Download as pdf or txt
Download as pdf or txt
You are on page 1of 102

APPENDIX-A

EQUIPMENT SCHEDULE
APPENDIX-B
Pre Startup Checklist
Must be completed, signed and provided to Daikin at atleast 2 weeks prior to startup request date

Job Details

Job name
Installation address
Purchasing contractor
Number of unit on site
Chiller model no.
Chiller serial no.
Chilled Water System Yes No N/A Remarks
Chiller installed as per IOM recommendation
Piping Completed
Water system flushed bypassing evaporator, filled & vented
Pumps installed and operational (rotation checked, strainers cleaned)
Controls operational (3-way valves, face/bypass dampers, bypass valves, etc.)
Water system operated and tested; flow meets unit design requirements
Strainer installed before evaporator inlet
Water flow switch installed as per recommendations
Condenser Water System (Water-cooled units)
Piping Completed
Water system flushed bypassing evaporator, filled & vented
Pumps installed and operational (rotation checked, strainers cleaned)
Controls (3-way valves, bypass valves, etc.) operable
Water system operated and flow balance to meet unit design requirements
Strainer installed in between Condenser inlet and Pump
Strainer installed before condenser inlet.
Water flow switch installed as per recommendations
Electrical
Power leads have been checked for proper phasing & terminates to chiller main switch
All interlock wiring complete and compliant with Daikin specifications
Pump starter and interlocks wired
Cooling tower fans and controls wired(For water cooled unit)
Incoming wire Details (size and Number of conductors) to Chiller Electrical isolator
Miscellaneous
Thermometers, wells, gauges, control, Flow switch etc., installed
Minimum system load of 80% capacity available for testing/adjusting controls
Warning: Under no condition should these units be started prior to authorize start-up by Daikin Service. Failure to follow this
warning may result in serious equipment damage All installation work has been completed as checked above, the system has been
inspected and unit is/will be ready for startup by__________________

Contractor Representative:
Name: _____________________
Sign:_ ____________________
Date:______________________
Phone/Email:_________________ Contractor Company stamp_____________

DAME/MB/PSC/REV02
APPENDIX-C
Power Quality Guidelines
Daikin strongly recommend to commission units on permanent electrical power supply as high risk
always associated with fluctuating frequency, voltage & other related parameters which might
affect adversely. However due to unavoidable circumstances if the contractor/customer still wishes
to operate on generator power ensure following guidelines:

Generator Made
Generator Type
Generator VA rating

S.no Unit Model Unit Serial

 Generator should be able to take Initial Starting current / maximum current of chiller without
dipping the voltage ( + /- 10% ).
 Voltage imbalance between phases shouldn’t be more than ± 2%
 Input Voltage and Frequency to chiller should be consistent during operation and within
design limit of chillers.
 No phase change allowed, once the chiller commissioned on Generator.
 Any input voltage, frequency deviation should be closely monitored.
 Harmonics distortion should be ≤5%

Failing to maintain the above shall effect the performance & reliability of the chillers, any breakdown
due to the above shall not be covered by standard warranty.

Thanking you and assuring you of our best attention at all times

Contractor Representative:

Name: _____________________
Sign:_ ____________________
Date:______________________
Phone/Email:_________________ Contractor Company stamp_____________

DAME/MB/PSC/REV02
APPENDIX-D
Specification Compliances for CHILLER STARTUP SERVICE (SECTION 23 64 26.13 Section 3.4 )
Sl No Specification Compliances
A Engage a factory-authorized service representative to comply
perform startup service.
B Inspect field-assembled components, equipment comply
installation, and piping and electrical connections for
proper assemblies, installations, and connections.
C Complete installation and startup checks according to comply
manufacturer's written instructions and perform the
following:
1. Verify that refrigerant charge is sufficient and comply
chiller has been leak tested.
2. Verify that pumps are installed and functional.
3. Verify that thermometers and gages are installed.
4. Operate chiller for run-in period according to
manufacturer's written instructions.
5. Check bearing lubrication and oil levels.
6. Verify proper motor rotation.
7. Verify static deflection of vibration isolators,
including deflection during chiller startup and
shutdown.
8. Verify and record performance of chilled water
flow and low-temperature interlocks.
9. Verify and record performance of chiller
protection devices.
10. Test and adjust controls and safeties. Replace
damaged or malfunctioning controls and
equipment.

D Prepare a written startup report that records results of comply


tests and inspections.

DEMONSTRATION

A Engage a factory-authorized service representative to comply


train Owner's maintenance personnel to adjust, operate,
and maintain chillers.
APPENDIX-E
H J L L \ T

  

  

! $

' * ' / 1 ' 1 1 ;

' A E '

           
          
APPENDIX-F
Customer reference chiller#____

Chiller Start-up Form


Screw/Scroll Compressor
(EWAD/ERAD/AWS/MNG/ACZC/EWAQ/EWWD)

Job Details

Job name
Installation address
Purchasing contractor
Startup Engineer / Technician
Chiller Application
Number of unit on site
Startup date
SOR number

Unit Information

Model number Serial number Refrigerant Type/Charge


Chiller
Evaporator NA
Compressor#01
Compressor#02
Compressor#03
Controller S/w ver.
Controller Bsp ver.
Starter Type

Measured Parameters

Water temperature (in/out) ◦C


Nominal water flow rate – Cooling Litre/Sec
Nominal Water pressure drop – Cooling Kpa
Design Ambient Temperature ◦C

DAME/MB/SF/Screw/REV_03 P a g e |1
DAME/MB/SF/Screw/REV_03 P a g e |2
Actual operating parameters

Parameter Unit Circuit#01 Circuit#02 Circuit#03


Mode
Leaving water temperature set point ⁰C
Pressure drop across evaporator Kpa
Ambient Temperature ⁰C
Entering Chilled Water Temperature ⁰C
Leaving Chilled Water Temperature ⁰C
Entering Condenser Water Temperature ⁰C
Leaving Condenser Water Temperature ⁰C
Unit Load %
Compressor Load %
Evaporator Pressure Kpa
Condenser Pressure Kpa
Evaporator Saturation Temperature ⁰C
Condenser Saturation Temperature ⁰C
Suction Temperature ⁰C
Discharge Temperature ⁰C
Suction Superheat Temperature ⁰C
Discharge Superheat Temperature ⁰C
Evaporator Approach Temperature ⁰C
Condenser Approach Temperature ⁰C
Oil Pressure Kpa
Oil Differential Pressure Kpa
Electronic Expansion valve position %
Econ SV output On/off
Liquid Injection output On/off
Sub cooling (before econ. & disabled) ⁰C
Operating run hours
No of starts

Phase Line voltage @ Line voltage Crank case heater ampere(A)


0% load(V) @full load(V)
L1-L2 Circuit#01
L2-L3 Circuit#02
L3-L1 Circuit#03
NOTE: Parameters should be recorded Line Current(A)
@100% load if possible. L1 L2 L3
Compressor#01
Compressor#02
Compressor#03
DAME/MB/SF/Screw/REV_03 P a g e |3
Remarks (Include any system or chiller control information pertaining to jobs)

____________________________________________________________________
____________________________________________________________________
____________________________________________________________________
____________________________________________________________________
____________________________________________________________________
____________________________________________________________________
____________________________________________________________________
____________________________________________________________________
____________________________________________________________________
____________________________________________________________________
____________________________________________________________________

Mechanical Contractor signature:…………………………….………..Date:……………......


Electrical Contractor signature:………………………………….……..Date:………………..
Daikin Engineer/Technician signature:………………………………..Date:………………..
Daikin applied service manager:……………………………………… Date:………………..

DAME/MB/SF/Screw/REV_03 P a g e |4
APPENDIX-G
Chiller Safety Test Report

1. High Pressure Alarm

SI. No. Running Condition Pressure Reading in Panel Remarks


( Kpa )
1. Normal Operation No Alarm

2. High Pressure Operation Alarm Raised

Crieteria : High Pressure Alarm Set Point : xx Kpa

Result :
Pass Fail
2. Low Pressure Alarm

SI. No. Running Condition Pressure Reading in Panel Remarks


( Kpa )
1. Normal Operation No Alarm

2. Low Pressure Operation Alarm Raised

Criteria : Low Pressure Alarm set Point : xx Kpa

Result :
Pass Fail

3. Rapid Restart Test

Sequence Chiller Status Time

1. Power Off

2. Power ON + Water Flow


Established
3. Chiller ON

Criteria : Time from Power on and Water Flow Establish to Chiller Start = 35 Secs

Result :
Pass Fail
Customer ref. chiller#________
Date: _____________________

Loss of Flow Test Form

Job Details
Job name Location
Unit Model no. Unit Serial no.

Methodology: The scope is to test the “loss of flow” or “no flow safety” of chiller. Once the
chiller is running smoothly, the water flow to the chiller is manually stopped via the pumps.
The chiller will sense “no flow “via the flow switch located across the evaporator line. The
alarm will be raised and chiller will be “OFF” due to loss of flow. The microtech panel will
reflect the error code.

Test Yes/NO
Pump off, Flow loss Alarm in Panel

Test Result: Test has been _______________

Comments & observations:


_____________________________________________________________________________
______________________________________________________________________________
______________________________________________________________________________

I acknowledge that all works carried out as detailed with my satisfaction.

