Short Circuit Simulator
Short Circuit Simulator
Short Circuit Simulator
UTILITY
TRANSFORMER
F0 SUMMARY
X
BASED ON THE CALCULATIONS, THE MINIMUM INTERRUPTING CAPACITY
MDP OF DIFFERENT PANEL BOARDS ARE AS FOLLOWS:
X X
PB01 PB02
MOTOR CONTRIBUTION
= 188.27
UTILITY
85000 KVA SC X= 85000 1.00
13.2 KV, SOURCCE 85000
MDP
#4/0 WIRE= 3 - 100 sq.mm. R= (1)(0.062x15/305)(85000) 4.90
LENGTH 15 M (1000)(0.23)^2
Z= 0.062 + j 0.041 OHMS/1000FT
X= (1)(0.041x15/305)(85000) 3.24
F0 (1000)(0.23)^2
X
TOTAL P.U. @ F0 15.10 24.64
FAULT @ F0
ZU
ZT
ZC
M
Motor
Contribution
IF0 = 85000
+ 376.53 A
28.90 X 1.732 X 0.23
IF0 = 7,759.93 A
KVA BASE = 85000
KV BASE = 0.230
IMPEDANCE DIAGRAM -2 PUR PUX
UTILITY
85000 KVA SC X= 85000 1.00
13.2 KV, SOURCCE 85000
MDP
WIRE= 3 - 100 sq.mm. R= (1)(0.062x15/305)(85000) 4.90
LENGTH 15 M (1000)(0.23)^2
Z= 0.062 + j 0.041 OHMS/1000FT
X= (1)(0.041x15/305)(85000) 3.24
F0 (1000)(0.23)^2
X
TOTAL P.U. @ F0 15.10 24.64
PB01
WIRE= 3 - 60 sq.mm. R= (1)(0.1x20/305)(85000) 10.54
LENGTH 20 M (1000)(0.23)^2
Z= 0.1 + j 0.043 OHMS/1000FT
X= (1)(0.043x20/305)(85000) 4.53
(1000)(0.23)^2
F1
X
TOTAL P.U. @ F1 25.64 29.17
FAULT @ F1
ZU
ZT
ZC
M
Motor
Contribution
IF1 = 85000
+ 376.53 A
38.83 X 1.732 X 0.23
IF1 = 5,870.83 A
KVA BASE = 85000
KV BASE = 0.230
IMPEDANCE DIAGRAM -3 PUR PUX
UTILITY
85000 KVA SC X= 85000 1.00
13.2 KV, SOURCCE 85000
MDP
WIRE= 3 - 100 sq.mm. R= (1)(0.062x15/305)(85000) 4.90
LENGTH 15 M (1000)(0.23)^2
Z= 0.062 + j 0.041 OHMS/1000FT
X= (1)(0.041x15/305)(85000) 3.24
F0 (1000)(0.23)^2
X
TOTAL P.U. @ F0 15.10 24.64
PB02
WIRE= 3 - 60 sq.mm. R= (1)(0.1x25/305)(85000) 13.17
LENGTH 25 M (1000)(0.23)^2
Z= 0.1 + j 0.043 OHMS/1000FT
X= (1)(0.043x25/305)(85000) 5.66
(1000)(0.23)^2
F2
X
TOTAL P.U. @ F2 28.27 30.30
FAULT @ F2
ZU
ZT
ZC
M
Motor
Contribution
IF2 = 85000
+ 376.53 A
41.44 X 1.732 X 0.23
IF2 = 5,525.08 A