 21142.0
23.10.1.4 800 amps 50 KA SC for 1 sec Mtr 24586.0
23.10.1.5 1000 amps 50 KA SC for 1 sec Mtr 27455.0
23.10.1.6 1250 amps 50 KA SC for 1 sec Mtr 31333.0
23.10.1.7 1600 amps 50 KA SC for 1 sec Mtr 37693.0

Chapter E -23
page 146
P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-23

Code No. Description Complete


Unit Rate
23.10.1.8 2000 amps 65 KA SC for 1 sec Mtr 46845.0
23.10.2 Sandwich Type Bus Duct
23.10.2.1 1000 Amps 50kA SC for 1 sec Mtr 21251.0
23.10.2.2 1250 Amps 65kA SC for 1 sec Mtr 24043.0
23.10.2.3 1600 Amps 80kA SC for 1 sec Mtr 29782.0
23.10.2.4 2000 Amps 80kA SC for 1 sec Mtr 38313.0
23.10.2.5 2500 Amps 120kA SC for 1 sec Mtr 51033.0
23.10.2.6 3200 Amps 120kA SC for 1 sec Mtr 57393.0
23.10.2.7 4000 Amps 120kA SC for 1 sec Mtr 72904.0
23.10.2.8 5000 Amps 120kA SC for 1 sec Mtr 93845.0
23.10.3 Out Door Bus Duct IP66 with Canopy
23.10.3.1 1000 Amps 50kA SC for 1 sec Mtr 24818.0
23.10.3.2 1250 Amps 65kA SC for 1 sec Mtr 27921.0
23.10.3.3 1600 Amps 80kA SC for 1 sec Mtr 35211.0
23.10.3.4 2000 Amps 80kA SC for 1 sec Mtr 43277.0
23.10.3.5 2500 Amps 120kA SC for 1 sec Mtr 58944.0
23.10.3.6 3200 Amps 120kA SC for 1 sec Mtr 66700.0
23.10.3.7 4000 Amps 120kA SC for 1 sec Mtr 83894.0
23.10.3.8 5000 Amps 120kA SC for 1 sec Mtr 105789.0

23.11 SITC of Bus Rising Main OEM manufactured following capacity End Feed Unit
Confirming to ANSI C37.23 standard & IS 8623 P-II suitable for Sandwich /
Compact Air Insulated type for use on 3 phase 4 wire 415 volts, 50Hz A.C. supply
made with 1.6mm thick steel sheet enclosure duly powder coated with
provision of MCCB/ACB (but without MCCB/ACB), Interlocking feature complete
with necessary joints including clamping brackets, angle iron bracket, steel
fasteners, connecting to earthing system etc. as required. All as per pre
approved by Engineer in charge. For additional technical parameters of
products/ work , refer Annexure "A" attached with this BSR .

23.11.1 For 200 Amp. (Without MCCB) Each 11634.0


23.11.2 For 250 Amp. (Without MCCB) Each 12099.0
23.11.3 For 325 Amp. (Without MCCB) Each 12719.0
23.11.4 For 400 Amp. (Without MCCB) Each 18611.0
23.11.5 For 500 Amp. (Without MCCB) Each 20142.0
23.11.6 For 630 Amp. (Without MCCB) Each 22741.0
23.11.7 For 800 Amp. (Without MCCB) Each 26311.0
23.11.8 For 1000/1250 Amp. (Without ACB) Each 106874.0
23.11.9 For 1600 Amp. (Without ACB) Each 124402.0
23.11.10 For 2000 Amp. (Without ACB) Each 153099.0

Chapter E -23
page 147
P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-23

Code No. Description Complete


Unit Rate
23.12 SITC of following capacity IK10 Compact Air Insulated Rising Mains / Bus Bar
trunking Confirming to IEC 61439 part 1 & part 6 standard & IS 8623 P-II and
Manufactured in India for use on 3 phase 4 wire , 50% internal earth , 415 volts,
50Hz A.C. supply , The busbars shall be supported through class “F” Insulator at
interval not exceeding 250mm. impulse withstand voltage 12 KV, min. seismic
zone 4 as per IS1892, with IP-54 enclosure made of 1.6mm thick sheet steel
duly powder coated in convenient sections complete with 4 Nos aluminium
(with 6101 or 63401 grade) bus bars, necessary joints & expansion joints, fire
barrier at each floor, provision of tapping at every metre, continuous earthing
with 2 Nos aluminium strip of suitable size (one on each side) including, G.I.
clamping brackets, angle iron bracket, steel fasteners, connecting to earthing
system including making opening in RCC / Brick Masonary and repairing the
same etc. as required.
Type Tests reports like (i) Short Circuit Test (ii) Degree of Protection (iii)
Temperature rise test of Rising main in CPRI / UL / ASTA accrediated lab will be
submitted by OEM & Routine test as per OEM's QAP in It's own Manufacturing
facility in India shall be witnessed by department Engineer virtually / Physically.
Complete Installation of Rising Mains shall be Vetted by Manufacturer before
Comissioning. All as per pre approved by Engineer in charge. For additional
technical parameters of products/ work , refer Annexure "A" attached with
this BSR .
23.12.1 200 amps 10 KA SC for 1 sec Mtr 11013.0
23.12.2 250 amps 15 KA SC for 1 sec Mtr 11479.0
23.12.3 315 amps 25 KA SC for 1 sec Mtr 12642.0
23.12.4 400 amps 30 KA SC for 1 sec Mtr 14115.0
23.12.5 500 amps 35 KA SC for 1 sec Mtr 15977.0
23.12.6 630 amps 50 KA SC for 1 sec Mtr 18924.0
23.12.7 800 amps 50 KA SC for 1 sec Mtr 24477.00
23.12.8 1000 amps 50 KA SC for 1 sec Mtr 27300.00

23.13 SITC of Bus Rising Main OEM manufactured following capacity Plug in / Tap off
Box suitable for Sandwich / Compact Air Insulated type bus bar trunking
Confirming to ANSI C37.23 standard & IS 8623 P-II & IEC-60947-2-2000 for use
on 3 phase 4 wire 415 volts, 50Hz A.C. supply made with 1.6mm thick steel
sheet enclosure duly powder coated with provision of MCB/MCCB / ACB (but
without MCB/MCCB/ACB) with Interlocking complete with necessary joints
including clamping brackets, angle iron bracket, steel fasteners, connecting to
earthing system etc. as required. All as per pre approved by Engineer in charge.
For additional technical parameters of products/ work , refer Annexure "A"
attached with this BSR .

23.13.1 Plug in Box suitable for Sandwich Type Bus rising Main
23.13.1.1 up to 32 amps (Suitable for MCB) without MCB Without Interlocking Each 7446.0
23.13.1.2 63 amps (Suitable for MCCB) without MCCB Each 9462.0
23.13.1.3 100/125 amps (Suitable for MCCB) without MCCB Each 9772.0
23.13.1.4 160/200/250 amps (Suitable for MCCB) without MCCB Each 11634.0
23.13.1.5 400 amps (Suitable for MCCB) without MCCB Each 15356.0
23.13.1.6 500 / 630 amps (Suitable for MCCB) without MCCB Each 21561.0
23.13.2 Plug in Box suitable for Compact Air Insulated Type Bus rising Main
23.13.2.1 up to 32 amps (Suitable for MCB) without MCB Without Interlocking Each 6360.0

Chapter E -23
page 148
P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-23

Code No. Description Complete


Unit Rate
23.13.2.2 63 amps (Suitable for MCCB) without MCCB Each 8299.0
23.13.2.3 100/125 amps (Suitable for MCCB) without MCCB Each 8531.0
23.13.2.4 160/200/250 amps (Suitable for MCCB) without MCCB Each 10548.0
23.13.2.5 400 amps (Suitable for MCCB) without MCCB Each 13805.0
23.13.2.6 630 amps (Suitable for MCCB) without MCCB Each 18459.0

SITC of Bus Rising Main OEM manufactured Tinned copper flexible joint with
enclosure of following capacity with Transformer / DG / Panel as required
23.14 complete in all respect. All as per pre approved by Engineer in charge. For
additional technical parameters of products/ work , refer Annexure "A"
attached with this BSR .
23.14.1 1000 Amp. Rating Each 48086.0
23.14.2 1250 Amp. Each 69802.0
23.14.3 1600 Amp. Each 85313.0
23.14.4 2000 Amp. Each 131848.0
23.14.5 2500 Amp. Each 162871.0
23.14.6 3200 Amp. Each 204752.0
23.14.7 4000 Amp. Each 266798.0
23.14.8 5000 Amp. Each 333498.0

23.15 SITC of following capacity bus trunking with aluminium bus bars, The busbars
shall be supported through class “F” Insulator, Enclosure made of 1.6mm thick
sheet steel duly powder coated in convenient sections for use on, 3 phase, 4
wire,415 V, 50 Hz, A.C. supply including jointing of sections, flexiblejoints,
expansion joints, bends and earthing with 2 runs of galvanised iron strips,
suspenders, angle iron bracket, steel fasteners, connecting to earthing system
etc. as required. All as per pre approved by Engineer in charge. For additional
technical parameters of products/ work , refer Annexure "A" attached with
this BSR .
23.15.1 800 Amp. Mtr 12750.0
23.15.2 1000 Amp. Mtr 15822.0
23.15.3 1250 Amp. Mtr 18769.0
23.15.4 1600 Amp. Mtr 22957.0
23.15.5 2000 Amp. Mtr 27921.0

23.16 SITC of HT metering cubical panel as approved By DISCOMs fabricated out of 18


SWG CRCA sheet steel in two compartment & MS angle of size 60mmX 6mm
having provision for Following: (i)Provision for fixing Trivector / Import - Export
Meter (To be supplied by DISCOMs) (ii)Provision for fixing of combined CT PT
Set with Copper strip for Connection (To be supplied by DISCOMs), (iii)Test
terminal Block, (iv) 6mm thick Bakelite sheet on all sides, (V) 3/6 corex 1.5 / 2.5
Sq.mm copper cable for interconnections, etc. as required. All as per pre
approved by Engineer in charge. For additional technical parameters of
products/ work , refer Annexure "A" attached with this BSR .
Each 32051.0

23.17 SITC of Radiator Cooled and Turbo charged Silent DG Set (As per latest CPCB
emission norms) having specifications as per A, B, C, D, E, F,G,H & I

Chapter E -23
page 149
P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-23

Code No. Description Complete


Unit Rate
A) 1500 RPM Diesel Engine conforming to BS:649/5514 of suitable BHP (up to
82.5 kVA 6 cylinder or Below required, 125 kVA & Above ratings 6 cylinder or
above required ) capable of taking 10% over loading for one hour after 12
hours of continuous operation., Dry exhaust mainfold with Hospital grade
silencer and catalytic convertor(isolated from main DG chamber), up to 3 M
exhaust piping (with LRB insulation & Alum. cladding ) as required .

B) AC Brush less SPDP Alternator conform to BS 5000 (part 99) or IS/IEC 60034-
1. . Alternator shall be self regulated with standard Alternator Protection( Over
voltage , over speed & under voltage, under speed warning & shutdown).Engine
& Alternator mounted on a common base Frame & coupled through a flexible
coupling or close coupled
C) CPCB / ARAI approved Standard canopy with Weatherproof, powdercoated
Accoustic enclosure for DG set for sound attenuation fabricated from 1.6 mm
CRCA sheet steel (structure) with sidewall fabricated from 1.6 mm CRCA sheet
& filled with glasswool (96Kg/m3) / Foam. as per IS8183 the doors of
28/40/50/85mm thick as perrating and fabricated from 1.6mm CRCA sheet
packed with accoustic material, All doors/opening are sealed with neoprene
/EPDNgaskets. The DG Set has Inbuilt / External in fuel tank to run 6 to 8 Hrs as
per OEM standard, with protection and tripping of DG set against temperature
of more than 50 degree centigrade.

D) Electronic / Mechanical governor, Manual & electric Start ,Batteries with


battry charger, Engine instruments panel,AVM pads All controls for operation
of DG set are from outside the enclosure with DG control panel having
Microprocessor based Genset monitoring like Running Hour, RPM, Low Lube Oil
tripping & control system, Panel mounted MCCB/ACB of suitable rating,
Ammeter, Voltmeter, PF meter, frequency meter, KWH meter,digital fuel
display meter, Ind.lamps etc. mounted inside enclosure , visible and accessible
from outside. The enclosure should be suitable for following capacity DG sets
and alternator. Noise level shall be less than 75 dB at a distance of 1 Mtrs. duly
certified by authorised agency etc. complete in all respect of following capacity :
E) (i) Accoustic glass wool wall thickness should not be less then 40mm and not
less then 20mm PU foam upto rating 100 KVA. (ii).Accoustic glass wool wall
thickness should not be less then 65mm and not less then 50mm PU foam upto
rating 250 KVA. (iii)Accoustic glass wool wall thickness should not be less then
100mm for rating above 250 KVA.
F) First filling of the fuel tank shall be done by contractor and the prevailing fuel
cost at that time shall be reimbursed to the contactor by department.

G) Servicing Contract of DG Set from OEM's Authorised Service Dealer as per


OEM guidelines during the DLP period shall be done by contractor including all
consumables, actual charges shall be reimbursed to the contractor by End User
Department.
H) Manufacturer / OEM must have its authorized service dealer in Rajasthan.
Which can provide service within 6 Hours of compalint registration.

I) DG set will be offered for Inspection and Testing at Manufacturer's Works in


presence of Departmental Engineers. All as per pre approved by Engineer in
charge. For additional technical parameters of products/ work , refer
Annexure "A" attached with this BSR .
23.17.1 20 KVA at 0.8 pf 415V 50Hz 3-ǿ Set 498872.0

Chapter E -23
page 150
P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-23

Code No. Description Complete


Unit Rate
23.17.2 25 KVA at 0.8 pf 415V 50Hz 3-ǿ Set 478546.0
23.17.3 30 KVA at 0.8 pf 415V 50Hz 3-ǿ Set 509457.0
23.17.4 40 KVA at 0.8 pf 415V 50Hz 3-ǿ Set 617432.0
23.17.5 50 KVA at 0.8 pf 415V 50Hz 3-ǿ Set 703132.0
23.17.6 62.5 KVA at 0.8 pf 415V 50Hz 3-ǿ Set 733247.0
23.17.7 82.5 KVA at 0.8 pf 415V 50Hz 3-ǿ Set 886085.0
23.17.8 100 KVA at 0.8 pf 415V 50Hz 3-ǿ Set 1049657.0
23.17.9 125 KVA at 0.8 pf 415V 50Hz 3-ǿ Set 1072760.0
23.17.10 140 KVA at 0.8 pf 415V 50Hz 3-ǿ Set 1373796.0
23.17.11 160 KVA at 0.8 pf 415V 50Hz 3-ǿ Set 1481181.0
23.17.12 180 KVA at 0.8 pf 415V 50Hz 3-ǿ Set 1620674.0
23.17.13 200 KVA at 0.8 pf 415V 50Hz 3-ǿ Set 1759163.0
23.17.14 250 KVA at 0.8 pf 415V 50Hz 3-ǿ Set 2137495.0
23.17.15 320 KVA at 0.8 pf 415V 50Hz 3-ǿ Set 2693450.0
23.17.16 400 KVA at 0.8 pf 415V 50Hz 3-ǿ Set 3318649.0
23.17.17 500 KVA at 0.8 pf 415V 50Hz 3-ǿ Set 3952709.0
23.17.18 625 KVA at 0.8 pf 415V 50Hz 3-ǿ Set 4844006.0
23.17.19 750 KVA at 0.8 pf 415V 50Hz 3-ǿ Set 6228007.0

23.18 Providing, Fixing, Jointing, Testing & Commissioning of Medium duty MS B class
pipes conforming to IS 3589 / 1239 part-I for DG Exhaust applications (beyond
1.5 Mtr. length) including cutting, welding etc & fittings like elbows,flanges,
tapers, reducer, gaskets etc. fixing the pipe on the wall/ceiling with suitable
clamps, hanger and nuts bolts . including the cost of thermal insulation with 50
mm thick layers of LRB rock wool as per IS : 8183-1993 (64 kg/m3 density) & 26
SWG aluminium sheet claddings etc complete as required complete in all
respect. (Cost of Steel Structure for Exhaust pipe will be paid Extra). All as per
pre approved by Engineer in charge. For additional technical parameters of
products/ work , refer Annexure "A" attached with this BSR .