On behalf of Daikin On behalf of Client

Engineer/Technician Name: ______________ Client Name:________________

Signature: _____________________________ Signature:__________________

Date: _________________________________ Date:______________________


APPENDIX-H
SAFETY DATA SHEET
Halocarbon 134a (1,1,1,2-Tetrafluoroethane)

Section 1. Identification
GHS product identifier : Halocarbon 134a (1,1,1,2-Tetrafluoroethane)
Chemical name : 1,1,1,2-Tetrafluorethane
Other means of : ASPEN R134a, 1,1,1,2-Tetrafluoroethane; Ethane, 1,1,1,2-tetrafluoro-; 1,1,1,
identification 2-Tetrafluoroethane (Refrigerant gas R134A); HFC 134a; HCF 134a; HCFC-134a
Product use : Synthetic/Analytical chemistry.Refrigeration.
Synonym : ASPEN R134a, 1,1,1,2-Tetrafluoroethane; Ethane, 1,1,1,2-tetrafluoro-; 1,1,1,
2-Tetrafluoroethane (Refrigerant gas R134A); HFC 134a; HCF 134a; HCFC-134a
SDS # : 001055
Supplier's details : Airgas USA, LLC and its affiliates
259 North Radnor-Chester Road
Suite 100
Radnor, PA 19087-5283
1-610-687-5253

24-hour telephone : 1-866-734-3438

Section 2. Hazards identification


OSHA/HCS status : This material is considered hazardous by the OSHA Hazard Communication Standard
(29 CFR 1910.1200).
Classification of the : GASES UNDER PRESSURE - Liquefied gas
substance or mixture

GHS label elements


Hazard pictograms :

Signal word : Warning


Hazard statements : Contains gas under pressure; may explode if heated.
May cause frostbite.
Precautionary statements
General : Read and follow all Safety Data Sheets (SDS’S) before use. Read label before use.
Keep out of reach of children. If medical advice is needed, have product container or
label at hand. Close valve after each use and when empty. Use equipment rated for
cylinder pressure. Do not open valve until connected to equipment prepared for use.
Use a back flow preventative device in the piping. Use only equipment of compatible
materials of construction. Always keep container in upright position.
Prevention : Use and store only outdoors or in a well ventilated place.
Response : Not applicable.
Storage : Protect from sunlight when ambient temperature exceeds 52°C/125°F. Store in a well-
ventilated place.
Disposal : Not applicable.
Hazards not otherwise : Liquid can cause burns similar to frostbite.
classified

Date of issue/Date of revision : 5/27/2016 Date of previous issue : No previous validation Version : 0.01 1/11
Halocarbon 134a (1,1,1,2-Tetrafluoroethane)

Section 3. Composition/information on ingredients


Substance/mixture : Substance
Chemical name : 1,1,1,2-Tetrafluorethane
Other means of : ASPEN R134a, 1,1,1,2-Tetrafluoroethane; Ethane, 1,1,1,2-tetrafluoro-; 1,1,1,
identification 2-Tetrafluoroethane (Refrigerant gas R134A); HFC 134a; HCF 134a; HCFC-134a

CAS number/other identifiers


CAS number : 811-97-2
Product code : 001055
Ingredient name % CAS number
1,1,1,2 - tetrafluoroethane 100 811-97-2
Any concentration shown as a range is to protect confidentiality or is due to batch variation.
There are no additional ingredients present which, within the current knowledge of the supplier and in the
concentrations applicable, are classified as hazardous to health or the environment and hence require reporting
in this section.
Occupational exposure limits, if available, are listed in Section 8.

Section 4. First aid measures


Description of necessary first aid measures
Eye contact : Immediately flush eyes with plenty of water, occasionally lifting the upper and lower
eyelids. Check for and remove any contact lenses. Continue to rinse for at least 10
minutes. Get medical attention if irritation occurs.
Inhalation : Remove victim to fresh air and keep at rest in a position comfortable for breathing. If
not breathing, if breathing is irregular or if respiratory arrest occurs, provide artificial
respiration or oxygen by trained personnel. It may be dangerous to the person providing
aid to give mouth-to-mouth resuscitation. Get medical attention if adverse health effects
persist or are severe. If unconscious, place in recovery position and get medical
attention immediately. Maintain an open airway. Loosen tight clothing such as a collar,
tie, belt or waistband.
Skin contact : Flush contaminated skin with plenty of water. Remove contaminated clothing and
shoes. Get medical attention if symptoms occur. In case of contact with liquid, warm
frozen tissues slowly with lukewarm water and get medical attention. Do not rub
affected area. Wash clothing before reuse. Clean shoes thoroughly before reuse.
Ingestion : Remove victim to fresh air and keep at rest in a position comfortable for breathing. Get
medical attention if adverse health effects persist or are severe. Ingestion of liquid can
cause burns similar to frostbite. If frostbite occurs, get medical attention. Never give
anything by mouth to an unconscious person. If unconscious, place in recovery position
and get medical attention immediately. Maintain an open airway. Loosen tight clothing
such as a collar, tie, belt or waistband. As this product rapidly becomes a gas when
released, refer to the inhalation section.

Most important symptoms/effects, acute and delayed


Potential acute health effects
Eye contact : Liquid can cause burns similar to frostbite.
Inhalation : No known significant effects or critical hazards.
Skin contact : Dermal contact with rapidly evaporating liquid could result in freezing of the tissues or
frostbite.
Frostbite : Try to warm up the frozen tissues and seek medical attention.
Ingestion : Ingestion of liquid can cause burns similar to frostbite.
Over-exposure signs/symptoms
Eye contact : Adverse symptoms may include the following:, frostbite
Inhalation : No specific data.
Skin contact : Adverse symptoms may include the following:, frostbite
Ingestion : Adverse symptoms may include the following:, frostbite
Date of issue/Date of revision : 5/27/2016 Date of previous issue : No previous validation Version : 0.01 2/11
Halocarbon 134a (1,1,1,2-Tetrafluoroethane)

Section 4. First aid measures

Indication of immediate medical attention and special treatment needed, if necessary


Notes to physician : Treat symptomatically. Contact poison treatment specialist immediately if large
quantities have been ingested or inhaled.
Specific treatments : No specific treatment.
Protection of first-aiders : No action shall be taken involving any personal risk or without suitable training. It may
be dangerous to the person providing aid to give mouth-to-mouth resuscitation.

See toxicological information (Section 11)

Section 5. Fire-fighting measures


Extinguishing media
Suitable extinguishing : Use an extinguishing agent suitable for the surrounding fire.
media
Unsuitable extinguishing : None known.
media

Specific hazards arising : Contains gas under pressure. In a fire or if heated, a pressure increase will occur and
from the chemical the container may burst or explode.
Hazardous thermal : Decomposition products may include the following materials:
decomposition products carbon dioxide
carbon monoxide
halogenated compounds

Special protective actions : Promptly isolate the scene by removing all persons from the vicinity of the incident if
for fire-fighters there is a fire. No action shall be taken involving any personal risk or without suitable
training. Contact supplier immediately for specialist advice. Move containers from fire
area if this can be done without risk. Use water spray to keep fire-exposed containers
cool.
Special protective : Fire-fighters should wear appropriate protective equipment and self-contained breathing
equipment for fire-fighters apparatus (SCBA) with a full face-piece operated in positive pressure mode. For
incidents involving large quantities, thermally insulated undergarments and thick textile
or leather gloves should be worn.

Section 6. Accidental release measures


Personal precautions, protective equipment and emergency procedures
For non-emergency : No action shall be taken involving any personal risk or without suitable training.
personnel Evacuate surrounding areas. Keep unnecessary and unprotected personnel from
entering. Do not touch or walk through spilled material. Avoid breathing gas. Provide
adequate ventilation. Wear appropriate respirator when ventilation is inadequate. Put
on appropriate personal protective equipment.
For emergency responders : If specialised clothing is required to deal with the spillage, take note of any information
in Section 8 on suitable and unsuitable materials. See also the information in "For non-
emergency personnel".

Environmental precautions : Ensure emergency procedures to deal with accidental gas releases are in place to avoid
contamination of the environment. Avoid dispersal of spilled material and runoff and
contact with soil, waterways, drains and sewers. Inform the relevant authorities if the
product has caused environmental pollution (sewers, waterways, soil or air).

Methods and materials for containment and cleaning up


Small spill : Immediately contact emergency personnel. Stop leak if without risk.
Large spill : Immediately contact emergency personnel. Stop leak if without risk. Note: see Section
1 for emergency contact information and Section 13 for waste disposal.

Date of issue/Date of revision : 5/27/2016 Date of previous issue : No previous validation Version : 0.01 3/11
Halocarbon 134a (1,1,1,2-Tetrafluoroethane)

Section 7. Handling and storage


Precautions for safe handling
Protective measures : Put on appropriate personal protective equipment (see Section 8). Contains gas under
pressure. Do not get in eyes or on skin or clothing. Avoid breathing gas. Empty
containers retain product residue and can be hazardous. Do not puncture or incinerate
container. Use equipment rated for cylinder pressure. Close valve after each use and
when empty. Protect cylinders from physical damage; do not drag, roll, slide, or drop.
Use a suitable hand truck for cylinder movement.

Advice on general : Eating, drinking and smoking should be prohibited in areas where this material is
occupational hygiene handled, stored and processed. Workers should wash hands and face before eating,
drinking and smoking. Remove contaminated clothing and protective equipment before
entering eating areas. See also Section 8 for additional information on hygiene
measures.

Conditions for safe storage, : Store in accordance with local regulations. Store in a segregated and approved area.
including any Store away from direct sunlight in a dry, cool and well-ventilated area, away from
incompatibilities incompatible materials (see Section 10). Keep container tightly closed and sealed until
ready for use. Cylinders should be stored upright, with valve protection cap in place,
and firmly secured to prevent falling or being knocked over. Cylinder temperatures
should not exceed 52 °C (125 °F).

Section 8. Exposure controls/personal protection


Control parameters
Occupational exposure limits
Ingredient name Exposure limits
1,1,1,2 - tetrafluoroethane AIHA WEEL (United States, 10/2011).
TWA: 1000 ppm 8 hours.

