Download as pdf or txt
Download as pdf or txt
You are on page 1of 63

EE6501 – POWER SYSTEM ANALYSIS

UNIT-I POWER SYSTEM


PART A
1. What is Power system? (K)
An electrical power system is a network of electrical components which supplies the generated
power to the consumers
2. What are the principle components of electrical power system? (U)
The various components of electrical Power system consists of Generation, Transmission and
Distribution.
3. What is power system analysis? (K)
The evaluation of power system using various methods like load flow study, short circuit study
and stability study is called as power system analysis.
4. What are the need of power system analysis in planning and operation of power system. (E)
 To monitor the voltage at various buses, real and reactive power flow between buses.
 To design the protective devices
 To plan future expansion of the existing system
 To analyze the system under different fault conditions
 To study the ability of the system under small and large disturbances (Stability studies)
5. What are the steps involved in Power system studies?(A)
The various steps in planning and operational studies are:
 Planning of power system
 Implementing the system
 Monitoring the system
 Corrective actions under considerable deviations
 Planning the system under undesirable deviations
6. Define load flow analysis.(A)
Determining the power flow solution of the power system under the steady state condition is called
as load flow analysis. The voltage magnitude , real power, phase angle of the voltage and reactive
power of the buses are determined.

7. Define short circuit Analysis.(U)


When fault occurs in the system the current increases manifolds and causes abnormalities. Inorder
to avoid the abnormalities protective devices are used. The protective devices are designed based on
the fault current and fault MVA determined from the fault analysis. Therefore fault analysis is the
determination of Fault Current and fault MVA under various faulty conditions.

8. What is Power system stability?(E)


The ability of the power system to regain synchronism under various disturbances is called as
stability. The stability study consists of transient, dynamic and steady state stability analysis.

9. What are the basic components of power system?(K) (May/ June 2012)
The components of power system are Generators, loads, transmission lines, transformers,
circuit breaker, busbar, etc.. The transformer may be an isolation transformer, two winding
transformer or three winding transformer. The loads includes lighting load, Motor load, Heating
load etc.
10. What are the various models of the transmission line?(U)
The transmission line models are short transmission line model, medium transmission line model
and long transmission line model. The medium transmission line models are model, T-model and
end condenser model.

11. Draw the П representation of a transformer with off nominal tap ratio ' α’. (K)
(May/ June 2009, Nov/ Dec 2009, May/ June 2009)

12. What is single line diagram? (K) (May/ June 2009, Nov/ Dec 2011, 2015)
A single line diagram is a pictorial representation of the power system in which each
components are represented by their standard symbols and interconnection between them are
shown by a straight lines. For simplification the neutral is omitted and the ratings are mentioned
near the symbol of it. The single line diagram varies according to the type of study. For example
the position of circuit breakers are important in fault analysis but not in load flow analysis.

13. What is the use of single line diagram? (K)


Every component are represented with its standard symbol and the connections are
represented by line. So a concise knowledge about the power system can be obtained from the
single line diagram.

14. Draw a sample single line diagram.(U)

15. Define per phase analysis. (K)


Analyzing an balanced power system by considering one of the three phase lines and
neutral is called as per phase analysis
16. What is impedance diagram?(R)
The impedance diagram is the equivalent circuit of power system in which the various
components of power system are represented by their equivalent impedances. The magnetizing
reactance of the transformer, shunt capacitance and neutral grounding are neglected. The impedance
diagram is used for load flow studies.
17. What are the approximations made in impedance diagram? (K)
i. The neutral reactance are neglected.
ii. The shunt branches in equivalent circuit of transformers are neglected.
iii. Shunt capacitances are neglected.
18. Draw an impedance diagram for the power system given below.(U)
19. What is reactance diagram? (K)
The reactance diagram is the simplified equivalent circuit of power system in which the various
components of power system are represented by their equivalent reactance. The reactance diagram
can be obtained from impedance diagram if all the resistive components are neglected. The
reactance diagram is used in the fault analysis.

20. What are the approximations made in reactance diagram? (k)


i. The neutral reactance are neglected.
ii. The shunt branches in equivalent circuit of transformers are neglected.
iii. The resistances are neglected.
iv. All static loads are neglected.
v. The capacitance of transmission lines are neglected.
21.How are loads represented in reactance and impedance diagram.
(K)(Nov/ Dec 2011, 2016)
The load is represented by impedance in the impedance diagram and
by a reactance in the reactance diagram.

22. Define per unit value of an electrical quantity. (K)


(May/ June 2009, Nov/ Dec 2009, 2015)
The per unit value of any quantity is defined as the ratio of the actual value of that
quantity to an arbitrary selected value of that quantity. The arbitrary value is called as the base
value. The per unit value is dimensionless..

23. What are the advantages of per unit system? (K)


(Nov/ Dec 2016, April/ May 2011)
i. Per unit data representation yields valuable relative magnitude information.
ii. Circuit analysis of systems containing transformers of various transformation ratios is
greatly simplified.
iii. Manufacturers usually specify the impedance values of equivalent in per unit of the
equipments rating. If the any data is not available, it is easier to assume its per unit value
than its numerical value.
iv. The per unit value of the transformer is same on both the sides of the transformer.
v. The circuit laws are valid in p.u systems, and the power and voltages equations are
simplified since the factors of √3 and 3 are eliminated.
vi. The p.u systems are ideal for the computerized analysis and simulation of complex power
system problems

24. What is the need for base values? (U)


The components of the power system are represented with various ratings like voltage,
current, MVA etc.. It will be convenient for analysis if all the rating are expressed with reference to
the base value.
25. Define base current. (K)
Base current is defined as the ratio of base power (MVA) to base voltage KV.

26. Write the equation for base impedance with respect to three phase system.
(K) (May/ June 2009, 2016)

26. What is per unit impedance? (K) (May/ June 2016)

27. What is the relation between percentage value and per unit value? (K)
The ratio in percentage is 100 times the p.u value

28. Write the equation transformation base KV on LV side.(K)

29. Write the equation for per unit impedance if change of base occurs. (K)

30. A generator rated at 30MVA, 11KV has a reactance of 20%.Calculate its per unit reactance for
a base of 50 MVA and 10KV. (A) (Nov/Dec
2011)
MVA new = 50
KV new = 10
MVA old = 30
KV old = 11
X p.u = 20% = 20/100 = 0.2 p.u

31. What is the new p.u impedance if the new base MVA is twice the old base MVA? (A)
32. If the reactance is 50 ohms, find the p.u value for a base of 15 KVA and 10 KV. (A) (May/
June 2012)
Kvb2 102
Base Re ac tan ce, X b    666.66
MVAb 15 *103
X 50
P.uvalue    0.075 p.u
X b 666.66
33. Draw the impedance diagram for the given single line representation of the power system. (A)

34. Why the neutral grounding impedance Zn appears as 3Zn in zero sequence equivalent
circuit? (U)
The zero sequence current is 3 times of the current so the impedance is referred as 3Zn.
35. What is bus admittance matrix? (K)
The matrix consisting of the self and mutual admittance of the network of the power system is
called bus admittance matrix (Ybus).