23.18.1 80 mm dia Mtr. 2453.0


23.18.2 100 mm dia Mtr. 3441.0
23.18.3 125 mm dia Mtr. 4462.0
23.18.4 150 mm dia Mtr. 5270.0
23.18.5 200 mm dia Mtr. 8175.0
23.18.6 250 mm Dia. Mtr. 10810.0

23.19 Supply, installation and testing of metal flexible coupling (bellow) of following
dia required for horizontal length more than 3 mtr.as per standard of guide line
of D.G. set company complete in all respect. All as per pre approved by
Engineer in charge. For additional technical parameters of products/ work ,
refer Annexure "A" attached with this BSR .

23.19.1 80 mm dia Each 14054.0


23.19.2 100 mm dia Each 16290.0
23.19.3 125 mm dia Each 18526.0
23.19.4 150 mm dia Each 23212.0

Chapter E -23
page 151
P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-23

Code No. Description Complete


Unit Rate
23.19.5 200 mm dia Each 26566.0
23.19.6 250 mm Dia. Each 35564.0

23.20 Supply & fabrication steel structure with MS channel / angle / joist / ISMB /
sheet etc. including welding, rivetting, cutting, nut & bolt , one coat of primer &
two coat of enamel paint etc. as required complete in all respect. All as per pre
approved by Engineer in charge. For additional technical parameters of
products/ work , refer Annexure "A" attached with this BSR .
Kg 135.0

23.21 Earth work in excavation/ by mechanical means (Hydraulic Excavator) / Manual


means over areas (exceeding 30 cm in depth, 1.5m in width as well as 10 sum
on plan) including disposal of excavated earth, lead upto 50 m and lift upto 1.5
m, disposed earth to be levelled and neatly dressed:

Cum 213.0

23.22 Random rubble masonry with hard stone in foundation and plinth including
levelling up with cement concrete 1:6:12 (1 cement : 6 coarse sand : 12 graded
stone aggregate 20 mm nominal size) upto plinth level with Cement Mortar 1:6
( 1-Cement : 6-Sand). Cum. 6699.0

23.23 Steel reinforcement for R.C.C. work including straightening, cutting, bending,
placing in position and binding all complete upto plinth level. Kg 101.0

23.24 Providing and laying in position specified grade of reinforced cement concrete,
excluding the cost of centering, shuttering, finishing and reinforcement - All
work up to plinth level
23.24.1 1:2:4 (1 cement : 2 coarse sand (zone-III) derived from natural sources : 4
graded stone aggregate 20 mm nominal size derived from natural sources)
Cum. 4977.0
23.24.2 1:3:6 (1 Cement : 3 coarse sand (zone-III) derived from natural sources : 6
graded stone aggregate 20 mm nominal size derived from natural sources)
Cum. 4707.00
23.24.3 1:4:8 (1 Cement : 4 coarse sand (zone-III) derived from natural sources : 8
graded stone aggregate 40 mm nominal size derived from natural sources)
Cum. 4437.00

23.25 Plaster on new surface on wall in cement sand mortar 1:4 including racking of
joints etc. complete fine finish :
23.25.1 20mm thick Sqm 471.00
23.25.2 12mm thick Sqm 376.00

23.26 Finishing wall with water proofing cement paint of approved brand and
manufacture and or required shade to give an even shade including all
scaffolding:
23.26.1 New work (Two or more coats applied @ 3.84 kg/10 sqm). Sqm 121.00

Chapter E -23
page 152
P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-23

Code No. Description Complete


Unit Rate
23.27 Providing and fixing welded mesh/expanded metal mesh 25 mmx 25 mm x 3mm
in frame work, flat iron beading 20x3mm including top cross laps inside and out
sides welding, iron bolts, crews, clips etc. including two coat of red oxide and
two coat of enamel paint or more required complete with frame work with 50
X 50 X 6mm angle iron post 30 cm in ground embeded in cement concrete 1:3:6
(30X30X45cm) at corner and every three mtr including painting with one coat of
primer and two coat of enamel paint work will be done as per direction of
engineer incharge of size complete in all respect. All as per pre approved by
Engineer in charge. For additional technical parameters of products/ work ,
refer Annexure "A" attached with this BSR . Sqm 1617.00

23.28 Gravelling of Transformer / RMU Yard with 100 mm Height Gravels of Size 20 to
25 mm including leveling, Dressing etc. as Required. Sqm 1347.00

23.29 SITC of PLC Based Auto main failure (AMF) Panel fabricated from CRCA sheet
steel 2 mmThick , Powder coated finish , Engine Start & Stop commands,
control Relays , Ammeter & Voltmeter with selector switches, Control & 2 nos 4
pole Power Contactors with 2 no. of required size 4 pole MCCB, Timers,
Electronic Hooter ,Visual & Alarm indication for faults, UPS, operator interface
panel complete in all respect suitable for following capacity DG sets:
Appropriate Test Certificate/ report of product/accessories from OEM/Panel
Manufecturer shall be submitted. All as per pre approved by Engineer in charge.
For additional technical parameters of products/ work , refer Annexure "A"
attached with this BSR .
23.29.1 20 to 40 KVA Set 71132.00
23.29.2 50 to 82.5 KVA Set 85454.00
23.29.3 100 to 140 KVA Set 106936.00
23.29.4 160 to 200 KVA Set 146082.00
23.29.5 250 KVA Set 189047.00
23.29.6 320 KVA Set 210529.00
23.29.7 380 KVA Set 232011.00
23.29.8 500 KVA Set 278318.00

Chapter E -23
page 153
P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-24

Chapter E - 24

Fire protection work

Code No. Description Unit Complete Rate

24.1 Supplying, Installation, Testing & Commissioning of Electrical Driven fire


fighting duty pump as per TAC and IS 12469-1988., Factory assembled in
Pump make OEM for Sprinkler / Hydrant applications suitable for automatic
operation and consisting of following details given as A, B, C, D, E, F, G and H.

(A) End Suction / Horizontal Axially split casing volute type Single / Multi stage
Centrifugal pump complete for delivery of below mentioned discharge and
Head
(B) Material of construction : Pump Casing - Cast Iron, Impellor - Bronze,
Shaft - SS 410, Packing - Mechanical Seal
(C)Pump shall be capable of furnishing not less than 150 % of rated capacity
at a head not less than 65 % of the rated head. The shut off head shall not
exceed 120 % of rated head
(D) Squirrel cage induction motor (IE-3 Class) suitable for 3 phase, 415 V, 50
HZ, Ac supply , Class -F Insulation, Synchronous speed 2900 / 1500 RPM,
T.E.F.C confirming to IP:55 , of required HP suitable for the above pump
,along with flexible (Love Joy type) coupling , coupling guard complete in all
respect .
( E) Common bed plate fabricated from mild steel channel for installation of
pump and Motor including anti vibration pads.
(F) The Hydrostatic tests (2 times of design operating head or 1.5 times the
shut off head whichever is higher) and performance tests (to determine
developed head, Pump BHP and efficiency v/s Flow) of pumps along with trip
test shall be carried out at manufacturer’s works in Physical presence of
Department’s representatives.
(G) Physical & Chemical Test reports of i) Pump casing (ii) Impeller (iii) Shaft
(iv) Shaft sleeve and Dynamic Balance certificate is to be submitted by OEM

(H)Suitable size Reinforced cement concrete (M-30) foundation with


foundation bolt, Nozing Angle of size 40mm x40mm x5 mm ( Cost of RCC
Foundation to be paid Extra ). All as per pre approved by Engineer in charge.
For additional technical parameters of products/ work , refer Annexure "A"
attached with this BSR .
24.1.1 1620 LPM suitable for 56 Mtr Head End Suction Back pull type Single Stage,
2900 RPM
Each 290,996.00
24.1.2 1620 LPM suitable for 70 Mtr Head End Suction Back pull type Single Stage,
2900 RPM
Each 295,165.00
24.1.3 1620 LPM suitable for 88 Mtr Head Horizontal Axially split casing volute type
Two stage, 1500 RPM
Each 741,468.00
24.1.4 2280 LPM suitable for 56 Mtr Head End Suction Back pull type Single Stage,
2900 RPM
Each 400,221.00
24.1.5 2280 LPM suitable for 70 Mtr Head End Suction Back pull type Single Stage,
2900 RPM
Each 418,616.00

Chapter E -24 page 154


P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-24

Code No. Description Unit Complete Rate

24.1.6 2280 LPM suitable for 88 Mtr Head Horizontal Axially split casing volute type
Two stage, 1500 RPM
Each 776,070.00
24.1.7 2850 LPM suitable for 56 Mtr Head End Suction Back pull type Single Stage,
2900 RPM
Each 428,685.00
24.1.8 2850 LPM suitable for 70 Mtr Head Horizontal Axially split casing volute type
Two stage, 1500 RPM
Each 740,500.00
24.1.9 2850 LPM suitable for 88 Mtr Head Horizontal Axially split casing volute type
Two stage, 1500 RPM
Each 873,004.00

24.2 Supplying, Installation, Testing & Commissioning of Diesel Engine Driven fire
fighting duty pump as per TAC and IS 12469-1988., Factory assembled in
Pump make OEM for Sprinkler / Hydrant applications suitable for automatic
operation and consisting of following details given as A, B, C, D, E, F, G and H.

(A) End Suction / Horizontal Axially split casing volute type Single / Multi stage
Centrifugal pump complete for delivery of below mentioned discharge and
Head
(B) Material of construction : Pump Casing - Cast Iron, Impellor - Bronze,
Shaft - SS 410, Packing - Mechanical Seal
(C)Pump shall be capable of furnishing not less than 150 % of rated capacity
at a head not less than 65 % of the rated head. The shut off head shall not
exceed 120 % of rated head
(D) Heat Exchanger cooled Diesel Engine as per NFPA 20 developing suitable
BHP for the below mentioned discharge at 1500 / 1800 RPM, flexible
coupling and coupling guard with the Pump, common bed plate for mounting
of the Engine and Pump,Antivibration damping arrangement by cushy foot,
Diesel Engine starting Panel for starting of the engine automatically if the
Normal electrical supply fails with a unit of battery bank of 12/24v,180 Ah,
Lead Acid Battery with Boost / Trickle charger as required for operation of
Diesel engine, Exhaust Pipe of suitable diameter upto 10 M length (with LRB
insulation & Alum. Cladding), with muffler, Diesel tank of 300 Lts capacity
(made out from 2 mm thick MS sheet with filling Cap) with drain cock, Diesel
level Indicator, Suitable MS angle iron stand for placing tank, first Filling of
Diesel tank.
(E) Diesel Engine Control comprising Automatic/Manual selctor switch & 3
attempts starting device, timers and relays as required, push buttons,
start/stop in manual mode Indicating lamp for high/ Low Lub. Oil pressure,
High Water Temp and Engine on indication, Battery charger suitbale for
12V/24 V DC with boost and trickle selector switch, 0-30 V DC volt meter, and
0- 20 A DC Ammeter, All standard relays and accessories for automatic
operation of diesel engine System Controller in Existing Fire Fighting Control
panel
(F) The Hydrostatic tests (2 times of design operating head or 1.5 times the
shut off head whichever is higher) and performance tests (to determine
developed head, Pump BHP and efficiency v/s Flow) of pumps along with trip
test shall be carried out at manufacturer’s works in Physical presence of
Department’s representatives.

Chapter E -24 page 155


P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-24

Code No. Description Unit Complete Rate

(G) Physical & Chemical Test reports of i) Pump casing (ii) Impeller (iii) Shaft
(iv) Shaft sleeve and Dynamic Balance certificate is to be submitted by OEM

(H) Pump to be placed on Suitable size Existing Reinforced cement concrete


(M-30) foundation with foundation bolt, Nozing Angle of size 40mm x40mm
x5 mm ( Cost of RCC Foundation to be paid Extra ). All as per pre approved by
Engineer in charge. For additional technical parameters of products/ work ,
refer Annexure "A" attached with this BSR .

24.2.1 1620 LPM suitable for 56 Mtr Head End Suction Back pull type Single Stage,
1800 / 2300 RPM
Each 623555.0
24.2.2 1620 LPM suitable for 70 Mtr Head End Suction Back pull type Single Stage,
1800 / 2300 RPM
Each 672465.0
24.2.3 1620 LPM suitable for 88 Mtr Head Horizontal Axially split casing volute type
Two stage, 1500 RPM
Each 863788.0
24.2.4 2280 LPM suitable for 56 Mtr Head End Suction Back pull type Single Stage,
1800 / 2300 RPM
Each 623555.0
24.2.5 2280 LPM suitable for 70 Mtr Head End Suction Back pull type Single Stage,
1800 / 2300 RPM
Each 853042.0
24.2.6 2280 LPM suitable for 88 Mtr Head Horizontal Axially split casing volute type
Two stage, 1500 RPM
Each 1110656.0
24.2.7 2850 LPM suitable for 56 Mtr Head End Suction Back pull type Single Stage,
1800 / 2300 RPM
Each 610237.0
24.2.8 2850 LPM suitable for 70 Mtr Head Horizontal Axially split casing volute type
Each 817114.0
Two stage, 1500 RPM
24.2.9 2850 LPM suitable for 88 Mtr Head Horizontal Axially split casing volute type
Two stage, 1500 RPM
Each 1143034.0

24.3 Supplying, Installation, Testing & Commissioning of Electrical Driven fire


fighting duty Jockey pump as per TAC and IS 12469-1988., Factory assembled
in Pump make OEM suitable for automatic operation and consisting of
following details given as A, B, C, D, E,F and G
(A) Horizontal End suction Single / Multi Stage Centrifugal Back pull type
pump complete for delivery of below mentioned discharge and Head

(B) Material of construction : Pump Casing - Cast Iron, Impellor - Bronze,


Shaft - SS 410, Packing - Mechanical Seal
(C) Squirrel cage induction motor (IE-3 Class) suitable for 3 phase, 415 V, 50
HZ, Ac supply , Class -F Insulation, Synchronous speed not Exceeding 2900
RPM, T.E.F.C confirming to IP:55 , of required HP suitable for the above
pump ,along with flexible (Love Joy type) coupling , coupling guard complete
in all respect .
(D) Common bed plate fabricated from mild steel channel for installation of
pump and Motor including anti vibration pads.
(E) The Hydrostatic tests (2 times of design operating head or 1.5 times the
shut off head whichever is higher) and performance tests (to determine
developed head, Pump BHP and efficiency v/s Flow) of pumps along with trip
test shall be carried out at manufacturer’s works in Virtual / Physical presence
of Department’s representatives.