Appropriate engineering : Good general ventilation should be sufficient to control worker exposure to airborne
controls contaminants.
Environmental exposure : Emissions from ventilation or work process equipment should be checked to ensure
controls they comply with the requirements of environmental protection legislation. In some
cases, fume scrubbers, filters or engineering modifications to the process equipment
will be necessary to reduce emissions to acceptable levels.

Individual protection measures


Hygiene measures : Wash hands, forearms and face thoroughly after handling chemical products, before
eating, smoking and using the lavatory and at the end of the working period.
Appropriate techniques should be used to remove potentially contaminated clothing.
Wash contaminated clothing before reusing. Ensure that eyewash stations and safety
showers are close to the workstation location.
Eye/face protection : Safety eyewear complying with an approved standard should be used when a risk
assessment indicates this is necessary to avoid exposure to liquid splashes, mists,
gases or dusts. If contact is possible, the following protection should be worn, unless
the assessment indicates a higher degree of protection: safety glasses with side-
shields.
Skin protection
Hand protection : Chemical-resistant, impervious gloves complying with an approved standard should be
worn at all times when handling chemical products if a risk assessment indicates this is
necessary. If contact with the liquid is possible, insulated gloves suitable for low
temperatures should be worn. Considering the parameters specified by the glove
manufacturer, check during use that the gloves are still retaining their protective
properties. It should be noted that the time to breakthrough for any glove material may
be different for different glove manufacturers. In the case of mixtures, consisting of
several substances, the protection time of the gloves cannot be accurately estimated.

Date of issue/Date of revision : 5/27/2016 Date of previous issue : No previous validation Version : 0.01 4/11
Halocarbon 134a (1,1,1,2-Tetrafluoroethane)

Section 8. Exposure controls/personal protection


Body protection : Personal protective equipment for the body should be selected based on the task being
performed and the risks involved and should be approved by a specialist before
handling this product.
Other skin protection : Appropriate footwear and any additional skin protection measures should be selected
based on the task being performed and the risks involved and should be approved by a
specialist before handling this product.
Respiratory protection : Use a properly fitted, air-purifying or air-fed respirator complying with an approved
standard if a risk assessment indicates this is necessary. Respirator selection must be
based on known or anticipated exposure levels, the hazards of the product and the safe
working limits of the selected respirator.

Section 9. Physical and chemical properties


Appearance
Physical state : Gas. [Liquefied compressed gas.]
Color : Colorless.
Molecular weight : 102.04 g/mole
Molecular formula : C2-H2-F4
Boiling/condensation point : -26°C (-14.8°F)
Melting/freezing point : -108°C (-162.4°F)
Critical temperature : 100.9°C (213.6°F)

Odor : Faint ethereal odor


Odor threshold : Not available.
pH : Neutral.
Flash point : [Product does not sustain combustion.]
Burning time : Not applicable.
Burning rate : Not applicable.
Evaporation rate : Not available.
Flammability (solid, gas) : Not available.
Lower and upper explosive : Not available.
(flammable) limits
Vapor pressure : 81.3 (psig)
Vapor density : 3.5 (Air = 1)
Specific Volume (ft /lb) 3
: 3.7078
Gas Density (lb/ft ) 3
: 0.2697 (25°C / 77 to °F)
Relative density : Not applicable.
Solubility : Not available.
Solubility in water : 1 g/l
Partition coefficient: n- : 1.06
octanol/water
Auto-ignition temperature : >743°C (>1369.4°F)
Decomposition temperature : Not available.
SADT : Not available.
Viscosity : Not applicable.

Date of issue/Date of revision : 5/27/2016 Date of previous issue : No previous validation Version : 0.01 5/11
Halocarbon 134a (1,1,1,2-Tetrafluoroethane)

Section 10. Stability and reactivity


Reactivity : No specific test data related to reactivity available for this product or its ingredients.

Chemical stability : The product is stable.

Possibility of hazardous : Under normal conditions of storage and use, hazardous reactions will not occur.
reactions

Conditions to avoid : No specific data.

Incompatible materials : No specific data.

Hazardous decomposition : Under normal conditions of storage and use, hazardous decomposition products should
products not be produced.

Hazardous polymerization : Under normal conditions of storage and use, hazardous polymerization will not occur.

Section 11. Toxicological information


Information on toxicological effects
Acute toxicity
Product/ingredient name Result Species Dose Exposure
1,1,1,2 - tetrafluoroethane LC50 Inhalation Vapor Rat 1500 g/m³ 4 hours

Irritation/Corrosion
Not available.
Sensitization
Not available.

Mutagenicity
Not available.

Carcinogenicity
Not available.
Reproductive toxicity
Not available.

Teratogenicity
Not available.

Specific target organ toxicity (single exposure)


Not available.
Specific target organ toxicity (repeated exposure)
Not available.
Aspiration hazard
Not available.

Information on the likely : Not available.


routes of exposure
Potential acute health effects
Eye contact : Liquid can cause burns similar to frostbite.
Inhalation : No known significant effects or critical hazards.
Date of issue/Date of revision : 5/27/2016 Date of previous issue : No previous validation Version : 0.01 6/11
Halocarbon 134a (1,1,1,2-Tetrafluoroethane)

Section 11. Toxicological information


Skin contact : Dermal contact with rapidly evaporating liquid could result in freezing of the tissues or
frostbite.
Ingestion : Ingestion of liquid can cause burns similar to frostbite.

Symptoms related to the physical, chemical and toxicological characteristics


Eye contact : Adverse symptoms may include the following:, frostbite
Inhalation : No specific data.
Skin contact : Adverse symptoms may include the following:, frostbite
Ingestion : Adverse symptoms may include the following:, frostbite

Delayed and immediate effects and also chronic effects from short and long term exposure
Short term exposure
Potential immediate : Not available.
effects
Potential delayed effects : Not available.
Long term exposure
Potential immediate : Not available.
effects
Potential delayed effects : Not available.
Potential chronic health effects
Not available.
General : No known significant effects or critical hazards.
Carcinogenicity : No known significant effects or critical hazards.
Mutagenicity : No known significant effects or critical hazards.
Teratogenicity : No known significant effects or critical hazards.
Developmental effects : No known significant effects or critical hazards.
Fertility effects : No known significant effects or critical hazards.

Numerical measures of toxicity


Acute toxicity estimates
Not available.

Section 12. Ecological information


Toxicity
Not available.

Persistence and degradability


Not available.

Bioaccumulative potential
Product/ingredient name LogPow BCF Potential
1,1,1,2 - tetrafluoroethane 1.06 - low

Mobility in soil
Soil/water partition : Not available.
coefficient (KOC)

Date of issue/Date of revision : 5/27/2016 Date of previous issue : No previous validation Version : 0.01 7/11
Halocarbon 134a (1,1,1,2-Tetrafluoroethane)

Section 12. Ecological information


Other adverse effects : No known significant effects or critical hazards.

Section 13. Disposal considerations


Disposal methods : The generation of waste should be avoided or minimized wherever possible. Disposal
of this product, solutions and any by-products should at all times comply with the
requirements of environmental protection and waste disposal legislation and any
regional local authority requirements. Dispose of surplus and non-recyclable products
via a licensed waste disposal contractor. Waste should not be disposed of untreated to
the sewer unless fully compliant with the requirements of all authorities with jurisdiction.
Empty Airgas-owned pressure vessels should be returned to Airgas. Waste packaging
should be recycled. Incineration or landfill should only be considered when recycling is
not feasible. This material and its container must be disposed of in a safe way. Empty
containers or liners may retain some product residues. Do not puncture or incinerate
container.

Section 14. Transport information


DOT TDG Mexico IMDG IATA
UN number UN3159 UN3159 UN3159 UN3159 UN3159
UN proper 1,1,1, REFRIGERANT GAS REFRIGERANT GAS 1,1,1, REFRIGERANT GAS
2-TETRAFLUOROETHANE R 134A; OR 1,1,1, R 134A; OR 1,1,1, 2-TETRAFLUOROETHANE R 134A
shipping name OR REFRIGERANT 2-TETRAFLUOROETHANE 2-TETRAFLUOROETHANE (REFRIGERANT GAS
GAS R 134A R 134A)

Transport 2.2 2.2 2.2 2.2 2.2


hazard class(es)

Packing group - - - - -
Environment No. No. No. No. No.
Additional Limited quantity Product classified as - - Passenger and Cargo
Yes. per the following AircraftQuantity
information sections of the limitation: 75 kg
Packaging instruction Transportation of Cargo Aircraft Only
Passenger aircraft Dangerous Goods Quantity limitation: 150
Quantity limitation: 75 Regulations: 2.13-2.17 kg
kg (Class 2).

Cargo aircraft Explosive Limit and


Quantity limitation: 150 Limited Quantity Index
kg 0.125

Special provisions Passenger Carrying


T50 Road or Rail Index
75

“Refer to CFR 49 (or authority having jurisdiction) to determine the information required for shipment of the
product.”

Special precautions for user : Transport within user’s premises: always transport in closed containers that are
upright and secure. Ensure that persons transporting the product know what to do in the
event of an accident or spillage.

Transport in bulk according : Not available.


to Annex II of MARPOL
73/78 and the IBC Code

Date of issue/Date of revision : 5/27/2016 Date of previous issue : No previous validation Version : 0.01 8/11
Halocarbon 134a (1,1,1,2-Tetrafluoroethane)

Section 15. Regulatory information


U.S. Federal regulations : TSCA 8(a) CDR Exempt/Partial exemption: Not determined
United States inventory (TSCA 8b): This material is listed or exempted.

