Download as pdf or txt
Download as pdf or txt
You are on page 1of 8

Caterpillar Generator Data Página 1 de 8

GENERATOR DATA NOVEMBER 19, 2018


For Help Desk Phone Numbers Click here

Selected Model
Engine: C32 Generator Frame: 1447 Genset Rating (kW): 1200.0 Line Voltage: 400
Fuel: Diesel Generator Arrangement: 5265096 Genset Rating (kVA): 1500.0 Phase Voltage: 230
Frequency: 50 Excitation Type: Permanent Magnet Pwr. Factor: 0.8 Rated Current: 2165.1
Duty: STANDBY Connection: SERIES STAR Application: EPG Status: Current
Version:
41205 /42661 /42865 /11046
Spec Information
Generator Specification
Generator Efficiency
Frame: 1447 Type: SR5 No. of Bearings: 1
Per Unit Load kW Efficiency %
Winding Type: RANDOM WOUND Flywheel: 18.0
0.25 300.0 94.3
Connection: SERIES STAR Housing: 0
0.5 600.0 95.8
Phases: 3 No. of Leads: 6
0.75 900.0 95.8
Poles: 4 Wires per Lead: 4
1.0 1200.0 95.4
Sync Speed: 1500 Generator Pitch: 0.6667

Reactances Per Unit Ohms


SUBTRANSIENT - DIRECT AXIS X''d 0.1359 0.0145
SUBTRANSIENT - QUADRATURE AXIS X''q 0.1538 0.0164
TRANSIENT - SATURATED X'd 0.1697 0.0181
SYNCHRONOUS - DIRECT AXIS Xd 3.7781 0.4030
SYNCHRONOUS - QUADRATURE AXIS Xq 2.2688 0.2420
NEGATIVE SEQUENCE X2 0.1453 0.0155
ZERO SEQUENCE X0 0.0328 0.0035

Time Constants Seconds


OPEN CIRCUIT TRANSIENT - DIRECT AXIS T'd0 3.9100
SHORT CIRCUIT TRANSIENT - DIRECT AXIS T'd 0.1800
OPEN CIRCUIT SUBSTRANSIENT - DIRECT AXIS T''d0 0.0320
SHORT CIRCUIT SUBSTRANSIENT - DIRECT AXIS T''d 0.0180
OPEN CIRCUIT SUBSTRANSIENT - QUADRATURE AXIS T''q0 0.2650
SHORT CIRCUIT SUBSTRANSIENT - QUADRATURE AXIS T''q 0.0180
EXCITER TIME CONSTANT Te 0.0600
ARMATURE SHORT CIRCUIT Ta 0.0270

Short Circuit Ratio: 0.3 Stator Resistance = 0.0025 Ohms Field Resistance = 0.506 Ohms
Voltage Regulation Generator Excitation
Voltage level adjustment: +/- 5.0% No Load Full Load, (rated) pf
Voltage regulation, steady state: +/- 0.5% Series Parallel
Voltage regulation with 3% speed change: +/- 0.5% Excitation voltage: 10.34 Volts 53.23 Volts Volts
Waveform deviation line - line, no load: less than 2.0% Excitation current 0.81 Amps 3.44 Amps Amps
Telephone influence factor: less than 50

https://tmiwebclassic.cat.com/tmi/servlet/TMIDirector?Action=RDButton&tab=RNRefN... 19/11/2018
Caterpillar Generator Data Página 2 de 8

Selected Model
Engine: C32 Generator Frame: 1447 Genset Rating (kW): 1200.0 Line Voltage: 400
Fuel: Diesel Generator Arrangement: 5265096 Genset Rating (kVA): 1500.0 Phase Voltage: 230
Frequency: 50 Excitation Type: Permanent Magnet Pwr. Factor: 0.8 Rated Current: 2165.1
Duty: STANDBY Connection: SERIES STAR Application: EPG Status: Current
Version:
41205 /42661 /42865 /11046
Generator Mechanical Information
Center of Gravity
Dimension X -686.5 mm -27.0 IN.
Dimension Y 0.0 mm 0.0 IN.
Dimension Z 0.0 mm 0.0 IN.
• "X" is measured from driven end of generator and parallel to rotor.
Towards engine fan is positive. See General Information for details
• "Y" is measured vertically from rotor center line. Up is positive.
• "Z" is measured to left and right of rotor center line. To the right is positive.
Generator WT = 2900 kg * Rotor WT = 1104 kg * Stator WT = 1796 kg
6,393 LB 2,434 LB 3,959 LB
Rotor Balance = 0.0508 mm deflection PTP
Overspeed Capacity = 150% of synchronous speed