Chapter E -24 page 156


P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-24

Code No. Description Unit Complete Rate

(F) Physical & Chemical Test reports of i) Pump casing (ii) Impeller (iii) Shaft
(iv) Shaft sleeve and Dynamic Balance certificate is to be submitted by OEM

(G)Suitable size Reinforced cement concrete (M-30) foundation with


foundation bolt, Nozing Angle of size 40mm x40mm x5 mm ( Cost of RCC
Foundation to be paid Extra ) All as per pre approved by Engineer in charge.
For additional technical parameters of products/ work , refer Annexure "A"
attached with this BSR .
24.3.1 180 LPM suitable for 88 Mtr Multi Stage Each 186055.0
24.3.2 180 LPM suitable for 70 Mtr Single Stage Each 160359.0
24.3.3 180 LPM suitable for 56 Mtr Single Stage Each 152021.0

24.4 Supplying, Installation, Testing & Commissioning of Electrical Driven fire


fighting duty Terrace pump as per TAC and IS 12469-1988., Factory
assembled in Pump make OEM suitable for automatic operation and
consisting of following details given as A, B, C, D, E, F, G and H.
(A) Horizontal End suction Centrifugal Back pull type pump complete for
delivery of below mentioned discharge and Head
(B) Material of construction : Pump Casing - Cast Iron, Impellor - Bronze,
Shaft - SS 410, Packing - Mechanical Seal
(C) Squirrel cage induction motor (IE-3 Class) suitable for 3 phase, 415 V, 50
HZ, Ac supply , Class -F Insulation, Synchronous speed not Exceeding 3000
RPM, T.E.F.C confirming to IP:55 , of required HP suitable for the above
pump ,along with flexible (Love Joy type) coupling , coupling guard complete
in all respect .
(D) Common bed plate fabricated from mild steel channel for installation of
pump and Motor including anti vibration pads.
(E) The Hydrostatic tests (2 times of design operating head or 1.5 times the
shut off head whichever is higher) and performance tests (to determine
developed head, Pump BHP and efficiency v/s Flow) of pumps along with trip
test shall be carried out at manufacturer’s works in Virtual / Physical presence
of Department’s representatives.
(F) Physical & Chemical Test reports of i) Pump casing (ii) Impeller (iii) Shaft
(iv) Shaft sleeve and Dynamic Balance certificate is to be submitted by OEM

(G) Suitable size Reinforced cement concreat (M-30) foundation with


foundation bolt, Nozing Angle of size 40mm x40mm x5 mm ( Cost of RCC
Foundation to be paid Extra )
(H) Weather proof hood fabricated from 5mm thick UV stablised FRP sheet
supported by 50 mm x 50 mm x 5 mm Angle Iron fram above pumpset to
protect it from weather All as per pre approved by Engineer in charge. For
additional technical parameters of products/ work , refer Annexure "A"
attached with this BSR .
24.4.1 450 LPM with 35 mtr head Each 119796.0
24.4.2 900 LPM with 35 mtr head Each 157612.0

Chapter E -24 page 157


P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-24

Code No. Description Unit Complete Rate

24.5 Supplying, Installation, Testing & Commissioning submersible type


dewatering pump of stainless steel casing and Noryl impellor of discharge
and head given below complete with all accessories suitable for operation on
230 V, single phase/415 V /3 phase, 50 Hz. AC supply complete with starter
for automatic operation including water level sensing device / float switch
inter connection with submersible cable etc. as required. All as per pre
approved by Engineer in charge. For additional technical parameters of
products/ work , refer Annexure "A" attached with this BSR .

24.5.1 180 LPM with 10 mtr head Each 28565.0

24.6 SITC of pressure switches of pressure range 3 to 15 Bar for Main, Jockey,
Terrace pump and Diesel pumps, Etc. as Required ( Control Cable from
Pressure switch to Panel to be Paid Extra ). All as per pre approved by
Engineer in charge. For additional technical parameters of products/ work ,
refer Annexure "A" attached with this BSR . Each 2024.0

24.7 Providing and fixing 20/25 mm dia. (PN - 1.6, Type-S1, Flanged, ISI marked) air
release valve confirming to IS - 14845 : 2000 with Double Flange isolating
valve (pressure rating PN 1.6) complete with 1 no. Matching Flanges
(Minimum 10 mm thick), nuts, bolts, washers, gaskets etc as required. All as
per pre approved by Engineer in charge. For additional technical parameters
of products/ work , refer Annexure "A" attached with this BSR .
Each 7012.0

24.8 SITC of UL listed and FM Approved Polyethelene vane type water flow switch
with actuation & delay mechanism for sensitivity in the range of 4 to 10 GPM
and suitable for installation in following sizes of Sprinkler pipe for a Static
pressure rating up to 250 PSI in cluding making connections, making hole in
pipe for inserting the vane etc. as required. All as per pre approved by
Engineer in charge. For additional technical parameters of products/ work ,
refer Annexure "A" attached with this BSR .

24.8.1 80 mm Dia. Each 6074.0


24.8.2 100 mm Dia. Each 7558.0
24.8.3 150 mm Dia. Each 9042.0
24.9 SITC of suitable Pressure release valve of 50 mm dia, of CI body, with
pressure setting range 7-15 kg/sqcm, on discharge header / Air Vessel,
complete in all respect etc. as required. All as per pre approved by Engineer
in charge. For additional technical parameters of products/ work , refer
Annexure "A" attached with this BSR . Each 7627.0
24.10 Providing & fixing pressure transducer in M.S. Pipe line (pressure range 0 to
10 kg/cm2) suitable for 12 volts/24 volt DC. Including connection etc. as
required. ( Control Cable from Pressure Transducer to Panel to be Paid Extra
). All as per pre approved by Engineer in charge. For additional technical
parameters of products/ work , refer Annexure "A" attached with this BSR .
Each 9383.0

Chapter E -24 page 158


P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-24

Code No. Description Unit Complete Rate

24.11 SITC of UL listed / FM Approved Brass Test and drain valve assembly for
sprinkler system comprising of 3-position ( off, test and Drain ) ball valves
with drain orifice having K-factor 5.6 and maximum working pressure 300 PSI
and Inbuilt sight glass etc. as required of following size.
All as per pre approved by Engineer in charge. For additional technical
parameters of products/ work , refer Annexure "A" attached with this BSR .

24.11.1 25 mm Dia. Each 6345.0


24.11.4 50 mm Dia. Each 13999.0
24.12 Providing, Fixing, Jointing, Testing & Commissioning of Heavy duty MS 'C '
class (Heavy) pipes conforming to IS 3589 / 1239 part-I for hydrant and
sprinkler applications including cutting, screwing, welding etc. & forged steel
fittings like elbows, tees, tapers, reducer, gaskets etc. fixing the pipe on the
wall/ceiling with suitable clamps, hanger and nuts bolts including cutting hole
and chase in brick or RCC walls/ slab and making good the same. complete
with painting of one coats of Red Oxide and two or more coats of synthetic
enamel paint of required shade complete as required. (Pipe to be tested @
10Kgf/Sqcm for 2 Hrs.). All as per pre approved by Engineer in charge. For
additional technical parameters of products/ work , refer Annexure "A"
attached with this BSR .
24.12.1 25 mm dia Mtr. 457.0
24.12.2 32 mm dia Mtr. 587.0
24.12.3 40 mm dia Mtr. 682.0
24.12.4 50 mm dia Mtr. 954.0
24.12.5 65 mm dia Mtr. 1218.0
24.12.6 80 mm dia Mtr. 1508.0
24.12.7 100 mm dia Mtr. 2172.0
24.12.9 150 mm dia Mtr. 3202.0
24.12.10 200 mm dia, 6.0 mm thick Mtr. 4852.0
24.12.11 250 mm dia, 6.35 mm thick Mtr. 6031.0
24.12.12 300 mm dia., 7.0 mm thick Mtr. 8003.0

24.13 Providing, Fixing, Jointing, Testing & Commissioning of Heavy duty MS 'C'
class (Heavy) pipe conforming to IS 3589 / 1239 part-I for hydrant and
sprinkler applications in Existing trench with cement concrete block as
supports including cutting, welding etc & forged steel fittings like elbows,
tees, tapers, reducer with cleaning,wrapping and coating of the pipe with 4
mm thick tar based polymaric corrosion protection tape including applying
uniform coat of cold pipekot primer as per IS; 10221 for protection against
corrosion complete in all respect. ( Pipe to be tested @ 10Kgf/Sqcm for 2 Hrs.
& Excavation of Trench and refilling of trench to be paid extra). All as per pre
approved by Engineer in charge. For additional technical parameters of
products/ work , refer Annexure "A" attached with this BSR .

24.13.1 80 mm dia Mtr. 1599.0


24.13.2 100 mm dia Mtr. 2300.0

Chapter E -24 page 159


P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-24

Code No. Description Unit Complete Rate

24.13.3 150 mm dia Mtr. 3392.0


24.13.4 200 mm dia, 6.0 mm thick Mtr. 5130.0
24.14 Providing, laying, testing & commissioning of 'C' class heavy duty G.I. pipe
conforming to IS 1239 including welding, Forged GI fittings like elbows, tees,
tapers, nuts, bolts, gaskets etc. and fixing the pipe on the wall/ceiling with
suitable clamp/support frame and painting with two or more coats of
synthetic enamel paint of required shade complete as required. (Pipe to be
tested @ 10Kgf/Sqcm for 2 Hrs.). All as per pre approved by Engineer in
charge. For additional technical parameters of products/ work , refer
Annexure "A" attached with this BSR .
24.14.1 25 mm dia Mtr. 493.0
24.14.2 32 mm dia Mtr. 634.0
24.14.3 40 mm dia Mtr. 737.0
24.14.4 50 mm dia Mtr. 1034.0
24.14.5 65 mm dia Mtr. 1318.0
24.14.6 80 mm dia Mtr. 1632.0
24.14.7 100 mm dia Mtr. 2303.0
24.14.8 150 mm dia Mtr. 3345.0

24.15 Supplying and fixing cylindrical air vessel of continuous welded construction
for pump room made of 450 mm dia,fabricated out of 10 mm thick dished
ends and 8 mm thick MS sheet, 2000 mm in height with flanged connection,
Provision for 25 mm dia drain valve,air release valve,safety valve pressure
gauge as required accessories and painting with two coats of Red Oxide and
two coat of post office red enamel paint including The tank shall be installed
on suitable vertical legs. The legs shall be provided with M.S. Angle of size 75
mm x 75 mm x 5 mm at the bottom. The legs shall be grouted in cement
concrete foundation. as required. ( Air Release valve, Drain valve, PRV,
Pressure Gauge shall be Paid Extra ). All as per pre approved by Engineer in
charge. For additional technical parameters of products/ work , refer
Annexure "A" attached with this BSR .
Each 40477.0

24.16 Supplying and fixing cylindrical air vessel of continuous welded construction
fixed at riser top made of 250 mm dia, fabricated out of 8 mm thick MS sheet,
1200 mm in height with flanged connection, Provision for 25 mm dia drain
valve,air release valve,safety valve pressure gauge as required accessories
and painting with two coats of Red Oxide and two coat of post office red
enamel paint including The tank shall be installed on suitable vertical legs.
The legs shall be provided with M.S. Angle of size 75 mm x 75 mm x 5 mm at
the bottom. The legs shall be grouted in cement concrete foundation. as
required. ( Air Release valve, Drain valve, PRV, Pressure Gauge shall be Paid
Extra ). All as per pre approved by Engineer in charge. For additional
technical parameters of products/ work , refer Annexure "A" attached with
this BSR .
Each 9022.0

Chapter E -24 page 160


P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-24

Code No. Description Unit Complete Rate

24.17 Supplying and Fixing of PN 16 Flanged Y strainer fabricated out of cast iron
body, SS 304 strainer with perforated screen with 3 mm. dia holes in existing
MS / GI pipe complete with 2 no. Matching Flanges (Minimum 16 mm thick),
nuts, bolts, washers, gaskets etc as required of following sizes. All as per pre
approved by Engineer in charge. For additional technical parameters of
products/ work , refer Annexure "A" attached with this BSR .

24.17.1 80 mm dia Each 8636.0


24.17.2 100 mm dia Each 11828.0
24.17.3 150 mm dia Each 23975.0
24.17.4 200 mm dia Each 41966.0
24.17.5 250 mm dia Each 63672.0

24.18 Supplying and Fixing of PN 16 Flanged sluice valve with non rising spindle,
bronze /gun metal seat confirming to IS:14846 complete with 2 no. Matching
Flanges (Minimum 16 mm thick), nuts, bolts, washers, gaskets, etc as
required of following sizes. All as per pre approved by Engineer in charge. For
additional technical parameters of products/ work , refer Annexure "A"
attached with this BSR .

24.18.1 80 mm dia Each 12446.0


24.18.2 100 mm dia Each 17631.0
24.18.3 150 mm dia Each 27077.0
24.18.4 200 mm dia Each 43892.0
24.18.5 250 mm dia Each 64377.0

24.19 Providing and constructing masonry chamber 90 x 90 x 100 cms inside


with brick work in cement mortar 1:5 (1cement : 5fine sand) for water meter
,M.S. cover (6mmthick sheet with locking arrangement, 600 x600 with M.S.
frame etc. all epoxy coated and R.C.C. top slab 1:2:4 mix(1 Cement : 2
coarsesand : 4 graded stone aggregate 20mm nominalsize) including
necessary excavation, back fillingfoundation concrete 1:5:10 mix (1 cement :
5 fine sand and 10 graded stone aggregate 20mmnominal size) leaving a
pocket of 30x30 cmwith out concrete and filled with pebbles andinside
plastering with cement mortar 1:3 (1 cement : 3 coarse sand) 12 mm thick
finishedwith a floating coat of neat cement and outside plaster finished rough
complete. All as per pre approved by Engineer in charge. For additional
technical parameters of products/ work , refer Annexure "A" attached with
this BSR . Each 23568.0

24.20 Supplying and Fixing of PN 16 Cast Iron Dual Plate Wafer Type Check Valve /
Non return valve with SS / Bronze flap complete with 2 no. Matching Flanges
(Minimum 16 mm thick), nuts, bolts, washers, gaskets, etc as required of
following sizes. All as per pre approved by Engineer in charge. For additional
technical parameters of products/ work , refer Annexure "A" attached with
this BSR .
24.20.1 65 mm dia Each 5423.0
24.20.2 80 mm dia Each 6181.0

Chapter E -24 page 161


P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-24

Code No. Description Unit Complete Rate

24.20.3 100 mm dia Each 7804.0


24.20.4 150 mm dia Each 10541.0
24.20.5 200 mm dia Each 22385.0

24.21 Supplying and Fixing of PN 1.6 Butterfly Valve (Wafer Type) with S.G Iron Disc
and confirming to IS:13095 complete with 2 no. Matching Flanges (Minimum
16 mm thick), nuts, bolts, washers, gaskets, etc as required of following sizes.
All as per pre approved by Engineer in charge. For additional technical
parameters of products/ work , refer Annexure "A" attached with this BSR .

24.21.1 50 mm dia Each 3181.0


24.21.2 65 mm dia Each 3452.0
24.21.3 80 mm dia Each 3756.0
24.21.4 100 mm dia Each 4891.0
24.21.5 150 mm dia Each 7648.0
24.21.6 200 mm dia Gear Operated Each 17320.0
24.21.7 250 mm dia Gear Operated Each 27788.0

24.22 Supplying and Fixing of PN 16 Brass/GM Ball valves with screwed end, SS Ball
including teflon tape etc. as required. All as per pre approved by Engineer in
charge. For additional technical parameters of products/ work , refer
Annexure "A" attached with this BSR .
24.22.1 20 mm dia. Each 1220.0
24.22.2 25 mm dia. Each 1489.0
24.22.3 32 mm dia Each 2841.0
24.22.4 40 mm dia Each 3943.0
24.22.5 50 mm dia Each 6164.0

24.23 Supplying and Fixing of Brass/GM gate valves with screwed end , Non rising
stem and conforming to IS:778 Class-1 including teflon tape etc. as required.
All as per pre approved by Engineer in charge. For additional technical
parameters of products/ work , refer Annexure "A" attached with this BSR .