Clean Air Act Section 112 : Not listed


(b) Hazardous Air
Pollutants (HAPs)
Clean Air Act Section 602 : Not listed
Class I Substances
Clean Air Act Section 602 : Not listed
Class II Substances
DEA List I Chemicals : Not listed
(Precursor Chemicals)
DEA List II Chemicals : Not listed
(Essential Chemicals)
SARA 302/304
Composition/information on ingredients
No products were found.
SARA 304 RQ : Not applicable.
SARA 311/312
Classification : Sudden release of pressure
Composition/information on ingredients
Name % Fire Sudden Reactive Immediate Delayed
hazard release of (acute) (chronic)
pressure health health
hazard hazard
1,1,1,2 - tetrafluoroethane 100 No. Yes. No. No. No.

State regulations
Massachusetts : This material is not listed.
New York : This material is not listed.
New Jersey : This material is not listed.
Pennsylvania : This material is not listed.
International regulations
International lists
National inventory
Australia : This material is listed or exempted.
Canada : This material is listed or exempted.
China : This material is listed or exempted.
Europe : This material is listed or exempted.
Japan : This material is listed or exempted.
Malaysia : Not determined.
New Zealand : This material is listed or exempted.
Philippines : This material is listed or exempted.
Republic of Korea : This material is listed or exempted.
Taiwan : This material is listed or exempted.
Canada
WHMIS (Canada) : Class A: Compressed gas.

Date of issue/Date of revision : 5/27/2016 Date of previous issue : No previous validation Version : 0.01 9/11
Halocarbon 134a (1,1,1,2-Tetrafluoroethane)

Section 15. Regulatory information


CEPA Toxic substances: This material is listed.
Canadian ARET: This material is not listed.
Canadian NPRI: This material is listed.
Alberta Designated Substances: This material is not listed.
Ontario Designated Substances: This material is not listed.
Quebec Designated Substances: This material is not listed.

Section 16. Other information


Canada Label requirements : Class A: Compressed gas.
Hazardous Material Information System (U.S.A.)
Health 1

Flammability 1
Physical hazards 0

Caution: HMIS® ratings are based on a 0-4 rating scale, with 0 representing minimal hazards or risks, and 4
representing significant hazards or risks Although HMIS® ratings are not required on SDSs under 29 CFR 1910.
1200, the preparer may choose to provide them. HMIS® ratings are to be used with a fully implemented HMIS®
program. HMIS® is a registered mark of the National Paint & Coatings Association (NPCA). HMIS® materials
may be purchased exclusively from J. J. Keller (800) 327-6868.
The customer is responsible for determining the PPE code for this material.
National Fire Protection Association (U.S.A.)

1 Flammability
Health 2 0 Instability/Reactivity
Special

Reprinted with permission from NFPA 704-2001, Identification of the Hazards of Materials for Emergency
Response Copyright ©1997, National Fire Protection Association, Quincy, MA 02269. This reprinted material is
not the complete and official position of the National Fire Protection Association, on the referenced subject
which is represented only by the standard in its entirety.
Copyright ©2001, National Fire Protection Association, Quincy, MA 02269. This warning system is intended to
be interpreted and applied only by properly trained individuals to identify fire, health and reactivity hazards of
chemicals. The user is referred to certain limited number of chemicals with recommended classifications in
NFPA 49 and NFPA 325, which would be used as a guideline only. Whether the chemicals are classified by NFPA
or not, anyone using the 704 systems to classify chemicals does so at their own risk.
Procedure used to derive the classification
Classification Justification
Press. Gas Liq. Gas, H280 Expert judgment
History
Date of printing : 5/27/2016
Date of issue/Date of : 5/27/2016
revision
Date of previous issue : No previous validation
Version : 0.01
Key to abbreviations : ATE = Acute Toxicity Estimate
BCF = Bioconcentration Factor
GHS = Globally Harmonized System of Classification and Labelling of Chemicals
IATA = International Air Transport Association
IBC = Intermediate Bulk Container
IMDG = International Maritime Dangerous Goods
LogPow = logarithm of the octanol/water partition coefficient
MARPOL 73/78 = International Convention for the Prevention of Pollution From Ships,
1973 as modified by the Protocol of 1978. ("Marpol" = marine pollution)
Date of issue/Date of revision : 5/27/2016 Date of previous issue : No previous validation Version : 0.01 10/11
Halocarbon 134a (1,1,1,2-Tetrafluoroethane)

Section 16. Other information


UN = United Nations
References : Not available.
Indicates information that has changed from previously issued version.
Notice to reader
To the best of our knowledge, the information contained herein is accurate. However, neither the above-named
supplier, nor any of its subsidiaries, assumes any liability whatsoever for the accuracy or completeness of the
information contained herein.
Final determination of suitability of any material is the sole responsibility of the user. All materials may present
unknown hazards and should be used with caution. Although certain hazards are described herein, we cannot
guarantee that these are the only hazards that exist.

Date of issue/Date of revision : 5/27/2016 Date of previous issue : No previous validation Version : 0.01 11/11
APPENDIX-I
R A < = 4 8 > > 5 < : F 5 > A 7 @ 8 7 @ 9 A 9 4 8 : = ; 9 5 @ A < B S : A T 5 > A = ; > < 5 @ 6 > ; 9 8 A 7 :

! " # $ % # & $ ' ( # ) * + $ " , & - ! & ! . * / % . + * " + # / ) 0 1 $ 2

< 5 U 6 8 < 5 ; H 5 < 8 A ? 8 = 8 7 : H 5 = 9 8 A 7 F B ; 7 ; 6 9 4 A < 8 V 5 ? ; @ 5 7 = B Q K > 5 ; : 5

* 1 1 ( # * / & ! . 0 / % ! " 1 " ! . . 0 " !

= 4 5 = W X 8 9 4 B A 6 < > A = ; > < 5 U 6 8 < 5 T 5 7 9 : Q

3 4 5 6 7 8 9 : ; < 5 8 7 = > 6 ? 5 ? 8 7 = ; 9 5 @ A < B C D A E 9 4 5 = > ; : : 8 E 8 = ; 9 8 A 7

5 : 9 ; F > 8 : 4 5 ? F B 9 4 5 G 6 < A H 5 ; 7 I 8 < 5 = 9 8 5 K G I L M N O " N G P Q

Y Z [ \ ] ^ _ ` a b c d e ] f Z d e c ] e Z e g ] h i a j i Z f f ]

k d l c a m n g c d o d c d ] l # ] ] $ \ p q a e c r \ p w ] Z i \ p % x ] Z l

a e Z \
s t A 9 5 u v

s t A 9 5 O v

y ] e ] i Z \ &

z 5 ; ? 8 7 @ A E A H 5 < ; 9 8 7 @ ? ; 9 ; s t A 9 5 " v '

D 8 : 6 ; > 8 7 : H 5 = 9 8 A 7 A E 6 7 8 9 E A < ; 7 B ? ; T ; @ 5 ; 7 ? N A < > A A : 5 7 8 7 @ '

D 5 < 8 E 8 = ; 9 8 A 7 A E 9 4 5 < T ; > 8 7 : 6 > ; 9 8 A 7 8 7 9 5 @ < 8 9 B '

P > 5 ; 7 ; 7 ? H ; 8 7 9 X 4 5 < 5 7 5 = 5 : : ; < B '

{ 7 ; > B : 8 : A E X ; 9 5 < s ( v '

P 4 5 = W A E E > A X : X 8 9 = 4 A H 5 < ; 9 8 A 7 '

| \ ] g c i d g Z \ &

D 5 < 8 E 8 = ; 9 8 A 7 A E = A 7 9 < A > : 5 U 6 5 7 = 5 '

D 5 < 8 E B = A 7 9 ; = 9 A < X 5 ; < } z 5 H > ; = 5 8 E 7 5 = 5 : : ; < B '

D 5 < 8 E B 9 4 ; 9 ; > > 5 > 5 = 9 < 8 = ; > 9 5 < T 8 7 ; > : ; < 5 9 8 @ 4 9 } 3 8 @ 4 9 5 7 8 E 7 5 = 5 : : ; < B
'

P > 5 ; 7 8 7 : 8 ? 5 9 4 5 5 > 5 = 9 < 8 = ; > = A 7 9 < A > F A ; < ? '

D 8 : 6 ; > 8 7 : H 5 = 9 8 A 7 A E = A T H A 7 5 7 9 : E A < ; 7 B : 8 @ 7 : A E A 5 < 4 5 ; 9 8 7 @ '

D 5 < 8 E B A H 5 < ; 9 8 A 7 A E = A T H < 5 : : A < ; 7 ? 5 > 5 = 9 < 8 = ; > < 5 : 8 : 9 ; 7 = 5 '

~ 5 ; : 6 < 5 = A T H < 5 : : A < T A 9 A < 8 7 : 6 > ; 9 8 A 7 6 : 8 7 @ 9 4 5 ~ 5 @ @ 5 < '

` ] m i d j ] i Z c d a e g d i g b d c &

P 4 5 = W E A < ; 7 B < 5 E < 8 @ 5 < ; 7 9 > 5 ; W ; @ 5 '

D 5 < 8 E B < 5 E < 8 @ 5 < ; 7 9 E > A X 6 : 8 7 @ 9 4 5 > 8 U 6 8 ? : 8 @ 4 9 @ > ; : : }  8 @ 4 9 @ > ; : : E 6 > > '

D 5 < 8 E B E 8 > 9 5 < ? < B 5 < H < 5 : : 6 < 5 ? < A H '

D 5 < 8 E B A 8 > E 8 > 9 5 < H < 5 : : 6 < 5 ? < A H s t A 9 5 € v '

{ 7 ; > B : 5 = A T H < 5 : : A < 8 F < ; 9 8 A 7 : '

{ 7 ; > B : 5 = A T H < 5 : : A < A 8 > ; = 8 ? 8 9 B s M v '

 a e ‚ ] e l ] i l ] g c d a e &

P > 5 ; 7 = A 7 ? 5 7 : 5 < F ; 7 W : s t A 9 5 ƒ v '

D 5 < 8 E B 9 4 ; 9 E ; 7 : ; < 5 X 5 > > 9 8 @ 4 9 5 7 5 ? '

D 5 < 8 E B = A 7 ? 5 7 : 5 < F ; 7 W E 8 7 : } P A T F 8 E 7 5 = 5 : : ; < B '

) * + , - .