36. What are the methods available for forming bus admittance matrix? (K)
 Direct method or inspection method.
 Singular transformation method.
37. What are the properties of admittance matrix? (E)
i. If the number of buses is n, then the size of the admittance matrix is n x n matrix.
ii. The diagonal element of the admittance matrix is the short circuit driving point or self
admittance at the ith bus.
iii. The off diagonal elements are the short circuit transfer admittance or neutral admittance.
iv. It is a symmetrical matrix.
v. The admittance matrix is a sparse matrix if the off diagnal elements have more number of
zeroes.
38. What is the use of admittance matrix?(U)
Admittance matrix is used in the Load flow study.
39. Write the equations for the elements of Y-bus when an element of admittance Y is added
The elements Yii, Yii, Yii and Yii changes as
Yiinew = Yii + Y
Yijnew = Yij - Y
Yjinew = Yji - Y
Yjjnew = Yjj +Y
40. Write the equations for the elements of Y-bus when an element of admittance Y is removed
across the buses i and j.(R)
The elements Yii, Yii, Yii and Yii changes as
Yiinew = Yii - Y
Yijnew = Yij + Y
Yjinew = Yji + Y
Yjjnew = Yjj -Y
41. Write the equations for the elements of Y-bus when a shunt element of admittance Y is added
at bus i.(R)
Yiinew = Yii + Y
42. Write the equations for the elements of Y-bus when a node is eliminated.
When a node n is eliminated,

where, i = 1,2,3, ... n , i≠n


j= 1,2,3,... n , j≠n

43. Define primitive network.(U)


If a network has both active and passive elements then it is called as a
primitive network
44. Define Graph .(E)
Graph is a representation of network obtained by replacing every element of the
network by a line segment and every bus by a node.
45. Define primitive admittance matrix.(A)
Matrix which contains information about the transmission line admittance is
called as a primitive admittance matrix.

PART( B &C)
1. Explain the modeling of generator, load, transmission line and transformer for power flow, short
circuit and stability studies. (U)
2. Draw the per unit reactance diagram for the power systems shown below. Neglect resistance and use
T1 T2
a base of 100MVA, 220KV in 50 ohms line. The ratings of the generator, motor and transformers
are: (A) G1 j 50Ω M

G: 40MVA, 25KV, X’’ = 20%


M: 50MVA, 11KV, X’’ = 30%
T1: 40MVA, 33 Y/ 220Y KV, X = 15%
T2: 30MVA, 11 Δ / 220Y KV, X = 15%
Load: 11KV, 50MW+j68 MVAR

3. Draw the reactance diagram using a base of 50MVA and 13.8KV on generator G1. (A)
T1 T3

Line 1 Line 2
G1 G3
j80Ω j100Ω

T2

G2

G1: 20MVA, 13.8KV, X’’=20% ; G2: 30MVA, 18.0KV, X’’=20%


G3: 30MVA, 20.0KV, X’’=20% ; T1: 25MVA, 220/13.8 KV, X=10%
T2:3Single phase unit each rated 10MVA, 127/18 KV, X =10%
T3: 35MVA, 220/22 KV, X =10%
4. A simple power system is shown in fig. Redraw this system where the per unit impedance of the
components are represented on a common 5000 VA base and common system base voltage of
250V. (A)

1000VA T1 T2 2500VA
250V G1
400V
Z = j0.2 p.u
Z=40 + j 150Ω
Load

2000VA 4000VA 8000VA


G2
250V 250/800V 1000/500V
Z = j0.3 p.u Z = j0.2 p.u Z = j0.06 p.u

5. The single line diagram of a three phase power system is shown in fig. Select a common base of
100MVA and 13.8KV on the generator side. Draw per unit impedance diagram. (A)

T1 T2
2
j 50Ω

G M
T3 T4
4
j70Ω

G: 90MVA, 13.8KV, X=18% ; T1 :50MVA, 13.8/220KV, X=10%


T2:50MVA, 220/11KV, X=10% ; T3 :50MVA, 13.8/132KV, X=10%
T4:50MVA, 132/11KV, X=10% ; M : 80MVA, 10.45KV, X=20%
LOAD: 57MVA, 0.8 p.f lagging at 10.45 KV ;
6. The one line diagram of a three phase power system is shown in figure. Select a common base of
100 MVA and 22 KV on the generator side. Draw an impedance diagram with all impedance
including the load impedance marked in per unit. The manufacturer’s data for each device is given
as follow: (A)
G: 90 MVA 22KV X=18%
T1: 50 MVA 22/220KV X=10%
T2: 40 MVA 220/11KV X=6.0%
T3: 40 MVA 22/110KV X=6.4%
T4: 40 MVA 110/11KV X=8.0%
M: 66.5 MVA 10.45 KV X=18.5%
The three phase load at bus 4 absorbs 57MVA, 0.6 power factor lagging at 10.45 KV. Line
1 and Line 2 have reactance of 48.4 and 65.43 ohms respectively.

7. The single line diagram of an unloaded power system is shown in fig. Reactances of the two
sections of the transmission line are shown on the diagram. The generator and transformers are
rated as follows: (A) (Nov/Dec 2015)

Generator G1: 20 MVA, 13.8 KV, X” = 20%


Generator G2: 30 MVA, 18.0 KV, X” = 20%
Generator G3: 30 MVA, 20.0 KV, X” = 20%
Transformer T1 : 25 MVA, 220 Y / 13.8 Δ KV, X = 10%
Transformer T2 :3 single phase units each rated at : 10 MVA, 127/18 KV, X = 10%
Transformer T3: 35 MVA, 220 Y / 22 Y KV, X = 10%
Draw the reactance diagram using a base of 50 MVA and 13.8 KV on generator G1.
8. Explain the need for system analysis in planning and operation of power system. Discuss about per
phase analysis of symmetrical three phase system. (U)
9. Draw the structure of an electrical power system and describe the components of the system with
typical values.(U)
10. Draw the reactance diagram using a base of 100 MVA, 220 KV in 50 ohm line. (A)
Generator : 40 MVA, 25 KV, X” = 20%, Star Grounded
Transformer : 50 MVA, 11 KV, X” = 20%, Star Star Grounded
Star – Star transformer : 40 MVA, 33 / 220 KV, X = 15%
Star – Delta transformer : 30 MVA, 11 / 220 KV, X = 15% (16)