24.23.1 20 mm dia. Each 1318.0


24.23.2 25 mm dia. Each 1977.0
24.23.3 32 mm dia Each 2783.0
24.23.4 40 mm dia Each 3689.0
24.23.5 50 mm dia Each 5378.0

Chapter E -24 page 162


P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-24

Code No. Description Unit Complete Rate

24.24 SITC of installation control valve of cast iron body and brass/bronze working
parts comprising of water motor alarm, bronze seat clapper, and clapper arm,
hydraulically driven mechanical gong bell to sound continous alarm when the
wet riser/Sprinkler system activates, pressure gauges, emergency releases,
strainer, pressure switch, cock valve complete with drain valve and bypass,
test control box, ball valves, with 2 no. Matching Flanges (Minimum 16 mm
thick), nuts, bolts, washers, gaskets, etc as required of following sizes. All as
per pre approved by Engineer in charge. For additional technical parameters
of products/ work , refer Annexure "A" attached with this BSR .

24.24.1 100 mm Each 48284.0


24.24.2 150 mm Each 53186.0

24.25 Supplying and fixing of SS 304 Single / Double headed oblique pattern
hydrant landing valve (internal/external) with 75 / 100 mm dia flanged inlet &
63 mm dia instantaneous type female outlet coupling with cast iron wheel
complete with ABS cap and chain and all accessories as per IS:5290-93 (Type-
A) in cluding matching flange (14 mm thick), nuts, bolts, washers, gaskets,
etc as required. All as per pre approved by Engineer in charge. For additional
technical parameters of products/ work , refer Annexure "A" attached with
this BSR .
24.25.1 Single Headed with 75 mm Dia. Flanged Inlet Each 8022.0
24.25.2 Double Headed with 100 mm Dia. Flanged Inlet Each 14686.0

24.26 Supplying and fixing orifice plate made of 6 mm thick stainless steel with
orifice of required size in between flange & landing valve of external and
internal hydrant to reduce pressure to working pressure of 3.5 kg/cm2
complete with rubber gasket, GI bolts, nuts, washers etc. as required. All as
per pre approved by Engineer in charge. For additional technical parameters
of products/ work , refer Annexure "A" attached with this BSR .
Each 1457.0

24.27 Supplying and fixing of flexible hose made with 100% polyester, black EPDM
internal rubber lining with External coat of synthetic elastomer (IS:636, type-
A) 63 mm dia, 15 mtr. Long RRL hose pipe with instanteneous type 63 mm
dia SS-304 male and female couplings (IS:903) duly bound and riveted to
hose pipes with copper rivets and SS wire etc. as required.Appropriate Test
Certificate/ report with liable warranty of product/accessories from OEM
shall be submitted. Each 7596.0

24.28 Supplying & fixing SS-304 Short Branch Pipe conforming to IS: 903:93 fitted
with 20mm (nominal internal diameter) bore nozzle, for projecting water in
form of solid jet. The Branch shall have 63mm Male Instantaneous Inlet,
suitable for use with 63 mm size Fire fighting hoses. H.P. tested to 21 kgf/cm²
for 2.5 minutes. All as per pre approved by Engineer in charge. For additional
technical parameters of products/ work , refer Annexure "A" attached with
this BSR . Each 2565.0

Chapter E -24 page 163


P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-24

Code No. Description Unit Complete Rate

24.29 Supplying and fixing first -Aid Fire hose reel Drum wall mounted swinging
type with MS construction powder painted in post office Red, conforming to
IS 884-1985 with upto date amendments, complete with the following as
required. (A) Thermoplastic / Rubber Hose (B)20 mm dia UL, FM Bronze / SS
nozzle with 5mm orifice (C)Drum and brackets for fixing the equipments on
wall. (D) Connections from riser with 20/25 mm dia Brass/GM gate valves
with screwed end and conforming to IS:778 Class-1 through Forged steel
Screwed Union & M.S. pipe. Etc. as required. All as per pre approved by
Engineer in charge. For additional technical parameters of products/ work ,
refer Annexure "A" attached with this BSR .

24.29.1 With 30 m x 20 mm Thermoplastic hose as per IS:12585 Type-2 and Bursting


pressure 42 Kg/sqcm Each 11872.0
24.29.2 With 30 m x 20 mm High Pressure Braided Rubber Hose as per IS:5132 - 1969
and Bursting pressure 42 Kg/sqcm Each 12479.0
24.30 Supplying and fixing Inlet Breeching Connection of CI body with Gun Metal
male instantaneous inlet couplings with Inbuilt NRV, Drainage Connection
with 50 mm Brass gate valve complete with PVC blank cap and chain as
required for 150mm dia Outlet with 1 no. Matching Flange (Minimum 16 mm
thick), nuts, bolts, washers, gaskets, etc as required of following Ways. All as
per pre approved by Engineer in charge. For additional technical parameters
of products/ work , refer Annexure "A" attached with this BSR .

24.30.1 2 Way Each 10214.0


24.30.2 3 Way Each 12034.0
24.30.3 4 Way Each 13854.0

24.31 Providing and fixing of 100 mm Dia. Flanged Gun Metal Fire brigade Suction
hose coupling (draw out connection) for female coupling as per IS:902-1974
complete with Matching Flange (Minimum 14 mm thick), nuts, bolts, washers,
gaskets, etc as required. All as per pre approved by Engineer in charge. For
additional technical parameters of products/ work , refer Annexure "A"
attached with this BSR .
Each 10548.0

24.32 Supply and Fixing of Cast iron body one side Flanged and other side strainer
ball type foot valve with Reinforced rubber Nitrile rubber coated Ball
including Matching Flange (Minimum 16 mm thick), nuts, bolts, washers,
gaskets, etc as required of following Sizes. All as per pre approved by
Engineer in charge. For additional technical parameters of products/ work ,
refer Annexure "A" attached with this BSR .

24.32.1 80 mm Dia. Each 7226.0


24.32.2 100 mm Dia. Each 11294.0
24.32.3 150 mm Dia. Each 22742.0
24.32.4 200 mm Dia. Each 45138.0

Chapter E -24 page 164


P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-24

Code No. Description Unit Complete Rate

24.33 Providing and Fixing of PN16 Resilient rubber lined single arch vibration
eliminators suitable for raw water up to 45 deg. C temperature, working
pressure 8.5 Kg/cm2 and test pressure 14 Kg/cm2 to provide relief from
stresses at pipe including Matching Flange (Minimum 16 mm thick), nuts,
bolts, washers, gaskets, etc as required of following Sizes. All as per pre
approved by Engineer in charge. For additional technical parameters of
products/ work , refer Annexure "A" attached with this BSR .

24.33.1 80 mm Dia. x 150 mm Oal Each 8357.0


24.33.2 100 mm Dia. x 150 mm Oal Each 10021.0
24.33.3 150 mm Dia. x 150 mm Oal Each 12838.0

24.34 Supplying and fixing of 750 mm x 600 mm x 250 mm Outdoor application Fire
Hose Cabinet made of 1.6 mm thick MS sheet Duly powder coated in red
color externally and white internally with 6 mm thick glazed doors with
Expanded Metal 2 mm thick Jali including necessary locking arrangement
suitable to accommodate 2 Nos 15 Mtr. Long RRL Hose and 1 No. branch pipe
on Existing Wall / Angle Iron Frame as required. (Cost of MS structure for
mounting Frame is to be Paid Extra) All as per pre approved by Engineer in
charge. For additional technical parameters of products/ work , refer
Annexure "A" attached with this BSR .
Each 5601.0

24.35 Supplying and fixing of 1000 mm x 600 mm x 500 mm Outdoor application


Fire Hose Cabinet made of 1.6 mm thick MS sheet Duly powder coated in red
color externally and white internally with 6 mm thick glazed doors with
Expanded Metal 2 mm thick Jali including necessary locking arrangement
suitable to accommodate External hydrant with butterfly valve, 2 Nos 15 Mtr.
Long RRL Hose and 1 No. branch pipe on Existing Wall / Angle Iron Frame as
required. (Cost of MS structure for mounting Frame is to be Paid Extra). All as
per pre approved by Engineer in charge. For additional technical parameters
of products/ work , refer Annexure "A" attached with this BSR .
Each 16869.0
24.36 Providing and fixing of Fire / Electrical Shaft Door made from powder coated
(50 Micron) aluminium partialy glazed with 6 mm thick glass and Partialy /
Fully Louvered with Outer frame of Aluminium Section of Size 100 mm x 45
mm x 1.5 mm and Shutter's Top, Middle & side Section of Size 82 mm x 45
mm x 1.5 mm, Bottom Section of Size 110 mm x 45 mm x 1.5 mm Complete
with Hinges, Tower bolt, Handle, Aldrop, Locking Arrangement including dash
fasteners of required dia and size, necessary filling up the gaps at junctions,
i.e. at top, bottom and sides with required EPDM rubber/ neoprene gasket
etc. as per drawings and the directions of Engineer-in-charge. All as per pre
approved by Engineer in charge. For additional technical parameters of
products/ work , refer Annexure "A" attached with this BSR .
Sqm 9852.0

Chapter E -24 page 165


P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-24

Code No. Description Unit Complete Rate

24.37 Providing and Fixing of 15 mm dia Bronze quartzoid bulb type sprinkler heads
with Maximum working pressure 11.6 Kg / Sqcm and suitable for 68 degree
centigrade rating standard response (UL Listed) chrome plated complete in all
respect of the following type. All as per pre approved by Engineer in charge.
For additional technical parameters of products/ work , refer Annexure "A"
attached with this BSR .
24.37.1 Pendant/ Upright type Each 290.0
24.37.2 Sidewall Sprinklers (ordinary) Each 303.0
24.37.3 Extended Throw Sidewall type . Each 506.0
Concealed type with Tin alloy fusible metal plate for temperature 57 degree
24.37.4 Centigrade
Each 1046.0

24.38 Providing & fixing of UL listed 1.5 mm thick chrome plated Dual type MS
Escutcheon plates fixed at junction of Sprinkler piping with the false ceiling.
All as per pre approved by Engineer in charge. For additional technical
parameters of products/ work , refer Annexure "A" attached with this BSR .
Each 108.0

24.39 Supply & Fixing of Fire Man's Axe with carbon steel head & rubber moulde
handel usable upto 20 KV and confirming to IS :926 with length approx 0.4 M
& weight 3.0 Kg. All as per pre approved by Engineer in charge. For additional
technical parameters of products/ work , refer Annexure "A" attached with
this BSR . Each 1918.0
24.40 Providing & fixing sprinkler flexible pipe (UL Listed) of stainless steel
complete with 15 NPT on reducer thread with maximum working pressure of
175 PSI test pressure of 875 PSI (Burst) with branch line (Inlet) 25mm NPT
male thread to sprinkler head (Outlet) 15mm NPT female thread with
reducer, nipple, 2 side brackets, center bracket, stockbar of following sizes
complete as required. All as per pre approved by Engineer in charge. For
additional technical parameters of products/ work , refer Annexure "A"
attached with this BSR .
24.40.1 700 mm Long Each 944.0
24.40.2 1000 mm Long Each 1106.0
24.40.3 1200 mm Long Each 1281.0
24.40.4 1500 mm Long Each 1450.0

24.41 Providing & fixing Stainless Steel pressure gauge with dial of 150 mm dia size
and range 0 to 20 kg/sq.cm with 3 / 8 " BSP bottom entry , Ball valve , SS
Syphon tube all fittings etc, duly calibrated before installation in MKS and FPS
units, Accuracy Level +/- 1% including Making Drilling in Existing MS Pipe Etc.
as required. All as per pre approved by Engineer in charge. For additional
technical parameters of products/ work , refer Annexure "A" attached with
this BSR . Each 2632.0

Chapter E -24 page 166


P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-24

Code No. Description Unit Complete Rate

24.42 SITC of UL 10th edition / EN54 / VDS certified Automatic Floating Sensitivity
type Analog addressable Multi criteria (two optical/Smoke sensor to reduce
false alarm) detector with mounting base & LED etc. as required. All as per
pre approved by Engineer in charge. For additional technical parameters of
products/ work , refer Annexure "A" attached with this BSR .
Each 3104.0

24.43 SITC of UL 10th edition / EN54 / VDS certified Rate of Rise Heat Detectors
(Thermal Detectors):GRADE-I Analouge Addressable type Heat Detectors with
solid state design with sensing element combination of fixed type and rate of
rise of temperature mounting base & LED etc. as required. All as per pre
approved by Engineer in charge. For additional technical parameters of
products/ work , refer Annexure "A" attached with this BSR .
Each 2969.0

24.44 SITC of UL 10th edition / EN54 / VDS certified Analouge Addressable type
Multi criteria (Heat & smoke) Beam detector along with interface module
having a coverage area with a distance of min. 10 m and max. 100 m
,Operating temperature range: -20 C to +55 C, Response sensitivity of 40% ,
shall UL/EN54 certification including transmitter and receiver unit with
mounting base & LED etc including the cost of all accessories, mouting
arrangement Etc. as required. All as per pre approved by Engineer in charge.
For additional technical parameters of products/ work , refer Annexure "A"
attached with this BSR . Set 48594.0

24.45 SITC of UL 10th edition / EN54 / VDS certified Addressable type fault isolator
with base for isolating shorted, dewired and loose circuits between two
successive fault, isolators with automatic resetting arrangement etc. as
required. All as per pre approved by Engineer in charge. For additional
technical parameters of products/ work , refer Annexure "A" attached with
this BSR . Each 2726.0

24.46 SITC of UL 10th edition / EN54 / VDS certified Addessable Manual Call point
(MCP) with LED / FIRE Indication Etc. as required. All as per pre approved by
Engineer in charge. For additional technical parameters of products/ work ,
refer Annexure "A" attached with this BSR . All as per pre approved by
Engineer in charge. For additional technical parameters of products/ work ,
refer Annexure "A" attached with this BSR .
Each 3509.0

24.47 SITC of UL 10th edition / EN54 / VDS certified Addressable sounder with
strobe light, Loop Powered / Direct powered from FACP with sound level 90
dB and programmable from the panel etc. as required. All as per pre
approved by Engineer in charge. For additional technical parameters of
products/ work , refer Annexure "A" attached with this BSR .
Each 8128.0

Chapter E -24 page 167


P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-24

Code No. Description Unit Complete Rate

24.48 SITC of UL 10th edition / EN54 / VDS certified addresaable automatic fire
detector for monitoring of ventilation ducts which can perform alarm pattern
analysis, with even response sensitivity for all fires with smoke development
with 1 no outlet tube & with 1 no. analogue addressable Photo Electric type
Smoke Detector with mounting base , address switch etc. as required. All as
per pre approved by Engineer in charge. For additional technical parameters
of products/ work , refer Annexure "A" attached with this BSR .
Each 11203.0
24.49 SITC of Response Indicator for indicating the activation of the Remotely
located Detector for Addressable type Detectors Etc. as required. All as per
pre approved by Engineer in charge. For additional technical parameters of
products/ work , refer Annexure "A" attached with this BSR .
Each 269.0