Generator Torsional Data

J1 = Coupling J2 = Rotor J3 = Exciter


and Fan TOTAL J = J1 + J2 + J3 End
K1 = Shaft Stiffness between K2 = Shaft Stiffness between
J1 + J2 (Diameter 1) J2 + J3 (Diameter 2)
J1 K1 Min Shaft Dia 1 J2 K2 Min Shaft Dia 2 J3
2 2
0.0 LB IN. s 0.0 MLB IN./rad 6.7 IN. 184.1 LB IN. s 119.5 MLB IN./rad 5.5 IN. 7.1 LB IN. s2
0.0 N m s2 0.0 MN m/rad 170.0 mm 20.8 N m s2 13.5 MN m/rad 140.0 mm 0.8 N m s2
Total J
191.2 LB IN. s2
21.6 N m s2

Selected Model
Engine: C32 Generator Frame: 1447 Genset Rating (kW): 1200.0 Line Voltage: 400
Fuel: Diesel Generator Arrangement: 5265096 Genset Rating (kVA): 1500.0 Phase Voltage: 230
Frequency: 50 Excitation Type: Permanent Magnet Pwr. Factor: 0.8 Rated Current: 2165.1
Duty: STANDBY Connection: SERIES STAR Application: EPG Status: Current
Version:
41205 /42661 /42865 /11046

https://tmiwebclassic.cat.com/tmi/servlet/TMIDirector?Action=RDButton&tab=RNRefN... 19/11/2018
Caterpillar Generator Data Página 3 de 8

Generator Cooling Requirements -


Temperature - Insulation Data
Cooling Requirements: Temperature Data: (Ambient 40 0C)
Heat Dissipated: 57.9 kW Stator Rise: 150.0 0C
Air Flow: 108.0 m3/min Rotor Rise: 150.0 0C
Insulation Class: H
Insulation Reg. as shipped: 100.0 MΩ minimum at 40 0C

Thermal Limits of Generator


Frequency: 50 Hz
Line to Line Voltage: 400 Volts
B BR 80/40 1132.0 kVA
F BR -105/40 1288.0 kVA
H BR - 125/40 1415.0 kVA
F PR - 130/40 1415.0 kVA
H PR - 150/40 1500.0 kVA
H PR27 - 163/27 1556.5 kVA

Selected Model
Engine: C32 Generator Frame: 1447 Genset Rating (kW): 1200.0 Line Voltage: 400
Fuel: Diesel Generator Arrangement: 5265096 Genset Rating (kVA): 1500.0 Phase Voltage: 230
Frequency: 50 Excitation Type: Permanent Magnet Pwr. Factor: 0.8 Rated Current: 2165.1
Duty: STANDBY Connection: SERIES STAR Application: EPG Status: Current
Version:
41205 /42661 /42865 /11046
Starting Capability & Current Decrement
Motor Starting Capability (0.4 pf)
Percent
SKVA
Volt Dip
219 2.5
449 5.0
692 7.5
948 10.0
1,219 12.5
1,506 15.0
1,811 17.5
2,134 20.0
2,478 22.5
2,845 25.0
3,238 27.5
3,658 30.0
4,110 32.5
4,596 35.0
5,122 37.5
5,691 40.0

https://tmiwebclassic.cat.com/tmi/servlet/TMIDirector?Action=RDButton&tab=RNRefN... 19/11/2018
Caterpillar Generator Data Página 4 de 8

Current Decrement Data


E Time
AMP
Cycle
0.0 15,879
1.0 12,533
2.0 10,698
3.0 9,452
4.0 8,467
5.0 7,628
7.5 5,938
10.0 5,294
12.5 6,156
15.0 6,881
20.0 7,686
25.0 7,908
30.0 7,510
35.0 7,065
40.0 6,754
45.0 6,572

Instantaneous 3 Phase Fault Current: 15879 Amps Instantaneous Line - Line Fault Current: 13293 Amps
Instantaneous Line - Neutral Fault Current: 20619 Amps

Selected Model
Engine: C32 Generator Frame: 1447 Genset Rating (kW): 1200.0 Line Voltage: 400
Fuel: Diesel Generator Arrangement: 5265096 Genset Rating (kVA): 1500.0 Phase Voltage: 230
Frequency: 50 Excitation Type: Permanent Magnet Pwr. Factor: 0.8 Rated Current: 2165.1
Duty: STANDBY Connection: SERIES STAR Application: EPG Status: Current
Version:
41205 /42661 /42865 /11046
Generator Output Characteristic Curves
Open Circuit Curve