11. A 120 MVA, 19.5 KV generator has a synchronous reactance of 0.15 p.u and it is connected to a
transmission line through a transformer rated 150 MVA, 230/18 KV (star/delta) with X = 0.1 p.u.
Calculate the p.u reactance by taking generator rating as a base values. Calculate the p.u reactance
by taking transformer rating as a base values. Calculate the p.u reactance for a base value of 100
MVA and 220 KV on H.T side of transformer. (A)
12. For the network shown in fig. form the bus admittance matrix. Determine the reduced admittance
matrix by eliminating node 4.(A)

13. Using Singular transformation method, Determine YBUS for the network shown in Fig. Where the
impedance labeled in p.u. (A)

14. Explain the formation of YBUS by Singular transformation with one example. (U)
15. Derive the Π – model for a transformers with off - nominal tap – ratio ‘α’. (C)
(May/ June 2016)
16. The parameters of a 4-bus systems are as under: (Nov/ Dec 2016)
Line charging
Line Starting bus Line ending bus Line impedance
admittance
1 2 0.2+j0.8 j0.02
2 3 0.3+j0.9 j0.03
2 4 0.25+j1 j0.04
3 4 0.2+j0.8 j0.02
1 3 0.1+j0.4 j0.01
Draw the network and find the bus admittance matrix. (A)
17. Find YBUS for the data given below: (A)
Line R X
1-2 0.05 0.15
1-3 0.10 0.30
2-3 0.15 0.45
2-4 0.10 0.30
18. Find out the Y 3-4 0.05 0.15 matrix of the
sample power system as shown in
fig. Data for this system is given in table. (AP)

Bus Line Charging


Impedance
Code admittance
1-2 0.02+j0.06 j0.03
1-3 0.08+j0.24 j0.025

2-3 0.06+j0.18 j0.02

19. Consider the system shown in fig. It shows a transmission network with impedance of transmission
lines all in p.u as shown. Compute Ybus matrix. (AP)
1 0.02+j0.04 2

0.01+j0.03 0.0125+j0.025

20. Find the bus admittances matrix for the system. Use the values of 220 KV and 100 MVA as base
quantities. Express all impedances and admittance in per unit it is given that all the lines are
characterized by a series impedances of 0.1+j0.7 ohm/km and shunt admittance of j0.35 ×10-5
mho/km. lines are rated at 220 KV. (AP)
21. Determine the Ybus matrix by inspection method for the line specification as mentioned below:
(A) (May/ June 2016)
Half Line charging
Line p-q Impedance in p.u
admittance in p.u
1-2 0.04+j0.02 j0.05
1-4 0.05+j0.03 j0.07
1-3 0.025+j0.06 j0.08
2-4 0.08+j0.015 j0.05
3-4 0.035+j0.045 j0.02
22. Prepare a per phase schematic of the system shopwn in Fig. and show all the impedances in per
unit on a 100 MVA, 132 Kv base in the transmission line circuit. The necessary data are given as
follows: (C) (Nov/ Dec 2016)
G1: 50 MVA, 12.2 kV, X= 0.15 p.u
G2: 20 MVA, 13.8 kV, X= 0.15 p.u
T1: 80 MVA, 12.2/161 kV, X= 0.1 p.u
T2: 40 MVA, 13.8/ 161 KV, X= 0.1 p.u
Load: 50 MVA, 0.8 p.f lagging operating at 154 kV

23. The data for the system whose single line diagram shown in Figure is as follows: (A)
(May/ June 2016)
G1: 30 MVA, 10.5 KV, X’’=1.6 ohms
G2: 15 MVA, 6.6 kV, X’’=1.2 ohms
G3: 25 mVA, 6.6 kV, X’’= 0.56 ohms
T1: 15 MVA, 33/11 kV, X= 15.2 ohms/Phase on H.T side
T2: 15 MVA, 33/6.2 kV, X=16.0 ohms/phase on L.T side
Tansmission line : 20.5 ohms/phase
Loads A : 40 Mw, 11 kV, 0.9 p.f lagging
B : 40 Mw, 6.6 kV, 0.85 p.f lagging
Choose the base power as 30 MVA and approximate bas voltages for different parts. Draw the
reactance diagram. Indicate p.u reactance on the diagram.

24. Form Ybus of the test system shown in Fig using singular transformation method. The impedance
data is given in the table. Take (1) as reference node. (AP) (Nov/ Dec 2015)

Self Mutual
Element No.
Bus code Impedance Bus Code Impedance
1 1-2 0.5
2 1-3 0.6
1-2 0.1
3 3-4 0.4
4 2-4 0.3
UNIT-II POWER FLOW ANALYSIS
PART A

1. What is a bus? (K)


The meeting point of various components in a power system is called a bus. The bus is a conductor
made of copper or aluminium having negligible resistance. At some of the buses power is being
injected into the network, whereas at other buses it is being tapped by the system loads.
2. What is power flow study or load flow study? (K)
Power flow analysis is a basic tool which is performed under the steady state condition. The load
flow study is used to determine the various voltages, real power and reactive in the system.
3. What are the information’s that are obtained from a load flow study? (K)
The information obtained from a load flow study are:
a. Magnitude and phase angle of voltages,
b. Real and reactive power flowing in each line and
c. Line losses.
d. Initial conditions of the system when the transient behavior of the system is to be studied.
4. What is the need for load flow study? (K) (Nov/Dec 2015, May/ June 2016)
Load flow study is important for:
i. Planning, operation , economic scheduling and controlling.
ii. Analyzing the losses, stability and security of the power system.
iii. Identifying the overloaded and under loaded lines, buses and transformers.
iv. Identifying the optimal location of the capacitors.
v. Committing the units without violating the operating limits.
5. What are the quantities associated with each bus in a system? (K)
A bus in a power system is associated with four quantities.
They are:
i. Real power (P)
ii. Reactive power (Q)
iii. Magnitude of voltage (V)
iv. Phase angle of voltage (δ).
6. State the ideal load flow problem.
For a network with the line impedance and half line charging admittances and
the power injection the state vector X is defined as

where, are the voltages


are the angles at all the buses
By knowing the voltages and angles at all the buses, the slack bus power,
power flow and power loss in the transmission line can be obtained.
7. What are the different types of buses in a power system? Or how the buses are classified and
what are its types? (A) (May/ June 2016)
Known or specified Unknown quantities
Types of bus
quantities or quantities to be determined
Slack or Swing or
V, δ P,Q
Reference bus
Generator or Voltage
P, V Q, δ
control or PV bus

Load or PQ bus P, Q V, δ
8. What is the need for slack bus? (U) (Nov/ Dec 2016)
The system power loss is initially unknown and network powe flow cannot be fixed in advance. So
a generator bus with larger rating is fixed as a slack bus or a swing bus. The power generated by
the slack bus is the difference between the power injected into the system at other buses and the
power used at various buses.
9. Write the power flow equation in polar form.(K)