24.50 SITC of UL 10th edition / EN54 / VDS certified Addressable control


(input/output) modules/ Relay Module for shutting down lifts, Hooters,
AHU's, Acknoledgement of Sprinkler system with potential free contact
monitoring Etc. as Required. All as per pre approved by Engineer in charge.
For additional technical parameters of products/ work , refer Annexure "A"
attached with this BSR . Each 5009.0

24.51 SITC of UL 10th edition / EN54 / VDS certified Microprocessor based


inteligent, Analogue addressable,modular, expandable networkable loop Fire
Alarm Control Panel with each loop capacity of min 125 detectors per loop
with total of 125 detectors & devices with Loop length up to 1 KM as per
NFPA 72 approval. The Panel shall be able to give pin point location of
addressable units via the address code for each unit. The Panel shall also be
able to automatically switch off all control switches when-ever any Alarm is
triggered. . The panel shall have 230 + 5 % volts power supply, Automatic
battery charger 24V, sealed lead acid maintanence free battries sufficient for
24 hours normal working and then be capable of operating the system for 30
minutes during emergency condtion. Loop interface cards, communication
module, LCD/LED unit to indicate Fire / Fault Signal of individual unit, inbuilt
networking port(both RS485&Ethernet),Serial port for printer,two
supervisory inputs,two position key switch and USB port for
programming.including the cost of all accessories Etc. as required. All as per
pre approved by Engineer in charge. For additional technical parameters of
products/ work , refer Annexure "A" attached with this BSR .
24.51.1 1 - Loop Panel Each 222644.0
24.51.2 2 - Loop Panel Each 296858.0
24.51.3 Add Extra for per Loop expansion beyond Two Loop per Loop 67462.0
Add Extra for Graphics User Inteface (GUI) Software for programming the fire
24.51.4 detection and voice alarm system through FACP / PC.
Each 121485.0

Chapter E -24 page 168


P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-24

Code No. Description Unit Complete Rate

24.51.5 Add Extra for Workstation latest Intel® i5 processor, Intel Chipset
motherboard, 08 GB RAM, 1 TB SATA HDD at 7200 rpm, with 2 x 4GB GPU
type higher end Graphic card for H.265 compression technique with dual
display ports/DVI/ HDMI port, Giga LAN Card, wireless Keyboard, wireless
optical Mouse. All as per pre approved by Engineer in charge. For additional
technical parameters of products/ work , refer Annexure "A" attached with
this BSR . Each 91130.0
24.52 SITC of UL 10th edition / EN54 / VDS certified Active Repeater Panel for Fire
Alarm System with inbuilt networking port (both RS485 & Ethernet),Serial
port for printer,two supervisory inputs,two position key switch and USB port
for programming. The Repeater Panel shall allow users to acknowledge,
reset,silence, program, view hisory events.etc (All functions similar to main
panel)The user interface of the repeater panel shall be same as the Main
Controller with menu driven user interface with smart search.including the
cost of all accessories Etc. as required. All as per pre approved by Engineer in
charge. For additional technical parameters of products/ work , refer
Annexure "A" attached with this BSR .
Each 80967.0

24.53 SITC of UL 10th edition / EN54 / VDS certified 6 ZONE Digital Voice Command
Center with FACP, it shall contain all equipment required for all audio
control, signaling and supervisory functions. This shall include speaker zone
indication and control, digital voice units, microphone etc. The Digital Voice
Command Center shall have digital voice call station suitable for 6 zone,
digital voice controller & router suitable for 6 zone, 4 nos 240 watt & 1no 480
watt amplifier & digital amplifier capable for 1440 watt load etc.including the
cost of all accessories Etc. as required. All as per pre approved by Engineer in
charge. For additional technical parameters of products/ work , refer
Annexure "A" attached with this BSR . Each 124186.0

24.54 SITC of EN / LPCB/ UL listed / approved conventional automatic fire Alarm


Optical/Photoelectric type smoke detectors of photo-optic sensing chamber,
12 / 24 volt D.C., visual alarm indicator (LED's) "Blink - green" in stand by and
"Steady - red" in alarm complete in all respects with base as
required.including the cost of all accessories Etc. as required. All as per pre
approved by Engineer in charge. For additional technical parameters of
products/ work , refer Annexure "A" attached with this BSR .
Each 1484.0

24.55 SITC of EN / LPCB/ UL listed / approved conventional automatic fire Alarm


Rate of Rise cum fixed temperature thermister type Heat Detectors , 12 / 24
volt D.C., visual alarm indicator (LED's) "Blink - green" in stand by and "Steady
- red" in alarm complete in all respects with base as required.including the
cost of all accessories Etc. as required. All as per pre approved by Engineer in
charge. For additional technical parameters of products/ work , refer
Annexure "A" attached with this BSR .
Each 1416.0

Chapter E -24 page 169


P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-24

Code No. Description Unit Complete Rate

24.56 SITC of EN / LPCB/ UL listed / approved conventional type Manual call point
resettable complete with Glass, hammer and chain etc.including the cost of
all accessories Etc. as required. All as per pre approved by Engineer in charge.
For additional technical parameters of products/ work , refer Annexure "A"
attached with this BSR . Each 606.0

24.57 SITC of EN / LPCB/ UL listed / approved conventional type Hooter cum


strobe including the cost of all accessories,Etc. as required. All as per pre
approved by Engineer in charge. For additional technical parameters of
products/ work , refer Annexure "A" attached with this BSR .
Each 673.0

24.58 SITC of Response Indicator for indicating the activation of the Remotely
located Detector for Conventional type detectors as required. All as per pre
approved by Engineer in charge. For additional technical parameters of
products/ work , refer Annexure "A" attached with this BSR .
Each 269.0

24.59 SITC of wall type following zone (each zone accessing minimum 20 units
(detectors/ devices )) Conventional Type microprocessor based with LCD
display EN / LPCB/ UL listed / approved main control panel fabricated from 16
SWG CRCA sheet steel sealed maintenance free (SMF) batteries of
min2X7AH of 12 V or as required.including the cost of all accessories, Etc. as
required. All as per pre approved by Engineer in charge. For additional
technical parameters of products/ work , refer Annexure "A" attached with
this BSR .
24.59.1 4 zone Each 40450.0
24.59.2 6 zone Each 63383.0
24.59.3 Add extra for every 2 Zone Each 16180.0

24.60 SITC of 2 way communication Fire Fighter's Telephone Jack.Complete as


required . All as per pre approved by Engineer in charge. For additional
Each 1753.0
technical parameters of products/ work , refer Annexure "A" attached with
this BSR .
24.61 SITC of 2 way communication Fire Fighter's Telephone Handset to make a call
to the Main FACP from Telephone Jack Location Complete as required . All as
per pre approved by Engineer in charge. For additional technical parameters Each 12222.0
of products/ work , refer Annexure "A" attached with this BSR .

24.62 Supplying and drawing Fire Resistant flexible / stranded bare copper
conductor, PVC / XLPE insulated, overall aluminium mylar tape shielded ATC
drain wire and outer PVC sheathed industrial Instrumentation
(shielded)cables voltage grade 300/500 V as per BS /EN 50288-7 in existing
surface or recessed PVC/ MS conduit/casing capping / Cable tray / Open Duct
making connections, testing etc. as required. OEM Must have its own in
house NABL lab setup for all testing facilities for cables. All as per pre
approved by Engineer in charge. For additional technical parameters of
products/ work , refer Annexure "A" attached with this BSR .

Chapter E -24 page 170


P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-24

Code No. Description Unit Complete Rate

24.62.1 2 x 1.5 Sq.mm Unarmoured With Outer Sheath in Red Color Mtr 94.0
24.62.2 2 x 1.5 Sq.mm Armoured With Outer Sheath in Red Color Mtr 158.0
24.63 SITC of PA system Operator Console of following wattage to be installed with
Conventional fire alarm system complete with following capacity , channel
mixing amplifier , 1 no cardioids goose neck microphone , 1 no professional
grade cassette deck/ CD Player , 16 zone floor selector console , equipment
rack complete in all respects. PA system shall be coupled to the Fire Alarm
System. Etc. as required. All as per pre approved by Engineer in charge. For
additional technical parameters of products/ work , refer Annexure "A"
attached with this BSR .

24.63.1 1 x 120 Watt Each 48607.0


24.63.2 1x 240 Watt Each 62782.0
24.63.3 1x 350 Watt Each 70203.0

24.64 SITC 6 watt Speaker mounted in M S sheet box with perforated front mesh
for PA and Emergency System. All as per pre approved by Engineer in charge.
For additional technical parameters of products/ work , refer Annexure "A"
attached with this BSR . Each 943.0

24.65 Supply & Fixing of Water + AFFF 6% Mechanical Foam type Fire Extinguisher
(Stored Pressure type) conforming to IS:15683:2018 , Powder coated Internal
& External Surface Deep drawn cylinder body of Mild Steel CR2 grade
conforming to IS: 513, Squeeze grip Forged brass release valve with Inbuilt
safety release device, Diaphragm Type, 0 to 25 bar range pressure gauge, 450
mm long EPDM discharge tube, QR code for Product Traceability including
Fixing on wall with suitable Anchor Fasteners as required of following
capacity. Test Certificates of all the Parameters along with Hydro test & Burst
test (For Cylinder Body) Certificate from OEM / External NABL Accrediated
Lab is to be submitted. All as per pre approved by Engineer in charge. For
additional technical parameters of products/ work , refer Annexure "A"
attached with this BSR .
24.65.1 Capacity - 6 Ltrs. Each 3577.0
24.65.2 Capacity - 9 Ltrs. Each 4522.0
24.66 Supply & Fixing of CO2 type Fire Extinguisher conforming to IS:15683:2018,
charged with CO2 gas (purity 99.7% conforming to IS 15222), Powder coated
Internal & External Surface Manganese steel ISI marked as per IS 7285
cylinder body , Wheel type Forged brass release valve ISI Marked as per IS
3224 with Inbuilt safety release device ((Fusible plug and Rupture Disc Type),
1.0 Mtr. Metal wire braided hose having minimum bursting pressure of 140
Kgf/cm2, Horn with metallic thread connection, QR code for Product
Traceability, including Fixing on wall with suitable Anchor Fasteners as
required of following capacity. Test Certificates of all the Parameters along
with Hydro test & Burst test (For Cylinder Body) Certificate from OEM /
External NABL Accrediated Lab is to be submitted. All as per pre approved by
Engineer in charge. For additional technical parameters of products/ work ,
refer Annexure "A" attached with this BSR .
24.66.1 Capacity 3.0 Kg. Each 7332.0

Chapter E -24 page 171


P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-24

Code No. Description Unit Complete Rate

24.66.2 Capacity 4.5 Kg. Each 8547.0

24.67 Supply & Fixing of Dry Powder Agent (as per IS 4308:2019), ABC type Fire
Extinguisher (Stored Pressure type) conforming to IS:15683:2018 , Powder
coated Internal & External Surface Deep drawn cylinder body of Mild Steel
CR2 grade conforming to IS: 513, Squeeze grip Forged brass release valve with
Inbuilt safety release device, Diaphragm Type, 0 to 28 bar range pressure
gauge, 450 mm long EPDM discharge tube, QR code for Product Traceability
including Fixing on wall with suitable Anchor Fasteners as required of
following capacity. Test Certificates of all the Parameters along with Hydro
test & Burst test (For Cylinder Body) Certificate from OEM / External NABL
Accrediated Lab is to be submitted. All as per pre approved by Engineer in
charge. For additional technical parameters of products/ work , refer
Annexure "A" attached with this BSR .
24.67.1 2 kg Each 2767.0
24.67.2 4 kg Each 4104.0
24.67.3 6 kg Each 4576.0
24.67.4 9 kg Each 5954.0

24.68 Supply & Fixing of Trolley mounted 22.5 Kg CO2 type Fire Extinguisher
conforming to IS: 16018:2012, charged with CO2 gas (purity 99.7%
conforming to IS 15222), Powder coated Internal & External Surface
Manganese steel ISI marked as per IS 7285 cylinder body , Wheel type Forged
brass release valve ISI Marked as per IS 3224 with Inbuilt safety release device
((Fusible plug and Rupture Disc Type), 1.5 Mtr. long Metal wire braided hose
having minimum bursting pressure of 140 Kgf/cm2, Horn with metallic thread
connection, QR code for Product Traceability, including Double mounted
handle as required of following capacity. Test Certificates of all the
Parameters along with Hydro test & Burst test (For Cylinder Body) Certificate
from OEM / External NABL Accrediated Lab is to be submitted. All as per pre
approved by Engineer in charge. For additional technical parameters of
products/ work , refer Annexure "A" attached with this BSR . Each 26442.0
24.69 Supply & Fixing of Ceiling mounted Dry Powder Agent (as per IS 4308:2019),
Modular stored pressure type ABC Fire Extinguisher , Powder coated Internal
& External Surface Deep drawn cylinder body of Mild Steel CR2 grade
conforming to IS: 513, Fixed Bulb with Temerature 68 deg C, QR code for
Product Traceability including Fixing on Ceiling with suitable Anchor Fasteners
as required of following capacity. Test Certificates of all the Parameters along
with Hydro test & Burst test (For Cylinder Body) Certificate from OEM /
External NABL Accrediated Lab is to be submitted. All as per pre approved by
Engineer in charge. For additional technical parameters of products/ work ,
refer Annexure "A" attached with this BSR .
24.69.1 5 Kg Capacity Each 6179.0
24.69.2 10 Kg Capacity Each 9349.0

Chapter E -24 page 172


P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-24

Code No. Description Unit Complete Rate

24.70 Supply & Fixing of Ceiling mounted UL listed clean Agent (HFC-236fa),
Modular type Fire Extinguisher , Powder coated Internal & External Surface
Deep drawn cylinder body of Mild Steel CR2 grade conforming to IS: 513,
Fixed Bulb with Temerature 68 deg C, QR code for Product Traceability
including Fixing on Ceiling with suitable Anchor Fasteners as required of
following capacity. Test Certificates of all the Parameters along with Hydro
test & Burst test (For Cylinder Body) Certificate from OEM / External NABL
Accrediated Lab is to be submitted. All as per pre approved by Engineer in
charge. For additional technical parameters of products/ work , refer
Annexure "A" attached with this BSR .
24.70.1 5 Kg Capacity Each 24304.0
24.70.2 10 Kg Capacity Each 44626.0
24.71 Supplying and Fixing of Galvanized Mild Steel fire bucket Confirming to IS:
2546 : 1974 with one coat of primer and two coat of enamel paint of
approved shade on Angle Iron ( 50 x 50 x 5 mm) Stand of Size 800 x 1240 x
400 mm with MS 22 SWG Galvanized Canopy, 4 Hooks for Buckets including
associated civil works etc. as required. All as per pre approved by Engineer in
charge. For additional technical parameters of products/ work , refer
Annexure "A" attached with this BSR .
Set 11466.0
24.72 Providing and fixing signages as per required content printed on
photoluminescent U1000 aluminium sheet of 1.0 mm (+-10%) containing
Lumigen II as base chemical, covered under UV stablized coating with suitable
colour combination (Glow in dark) with high intensity properties for
indoor surface glow visibility not less than 6 hrs. in total darkness and of
appropriate size including fixing on wall, door, ceiling etc. with proper
clamps, hangers, cleats, anchor fasteners etc. complete in all respects
required. All as per pre approved by Engineer in charge. For additional
technical parameters of products/ work , refer Annexure "A" attached with
this BSR .
24.72.1 Single sided signage board Sq.Inch 9.00
24.72.2 Double sided signage board Sq.Inch 14.00

24.73 Providing and fixing of Aluminium housing body self contained


Rechargeable LED Emergency Light with required content and Size Approx.
300 mm x 180 mm, confirming to IS:9583 :1981with Ni-Mh / Ni - Cd Battery, 3
Hrs Back Up, Constant Current Charger, Input Voltage 230 V , 50 Hz including
fixing on wall, door, ceiling etc. with proper clamps, hangers, cleats, anchor
fasteners etc. complete in all respects required. All as per pre approved by
Engineer in charge. For additional technical parameters of products/ work ,
refer Annexure "A" attached with this BSR .
24.73.1 Single sided signage Each 4386
24.73.2 Double sided signage Each 5128

Chapter E -24 page 173


P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-25

Chapter E - 25

Hire Charges for PA System & Temporary Lighting


Code No. Description Unit Complete Rate

25.1 Hire charges for LED Flood light luminaire ( white or warm white as required
)for 90- 150 watt with the standard housing ,pole & mounting accessories
with wiring, connection with skilled operator to operate system as and
when etc as required. (If work contineue for more then one day , rates
for next subsequent days will be 50% of the original rates.)