/ 0 1 * 2 + 3 4 5 6 7 + 8 9 8 + 8 , - 8 2 7 4 : ; , 6 4 4 + 3 , < , , = 4 5 * 2 , - 0

> 0 ? 3 , 6 2 2 : 6 4 @ * A , 6 A 4 5 - , 6 - * 2 B 6 7 + 8 9 8 + 8 , - 8 2 7 4 : ; , 6 4 4 < , , = 4 5 6 2 ; C * 2 + 3 4 5 6 7 + 8 9 8 + 8 , - 0

D 0 E 2 8 + * F , A 6 + 8 2 G 9 6 4 : , - - 3 * : 4 ; H , A , 6 ; * 2 6 ; 6 8 4 5 H 6 - 8 - + 3 : - = , , F 8 2 G 3 8 G 3 * H - , A 9 6 + 8 * 2 - + 6 2 ; 6 A ; - 0

I 0 J 2 , 2 9 8 A * 2 C , 2 + - < 8 + 3 6 3 8 G 3 7 * 2 7 , 2 + A 6 + 8 * 2 * K 6 8 A L H * A 2 , F 6 A + 8 7 4 , - M 8 + C 8 G 3 + H , 2 , 7 , - - 6 A 5 + * 7 4 , 6 2 + 3 , 7 * 2 ; , 2 - , A H 6 2 = C * A , * K + , 2 0

N 0 O , F 4 6 7 , + 3 , * 8 4 K 8 4 + , A < 3 , 2 + 3 , F A , - - : A , ; A * F 6 7 A * - - 8 + A , 6 7 3 , - > 0 P H 6 A 0

Q 0 R 3 , 7 = K * A 6 2 5 ; 8 - - * 4 9 , ; C , + 6 4 - 0

S 0 ? T ) @ ? * + 6 4 T 7 8 ; ) : C H , A B . P M / P . ) * 6 7 + 8 * 2

£ U , + < , , 2 P 0 / P 6 2 ; P 0 / V . O , F 4 6 7 , 6 2 + 8 L 6 7 8 ; K 8 4 + , A - 6 2 ; A , L 7 3 , 7 = 6 K + , A / P P P A : 2 2 8 2 G 3 * : A - 0 R * 2 + 8 2 : , + * A , F 4 6 7 , K 8 4 + , A -

: 2 + 8 4 + 3 , ? T ) 8 - 4 * < , A + 3 6 2 P 0 / P 0

P M / V . O , F 4 6 7 , * 8 4 M * 8 4 K 8 4 + , A 6 2 ; K 8 4 + , A ; A 5 , A 0 W , A 8 K 5 6 + A , G : 4 6 A 8 2 + , A 9 6 4 - 0

>

„ … 1 $ " + * / + # / 2 $ " … * + # $ / " ! ) * " % # / ) + - ! " ! 2 " # ) ! " * / +

‹ d l h a l Z \

0 . ! %

3 4 5 6 7 8 9 8 : T ; ? 5 A E T 5 9 ; > S H > ; : 9 8 = ; 7 ? 5 > 5 = 9 < A 7 8 = H ; < 9 : Q { > >

9 4 5 : 5 H ; < 9 : T 6 : 9 F 5 ? 8 : H A : 5 ? A E 8 7 ; = = A < ? ; 7 = 5 X 8 9 4 9 4 5 > A = ; >

3 4 8 : H < A ? 6 = 9 = A 7 9 ; 8 7 : E > 6 A < 8 7 ; 9 5 ? @ < 5 5 7 4 A 6 : 5 @ ; : 5 : = A 5 < 5 ?

< 5 @ 6 > ; 9 8 A 7 : 8 7 9 5 < T : A E ? 8 : H A : ; > Q

F B 9 4 5 † B A 9 A K < A 9 A = A > Q I A 7 A 9 5 7 9 @ ; : 5 : 8 7 9 A 9 4 5 ; 9 T A : H 4 5 < 5 Q

Π5 ; ? F ; 9 9 5 < 8 5 : T 6 : 9 F 5 = A > > 5 = 9 5 ? ; 7 ? : 5 7 9 9 A : H 5 = 8 E 8 = < 5 E 6 : 5

z 5 E < 8 @ 5 < ; 7 9 9 B H 5 ‡ z u " ƒ ;

= A > > 5 = 9 8 A 7 = 5 7 9 < 5 : Q

ˆ ‰ K s u v ; > 6 5 ‡ u " Š Š

 8 > T 6 : 9 F 5 = A > > 5 = 9 5 ? ; 7 ? : 5 7 9 9 A : H 5 = 8 E 8 = < 5 E 6 : 5 = A > > 5 = 9 8 A 7

s u v ˆ ‰ K X @ > A F ; > X ; < T 8 7 @ H A 9 5 7 9 8 ; >

= 5 7 9 < 5 : Q

3 4 5 < 5 E < 8 @ 5 < ; 7 9 U 6 ; 7 9 8 9 B 7 5 = 5 : : ; < B E A < : 9 ; 7 ? ; < ? A H 5 < ; 9 8 A 7 8 :

8 7 ? 8 = ; 9 5 ? A 7 9 4 5 6 7 8 9 7 ; T 5 H > ; 9 5 Q

z 5 ; > < 5 E < 8 @ 5 < ; 7 9 U 6 ; 7 9 8 9 B = 4 ; < @ 5 ? 8 7 9 4 5 6 7 8 9 8 : > 8 : 9 5 ? A 7 ; : 8 > 5 <

: 9 8 = W 5 < 8 7 : 8 ? 5 9 4 5 5 > 5 = 9 < 8 = ; > H ; 7 5 > Q

K 5 < 8 A ? 8 = ; > 8 7 : H 5 = 9 8 A 7 : E A < < 5 E < 8 @ 5 < ; 7 9 > 5 ; W : T ; B F 5 < 5 U 6 8 < 5 ?

? 5 H 5 7 ? 8 7 @ A 7 G 6 < A H 5 ; 7 A < > A = ; > > 5 @ 8 : > ; 9 8 A 7 Q

K > 5 ; : 5 = A 7 9 ; = 9 B A 6 < > A = ; > ? 5 ; > 5 < E A < T A < 5 8 7 E A < T ; 9 8 A 7 Q

Y Z [ \ ] ^ _ ` ^ a [ \ ^ b c d Z _ [ d ^ a ^ [ e ^ _ e e f c \ _ f b g c h g c \ c _ b ^ i [ _ e [ _ j f k k c g l Y Z c d f _ b c _ b d ^ _ _ f b i c Z c a e ^ \ c m h a [ d [ b a n f g [ ] h a [ d [ b a n j ` ^ g ^ _ b c c e ^ \ d f ] h a c b c o h g c d [ \ c f g g c a [ ^ i a c l p a a e ^ b ^ ^ _ e

\ h c d [ k [ d ^ b [ f _ \ d f _ b ^ [ _ c e Z c g c [ _ ] ^ n i c ] f e [ k [ c e q [ b Z f ` b _ f b [ d c l Y Z c e ^ b ^ d f ] ] ` _ [ d ^ b c e ^ b b Z c ] f ] c _ b f k b Z c f g e c g \ Z ^ a a Z f a e k [ g ] l

Y Z c ] ^ _ ` k ^ d b ` g c g \ Z ^ a a ^ \ \ ` ] c _ f a [ ^ i [ a [ b n q Z ^ b \ f c r c g k f g ^ _ n e [ g c d b f g [ _ e [ g c d b e ^ ] ^ j c o [ _ b Z c q [ e c \ b \ c _ \ c f k b Z c b c g ] o c _ \ ` [ _ j k g f ] f g d f _ _ c d b c e q [ b Z b Z c ` \ c ^ _ e s f g [ _ b c g h g c b ^ b [ f _

f k b Z [ \ ] ^ _ ` ^ a l

t c g c \ c g r c b Z c g [ j Z b b f ] ^ u c d Z ^ _ j c \ [ _ e c \ [ j _ ^ _ e d f _ \ b g ` d b [ f _ ^ b ^ _ n b [ ] c q [ b Z f ` b _ f b [ d c o b Z ` \ b Z c d f r c g h [ d b ` g c [ \ _ f b i [ _ e [ _ j l

! " # $ % & ' ' ( ' ) ! * ) " + ! * , * - (


APPENDIX-J
Technical Data Sheet
EWAD980C-PS
> Air cooled chiller
> Asymm Single Screw compressor
> Premium efficiency version
> Standard sound configuration
> R134a refrigerant

➔ Unit description: Daikin air-cooled chiller with single screw compressor and R134a refrigerant. Color: Ivory White
{Munsell code SY7.5/1) {±RAL7044).

➔ Compressor : single-screw type with gate-rotor made with the latest high-strength fibre reinforced star material.
The compressor has an asymmetric slide regulation managed by the unit controller for infinitely modulating
capacity from 100% to 25%. An integrated high efficiency oil separator maximizes the oil separation and standard
start is Wye-Delta (Y-�) type.

➔ Evaporator : New generation of direct expansion shell&tube evaporator with refrigerant evaporating inside the
tubes and water flowing outside. The tubes are enhanced for maximum heat transfer and rolled into steel tube
sheet and sealed. shell and tube manufactured according to 97/23/EC directive (PED).