10. Why do we go for iterative methods to solve load flow problems? (U)
The load flow equations are non linear algebraic equations and so explicit solution as not possible.
The solution of non linear equations can be obtained only by iterative numerical techniques.
11. What are the methods mainly used for solution of load flow study? (K)
The various methods for solving the load flow problem are:
i. Gauss seidal method
ii. Newton Raphson method
iii. Fast decouple method
12. What do you mean by a flat voltage start? (K)
The initial voltages of all buses except slack bus assumed as 1+j0 p.u. This is referred to as flat
voltage start.
13. Discuss the effect of acceleration factor in load flow study. (A)
Acceleration factor is used in gauss seidal method of load flow solution to increase the rate of
convergence or to reduce the number of iterations. The acceleration factor is normally chosen as
between 1.3 and 1.7.
14. When the generator buses are treated as load bus.(U) (A)(Nov/Dec 2015)
If the reactive power constraints of a generator bus violates the specified limits then the generator
is treated as load bus.
15. What are the advantages of Gauss seidal method? (K)
The advantages of Gauss seidal method are:
i. Reliable
ii. Calculations are simple and so the programming task is less.
iii. The memory requirement is less.
iv. Linea r convergence characteristics
16. What are the disadvantages of Gauss seidal method? (K)
The disadvantages of Gauss seidal method are:
i. Speed of convergence is slow
ii. Not suitable for large systems.
iii. Convergence time increases with size of the system
17. How approximation is performed in Newton-Raphson method? (K)
In Newton-Raphson method, the set of nonlinear simultaneous (load flow) equations are
approximated to a set of linear simultaneous equations using Taylor’s series expansion and the
terms are limited to first order approximation
18. What is Jacobian matrix? How the elements of Jacobian matrix are computed? (K)
(Nov/ Dec 2016)
The matrix formed from the first derivatives of load flow equation is called Jacobian matrix and it
is denoted by J.
The elements of Jacobian matrix will change in every iteration the elements of the Jacobian matrix
are obtain matrix are obtained by partially differentiating the load flow equation with respect to a
unknown variable and then evaluating the first derivatives using the solution of previous iteration .
19. What are the advantages of N.R method? (K)
i. Speed of convergence is faster
ii. More reliable
iii. Not dependant on size
iv. Results are accurate
v. Require less number of iterations
vi.
20. What are the disadvantages of N.R method? (K)
i. Programming is more complex
ii. Requires more memory

21. Compare Gauss seidel and Newton raphson methods of load flow study. (A)

S.No Gauss Seidal Method Newton Raphson Method

Require large number of iterations Require less number of iterations to


1
to reach convergence. reach convergence.
Computation time per iteration is Computation time per iteration is
2
less more
It has linear convergence It has quadratic convergence
3
characteristics characteristics
The number of iterations required
The number of iterations are
4 for convergence increases with size
independent of the size of the system
of the system

5 Less memory requirements. More memory requirements.

PART (B & C)
1. Derive static load equations for ‘n’ bus system.(C)
2. The figure below shows the one line diagram of a simple three bus power system with generators at
buses 1 and 3. The magnitude of voltage at bus 1 is adjusted to 1.05 .u. voltage magnitude at bus 3
is fixed at 1.04 p.u with a real power generation of 200 MW. A load consisting of 400 MW and
250 MVAR is taken from bus 2. Line impedances are marked in per unit on a 100 MVA base, and
the line charging susceptances are neglected. Obtain the power flow solution by the gauss seidal
method at the end of first iteration. (AP) (Nov/ Dec 2016)
3. Explain load flow algorithm using Gauss – Seidal method with flow chart and discuss the
disadvantages of the method. (U)
(OR)
Draw the flow chart and explin the algorithm of Newton Raphson iterative method when the
system contains all types of buses.
(May/ June 2016)
(OR)
Draw and explain the step by step procedure of load flow solution for the Gauss seidal method
when PV buses are present.
(Nov/ Dec 2015)
4. With a neat flow chart, explain the computational procedure for load flow solution using Newton
Raphson method when the system contains all types of buses. (U) (May/ June 2016, Nov/ Dec
2016)
5. The system data for a load flow solution are given in tables. Determine the voltages at the end of the
first iteration using the Gauss seidal method. Take α =1.6.(AP) (Nov/ Dec 2015)
Bus P in Q in V in
Admittance Bus Code Remarks
Code p.u p.u p.u
1-2 2-j8.0 1 - - 1.06 Slack
1-3 1-j4.0 2 0.5 0.2 1+j0.0 PQ
2-3 0.666-j2.664 3 0.4 0.3 1+j0.0 PQ
2-4 1-j4.0 4 0.3 0.1 1+j0.0 PQ
3-4 2-j8.0

6. The following is the system data for a load flow solution:


Bus Code Admittance
1-2 2.0-j8.0
1-3 1.0-j3.0
2-3 0.6-j2.0
2-4 1.0-j4.0
3-4 2.0-j8.0
The schedule of active and reactive power is:
Bus No. P Q V Remarks
1 - - 1.0+j0.0 Slack
2 0.5 0.2 1.0+j0.0 PQ
3 0.4 0.3 1.0+j0.0 PQ
4 0.3 0.1 1.0+j0.0 PQ
Determine the voltage at the end of first iteration Using Gauss Seidal method. Take acceleration
factor = 1.4. (AP)
UNIT- III SYMMETRICAL FAULT ANALYSIS
PART A
1. What is meant by a fault? (K)A fault in a circuit is any failure which interferes with the normal
flow of current. The faults are associated with abnormal change in current, voltage and frequency
of the power system.
2. Why faults occur in a power system? (K) (Nov/Dec 2015)
The faults occur in a power system due to
 Insulation failure of equipment
 Flashover of lines initiated by a lighting stroke
 Due to permanent damage to conductors and towers or due to accidental faulty operations.
3. List the various types of faults. (K)
OR
How are shunt and series faults classified. (Nov/ Dec 2016)
 Series fault or open circuit fault
o One open conductor fault
o Two open conductor fault
 Shunt fault or short circuit fault.
o Symmetrical fault or balanced fault
 Three phase fault
o Unsymmetrical fault or unbalanced fault
 Line to ground (L-G) fault
 Line to Line (L-L) fault
 Double line to ground (L-L-G) fault
4. Write the relative frequency of occurrence of various types of faults. (K)
Relative frequency of
Types of fault
occurrence of faults
Three phase fault 5%
Double line to ground fault 10%
Line to Line fault 15%
Line to ground fault 70%
5. State and explain symmetrical fault or balanced three phase fault. (K)
(May/ June 2016)
This type of fault is defined as the simultaneous short circuit across all the three phases. It
occurs infrequently, but it is the most severe type of fault encountered. Because the network is
balanced, it is solved by per phase basis using Thevenins theorem or bus impedance matrix or
KVL, KCL laws.
6. What is the need for short circuit studies or fault analysis? (U) (Nov/ Dec 2016)
Short circuit studies are essential in order to design or develop the protective schemes for
various parts of the system .To estimate the magnitude of fault current for the proper choice of
circuit breaker and protective relays.
7. What is bolted fault or solid fault? (K) (May/ June 2016)
A Fault represents a structural network change equivalent with that caused by the addition of
impedance at the place of a fault. If the fault impedance is zero, the fault is referred as bolted fault
or solid fault.
8. What is the reason for transients during short circuits? (K)
The faults or short circuits are associated with sudden change in currents. Most of the components
of the power system have inductive property which opposes any sudden change in currents, so the
9. What is meant by doubling effect? (K)
If a symmetrical fault occurs when the voltage wave is going through zero then the maximum
momentary short circuit current will be double the value of maximum symmetrical short circuit
current. This effect is called doubling effect.
10. Define DC off set current. (K)
The unidirectional transient component of short circuit current is called DC off set current.
11. What is synchronous reactance or steady state condition reactance? (K)The synchronous
reactance is the ratio of induced emf and the steady state rms current. It is the sum of leakage
reactance (Xl) and the armature reactance (Xa).