25.1.1 With suitable pole Each/Day 254.0


25.1.2 With out pole Each/Day 170.0

25.2 Hire charges for LED Flood light luminaire ( white or warm white as required
)for 200- 250 watt with the standard housing ,pole & mounting accessories
with wiring, connection with skilled operator to operate system as and
when etc as required. (If work contineue for more then one day , rates
for next subsequent days will be 50% of the original rates.)

25.2.1 With suitable pole Each/Day 339.0


25.2.2 With out pole Each/Day 254.0

25.3 Hire charges for weather proof round LED Rope/neon flex LED / Flexible strip
type LED having 2 to 5 watts/meter capacity and consisting suitable power
adapter with mains , switchgear etc complete with connection with skilled
operator to operate system as and when etc as required. (If work Mtr/day 8.0
contineue for more then one day , rates for next subsequent days will be
50% of the original rates.)

25.4 Hire charges for IP 66 protected programmable RGB LED flood light with
alluminium alloy housing and having 180 degree bracket adjustment
complete with driver switchgear , wiring, connection , testing etc. with
skilled operator to operate system as and when etc as required. (If work
contineue for more then one day , rates for next subsequent days will be
50% of the original rates.)
25.4.1 100 watt Each/Day 509.0
25.4.2 150 watt Each/Day 576.0
25.4.3 180 watt Each/Day 848.0
25.4.4 300 watt Each/Day 1187.0

25.5 Hire Charges for LED Screen Day light type of suitable size for Display
complete with mounting arrangement/scaffolding, masking of mounting
stand, signal booster, network switch /splitter, data and power cables and
sound system arrangement etc. with skilled operator to operate system as sq.ft/ day 264.0
and when etc as required. (If work contineue for more then one day , rates
for next subsequent days will be 50% of the original rates.)

25.6 Hire Charges for HD Video camera suitable for HDMI output, recording in
DVD/hard disk fuction complete with two operator as and when etc as
required. (If work contineue for more then one day , rates for next Each/Day 5528.0
subsequent days will be 50% of the original rates.)

Chapter E -25 Page 174


P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-25

Code No. Description Unit Complete Rate

25.7 Hire charges for video Projection Arrangement (excluding screens) with 3
Nos. Video Camera (PWM 120 sony NX 5Z7/Equivalent) including mixer
(Pansonix MX70/Data Video MX500/ Equivalent) Complete with required
HDMI/VGA etc. wiring VTR, switchers, with skilled operator to operate Each/Day 35382.0
system as and when etc as required. (If work contineue for more then one
day , rates for next subsequent days will be 50% of the original rates.)

25.8 Hire charges of Crane with operators for video camera for 360° movement
complete arrangement with skilled operator to operate system as and when
etc as required. (If work contineue for more then one day , rates for next Job / day 10615.0
subsequent days will be 50% of the original rates.)

25.9 Providing experienced and Highly skilled/skilled/ semi-skilled/Un Skilled


labour for electric repair/ maintenance / operation of Air conditioning/Air
cooling/Fire fighting/Lift/DG set/CCTV/EPABX or any other
electromechanical systems as per requirement (one shift of 8 Hrs per day for
26 Working Days in a month)
25.9.1 Highly skilled Labour Each Per Month 11334.0
25.9.2 skilled Labour Each Per Month 9596.0
25.9.3 Semi skilled labour Each Per Month 9179.0
25.9.4 Un skilled labour Each Per Month 8761.0

25.10 Add for extra working on Holidays.


25.10.1 Highly skilled Labour Each Per Day 436.0
25.10.2 skilled Labour Each Per Day 369.0
25.10.3 Semi skilled labour Each Per Day 353.0
25.10.4 Un skilled labour Each Per Day 337.0

25.11 NOTE: Over time rates shall be two times of that category.
25.12 NOTE: Part time rates up to 4 Hours shall be charged @ 50% of that category
.
25.13 NOTE: Part time rates for more than 4 Hours but less than 8 Hours shall be
charged @ 100% of that category .

25.14 Charges for Providing of experienced and Highly skilled/ skilled/semi-skilled/


Un skilled labour for electric repair/ maintenance/operation of Air
conditioning /Air cooling / Fire fighting /Lift/D G set /CCTV/EPABX or any
other electromechanical services/ systems as required.( One shift of 8 Hours
per day )
25.14.1 Highly Skilled Labour shift / day 436.0
25.14.2 Skilled Labour shift / day 369.0
25.14.3 Semi skilled labour shift / day 353.0
25.14.4 Un skilled labour shift / day 337.0

25.15 Hire charges for 42" HD LED/Plazma TV complete with mounting


arrangement , connections, testing etc. with skilled operator to operate
system as and when etc as required. (If work contineue for more then one Job / day 3538.0
day , rates for next subsequent days will be 50% of the original rates.)

25.16 Hire charges for 50/55" HD LED/Plazma TV complete with mounting


arrangement , connections, testing etc.with skilled operator to operate
system as and when etc as required. (If work contineue for more then one Job / day 4193.0
day , rates for next subsequent days will be 50% of the original rates.)

Chapter E -25 Page 175


P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-25

Code No. Description Unit Complete Rate

25.17 Hire charges for Equipments Required for Public Address & Sound System for
a very important public function/ VVIP visits including
transportation,T&P,Scafolding, testing and connections with trial etc. with
skilled operator to operate system as and when etc as required. (If work
contineue for more then one day , rates for next subsequent days will be
50% of the original rates.)
25.17.1 VERTEK / RCF TT+ (55/56) 3 way Speakers 3500 to 8000 watt JBL or
Each/Day 3156.0
Equivalent make

25.17.2 VERTEK / RCF TT+ (55/56) 3 way Speakers above 8000 watt JBL or
Each/Day 4497.0
Equivalent make.

25.17.3 VERTEK / RCF TT+ (55/56) sub Woofers sound output 4000 to 8000 watt
Each/Day 3156.0
JBL or Equivalent make.

25.17.4 VERTEK / RCF TT+ (55/56) sub Woofers sound output above 8000 watt JBL
Each/Day 4497.0
or Equivalent make.

25.17.5 Core i5/i7 Laptop with HDMI cable & Stereo sound output make-
Each/Day 631.0
HP/Dell/Lenovo or Equivalent.

25.17.6 Digital CD consoles with built in CD players & DJ mixer make : pioneer or
Each/Day 3156.0
equivalent.

25.17.7 D.I. Boxes of Make DBX or equivalent . Each/Day 1262.0

25.17.8 32 Channels Equilizers make-DBX or Equivalent. Each/Day 5049.0

25.17.9 Cross Overs for the speakers Distributions make- DBX or equivalent. Each/Day 3156.0

25.17.10 5000 watts Amplifiers for up to the 06 nos Vertek 3 way speakers make -
Each/Day 3156.0
crown or equivalent

25.17.11 6000 watts Amplifiers for up to the 04 nos Vertek sub woofers make-Crown
Each/Day 3156.0
or Equivalent.

25.17.12 Suspension kits with suitable stand for the High wattage speakers Each/Day 1262.0

25.17.13 Required necessary audio connection cables, speakers cables,electrical


wiring, boards, connector etc for speakers/horns etc. as required Job/Day 3156.0

25.17.14 Flying Speakers 1200 watts RMS JBL/Yamaha/RCF/ Eq Each/Day 2525.0

25.17.15 Top Speakers 1200 watts RMS JBL/Yamaha/RCF/Eq Each/Day 2525.0

25.17.16 Monitor Speakers JBL/Yamaha/RCF/ Eq (For Stage) Each/Day 1893.0

25.17.17 Cordless Mike Make:-Shure/AKG or equivalent . Each/Day 379.0

25.17.18 CD Player Make:-Pioneer /Philips or Equivalent. Each/Day 631.0

Chapter E -25 Page 176


P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-25

Code No. Description Unit Complete Rate

25.17.19 Digital Mixer 32 Channel, 12 output Make:-Yamaha/Sound Craft or


Each/Day 3156.0
equivalent.

25.17.20 Analog Mixer 24 Channel, 7 output Make:- Yamaha/Sound Craft or


Each/Day 2525.0
equivalent.

25.17.21 Effect Processors. Make:-LSS/Behringer or equivalent. Each/Day 631.0

25.17.22 Compressors. Make:-LSS/Behringer or equivalent. Each/Day 631.0

25.17.23 Amplifiers 700 Watt RMS at 100 Ohm. Make:-Ahuja/QSC or equivalent.


Each/Day 631.0

25.17.24 Podium Microphones. Make:-Shure/AKG or equivalent. Each/Day 631.0

25.17.25 Mikes with Big stand. Make:-Shure/AKG or equivalent. Each/Day 631.0

25.17.26 Head Phone. Make:-Shure/AKG or equivalent. Each/Day 947.0

25.17.27 Digital Audio recorder. Make:-Cinex or equivalent. Each/Day 2525.0

25.17.28 31 Band Equalizer. Make:-LSS/Behringer or equivalent. Each/Day 2525.0

25.17.29 Snake Cable 2 x 100 mtr as required. Job/Day 505.0

25.17.30 Crossover Make:-LSS/Behringer or equivalent. Job/Day 1262.0

25.18 Hire charges for 500/1000 Watt halogen flood luminaire(with lamp) with
skilled operator to operate system as and when etc as required. (If work
contineue for more then one day , rates for next subsequent days will be
50% of the original rates.)
25.18.1 With suitable pole Each/Day 42.0
25.18.2 With out pole Each/Day 25.0

25.19 Hire charges for LED post top lantern upto 25-45 watt on suitable pole with
skilled operator to operate system as and when etc as required. as required.
Each/Day 93.0
(If work contineue for more then one day , rates for next subsequent
days will be 50% of the original rates.)

25.2 Hire charges for light point complete with lamp,holder,wiring in casing or in
PVC conduit , controlling switch and circuit protection MCB's with skilled
operator to operate system as and when etc as required. for shops/ stalls Each/Day 68.0
etc. (If work contineue for more then one day , rates for next subsequent
days will be 50% of the original rates.)

Chapter E -25 Page 177


P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-25

Code No. Description Unit Complete Rate

25.21 Hire charges for power/light plug on board incl. wiring in PVC casing or in
PVC conduit , controlling switch and circuit protection MCB's with skilled
operator to operate system as and when etc as required. for shops/ stalls Each/Day 102.0
etc. (If work contineue for more then one day , rates for next subsequent
days will be 50% of the original rates.)

25.22 Hire charges for Jhalar bulb15/25 watt coloured/clear with skilled operator
to operate system as and when etc as required. (If work contineue for
Each/Day 4.0
more then one day , rates for next subsequent days will be 50% of the
original rates.)

25.23 Hire charges for miniature bulb with skilled operator to operate system as
and when etc as required. (If work contineue for more then one day , rates
for next subsequent days will be 50% of the original rates.)

25.23.1 for 60 nos. 6.2 v miniature bulb Each/Day 12.0

25.23.2 for 50 nos. 0.25 v LED miniature bulb Each/Day 14.0

25.24 Hire charges of niwar patti with skilled operator to operate system as and
when etc as required. (If work contineue for more then one day , rates
for next subsequent days will be 50% of the original rates.)

25.24.1 niwar patti 60 no. 6.2 v miniature lamps. Each/Day 15.0

25.24.2 niwar patti 50 no. 0.25 v LED miniature lamps. Each/Day 20.0

25.25 Hire charges for LED tube light fixture with 18/20 watt with skilled operator
to operate system as and when etc as required. (If work contineue for
Each/Day 34.0
more then one day , rates for next subsequent days will be 50% of the
original rates.)

25.26 Hire charges for Light fixture with CFL 9 / 11/ 13 / 15 watt with skilled
operator to operate system as and when etc as required. (If work
Each/Day 17.0
contineue for more then one day , rates for next subsequent days will be
50% of the original rates.)

25.27 Hire charges for LED bulb 6 watt to 13 watt of white/ warm white colour etc.
mounted on wooden batten/niwar patti or in holder (with required CCT )as
per choice of client or engineer in charge complete with wiring etc with Each/Day 10.0
skilled operator to operate system as and when etc as required. (If work
contineue for more then one day , rates for next subsequent days will be
50% of the original rates.)

25.28 Hire charges for 250/400 watt metal halide luminaire with lamp and pole of
required height with skilled operator to operate system as and when etc as
Each/Day 127.0
required. (If work contineue for more then one day , rates for next
subsequent days will be 50% of the original rates.)

25.29 Hire charges for 500/1000 watt appollo light for shops/ stalls with skilled
operator to operate system as and when etc as required. (with lamp) (If
Each/Day 68.0
work contineue for more then one day , rates for next subsequent days
will be 50% of the original rates.)

25.30 Hire charges for Silent type D.G. Set, including change over switch. Control
panel etc. and excluding POL with skilled operator to operate system as and
when etc as required. of following capacity:
25.30.1 15 to 25 KVA Each/Day 3052.0
25.30.2 40 KVA Each/Day 3899.0
25.30.3 62.5 KVA Each/Day 5086.0
25.30.4 82.5 KVA Each/Day 6103.0
25.30.5 125 KVA Each/Day 8477.0
25.30.6 180 KVA Each/Day 11020.0
25.30.7 250 KVA Each/Day 15259.0

Chapter E -25 Page 178


P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-25

Code No. Description Unit Complete Rate

25.30.8 500 KVA Each/Day 21193.0

25.31 Hire charges of Main service line for 3 phase connection upto 50 mtr. Length
(without any joint) including meter board, panel/distribution Board and
supports with skilled operator to operate system as and when etc as
required. (If work contineue for more then one week , rates for next
subsequent weeks will be 50% of the original rates.)
25.31.1 Upto 25.0 sq.mm size PVC insulated and Sheathed cable(Armoured or Un-
Each / week 254.0
armoured as required.)

25.31.2 above 25.0 sq.mm & upto 95 Sq.mm PVC insulated and Sheathed
Each / week 381.0
cable(Armoured or Un-armoured as required.)

25.31.3 above95.0 sq.mm PVC insulated and Sheathed cable(Armoured or Un-


Each / week 678.0
armoured as required.)

25.32 Hire charges of Sub service line for single/ three phase connection upto 30
mtr. Length including dist. Board and supports with skilled operator to
operate system as and when etc as required. (If work contineue for more
then one week , rates for next subsequent weeks will be 50% of the
original rates.)
25.32.1 Single phase upto 6 Sqmm PVC insulated and Sheathed cable Each / week 68.0

25.32.2 Three phase & neutral upto 10 SqmmPVC insulated and Sheathed cable
Each / week 136.0

25.33 Hire charges for Desert cooler of size 20" fan with stand, wiring including
filling of water complete with skilled operator to operate system as and Each / week 212.0
when etc as required.