➔ Condenser : internally enhanced seamless copper tubes arranged in a staggered row pattern and mechanically
expanded into lanced and rippled aluminum condenser fins with full fin collars. An integral sub-cooler circuit
provides sub-cooling to effectively eliminate liquid flashing and increase cooling capacity without increasing the
power input.

➔ Condenser coil fans : The condenser fans are propeller type with high efficiency design blades to maximize
performances. The material of the blades is glass reinforced resin and each fan is protected by a guard. Fan motors
are internally protected from overtemperature and are IP54.

➔ Refrigerant circuit : Each unit has two independent refrigerant circuits and each one includes: Compressor with
integrated oil separator, Electronic expansion valve, Discharge line shut off valve, Liquid line shut off valve, Sight
glass with moisture indicator, Filter drier, Charging valves, High pressure switch, High pressure transducers, Low
pressure transducers, Oil pressure transducer, Suction temperature sensor.

➔ Electrical : Control panel Power and control are located in the main panel that is manufactured to ensure
protection against all weather conditions. The electrical panel is IP54 and (when opening the doors) internally
protected against possible accidental contact with live parts. The main panel is fitted with a main switch
interlocked door that shuts off power supply when opening.

➔ Controller : Latest generation MicroTech Ill Type. Providing monitoring and control functions required for an
efficient and trouble free operation of the chiller. Sophisticated software with predictive logic selects the most
energy efficient combination of compressor load and electronic expansion valve position keeping stable operating
conditions and maximizing chiller efficiency and reliability. Unit is compatible with Daikin on Site platform for
remote monitoring, preventive maintenance and system optimization.

0 �
t::::::i
� □□□------------------------------------
Specifications are subject to change without any prior notice 28/5/2020 CSS Web 10.23
Page 1/4
Power Consumption @ Design conditions
Cooling capacity = 1132kW / 3.516 = 321.9 TR
Power Input = 382.3 kW
Power consumption = 382.3 kW / 321.9 TR = 1.1876 kW / TR
APPENDIX-K
Technical data
Contact
E-mail Glanded standard single pump
Phone IL 100/260-11/4
Customer Project name

Project ID
Contact Installation location
E-mail Customer pos.no
Phone

Date 2020-06-08

Duty chart Requested data


H/m Head - Ø 250 ∆p / MPa Flow 30,14 l/s
20 Eff. 73,1% Head 16,50 m
18,03 0,177 Media Water 100 %
16 0,16 Fluid temperature 20,00 °C
A1 Density 998,30 kg/m³
12 0,12 Kin. viscosity 1,00 mm²/s
Hydraulic data (Duty point)
8 0,08
Flow 31,50 l/s
Q: 30,18 l/s
4 0,04 Head 18,03 m
H: 18,51 m
Shaft power P2 7,56 kW
▕◄ Application range ► ▏ P₂: 7,42 kW
0 0 Hydraulic efficiency 72,66 %
P₂ / kW Shaft power P2
NPSH 2,90 m
8 Product data
7,562
7 Glanded standard single pump
6 IL 100/260-11/4
5 Max. operating pressure 1,6 MPa
4 Fluid temperature -20 °C ... + 140 °C
3 Max. ambient temperature 40 °C
Minimum efficiency index (MEI) ≥ 0,4
2
1 Motordata per Motor/Pump
0 Motor efficiency level IE3
31,5 Mains connection 3~ 400 V / 50 Hz
0 4 8 12 16 20 24 28 32 36 40 44 Q / l/s
Permitted voltage tolerance ±10 %
Rated speed 1450 1/min
Rated power P2 11,00 kW
Rated current 22,00 A
Power factor 0,8
Efficiency
50% / 75% / 100% 90,1/ 91,6/91,4%
Degree of protection IP55
Insulation class F
Motor protection
Fitting dimensions
Pipe connection on the suction side DN 100, PN16
Pipe connection on the pressure sideDN 100, PN16
Port to Port 550 mm
Materials
Pump housing 5.1301, KTL-coated
Impeller EN-GJL-200
Lantern 5.1301, KTL-coated
Shaft 1.4122
Shaft seal AQ1EGG
Information for order placements
Weight approx. 205 kg
Item number 2120790

Software version Spaix, Version 4.3.12 - 2019/12/06 (Build 293)


Subject to change Data version 04.05.2020 Pages 1/1
APPENDIX-L
DMA-SMF-05 Rev. 0
Date 6-Sep-15
HSSE Risk Assessment & Controls
LIKELIHOOD OF OCCURRENCE (L) RISK RATING (R)
V.LOW LOW MED HIGH V.HIGH
NEGLIGIBLE 1 2 3 4 5 >6 No immediate action required. Proceed with care.

HAZARD MODERATE 2 4 6 8 10 Hazard to be investigated in conjunction with Safety Rep. with a view to
>15
SEVERITY SERIOUS 3 6 9 12 15 reducing the risk
(S) MAJOR 4 8 12 16 20 Immediate action must be taken to eliminate the risk or Substantially
20<
CATASTROPHIC 5 10 15 20 25 reduce the risk.

LOCATION APOLLO DATA CENTER ACTIVITY Chiller Start Up


TASK HAZARD PERSONS AFFECTED RISK CONTROL MEASURES RESIDUAL RISK
L S R PROVIDED & REQUIRED L S R
Competent, experienced
Individual Capability 3 3 9 1 2 2
operator(s)/Training
Ergonomic 3 3 9 Training 1 1 1
Visibility 2 3 6 Controlled Luminance (lighting) 1 2 2
Maintenance/Signage/Workplace
Uneven Walkway 1 3 3 1 2 2
Operator(s), Nearby Inspection before start of job
Manual Handling of Unknown weight People, Property 2 4 6 SWL/Weight Labels/Load Analysis 1 2 2
Material(s) (Equipment/Tools/ PPE (Safety Hand
Sharp edges Building) 2 3 6 1 2 2
Gloves)/Sleeves/Training
Cautions/Signage/Workplace
Blind corners 1 3 3 1 2 2
Inspection prior to start of job
Use of designated upright trolley as
Carrying compressed
2 5 10 per cylinder classification for 1 3 3
gas cylinder
movement
PPE (Safety Hand
Sharp Edges 2 3 6 1 2 2
Gloves)/Sleeves/Training
Loose Handles Operator(s), Nearby 2 3 6 Maintenance of Tools & Equipment 1 1 1
Working with Hand People, Property
Mushroom heads 2 3 6 Maintenance of Tools & Equipment 1 1 1
Tools (Equipment/Tools/
Clutter 2 2 4 Housekeeping 1 1 1
Building)
Slip and trip due to
2 3 6 Housekeeping 1 2 2
lying tools
Trained & Qualified
Operator(s)/Maintenance of Tools &
Electricity 3 5 15 1 3 3
Equipment/Inspection of Tools &
Equipment/Use of PPE
Operator(s), Nearby Machine
Working with Power Moving parts People, Property 2 4 8 Guards/Signage/Maintenance of 1 2 2
Tools (Equipment/Tools/ Tools & Equipment/Use of PPE
Building)
PPE (Safety Hand
Sharp edges 2 3 6 1 2 2
Gloves)/Sleeves/Training
Slip and trip due to
2 3 6 Housekeeping 1 2 2
lying cables & tools
Inspection of Tools &
Equipment/Workplace
Fire 2 5 10 Inspection/Fire Watch/Fire 1 3 3
Blanket/Fire Extinguisher/Trained
Fire Warden
Inspection of Tools &
Equipment/Workplace
Inspection/Labelling of
Blast 1 5 5 1 3 3
Cylinders/Flashback
Arrestors/Gauges/Follow
SOP's/Training
Signage/PPE (Safety Hand Gloves,
Burn Operator(s), Nearby 2 4 8 1 2 2
Safety Shoes etc.)
People, Property
Hot Works Signage/PPE (Safety Hand Gloves,
Hot Surface (Equipment/Tools/ 2 4 8 1 2 2
Safety Shoes etc.)
Building)
Ventilation in Confined
Lack of Oxygen in Space/Continuously Monitoring with
2 4 8 1 3 3
confined area Oxygen Detector/Confined Space
Attendand (a Hole-Watch)/Training

Slip & trip due to


2 3 6 Housekeeping 1 2 2
trailing hoses
Use of designated upright stands as
Storage of per cylinder classification for storage
compressed gas 2 5 10 of cylinders/ 1 3 3
cylinder(s) Signage/Barricade/Ventilated
space/Training
DMA-SMF-05 Rev. 0
Date 6-Sep-15
HSSE Risk Assessment & Controls
LIKELIHOOD OF OCCURRENCE (L) RISK RATING (R)
V.LOW LOW MED HIGH V.HIGH
NEGLIGIBLE 1 2 3 4 5 >6 No immediate action required. Proceed with care.

HAZARD MODERATE 2 4 6 8 10 Hazard to be investigated in conjunction with Safety Rep. with a view to
>15
SEVERITY SERIOUS 3 6 9 12 15 reducing the risk
(S) MAJOR 4 8 12 16 20 Immediate action must be taken to eliminate the risk or Substantially
20<
CATASTROPHIC 5 10 15 20 25 reduce the risk.
PPE (Full Body Harness with
Lanyard) Training, Guardrails, Toe
Fall from height 3 5 15 Plates/Inspection of Equipment 2 2 4
(Ladder/Scaffolding etc) Following
SOP
Floor (uneven Maintenance/Signage/Workplace
2 3 6 1 2 2
surface) Inspection prior to start of job
Operator(s), Nearby
People, Property Use of Waist Tool Bags for carrying
Working at Height tools/Not throwing material up or
Fall of Material (Equipment/Tools/ 2 4 8 1 3 3
Building) down/Use of rope & pully to transfer
material/ Signage/Barricade

Ergonomic 3 3 9 Training 1 1 1
Inspection & Maintenance of
Scaffolding / Ladder Ladders/Inspection & Maintenance
3 4 12 2 2 4
failure of Scaffolding/Following
SOP's/Training

1-Strictly No Work on Live Circuites,


2-Trained & Qualified Operators, 3-
Must follow Lock Out/Tag Out
Operator(s), Nearby
Procedure with Proper Equipment. 4-
Working with People, Property
Electricity 3 5 15 Use of Proper Electrical PPE (Safety 2 2 4
Electrical Installations (Equipment/Tools/
Gloves, Safety Shoes, Safety Goggles,
Building)
Electrical Rubber Mat), 5-Proper
Luminance, 6-Housekeeping,
Cordoning Off Area with Signs.