12. What is sub transient reactance? (K)


The synchronous reactance is the ratio of induced emf on no load and the sub transient
symmetrical rms current.

13. What is transient reactance? (K)


The synchronous reactance is the ratio of induced emf on no load and the transient
symmetrical rms current.

14. Define short circuit capacity of power system or fault level. (K)
(Nov/ Dec 2016)
Short circuit capacity (SCC) or Short circuit MVA or fault level at a bus is defined as the product
of the magnitude of the prefault bus voltage and the post fault current.

SCC or Short circuit MVA = or

SCC =
15. Find the fault current in fig., if the prefault voltage at the fault point is 0.97 p.u.? (E)

j0.2 F

j0.1 j0.1
5 5

16. What is bus impedance matrix? (K)


Bus impedance matrix is the inverse of the bus admittance matrix.
The matrix consisting of driving point impedance and transfer impedances of the network is
17. Give the methods available for forming bus impedance matrix. (U)
Form bus admittance matrix and take the inverse to get bus impedance matrix.
 Using bus building algorithm.
 Using L-U factorization of Y-bus matrix.

19. Write in brief about Bus building algorithm.(U)


It is an indirect method of taking the inverse of the admittance matrix by considering one
bus at a time.
20. What are the advantages of bus building algorithm?(R)
The advantages are:
a. It is suitable for large power systems.
b. Modification is easy

PART (B & C)

1. A 25 MVA, 11 KV generator with Xd’’=20% is connected through a transformer to a bus which


supplies four identical motors as shown in figure. Each motor has Xd’’ =20% and Xd’=25% on a base
of 5 MVA, 6.6 KV. The three phase rating of the transformer is 25 MVA, 11/6.6 KV with a leakage
reactance of 10%. The bus voltage at the motors is 6.6 KV when a three phase fault occurs at point P.
for the faults specified, Calculate (i) the sub transient current in the fault (ii) the sub transient current in
breaker A. (iii) momentary current in breaker A. (AP)

2. A three phase transmission line operating at 33 KV and having a resistance and reactance of 5 ohms and
15 ohms respectively is connected to the generating station bus-bar through a 5000 KVA step up
transformer which has a reactance of 0.05 p.u. Connected to the bus-bars are two alternators, one
10000 KVA having 0.08 p.u. reactance, and another 5000 KVA having 0.06 p.u. reactance. Calculate
the KVA at a short-circuit fault between phases occurring (a) at the high voltage terminals of the
transformers (b) at load end of transmission line. (AP)

3. A synchronous generator and a synchronous motor each rated 25 MVA, 11 KV having 15% sub –
transient reactance are connected through transformers and a line as shown in fig. The Transformers
are rated 25 MVA, 11/66 KV and 66/11 KV with leakage reactance of 10% each. The line has a
reactance of 10% on a base of 25 MVA, 66 KV.The motor is drawing 15 MW at 0.5 power factor
leading at a terminal voltage of 10.6 KV. When a symmetrical three phase fault occurs at the motor
terminals. Find the sub – transient current in the generator, Motor and Fault. (E)

4. A generator is connected through a transformer to a synchronous motor. The subtransient reactance of


generator and motor are 0.15 p.u. and 0.35 p.u.respectively. The leakage reactance of the transformer
is 0.1p.u. All the reactances are calculated on a common base. A three phase fault occurs at the
terminals of the motor when the terminal voltage of generator is 1 p.u. and 0.8 p.f. leading. Find the
subtransient current in p.u. in the fault, generator and motor. Use the terminal voltage of generator as a
reference vector. (E)

5. The currents flowing in the lines towards a balanced load connected in Δ are Ia = 100∟0°, Ib = 141.4
∟225°, Ic = 100∟∟90°. Find the symmetrical components of the given line currents and draw phasor
Derive the expression of three phase power in terms of symmetrical components. (C)
6. A 3 phase, 5 MVA, 6.6 KV alternator with a reactance of 8 % is connected to a feeder series impedance
(0.12+j0.48) ohm/phase/km through a step up transformer. The transformer is rated at 3 MVA, 6.6kV/
33kV and has a reactance of 5%. Determine the falt current supplied by the generator operating under
no load with a voltage of 6.9 kV, when a three phase symmetrical fault occurs at a poing 15 km along
the feeder. (AP) (Nov/ Dec 2016)
7. For the radial network shown in figure a three phase fault occurs at point F. Determine the fault current
and the line voltage at 11.8 kV bus under fault condition. (E)

8. A Symmetrical fault occurs at bus 4 for the system shown in Fig. Determine the fault current using Zbus
building Algorithm. (AP)
(May/ June 2016)

G1, G2 : 100 MVA, 20 kV, X+=15%


Transformer : Xleak =9%
L1, L2 : X+ =10%
9. A generating station feeding a 132 Kv system is hown in figure. Determine the total fault current, fault
level and fault current supplied by each alternator for a three phase fault at the receiving end bus. The
line is 200km long. (AP)
G1 : 100 MVA, 11kV, X=15%
G2 : 50 MVA, 11 kV, X=10%
T1 : 100 MVA, 11/132 kV, X=10%
T2 : 50 mVA, 11/132 kV, X=8%

10. Generator G1 and G2 are identical and rated 11 KV. 20 MVA and have a transient reactance of 0.25
p.u at own MVA base. The transformers T1 and T2 are also identical and are rated 11/66 kV, 5 MVA
between the two generators. Calculate three phase fault current, when fault occurs at middle of the line
as shown in Fig. (AP) (Nov/ Dec 2015)

11. A synchronous generator and synchronous motor each rated 30 MVA, 13.2 kV and both have sub
transient reactance of 20% and the line reactance of 12% on a base of machine ratings. The motor is
drawing 25 Mw at 0.85 p.f leading. The terminal voltage is 12 kV when a three phase short circuit
fault occurs at motor terminals. Find the subtransient current in generator, motor and at the fault point.
(E)
(Nov/ Dec 2015)