25.34 Hire charges for pedestal fan of size 18" / ceiling fan of size 48"/56" sweep
including connections etc.with skilled operator to operate system as and
when etc as required. (If work contineue for more then one day , rates Each / day 85.0
for next subsequent days will be 50% of the original rates.)

25.35 Supply and filling of POL for DG sets KVA / Hour 17.0

25.36 Hire charges for LPG Heater including commercial gas cylinder,regulator and
operator with skilled operator to operate system as and when etc as
required. (If work contineue for more then one day , rates for next Each / day 2034.0
subsequent days will be 50% of the original rates.)

25.37 Hire charges for Mist Fan complete with required connections and operator
with skilled operator to operate system as and when etc as required. (If
Each / day 848.0
work contineue for more then one day , rates for next subsequent days
will be 50% of the original rates.)

25.38 Hire charges for Jumbo polycarbonate/fiber body moveable desert cooler
complete with water filling and operator with skilled operator to operate
system as and when etc as required. (If work contineue for more then one Each / day 1187.0
day , rates for next subsequent days will be 50% of the original rates.)

25.39 Hire charges for following type of Airconditioners including copper piping ,
drain piping and electrical connections with skilled operator to operate
system as and when etc as required. (If work contineue for more then one
day , rates for next subsequent days will be 50% of the original rates.)

25.39.1 1.5 TR Split AC Each / day 3258.0


25.39.2 2.0 TR Split AC Each / day 3450.0
25.39.3 3.0 /4.0 TR Tower type split AC Each / day 6708.0
25.39.4 5.0/5.5 TR ductable type Split AC Each / day 9583.0

Chapter E -25 Page 179


P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-25

Code No. Description Unit Complete Rate

25.40 Hire charges of public address system for a important public function with 5/
6 no. of microphones with following nos of stand Hi Fi box, speakers/ Horns,
stand by amplifiers , battery backup complete including transportation etc.
with skilled operator to operate system as and when etc as required. : ( At
district Head Quarters ) (If work contineue for more then one day , rates
for next subsequent days will be 50% of the original rates.)

25.40.1 4 Nos 3 Way Big Box Speakers,(upto 5000 audiences) Each / day 5256.0

25.40.2 6 Nos 3 Way Big Box Speakers,(above 5000 to 10000 audiences) Each / day 10172.0

25.40.3 8 Nos 3 Way Big Box Speakers,(above 10000 to 25000 audiences) Each / day 14411.0

25.40.4 10 Nos 3 Way Big Box Speakers,(above 25000 audiences) Each / day 18649.0

25.40.5 With 5/6 Mikes, 15 to 20 nos. reflex horns (upto 25000 audiences) Each / day 6782.0

25.40.6 With 5/6 Mikes, 25-30 nos. reflex horns (above 25000 audiences) Each / day 9325.0

25.40.7 Hire charges for table microphone ( Delegate type ) (If work contineue for
more then one day , rates for next subsequent days will be 50% of the Each / day 339.0
original rates.)

25.40.8 Hire charges for clip microphone with long lead lavilier. (If work contineue
for more then one day , rates for next subsequent days will be 50% of the Each / day 407.0
original rates.)

25.40.9 Hire charges for collar cordless/ Handheld microphone with long lead
lavilier. (If work contineue for more then one day , rates for next Each / day 509.0
subsequent days will be 50% of the original rates.)

25.41 Hire charges for public address system consisting of 2 Microphone with
stand, Battery Backup, Amplifier,2 Loudspeakers with skilled operator to
operate system as and when etc as required. (If work contineue for more Each / day 2204.0
then one day , rates for next subsequent days will be 50% of the original
rates.)

25.42 Hire charges for 2 nos. 3 way Bigbox speakers with 5/6 Microphones, mixer,
echo chamber, Amplifier, Battery back up with skilled operator to operate
system as and when etc as required. for Musical programme. (If work Job / day 8477.0
contineue for more then one day , rates for next subsequent days will be
50% of the original rates.)

25.43 Hire charges for extra battery of 12 V , 125 AH with skilled operator to
operate system as and when etc as required. (If work contineue for more
Each / day 254.0
then one day , rates for next subsequent days will be 50% of the original
rates.)

25.44 Hire charges for cut glass chendilier of 20 lamps with skilled operator to
operate system as and when etc as required. (If work contineue for more
Each / day 678.0
then one day , rates for next subsequent days will be 50% of the original
rates.)

25.45 Hire charges for cut glass chendilier of 15 lamps with skilled operator to
operate system as and when etc as required. (If work contineue for more
Each / day 509.0
then one day , rates for next subsequent days will be 50% of the original
rates.)

25.46 Hire charges for cut glass chendilier of 7 lamps with skilled operator to
operate system as and when etc as required. (If work contineue for more
Each / day 237.0
then one day , rates for next subsequent days will be 50% of the original
rates.)

Chapter E -25 Page 180


P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-25

Code No. Description Unit Complete Rate

25.47 Hire charges for spot /palican lights (1000 watt) for stage function with
dimmer as required. (If work contineue for more then one day , rates for Each / day 339.0
next subsequent days will be 50% of the original rates.)

25.48 Hire charges for colour effect scanners for stage functions with skilled
operator to operate system as and when etc as required. (If work contineue
Each / day 1865.0
for more then one day , rates for next subsequent days will be 50% of the
original rates.)

25.49 Hire charges for jumbo strove light for stage functions with skilled operator
to operate system as and when etc as required. (If work contineue for
Each / day 1187.0
more then one day , rates for next subsequent days will be 50% of the
original rates.)

25.5 Hire charges for Back or Front Projection Screen with skilled operator to
operate system as and when etc as required. (If work contineue for more
Each / day 509.0
then one day , rates for next subsequent days will be 50% of the original
rates.)

25.51 Hire charges for High Lumens LCD Projectors with operator ( 3500 Lumens )
and projector screen of size 8' X 6' with skilled operator to operate system
as and when etc as required. (If work contineue for more then one day , Each p. day 2543.0
rates for next subsequent days will be 50% of the original rates.)

25.52 Hire charges for Medium Lumens LCD Projectors with operator ( 2500
Lumens ) and projector screen of size 8' X 6' with skilled operator to operate
system as and when etc as required. (If work contineue for more then one Each p. day 2034.0
day , rates for next subsequent days will be 50% of the original rates.)

25.53 Hire charges for Cable fault locator machine with manpower for detecting Each per Fault 10172.00
fault in underground cable of LT 1.1 KV grade or 11/33KV HT cable

Chapter E -25 Page 181


P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-26

Chapter E -26

Repairing of Fans, Coolers, Pumps, Motors, Fridges & Airconditioners

Code No. Description Unit Complete Rate

26.1 Rewinding of ceiling fan motor (starting and running winding) including all necessary
material. The motor is to be wound taking no. of coils, turns and pitch as it was originally
wound with required size super enamelled wire with 'E' class insulation material and making
connections etc. as required. Replacement of material or components shall be use as per
guidelines of OEM of original product. All the scrap material should be retained by the
contractor. (New model ceiling fan)
26.1.1 900/1200 mm sweep (New model ceiling fan) Each 525.0
26.1.2 1400 mm sweep (New model ceiling fan) Each 620.0
26.1.3 All sizes (Old model ceiling fan) Each 1666.0

26.2 Labour charges for removing and refixing of Ceiling fan/ Exaust fan from site Each 67.0

26.3 Charges for oiling, overhauling of ceiling fan, table fan, pedestal fan irrespect to the size of
fan including removing,refixing of fan from site and testing etc. as required.
26.3.1 Fans w/o Removing & Refixing Each 40.0

26.3.2 Fans with Removing & Refixing at Suitable Location Each 107.0

26.4 Providing and Replacement of ball bearing of ceiling/ exhaust fan and refixing the same at
suitable location as requiredand as per OEM recommendations. Replacement of material or
components shall be use as per guidelines of OEM of original product. All the scrap material
should be retained by the contractor. Each 261.0

26.5 Provinding & Replacement of M.S. Shaft of ceiling fan. Replacement of material or
components shall be use as per guidelines of OEM of original product. All the scrap material
should be retained by the contractor. Each 154.0

26.6 P & Replacement of cover/ bearing seat of ceiling/ exhaust fan. Replacement of material or
components shall be use as per guidelines of OEM of original product. All the scrap material
should be retained by the contractor. Each 140.0

26.7 P & F Aluminium Blades (a set of 3 blades) duly painted and well finished 900/ 1200 mm. The
material of the fan blade shall be of designation 31500B with condition HX6 aluminium alloy
sheet confirming to IS 737/2008 Each 247.0

26.8 P & F Aluminium Blades (a set of 3 blades) duly painted/ powder coated. ( 1400/ 1500 mm)
The material of the fan blade shall be of designation 31500B with condition HX6 aluminium
alloy sheet confirming to IS 737/2008 Each 314.0

26.9 P & F of rubber gromet (fan insulator) Each 36.0

26.10 Providing and Replacement of Gun metal bush of ceiling/exhaust/cooler fan/ as required.
Replacement of material or components shall be use as per guidelines of OEM of original
product. All the scrap material should be retained by the contractor. Each 154.0

26.11 P & F 3 Speed rotary switch for Desert Cooler complete with testing etc as required. Each 83.0

26.12 P & Replacement of M.S. Shaft of fan motor for Desert Cooler/ exhaust fan. Replacement of
material or components shall be use as per guidelines of OEM of original product. All the Each 160.0
scrap material should be retained by the contractor.

26.13 P & replacement of supporting legs(4 no.) of vertical pump of desert cooler as required for
Desert Cooler/ exhaust fan. Replacement of material or components shall be use as per
Each 114.0
guidelines of OEM of original product. All the scrap material should be retained by the
contractor.

Chapter E - 26
Page 182
P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-26

Code No. Description Unit Complete Rate


26.14 P & F of stud with nuts and washer for Desert Cooler/ exhaust fan.All the scrap material
should be retained by the contractor. Each 49.0

26.15 Servicing and overhauling of 20" sweep desert cooler including oiling, greasing, painting of
tank from inside with rubber paint after properly desmantling each assembly and refixing
the same as required. Each 247.0

26.16 Painting of desert cooler with two coats of rubber paint inside of water tank and two coat
of synthetic enamelled paint on both side of cooler body, fan body, grills etc.after cleaning
with sand paper, complete in all respect as required. Each 428.0

26.17 Replacement of cooler pads (heavy) set of 3 no. of size 25" x 27" Each 100.0

26.18 P & F Brass float valve of weighing approx. 250 gm, 8" long rod,PVC ball of 4" dia. For desert
Each 227.0
coler as required.

26.19 P & F adjustable M.S.grill 20/22 gauge of size approx. 24" x 26" including painting etc. as
required. Each 314.0

26.20 P & F aluminiun blade for 20'' desert cooler fan as required. Each 221.0

26.21 P & F outer/inner threaded PVC nipple 1/2" dia and 2" long Each 13.0

26.22 P & Replacement of pvc pipe of 1/2" size for vertical pump of desert cooler as required.
Replacement of material or components shall be use as per guidelines of OEM of original
product. All the scrap material should be retained by the contractor. Each 31.0

26.23 P & replacement of shaft for vertical pump of desert cooler as required. Replacement of
material or components shall be use as per guidelines of OEM of original product. All the
scrap material should be retained by the contractor. EACH 67.0

26.24 Spray painting of ceiling fan of size 900/1200/ 1400/ 1500 mm with two coats of white/
brown enamelled paint after cleaning with sand paper. Filling etc. as required.
Each 154.0

26.25 P & replacement of 4 nos. supporting legs of 20'' fan motor with rubber pads of desert
cooler as required.Replacement of material or components shall be use as per guidelines of
OEM of original product. All the scrap material should be retained by the contractor.
Each 147.0

26.26 P & replacement of high quality pvc distribution ' T 'and 3 no. elbow for cooler Each 23.0

26.27 P & F ISI marked commercial plywood 4.0 mm thick including cutting, hardwares etc. as
required. SQ.Mtr. 281.0

26.28 Labour Charges for fixing of desert cooler in windows including handling of cooler upto
desired location, making electrical/water connections, testing etc. as required.
26.28.1 Ground floor Each 74.0
26.28.2 First floor Each 120.0
26.28.3 Second floor Each 154.0

26.29 P & F of ISI marked vertical pump suitable for 20" desert cooler including making
connection testing etc. as required.
26.29.1 ISI marked vertical pump Each 542.0

26.3 P & F of submercible pump set suitable for 18/24 "Desert coolers. Each 308.0

26.31 P & F of submercible pump set suitable for 36 "Desert coolers. Each 675.0

26.32 P & F fan motor suitable for 20" desert cooler including making connection testing etc. as
required.
26.32.1 with copper winding Motor ISI Marked Each 3510.0
26.32.2 with Aluminium winding Motor ISI Marked Each 2025.0

Chapter E - 26
Page 183
P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-26

Code No. Description Unit Complete Rate

26.33 Rewinding of Heavy duty Exhaust fan motor including all necessary material,The motor is to
be wound taking no. of coils,turns and pitch as it was originally wound with required size
super enamelled wire with 'E' class insulation material and making connections etc. as
required. Replacement of material or components shall be use as per guidelines of OEM of
original product. All the scrap material should be retained by the contractor.

26.33.1 300/ 380 mm sweep Each 783.0


26.33.2 450 mm sweep Each 1016.0
26.33.3 600 mm sweep Each 1429.0

26.34 Rewinding of 400 mm table fan/pedestal fan motor including all necessary material,The
motor is to be wound taking no. of coils,turns and pitch as it was originally wound with
required size super enamelled wire with 'E' class insulation material and making connections
Each 425.0
etc. as required. Replacement of material or components shall be use as per guidelines of
OEM of original product. All the scrap material should be retained by the contractor.

26.35 Rewinding of single phase motor of 1400 RPM including all necessary material and of the
same characteristics as original with required size of super enamelled wire 'E' class
insulation material and testing etc. as required. Replacement of material or components
shall be use as per guidelines of OEM of original product. All the scrap material should be
retained by the contractor.
26.35.1 0.25 H.P. To 0.50 H.P. Each 915.0
26.35.2 0.75 H.P. To 1.0 H.P. Each 1256.0
26.35.3 2.0 H.P. Each 2073.0

26.36 Rewinding of three phase squirrel cage induction motor of 1400 to 2800 RPM including all
necessary material and of the same characteristics as original with required size of super
enamelled wire 'E' class insulation material and testing etc. as required. Replacement of
material or components shall be use as per guidelines of OEM of original product. All the
scrap material should be retained by the contractor.

26.36.1 3.0 H.P. Each 3400.0


26.36.2 5.0 H.P. Each 4220.0
26.36.3 7.5 H.P. Each 4941.0
26.36.4 10.0 H.P. Each 6292.0
26.36.5 12.5 H.P. Each 7622.0
26.36.6 15.0 H.P. Each 9648.0

26.37 Rewinding of motor of desert cooler pump with super enamelled copper wire, 'E ' class
insulation material including removing,refixing,testing etc. as required. Replacement of
material or components shall be use as per guidelines of OEM of original product. All the
scrap material should be retained by the contractor. Each 250.0

26.38 Rewinding of motor of desert cooler fan with super enamelled copper wire, 'E ' class
insulation material including removing,refixing,testing etc. as required. Replacement of
material or components shall be use as per guidelines of OEM of original product. All the
scrap material should be retained by the contractor. Each 891.0

26.39 Providing and replacement of heating element of blower type heat convector as required.
Replacement of material or components shall be use as per guidelines of OEM of original
product. All the scrap material should be retained by the contractor. Each 120.0

26.40 Providing and replacement of heating element rod of radiation type heat convector as
required. Replacement of material or components shall be use as per guidelines of OEM of
original product. All the scrap material should be retained by the contractor.
Each 114.0

26.41 Providing and replacement of Superior quality Chrome plated reflector of radiation type
heat convector as required.Replacement of material or components shall be use as per
guidelines of OEM of original product. All the scrap material should be retained by the
contractor.
26.41.1 single rod Each 134.0
26.41.2 double rod Each 160.0

Chapter E - 26
Page 184
P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-26

Code No. Description Unit Complete Rate

26.42 Supplying and charging of fresh refrigerant and testing of performance of air conditioner/
fridge/ water cooler of following capacity including capillary and strainer/ filter.