ASSESSMENT NO. MANAGER SIGNATURE


ASSESSOR(S) DATE 26/11/20
REVISION 00
METHOD STATEMENT SUBMITTAL
(MTS)

HSSE Risk Assessment

Risk Rating Likelihood (L) Severity (S)


L Low Risk Rating 1 Extremely improbable Rating 1 Negligible
M Medium Risk Rating 2 Extremely Remote (Improbable) Rating 2 Minor
H High Risk Rating 3 Remote Rating 3 Major
Rating 4 Reasonably probable (Occasional) Rating 4 Extensive/Hazardous
Rating 5 Frequent Rating 5 Catastrophic
Risk (R) = Likelihood (L) x Severity (S)

Groups Factors of
Date
Exposed Harm / Control measures
Risk to be Residual Risk
(Inc. Current Risk Implemented by
Activities Hazard Activiti Existing Control Measures Additional Control measures compl
Nos. & Rating
es eted
Patterns
L S R by L S R
)
Mobilization Unauthorize Prepare All  TBT/DSTI to be conducted by 4 3 12  Daily safety inspection should be carried Prior to 2 3 6 Site Engineer /
d, untrained work workers the foreman/ safety officer prior and eliminate the hazard. start Supervisor /
workers area to work commencement the Foreman
 Task specific safety training to be work
provided
 Authorized personnel to
undertake the job.

HWI-APO-CN-MSS-0009-02 – METHOD STATEMENT SUBMITTAL FOR START-UP COMMISSIONING OF AIR COOLED CHILLERS
METHOD STATEMENT SUBMITTAL
(MTS)

Groups Factors of
Date
Exposed Harm / Control measures
Risk to be Residual Risk
(Inc. Current Risk Implemented by
Activities Hazard Activiti Existing Control Measures Additional Control measures compl
Nos. & Rating
es eted
Patterns
L S R by L S R
)
Manual Handling Incorrect Back All  Any lifting tasks shall be carried 4 4 16  Deploy enough number of personnel for Prior 3 4 12 Site Engineer /
lifting of Injuries workers out by persons physically lifting shall be appointed to the task to Supervisor /
loads Cut to capable to do so depending upon the type of load to be start Foreman
Sharp finger  No employee should be asked to lifted. the
edges. Strain carry loads above his capacity and  Use easy mode of transport like trolley etc. wor
Placing the Musculo in any case no load shall exceed  Area to be illuminated with adequate k
object while skeletal 23kg per man. lighting
fingers Injuries  Mass of the load is more then to be  Periodic trainings will be given for manual
underneath. equally shared handling techniques.
Slip/trip/fall  Load not to be lifted above your  Daily TBT.
( same shoulder height  Rest timings in between the job if the job
level )  Keep your fingers away from time is too long.
Unsafe pinch point while placing the load
posture  Proper personal protective
equipment to be used while
manual handling of materials and
loads.
Stacking and Unauthorize Crush All  All materials shall be stored 4 3 12  Ensure the storage is enough for storing Prior 3 3 12 Site Engineer /
Storing d, untrained Cut and workers below 2 meter height. otherwise will get additional storing area. to Supervisor /
workers abrasion  If the material is too heavy, use start Foreman
Material fall Damage hydraulic trolley to shift the  Daily TBT. the
from height to material. wor
Improper property  No storage of materials to be k
stacking done in the work place, only
Collapse required quantity to be taken for
the job.
• Personnel protective equipment
must wear at all time during the
activity. (Helmet, shoe, vest,
overall, gloves, goggles, mask.)

HWI-APO-CN-MSS-0009-02 – METHOD STATEMENT SUBMITTAL FOR START-UP COMMISSIONING OF AIR COOLED CHILLERS
METHOD STATEMENT SUBMITTAL
(MTS)

Groups Factors of
Date
Exposed Harm / Control measures
Risk to be Residual Risk
(Inc. Current Risk Implemented by
Activities Hazard Activiti Existing Control Measures Additional Control measures compl
Nos. & Rating
es eted
Patterns
L S R by L S R
)
Working with Slip, trip Crush All  Don’t extend the spanner by 4 4 16  Defective tools should not be issued or Prior 3 4 12 Site Engineer /
Hand tools and fall Damage workers using a pipe as an extension bar used to Supervisor /
Damaged to  Hand tools shall be free from oil,  to perform the task, to be checked by start Foreman
warn out property grease & etc. store the
hand tools Fatigue  Chisel’s head shall have safety  keeper work
Flying Trigger cap to avoid finger injury.  Never use a screw driver as a chisel
objects finger  Never use a file as a lever  Don’t work with oily or greased hands
Mushroom Cuts
Heads and  Use right tools for the job.  Use eye/ face protection when there is
flying materials hazard, wear gloves
Using abrasion while required to protect the hands
incorrect s
type  Daily TBT
Working with Defective Eye All  PTW to be applied and obtained 4 4 16 Prior 2 4 8 Site Engineer /
power tools equipment injury workers prior to start, If spark producing  Don’t lay the cables around the access to Supervisor /
Electricity Crushi activity is performed way, it should be proper routing start Foreman
Improper ng  Defective tools should not be  Industrial distribution board and socket the
use of Back issued or used to perform a task. only to be used at site work
equipment injury  Monthly inspection should be  No joints shall be made in electrical
Poor Burns carried out by the electrician and cable.
maintenance Electro record to be kept at the store  Cable hangers shall be used to avoid the
Untrained cution  All portable power tools should direct contact of power tools cable with
workers be fitted with adequate fuse the scaffolding members.
Flying protection either in the tool body  Electrical connection shall be routed
object or in its electrical plug through ELCB only.
Noise and  The weight, size and type of tool  Correct rate of ELCB should be used.
vibration should be selected to suit the job  Only those persons who have been
Fire being carried out. adequately trained and experienced in the
Dust  Tools should be stored and use of the tool should be allowed to use
maintained in good working the same.
condition.  Periodic trainings will be given for safe
 Appropriate PPE Should use use of electrical equipment.
 Daily TBT.
 Power tools shall have inspection
sticker.
 Ensure the use of drip trays for
any hydraulic power tools.

HWI-APO-CN-MSS-0009-02 – METHOD STATEMENT SUBMITTAL FOR START-UP COMMISSIONING OF AIR COOLED CHILLERS
METHOD STATEMENT SUBMITTAL
(MTS)

Groups Factors of
Date
Exposed Harm / Control measures
Risk to be Residual Risk
(Inc. Current Risk Implemented by
Activities Hazard Activiti Existing Control Measures Additional Control measures compl
Nos. & Rating
es eted
Patterns
L S R by L S R
)
Working with Fall from Sprain All  The ladder should extend 4 3 12  Ladder to be used for short duration Prior 3 3 9
ladder height and workers minimum one meter from the top works only limited to 15 min. to Site Engineer /
Over strain for safe movement  Colour coded system to be implemented start Supervisor /
reaching Fracture  Heavy materials should not be  Inspection and maintenance to be the Foreman
Over Injury to carried registered and recorded by the store work
loading the  Do not erect in slippery, uneven keeper
Obstructing person surface  Defective ladder should not be used and
the access  Should be set up with a 4 vertical report it immediately
way to 1 horizontal slope ( 4:1 )  Daily TBT
Slippery or  Step ladder must fully open and  Periodic trainings.
uneven lock and the devices to be as per
surface manufacturer
 Do not work from the top of two
rungs
 Remember the 3 point contact
 Do not work in front of the door.
If work is carried then locked the
door or blocked off
Working on Uneven Sprain All  Do not stack materials on to the 4 4 16  Visual inspection should carry before use Prior 3 4 12 Site Engineer /
mobile scaffold surface and workers scaffold to Supervisor /
Overhead strain  Out rigger fitted and breaks are  Safety harness to be used above 2mtr start Foreman
structure Fracture locked on height and anchored in above shoulder the
height at all time
and cable Spinal  Only trained scaffolders shall be work
Materials cord involved in erection &  Tagging system to be implemented
and worker damage dismantling activities.  Keep walkways free of obstacles, tools
fall from Musculo  No person to be on the scaffold and Equipment
height skeletal
Untrained, Injury
while it is being moved
 Scaffold only use in on level and
 Daily TBT
unauthorize Fatality surface area  Periodic trainings.
d Workers  Never stand and sit on the hand
Collapse of rails
scaffold

HWI-APO-CN-MSS-0009-02 – METHOD STATEMENT SUBMITTAL FOR START-UP COMMISSIONING OF AIR COOLED CHILLERS
METHOD STATEMENT SUBMITTAL
(MTS)

 Start-up  1.Eye Sprain T&C  All tools provided must be assessed 3 4 12  Whilst taking RPM readings on rotating Prior 2 4 8 Commissioning
Commissioni injury and Team to ensure that they are fit for equipment an assistant will man the isolator to to Manager
ng of Air  2.Injury to strain purpose, fit for the environment in allow the stopping of motors if contact occurs. start Com. Engineer
Fracture which they are to be used and they the Supervisor
Cooled hands, feet are in good condition.
Chiller and body Spinal work Safety Supervisor
 Visual checks must be completed
 3.Electrical cord by operatives on tools prior to their
Shock. damage use.
 4.Fall from Musculo  Tools are required to be suitable for
step skeletal the purpose for which they will be
ladders. Injury used.
Fatality  Eye protection is to be provided and
 5. Contact
used whenever work is done and
with there is the danger of dust being
rotating blown into the operatives’ eyes
 during air system commissioning or
where test holes are being drilled in
ductwork and swarf can fall into the
operatives’ eyes.
 Insulated tools must be used where
there is a possibility of live
electrical work.
 Prior to taking amp readings on live
conductors the tightness of the
terminations will be checked with
the circuit dead to ensure no cables
come loose during live testing.
 Prior to taking RPM readings on
rotating equipment the engineer will
check his clothing to ensure that
there are no loose pieces of material
which could become entangled in
rotating equipment.