13. Determine the Z bus for the system whose reactance diagram is shown in the Fig. where the
impedance is given in p.u.(A)

14. Explain the step by step procedure of the formation of ZBUS by bus building algorithm. (U)
15. Find the bus impedance matrix for the system whose reactance diagram is shown fig. All the
impedance are in p.u. (A)

16. Using building algorithm method, determine ZBUS for the network shown in Fig where the
impedances are labeled are shown in per unit. (A)
UNIT- IV UNSYMMETRICAL FAULT ANALYSIS

PART A

1. What are the symmetrical components of a 3 phase system? (K)


(Nov/Dec 2015, May/ June 2016)
In a 3 phase system, the unbalanced vectors (either currents or voltage) can be resolved into three
balanced system of vectors.
They are:
 Positive sequence components
 Negative sequence components
 Zero sequence components
Unsymmetrical fault analysis can be done by using symmetrical components.
2. What are the positive sequence components? (K)
It consists of three components of equal magnitude, displaced each other by 120˚ in phase
and having the phase sequence abc .

3. What are the negative sequence components? (K)


It consists of three components of equal magnitude, displaced each other by 120˚ in phase
and having the phase sequence acb .

4. What are the zero sequence components? (K)


It consists of three phasors equal in magnitude and with zero phase displacement from each
other.
Ia0
Ib0 Ia0 = Ib0 = Ic0
Ic0
5. What is sequence operator? (K) (Nov/Dec 2015)
In unbalanced problem, to find the relationship between phase voltages and phase currents, we use
sequence operator ‘a’.
a = 1∠120˚ = = - 0.5+j0.866

6. Write down the equations to convert symmetrical components into unbalanced phase
currents. (Or) Determination of unbalanced currents from symmetrical currents. (K)
Let, Ia, Ib, Ic be the unbalanced phase currents
Let, Ia0, Ia1, Ia2 be the symmetrical components of phase a

7. Write down the equations to convert unbalanced phase currents into symmetrical
components. (Or) Determination of symmetrical currents from unbalanced currents. (K)
(May/ June 2016)
Let, Ia, Ib, Ic be the unbalanced phase currents
Let, Ia0, Ia1, Ia2 be the symmetrical components of phase a

8. What are sequence impedance and sequence network? (K)


The sequence impedances are the impedances offered by the power system components or
elements to +ve, -ve and zero sequence current.
The single phase equivalent circuit of power system consisting of impedances to current of any one
sequence only is called sequence network.

9. Write the equation to determine fault current for L-G, L-L and L-L-G fault with impedance.
(K)
= Ia = =

10. Write the equation to determine fault current for L-L fault with
impedance. (K)
=
11. Write the equation to determine fault current for L-L-G fault with impedance. (K)
=

12. Draw the equivalent sequence network diagram for L-G fault. (K)
13. Draw the equivalent sequence network diagram for L-L fault. (K)

14. Draw the equivalent sequence network diagram for Double Line to Ground Fault. (K)

PART (B&C)

1. Explain the sequence impedance of synchronous machine, transmission lines and star connected
loads. (U)
2. Draw the transformer zero sequence equivalent circuits for the various winding connections. (K)
3. A 25MVA, 11KV, three phase generator has a sub transient reactance of 20%. The generator
supplies two motors over a transmission line with transformers at both ends as shown in one line
diagram. The motors have rated inputs of 15 and 7.5 MVA both 10KV with 25% sub transient
reactance. The three phase transformers are rated 30MVA, 10.8/121KV, and connection delta-star
with leakage reactance of 10% each. The series reactance of the line is 100 ohms. Draw the
positive and negative sequence networks of the system with reactance marked in per unit. (AP)

4. Develop the sequence network for a double line to ground (LLG) fault. (C)
5. A salient pole generator without dampers is rated 20 MVA, 13.6 KV and has direct axis sub –
transient reactance of 0.2 per unit. The negative and zero sequence reactance are 0.35 and 0.1 per
unit respectively. The neutral of the generator is solidly grounded. With the generator operating
unloaded at rated voltage with Ean = 1.0 ∟0° per unit, a single line to ground fault occurs at the
machine terminals, which then have per – unit voltage to ground.
Va = 0; Vb = 1.013∟-102.25°; Vc = 1.013∟102.25°
Determine the sub transient current in the generator and the line to line voltage for sub transient
conditions due to the fault. (AP)
6. Derive the expression for fault current in single line to ground fault on unloaded generator. Draw an
equivalent network showing the inter connection of networks to simulate single line to ground
fault. (C)
7. Derive the expression for fault current in double line to ground fault on unloaded generator. Draw
an equivalent network showing the inter connection of networks to simulate double line to ground
fault.
OR
Deduce and draw the sequence network for LLG fault at the terminal of the unloaded generator.
(C) (May/ June 2016)
8. Derive the expression for fault current in line to line fault on unloaded generator. Draw an
equivalent network showing the inter connection of networks to simulate double line to line fault.
(C)
(May/ June 2016, Nov/ Dec 2016)
9. An unloaded star connected solidly grounded 10 MVA, 11 KV, generator has Positive, Negative and
zero sequence impedances as j 1.3 ohms, J 0.8 ohms and j 0.4 ohms respectively. Single line to
ground fault occurs at terminals of the generator.
i. Calculate the fault current.
ii. Determine the value of the inductive reactance that must be inserted at the generator neutral
to limit the fault current to 50% of the value obtained in Determine the fault current and
MVA at faulted bus for a line to ground (solid) fault at bus 4 as shown in figure.
G1, G2 : 100 MVA, 11 KV, X+ = X - 15%, Xn = 6%
T1, T2 : 100 MVA, 11 KV/220 KV, Xleak = 9%
L1, L2 : X+ = X - = 10% on a base of 100 MVA. Consider Fault at
phase ‘a’. (AP)
10. A 30 MVA, 11 Kv generator has Z1= Z2= j0.05. A line to Ground fault occurs at generator
terminals. Find the fault current and line voltages during fault conditions. Assume that the
generator neutral is solidly grounded and the generator is operating at no load and at rated voltage
during occurrence of fault. (AP) (Nov/ Dec 2016)
11. What are the assumptions in short circuit studies? (K)
(May/ June 2016)
12. Derive the expression for the three phase power in terms of symmetrical components. (C)
(Nov/ Dec 2015)
13. A 30 MVA, 11 kV, 3Ф synchronous generator has a direct subtransient reactance of 0.25 p.u. The
negatice and zero sequence rcactances are 0.35 and 0.1 p.u respectively. The neutral of the
generator is solidly grounded. Determine the subtransient current in the generator and the line to
line voltages for sub transient conditions when a single line to ground fault occurs at the generator
terminals with the generator operating unloaded at rated voltage. (AP)
(Nov/ Dec 2015)
UNIT- V STABILITY ANALYSIS
PART A