26.42.1 1.0 TR Window/ Split A.C. Each 1738.0


26.42.2 1.5 TR Window/ Split A.C. Each 2407.0
26.42.3 2.0 TR Window/ Split A.C. Each 3076.0
26.42.4 25/50 / 40/80 Ltr. Water cooler Each 1872.0
26.42.5 60/120 Ltr. Water cooler Each 2140.0
26.42.6 150/150 Ltr. Water cooler Each 2541.0
26.42.7 165 Ltr Refrigerator Each 1404.0
26.42.8 200/210 Ltr Refrigerator Each 1939.0
26.42.9 280/310 Ltr Refrigerator Each 2340.0

26.43 Replacement of defective compressor by company repaired compressor as per OEM


recommendations of following gadgets including testing etc. as required. Replacement of
material or components shall be use as per guidelines of OEM of original product. All the
scrap material should be retained by the contractor.
26.43.1 1.0 TR A.C. Each 10698.0
26.43.2 1.5 TR A.C. Each 12035.0
26.43.3 2.0 TR A.C. Each 12703.0
26.43.4 25/50 / 40/80 Ltr. Water cooler Each 5951.0
26.43.5 60/120 Ltr. Water cooler Each 7956.0
26.43.6 150/150 Ltr. Water cooler Each 8625.0
26.43.7 165 Ltr Refrigerator Each 3544.0
26.43.8 200/210 Ltr Refrigerator Each 4279.0
26.43.9 280/310 Ltr Refrigerator Each 4613.0

26.44 P & Replacement of condensing/ cooling coil of copper fins for following capacity A.C./
Water cooler/ Fridge as required. Replacement of material or components shall be use as
per guidelines of OEM of original product. All the scrap material should be retained by the
contractor.
26.44.1 1.0 TR A.C. Each 3209.0
26.44.2 1.5 TR A.C. Each 3610.0
26.44.3 2.0 TR A.C. Each 4012.0
26.44.4 25/50 / 40/80 Ltr. Water cooler Each 2407.0
26.44.5 60/120 Ltr. Water cooler Each 2942.0
26.44.6 150/150 Ltr. Water cooler Each 3209.0
26.44.7 165 Ltr Refrigerator Each 1471.0
26.44.8 200/210 Ltr Refrigerator Each 1738.0
26.44.9 286/310 Ltr Refrigerator Each 2006.0

26.45 Servicing of 1.0/1.5/2.0 TR capacity Split/ Window type air conditioner Each 669.0

26.46 P & Replacement of overload protection of A.C./ Water cooler as required. Replacement of
material or components shall be use as per guidelines of OEM of original product. All the
scrap material should be retained by the contractor. Each 468.0

26.47 P & Replacement of thermostat of A.C./ Water cooler/fridge as required. Replacement of


material or components shall be use as per guidelines of OEM of original product. All the
scrap material should be retained by the contractor. Each 401.0

26.48 P & Replacement of selector switch of 1.0/1.5/2.0 TR A.C Fan as required. Replacement of
material or components shall be use as per guidelines of OEM of original product. All the
scrap material should be retained by the contractor. Each 120.0

26.49 P & Replacement of starting relay of A.C/water cooler/fridge compressor as required.


Replacement of material or components shall be use as per guidelines of OEM of original
product. All the scrap material should be retained by the contractor. Each 468.0

Chapter E - 26
Page 185
P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-26

Code No. Description Unit Complete Rate


26.50 P & Replacement of door liner of 165/200 Ltr. Fridge as required. Replacement of material or
components shall be use as per guidelines of OEM of original product. All the scrap material
should be retained by the contractor. Each 1203.0

26.51 P & Replacement of door liner of 286/310 Ltr. Fridge as required. Replacement of material or
components shall be use as per guidelines of OEM of original product. All the scrap material
should be retained by the contractor. Each 1471.0

26.52 P & Replacement of main liner of 165/200 Ltr. Fridge as required. Replacement of material
or components shall be use as per guidelines of OEM of original product. All the scrap
material should be retained by the contractor. Each 2006.0

26.53 P & Replacement of main liner of 286/310 Ltr. Fridge as required. Replacement of material
or components shall be use as per guidelines of OEM of original product. All the scrap
material should be retained by the contractor. Each 2273.0

26.54 P & Replacement of door gasket of 165/200 Ltr. Fridge as required. Replacement of material
or components shall be use as per guidelines of OEM of original product. All the scrap
material should be retained by the contractor. Each 234.0

26.55 P & Replacement of door gasket of 286/310 Ltr. Fridge as required. Replacement of material
or components shall be use as per guidelines of OEM of original product. All the scrap
material should be retained by the contractor. Each 374.0

26.56 P & Replacement of PVC/ acrylic vegetable basket of 165/200 Ltr. Fridge as required.
Replacement of material or components shall be use as per guidelines of OEM of original
product. All the scrap material should be retained by the contractor. Each 374.0

26.57 P & Replacement of PVC/acrylic vegetable basket of 280/310 Ltr. Fridge as required.
Replacement of material or components shall be use as per guidelines of OEM of original
product. All the scrap material should be retained by the contractor. Each 374.0

26.58 P & Replacement of glass/acrylic cover for vegetable basket of 165/200 Ltr. Fridge as
required. Replacement of material or components shall be use as per guidelines of OEM of
original product. All the scrap material should be retained by the contractor.
Each 274.0

26.59 P & Replacement of glass/acrylic cover for vegetable basket of 286/310 Ltr. Fridge as
required. Replacement of material or components shall be use as per guidelines of OEM of
original product. All the scrap material should be retained by the contractor.
Each 308.0

26.60 P & Replacement of PVC /acrylic bottle supporter of 165/200/ 286/310 Ltr. Fridge as
required. Replacement of material or components shall be use as per guidelines of OEM of
original product. All the scrap material should be retained by the contractor. Each 140.0

26.61 P & Replacement of aluminium bottle supporter of 165/200/ 286/310 Ltr. Fridge as required.
Replacement of material or components shall be use as per guidelines of OEM of original
product. All the scrap material should be retained by the contractor. Each 160.0

26.62 P & Replacement of PVC./acrylic freezer door of 165/200 Ltr. Fridge as required.
Replacement of material or components shall be use as per guidelines of OEM of original
product. All the scrap material should be retained by the contractor. Each 334.0

26.63 P & Replacement of PVC./acrylic freezer door of 286/310 Ltr. Fridge as required.
Replacement of material or components shall be use as per guidelines of OEM of original
product. All the scrap material should be retained by the contractor. Each 401.0

26.64 P & Replacement of door handle of 165/200/286/310 Ltr. Fridge as required. Replacement of
material or components shall be use as per guidelines of OEM of original product. All the
scrap material should be retained by the contractor. Each 301.0

26.65 P & Replacement of lamp of Fridge as required. Replacement of material or components


shall be use as per guidelines of OEM of original product. All the scrap material should be
retained by the contractor. Each 33.0

Chapter E - 26
Page 186
P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-26

Code No. Description Unit Complete Rate


26.66 P & Replacement of PVC/acrylic chiller tray of 165/200 Ltr. Fridge as required. Replacement
of material or components shall be use as per guidelines of OEM of original product. All the
scrap material should be retained by the contractor. Each 294.0

26.67 P & Replacement of PVC/acrylic chiller tray of 286/310 Ltr. Fridge as required. Replacement
of material or components shall be use as per guidelines of OEM of original product. All the
scrap material should be retained by the contractor. Each 328.0

26.68 P & Replacement of fridge lock complete as required. Replacement of material or


components shall be use as per guidelines of OEM of original product. All the scrap material
should be retained by the contractor. Each 207.0

26.69 Spray painting of complete fridge (inside and outside ) of 165/ 200 Ltr. Capacity. Each 1404.0

26.70 Spray painting of complete fridge (inside and outside ) of 286/310 Ltr. Capacity. Each 1538.0

26.71 P & Replacement of fan motor of evaporator/ condensor complete as required.


Replacement of material or components shall be use as per guidelines of OEM of original
product. All the scrap material should be retained by the contractor. Each 2073.0

26.72 S & F of capacitor of 230V/ 275V, 50Hz rating of plastic casing and terminals -Lugs or copper
wire.
26.72.1 Starting capacitor
26.72.1.1 20-30 micro farad Each 134.0
26.72.1.2 40-60 micro farad Each 177.0
26.72.1.3 60-80 micro farad Each 233.0
26.72.1.4 80-100 micro farad Each 294.0
26.72.1.5 100-120 micro farad Each 308.0
26.72.1.6 120-150 micro farad Each 361.0

26.72.2 Running capacitor


26.72.2.1 2.5/3.15 micro farad Each 47.0
26.72.2.2 4.0 micro farad Each 56.0
26.72.2.3 6.0 micro farad Each 72.0
26.72.2.4 8.0 micro farad Each 82.0
26.72.2.5 10.0 micro farad Each 95.0
26.72.2.6 15.0 micro farad Each 127.0
26.72.2.7 20.0 micro farad Each 206.0
26.72.2.8 25.0 micro farad Each 229.0

26.73 P & Replacement of plastic/metallic sheet condensor holder suitable for ceiling fan/ exhaust
fan /motor etc complete as required. Replacement of material or components shall be use
Each 23.0
as per guidelines of OEM of original product. All the scrap material should be retained by the
contractor.

26.74 Rewinding of single phase/3phase submersible motor including all necessary material and of
the same characteristics as original with required size of super enamelled wire 'E' class
insulation material and testing etc. as required. Replacement of material or components
shall be use as per guidelines of OEM of original product. All the scrap material should be
retained by the contractor.
26.74.1 0.5 H.P. To 1.0 H.P. Each 3610.0
26.74.2 2.0 H.P.to 3.0 HP Each 6285.0
26.74.3 Above 3.0 HP to 5.0 HP Each 8291.0
26.74.4 From7. 5 HP to 10.0 HP Each 10296.0

26.75 Repairing of submersible pump of with replacement of broken impellers


,diffuser,bush/bearing set , oil seal complete with testing etc. as required. Replacement of
material or components shall be use as per guidelines of OEM of original product. All the
scrap material should be retained by the contractor.
26.75.1 0.5 H.P. To 1.0 H.P. Each 2541.0
26.75.2 2.0 H.P.to 3.0 HP Each 3945.0
26.75.3 Above 3.0 HP to 5.0 HP Each 5349.0

Chapter E - 26
Page 187
P.W.D. Rajasthan Electrical B.S.R. 2022 Chapter E-26

Code No. Description Unit Complete Rate


26.75.4 From7. 5 HP to 10.0 HP Each 6686.0

Chapter E - 26
Page 188
P.W.D. Rajasthan Electrical B.S.R. 2022 Annexure "A"

Annexure-A
Additional Technical parameters of products/ work
1. PWD specifications for Electrical works -2012 (as amended upto date ), relevent IS
codes, National Building Code / National Lighting Code / National electric Code / Indian
Electricty Rules ( all as amended upto date ) shall be treated as part of this Electric BSR-
2022 for the purpose of detailed specifications & clarifications, if any. Henceforth this BSR-
2022 shall be considered as part of all contracts/ agrements, controversy / dispute in
interpretation of BSR -2022, decision of Chief Engineer (Electrical ) PWD Rajasthan shall
be final & binding.

2. Agency must ensure to take prior approval for makes and models in writing before / at
the time of layout by Engineer-in-Charge as per specifications with submitting TDS of
products & all items used from any particular chapter of this BSR for any individual project,
should be of same brand which is approved before execution as per availability.

3. OEM installation mannual guideline practice for execution of work at site must be
followed by agency's engineer & verified by department.
4. Agency must ensure to execute all hidden items in presence of engineer-in-charge or site
engineer. GPS Photo be attach at the time of measurment.
5. Tests of specified items below must be done in Government approved OEM's
authorised Labs / outsource from government approved any authorised Lab by agency &
no extra payment shall be made for below mentioned tests & procedures at all :-↓

Item Name Tests must be done in Government approved OEM's


Sr.No. authorised Labs / outsource from government
approved any authorised Lab as mentioned below :-


Wiring accessories ( switch / socket)
01 test if quantity in BOQ/execution is more then ↓
500 wiring points
1

2 Wiring accessories Regulator / dimmer 150 Nos.

3 PVC / Steel Conduit ( Total of all sizes) 500 wiring points


Sheet Steel Box/ M.S. Box/ GI Box/ PVC
4 Box ( Total of all sizes) 300 Nos. ( Total of all sizes)

MCB/RCCB/Isolator ( 1 Pole to 4 Pole) 150 Nos. ( Total of all amp rating)


5 ( Total of all amp rating)
Ceiling Fan/ Exhaust /fresh air/ wall 100 Nos. (Total All sizes )
6 mounting fan. (Total All sizes )

Annexure-A Page 189


P.W.D. Rajasthan Electrical B.S.R. 2022 Annexure "A"

6. Factory Inspection for testing of specified items below must be done in Government
approved OEM's authorised Labs by departmental Engineer. Agency must ensure to make
all necessory permission and arrangements for the visit & no extra payment shall be made
for all this procedure :-↓
Item Name Factory inspection for testing in Government
Sr.No. approved OEM's authorised Labs by department
engineer as mentioned below :-

↓ If quantity in BOQ/execution is more then ↓

1 Indoor LED Lighting fixture all types 200 Nos.

2 Outdoor LED Lighting fixture all types 50 Nos.

3 Lattice tower all sizes 5 Nos.

4 Air Conditioner 30 Nos.

5 Air cooling machine/ Chillers 5 Nos.

6 Street light pole 30 Nos.

7 Transformer compelsary for Each quantity

8 High mast pole compulsary for each if height is16 Mtr.or more.

9 DG set compelsary for Each quantity

10 RMU compelsary for Each quantity

11 Bus Bar Trukning compelsary for Each quantity

7. Any Items can be send for testing by Engineer-in-Charge in Government Authorised


any approved Lab. Payment of testing charge shall be borne by department for that. Agency
is liable to make all necessary arrangement to send the sample & get reports from lab
without ant extra cost.

8. Agency will submit minimum one year valid gaurentee certificate of Product & Liable
product genuineness purchase proof from OEM/ Authorised Dealer .

Annexure-A Page 190


P.W.D. Rajasthan Electrical B.S.R. 2022 Annexure "A"

9. Appropriate/ Routeen type Test Certificates/ reports related to IS code with liable
standard warranty proof / certificate of product from OEM / authorised dealer shall be
submitted by agency during / at the time of execution & duly verified by Engineer-in-
Charge.

10. Agency must ensure to prepare the Satisfactory installation service report from OEM
engineer for major items like DG set, Transformer, PSS, RMU, Fire fighting pumps,
VRF/VRV, package AC units, ACB, High Mast ( 16 mtr. or heigher ) etc. and submit the
same in Engineer In charge office. All record be kept with agreement file.

************

Annexure-A Page 191