Field Line -
Current Line Volt
0.0 0
15.6 240
18.4 280
21.6 320
25.6 360
31.7 400
42.8 440
65.8 480
117.8 520
239.7 560

https://tmiwebclassic.cat.com/tmi/servlet/TMIDirector?Action=RDButton&tab=RNRefN... 19/11/2018
Caterpillar Generator Data Página 5 de 8

Short Circuit Curve

Field Armature
Current Current
0.0 0
58.5 1,299
68.3 1,516
78.0 1,732
87.8 1,949
97.5 2,165
107.3 2,382
117.0 2,598
126.8 2,815
136.5 3,031

Selected Model
Engine: C32 Generator Frame: 1447 Genset Rating (kW): 1200.0 Line Voltage: 400
Fuel: Diesel Generator Arrangement: 5265096 Genset Rating (kVA): 1500.0 Phase Voltage: 230
Frequency: 50 Excitation Type: Permanent Magnet Pwr. Factor: 0.8 Rated Current: 2165.1
Duty: STANDBY Connection: SERIES STAR Application: EPG Status: Current
Version:
41205 /42661 /42865 /11046
Generator Output Characteristic Curves
Zero Power Factor Curve

Field Line -
Current Line Volt
97.5 0
113.5 200
116.4 240
119.7 280
124.1 320
130.9 360
143.8 400
171.2 440
233.7 480
380.9 520

https://tmiwebclassic.cat.com/tmi/servlet/TMIDirector?Action=RDButton&tab=RNRefN... 19/11/2018
Caterpillar Generator Data Página 6 de 8

Air Gap Curve

Field Line -
Current Line Volt
0.0 0
15.4 240
18.0 280
20.5 320
23.1 360
25.7 400
28.3 440
30.8 480
33.4 520
36.0 560

Selected Model
Engine: C32 Generator Frame: 1447 Genset Rating (kW): 1200.0 Line Voltage: 400
Fuel: Diesel Generator Arrangement: 5265096 Genset Rating (kVA): 1500.0 Phase Voltage: 230
Frequency: 50 Excitation Type: Permanent Magnet Pwr. Factor: 0.8 Rated Current: 2165.1
Duty: STANDBY Connection: SERIES STAR Application: EPG Status: Current
Version:
41205 /42661 /42865 /11046
Reactive Capability Curve

https://tmiwebclassic.cat.com/tmi/servlet/TMIDirector?Action=RDButton&tab=RNRefN... 19/11/2018
Caterpillar Generator Data Página 7 de 8

Selected Model
Engine: C32 Generator Frame: 1447 Genset Rating (kW): 1200.0 Line Voltage: 400
Fuel: Diesel Generator Arrangement: 5265096 Genset Rating (kVA): 1500.0 Phase Voltage: 230
Frequency: 50 Excitation Type: Permanent Magnet Pwr. Factor: 0.8 Rated Current: 2165.1
Duty: STANDBY Connection: SERIES STAR Application: EPG Status: Current
Version:
41205 /42661 /42865 /11046

https://tmiwebclassic.cat.com/tmi/servlet/TMIDirector?Action=RDButton&tab=RNRefN... 19/11/2018
Caterpillar Generator Data Página 8 de 8

General Information
DM7825 Caterpillar SR5 Generators (50 Hz, 60 Hz)
Data for 1400, 1600, 1700, 1800 and 1900 frames Caterpillar SR5
generators built by Leroy Somer - USA and Leroy Somer France.

Refer to DM7821 for explanation of all generator data in Technical


Marketing Information (TMI) except generator efficiency for which the
explanation is given below.

GENERATOR EFFICIENCY
Generator efficiency is the percentage of engine flywheel (or other
prime mover) power that is converted into electrical output. The
generator efficiency shown is calculated by the summation of all
losses method, and is determined in accordance with the IEC Standard
60034. The efficiency considers only the generator. There is no
consideration of engine or parasitic losses here.

Refer to DM7829 for low and medium voltage protective setting values a
nd limits.

Caterpillar Confidential: Green


Content Owner: Commercial Processes Division
Web Master(s): PSG Web Based Systems Support
Current Date: 19/11/2018 09:29:22 a.m.
© Caterpillar Inc. 2018 All Rights Reserved.
Data Privacy Statement.

https://tmiwebclassic.cat.com/tmi/servlet/TMIDirector?Action=RDButton&tab=RNRefN... 19/11/2018

You might also like