1. What is power system stability? (K)


The stability of an interconnected power system means is the ability of the power system is to
return or regain to normal or stable operating condition after having been subjected to some form
of disturbance.
2. How power system stability is classified? (A) (Nov/Dec 2015)

3. What is rotor angle stability? (K)


Rotor angle stability is the ability of interconnected synchronous machines of a power system to
remain in synchronism.
4. What is steady state stability? (K) (Nov/ Dec 2012)
Steady state stability is defined as the ability of the power system to bring it to a stable condition or
remain in synchronism after a small disturbance.
5. What is steady state stability limit? (K)
The steady sate stability limit is the maximum power that can be transferred by a machine to
receiving system without loss of synchronism
6. What is transient stability? (K) (Nov/ Dec 2009, Nov/ Dec 2012, May/ June 2016)
Transient stability is defined as the ability of the power system to bring it to a stable condition or
remain in synchronism after a large disturbance.

7. What is transient stability limit? (K)


The transient stability limit is the maximum power that can be transferred by a machine to a fault
or a receiving system during a transient state without loss of synchronism.
Transient stability limit is always less than steady state stability limit.
8. What is dynamic stability? (K)
It is the ability of a power system to remain in synchronism after the initial swing (transient
stability period) until the system has settled down to the new steady state equilibrium condition
9. What is voltage stability? (K) (Nov/ Dec 2016)
It is the ability of a power system to maintain steady acceptable voltages at all buses in the system
under normal operating conditions and after being subjected to a disturbance.
10. State the causes of voltage instability. (K)
A system enters a state of voltage instability when a disturbance, increase in load demand,or
change in system condition causes a progressive and uncontrollable drop in voltage
The main factor causing instability is the inability of the power system to meet the demand for
reactive power.
11. Write the power angle equation and draw the power angle curve. (K)
(Nov/Dec 2015)

Where, P – Real Power in watts


Vs – Sending end voltage
Vr- Receiving end voltage
XT - Total reactance between sending end receiving end
- Rotor angle.

12. Write the expression for maximum power transfer. (K)

13. Write the swing equation for a SMIB (Single machine connected to an infinite bus bar)
system. (K)

M
Where H = inertia constant in MW/MVA
f = frequency in Hz
M = inertia constant in p.u
14. Define swing curve. (K)
The swing curve is the plot or graph between the power angle δ and time t. From the nature of
variations of δ the stability of a system for any disturbance can be determined.
15. In a 3 machine system having ratings G1, G2 and G3 and inertia constants M1, M2 and
M3.What is the inertia constants M and H of the equivalent system. (K)

Where G1, G2, G3 – MVA rating of machines 1, 2, and


Gb = Base MVA or system MVA
16. State the assumptions made in stability studies. (K)
 Machines represents by classical model
 The losses in the system are neglected (all resistance are neglected)
 The voltage behind transient reactance is assumed to remain constant.
 Controllers are not considered ( Shunt and series capacitor )
 Effect of damper winding is neglected.

17. State Equal Area Criterion. (K) (May/ June 2016)


The equal area criterion for stability states that the system is stable if the area under P – δ
curve reduces to zero at some value of δ. This is possible if the positive (accelerating) area under P
– δ curve is equal to the negative (decelerating) area under P – δ curve for a finite change in δ.
hence stability criterion is called equal area criterion.

18. Define critical clearing angle. (K)


The critical clearing angle , is the maximum allowable change in the power angle δ
before clearing the fault, without loss of synchronism.
The time corresponding to this angle is called critical clearing time, .It can be defined as
the maximum time delay that can be allowed to clear a fault without loss of synchronism.
19. Define critical clearing time. (K)
The corresponding critical time for removing the fault is called critical clearing time
20. List the methods of improving the transient stability limit of a power system. (K)
(Nov/ Dec 2016)
 Reduction in system transfer reactance
 Increase of system voltage and use AVR
 Use of high speed excitation systems
 Use of high speed reclosing breakers
21. What are the numerical integration methods of power system stability? (K)
 Point by point method or step by step method
 Euler method
 Modified Euler method
 Runge-Kutta method(R-K method)
22. State the application of equal area criterion. (K)
We apply the equal area criterion to two different systems of operation
 Sustained line fault
 line fault cleared after sometime by the simultaneous tripping of the breakers at both the
end

PART ( B &C)

1. Derive swing equation and discuss the importance of stability studies in power system planning and
operation. (C) (Nov/ Dec 2015, Nov/ Dec 2016)
2. Describe the equal area criterion for transient stability analysis of a system. (K)
3. Write the computation algorithm for obtaining swing curves using modified Euler’s method. (K)
(May/ June 2016)
4. A 60 Hz synchronous generator having inertia constant 5 MJ/MVA and X 1d =0.3p.u is connected to a
infinite bus through circuit shown. Reactance marked on common base value real power Pe is 0.8 p.u
reactive power is 0.074 p.u and bus voltage is V=1p.u. three phase fault occur at mid of line. When
fault is cleared calculate clearing angle and clearing time and current of system stability. (AP)

5. Derive Expression for critical clearing angle. (C)


6. A 150 MVA generator – transformer unit having an overall reactance of 0.3 p.u. is delivering 150 MW
to infinite bus bar over a double circuit 220 KV line having reactance per phase per circuit of 100
ohms. A 3 - phase fault occurs midway along one of the transmission lines. Calculate the maximum
angle of swing that the generator may achieve before the fault is cleared without loss of stability. (AP)
7. A 50 Hz, 500 MVA, 400 KV generators (with transformer) is connected to a 400 KV infinite bus bar
through an interconnector. The generator has H = 2.5 MJ/MVA, Voltage behind transient reactance of
450 KV and is loaded 460 MW. The transfer reactance between generator and bus bar under various
conditions are:
Prefault 0.5 Pu
During Fault 1.0 Pu
Post fault 0.75 Pu
Calculate the swing curve using intervals of 0.05 sec and assuming that the fault is cleared at 0.15
sec. (AP)
8. Find the critical clearing angle and time for clearing the fault with simultaneous opening of the breakers
when a three phase fault occurs at point P close to bus 1 as shown in Fig. The generator is delivering
1.0 p.u power at the instant proceding the fault. (E) (Nov/ Dec 2016)

9. A generator is operating at 50 Hz delivers 1.0 p.u power to an infinite bus through a transmission circuit
in which resistance is ignored. A fault takes place reducing the maximum power transferable to 0.5
p.u. Before the fault, this power was 2.0 p.u and after the clearance of the fault it is 1.5 p.u. By the use
of equal area criterion determine the critical clearing angle. (AP)
(April/ May 2016)
10. Discuss the method by which transient stability can be improved. (U) (April/ May 2016)
11. A Synchronous motor is receiving 30% of the power that is capable of receiving from an infinite bus.
If the load on the motor is doubled calculate the maximum value of δ during the swinging of the motor
around its new equilibrium position. (AP) (Nov/ Dec 2015)
12. The moment of inertia of a 4 pole, 100 mVA, 11 kV, 3 Ф, 0.8 power factor, 50 Hz turbo alternator is
10000kg-m2. Calculate H and M. (AP)
(May/ June 2015)
Reg. No:

PANIMALAR ENGINEERING COLLEGE


An Autonomous Institution, Affiliated to Anna University,
Chennai
CHENNAI -600 123

B.E./ B.Tech. DEGREE END SEMESTER


EXAMINATIONSNOVEMBER/DECEMBER 2021
Fifth Semester
Electrical and Electronics Engineering
EE8501 – POWER SYSTE ANALYSIS
(Regulation 2017)
Time : Three hours Maximum : 100 Marks

Answer ALL Questions


PART A (10×2=20 Marks)
1. What are the components of power system?

2. Write the equation for per unit impedance.


3. What is the need for load flow study?
4. Why is it necessary to use acceleration factor in Gauss Seidal method of load flow studies?
5. What is the need for short circuit studies?
6. Name the faults in which all the three sequence component currents are equal and in
whichpositive and negative sequence currents together is equal to zero sequence
currents.
7. What is the significance of ‘a’ operator?
8. Write the symmetrical components of three phase system.
9. What is an infinite bus?
10. Write the swing equation and explain the terms involved in it.

PART – B (5x13 = 65 Marks)


(13)
11. a. Examine the reactance diagram for the Power system shown in fig. Neglect
resistance and use a base of 100MVA, 220kV in j50 ohms line. The
ratings of the generator motor and transformer are given below.
Generator: 40MVA, 25KV, X’’ =20%.
Synchronous Motor: 50MVA, 11KV, X’’ =30%
T1: Y-Y transformer : 40MVA , 33/220KV,
X=15%T2:Y- Y transformer : 30 MVA
11/220KV, X=15%
(OR) (13)

b. A 300 MVA , 20KV, 3Φ generator has a reactance of 25%.The generator


supplies two motors through transformer and transmission line as shown in
fig. The transformer T1 isa 3Φ transformer, 350 MVA, 20/230 KV, 10%
reactance.
The transformer T2 is composed of 3 single phase units eachrated, 100 MVA,
127/13.2 KV, with 10% reactance. The connection of T1 and T2 are shown
fig. The motors are rated at 200 MVA and 100 MVA both 13.2KV and 20%
reactance.
Taking the generator rating as base.Draw reactance diagram. Reactance of
the line is j0.5Ω with 64km lomg.

12 a. The load flow data for a 4 bus system shown in figure is given in table with (13)
bus 1 as slack. Determine voltages at the end of I iteration using Gauss Seidal
method with α=1.6.

Bus P in Q in V in p.u Remarks


p.u p.u
1 - - 1.06∟0o Slack bus
2 0.5 0.2 1pu PQ bus
3 0.4 0.3 1pu PQ bus
4 0.3 0.1 1pu PQ bus

(OR)

b. Derive N-R method of load flow algorithm and explain the implementation of this (13)
algorithm with the flowchart.

13 a. Determine Zbus for a 3 bus system as shown in figure where impedances are shown
(13)
and values are in p.u.
(OR)

b. A symmetrical fault occurs on bus 4 of system shown in figure, Compute the (13)
faultcurrent, post fault voltages and line current.
Generator G1 ,G2 :100MVA,20KV,X1=15%. ;
Transformer T1, T2:, Xleak=9%,
Transmission line L1,L2:
X1=10%

(13)

14 a. A salient pole generator without dampers is rated 25 MVA, 13.2 KV and has
direct axis sub – transient reactance of 0.2 per unit. The negative and zero
sequence reactances are 0.35 and 0.1 per unitrespectively. The neutral of the
generator is solidly grounded.Determine the sub transient current in the
generator and the line to line voltage for sub transient conditions when a
single line to ground fault occurs at terminals of an unloaded generator.
(13)
(OR)

b. Derive the expression for fault current in line to line fault on unloaded
generator. Draw an equivalent network showing the inter connection of
networks to simulate line to linefault

15. a. Derive the expression for Swing Equation. (13)

(OR)

b. Derivethe critical clearing angle and critical clearing time for transient stability. (13)

PART – C (1x15 = 15 Marks)

16 a. Derive the expression for fault current in double line to ground fault on (15)
unloaded generator. Draw an equivalent network showing the inter
connection of networks to simulate double line to ground fault.

b. The one line diagram of a 3Ø power system is shown in figure. Select a (15)
commonbase of 100MVA and 20kV on the geenerator side. Draw an
impedance diagram.
G1: 85 MVA; 20kV; X’’ = 16%
T1: 60 MVA; 20/220 kV; X’’ =
10%T2: 50 MVA; 220/11 kV; X’’
= 5% T3: 50 MVA; 20/110 kV; X’’
= 7% T4: 40 MVA; 110/11 kV; X’’
= 9% M: 65 MVA; 10.5 kV; X’’ =
17.7%
The 3Ø load at bus 4 absorbs 62 MVA, 0.8 pf lagging at 10.5 kV, line 1
andline 2 reactance of 45Ω and 60Ω respectively.

**********
1st Semester Anna University EEE- Reg 2021
Professional English – I
2nd Semester 3rd Semester
Matrices and Calculus
Probability and Complex
Professional English - II Functions
Engineering Physics
Statistics and Numerical Electromagnetic Fields
Engineering Chemistry Methods
Problem Solving and Physics for Electrical Digital Logic Circuits
Python Programming Engineering
Electron Devices and
Physics and Chemistry Basic Civil and Mechanical Circuits
Laboratory Engineering
Electrical Machines - I
Engineering Graphics
C Programming and Data
4th Semester Electric Circuit Analysis Structures
Environmental Sciences
and Sustainability 6th Semester
Transmission and 5th Semester
Distribution Protection and
Linear Integrated Power System Analysis Switchgear
Circuits
Power Electronics Power System
Measurements and Operation and Control
Instrumentation Control Systems
Open Elective – I
Microprocessor and
Microcontroller Professional Elective I
Professional Elective IV
Electrical Machines - II Professional Elective II
Professional Elective V
Professional Elective III
7th Semester Professional Elective VI
High Voltage Mandatory Course-I& Mandatory Course-
Engineering II& MC
Human Values and 8th Semester
Ethics
Elective –
Management Project Work /
Internship
Open Elective – II
Open Elective – III
Open Elective – IV
Professional Elective
VII Click on Clouds to navigate other department

https://www.poriyaan.in/

You might also like