HWI-APO-CN-MSS-0009-02 – METHOD STATEMENT SUBMITTAL FOR START-UP COMMISSIONING OF AIR COOLED CHILLERS
METHOD STATEMENT SUBMITTAL
(MTS)

Groups Factors of
Date
Exposed Harm / Control measures
Risk to be Residual Risk
(Inc. Current Risk Implemented by
Activities Hazard Activiti Existing Control Measures Additional Control measures compl
Nos. & Rating
es eted
Patterns
L S R by L S R
)
Emergency Unauthorize Fatality All  Only qualified and trained 4 4 16  Emergency evacuation plan shall be Prior 3 4 12 Site Engineer /
procedure d/ untrained Property workers person to do the job. readily available according to site to Supervisor /
Person damage  Emergency procedure to be condition and developed to the all start Foreman
Faulty Fracture briefed to all personnel prior to workforce. the
Instrument s start the activity.  Trained first aider, fire warden and work
Improper  Calibrated pressure gauge only emergency vehicle to be available at the
identificatio to be used and increase pressure site during the activity.
n
High
gradually.  Daily TBT
 Periodic trainings
pressure
While working at Poor Fatality All  light post to be secured from fall 3 3 9  Daily TBT Prior 2 3 6 Site Engineer /
night shift illumination Cuts workers  Proper cable management  Periodic trainings to Supervisor /
Slip/trip/fall system to be followed start Foreman
 Proper illumination to be provided.
 All materials to be staged in the
proper manner without obstacles work
Working in hot Heat Dehydra All  Drink plenty of water 4 3 12  Proper awareness of heat stress Prior 3 3 9 Site Engineer /
weather tion workers  Avoid highly physical tasks symptoms to Supervisor /
Sunburn during the hottest part of the day  Isotonic drinks to be provided start Foreman
Skin
Cancer
 Daily TBT the
work
 Periodic trainings

Work Poor Fire All  General housekeeping. 4 4 16  Daily TBT Prior 3 4 12 Site Engineer /
Completion housekeepin Fatality workers  Remove all surface, unwanted  Periodic trainings to Supervisor /
g Cuts waste materials from the start Foreman
Slip/trip/fall Property building the
damage  All necessary precautions will be work
Fracture adopted to prevent fire and
s work
compl
etion.

HWI-APO-CN-MSS-0009-02 – METHOD STATEMENT SUBMITTAL FOR START-UP COMMISSIONING OF AIR COOLED CHILLERS
APPENDIX-M
OPERATING MANUAL
MicroTech III ® Controller
MODBUS PROTOCOL INFORMATION SUMMARY
Application Software Name: ACZC-ACZH-ATLAS-AWS-EWWD-GIZMO-MNG-PFS-WATER STREAM

D-EOMOC002(04)09-15EN

D-EOMOC002(04)09-15EN - 1/35
Table of Contents
PREMISE .................................................................................................................................................................. 3
INTRODUCTION ...................................................................................................................................................... 4
Revision History .............................................................................................................................................................. 4
Reference Documents .................................................................................................................................................... 4
BASIC INFORMATION ............................................................................................................................................ 5
Compatibility ................................................................................................................................................................... 5
Configuring the Microtech III for Modbus Network .......................................................................................................... 5
Modbus Registers Addressing ........................................................................................................................................ 5
MINIMUM INTEGRATION ........................................................................................................................................ 6
DATA POINTS ......................................................................................................................................................... 7
Data Points for Chiller Models......................................................................................................................................... 7
Comprehensive Data Points List ..................................................................................................................................... 9
ALARM POINTS ....................................................................................................................................................18
Alarm Points for Chiller Models ....................................................................................................................................... 18
Comprehensive Alarm Points List ................................................................................................................................... 20
APPENDIX A – ASCII CHARACTERS CONVERSION TABLE ...........................................................................25
APPENDIX B – OVERALL REGISTERS TABLE .................................................................................................26

D-EOMOC002(04)09-15EN - 2/35
Premise
The Modbus protocol is a standardized Application Level (OSI Level 7) protocol used in interoperable
Industrial Control networks. Modbus provides the communication infrastructure necessary to integrate
products manufactured by different vendors and to integrate control services that are now independent.

D-EOMOC002(04)09-15EN - 3/35
Introduction
This document describes the present status of Modbus communication profile for all MicroTech III application
®
software, providing the necessary information to incorporate a MicroTech III Chiller Unit Controller into a
Building Automation System (BAS).
Modbus terms and principles are not defined. Refer to the appropriate specifications for definitions and
details.

Revision History
1) D-EOMOC00011-14EN November 2014 Created
2) D-EOMOC002(17)12-14EN 17 December 2014 Upgraded ATLAS Holding Registers 40025, 40026
3) D-EOMOC002(19)12-14EN 19 December 2014 Improved ATLAS Holding Registers 40900, 40901, 40902
Improved Appendix B
Upgraded Holding Registers 40011, 40034
Upgraded Revision History
4) D-EOMOC002(04)09-15EN 04 September 2015 Improved GIZMO units
Improved WaterStream units
Upgraded Table 2
Upgraded Table 3
Upgraded Table 4
Upgraded Table 5
Upgraded Table 5
Upgraded Revision History

Reference Documents
Ref.#1 www.Modbus.org

D-EOMOC002(04)09-15EN - 4/35
Basic Information

Compatibility
The MicroTech III Chiller Unit Controller conforms to the published Modbus standards. Controllers can
communicate on standard Modbus networks using ASCII or RTU transmission mode. The MicroTech III
Chiller Unit Controller uses the RTU mode only. Refer to Ref.#1 for more detailed information.

Configuring the Microtech III for Modbus Network


The MicroTech III Chiller Unit Controller can be configured in an interoperable Modbus network. The
controller must have the corresponding Modbus Communication Module installed.
The MicroTech III Chiller Unit Controller and the Modbus Communication Module are shipped with default
parameter values. Default values may be changed with the unit keypad. Parameters must be adjusted to
accommodate your particular network. See the appropriate Operation Manual for default values and keypad
operating instructions. See the MicroTech III Modbus Communication Module Installation Manual for details
regarding network parameters available via the unit controller keypad/display.
Once communication module is set up and communication with network is established, in order to control the
MicroTech III over the network, the Unit control source must be turned in “Network” (default is Local). From
keypad/display set the Main Menu_View/Set Unit_Status/Settings_Control Source to “Network”.

Modbus Registers Addressing


The Modbus Communication Module supports zero-based addressing. For example, holding register 40002
is addressed as 0001 in a Modbus message. The following tables assume 4xxxx addressing.

D-EOMOC002(04)09-15EN - 5/35
Minimum Integration
This section describes the information that assure compliance of Microtech III to the integration criteria for a
Modbus network integration. The data/alarm points that represent the minimum integration data points are
listed in Table 1 below and in boldface in Table 2 to Table 5.

Table 1. MicroTech III Chiller Unit Controller Registers for minimum integration

Data/Alarm points
Actual Capacity
Chiller Enable Setpoint
Chiller Mode Setpoint - Network
Chiller Status
Clear Alarms - Network
Evaporator Entering Fluid Temperature
Evaporator Leaving Fluid Temperature
Capacity Limit Setpoint – Network
Cool Setpoint – Network
Problem Alarm Code
Fault Alarm Code
Warning Alarm Code

D-EOMOC002(04)09-15EN - 6/35
Data Points

Data Points for Chiller Models


Table 2 contains the list of Modbus data points available from the MicroTech III Chiller Unit Controller
depending on the chiller model and corresponding unit controller application software. Application software
name is available in the unit HMI: see in Main Menu, “About Chiller”. The data points in boldface represent
the minimum integration data points listed in Table 1.

Table 2. MicroTech III Unit Controller Data Points List for Chiller Model

STREAM
WATER
ATLAS

EWWD

GIZMO
ACZC

ACZH

AWS

MNG
ADZ

PFS
Data Point

Active Capacity Limit Output X X X X X X X X X X

Active Energy X X X

Active Setpoint X X X X X X X X X X

Actual Capacity X X X X X X X X X X

Alarm Digital Output X X X X X X X X X X

Application Software Version X X X X X X X X X X

Capacity Limit Setpoint - Network X X X X X X X X X X

Chiller Capacity Limited X X X X X X X X X X

Chiller Current X X X X X X X X X

Chiller Enable Output X X X X X X X X X X

Chiller Enable Setpoint X X X X X X X X X X

Chiller Local/Remote X X X X X X X X X X

Chiller Location X X X X X X X X X X

Chiller Mode Output X X X X X X X X X X

Chiller Mode Setpoint – Network X X X X X X X X X X

Chiller Model X X X X X X X X X X

Chiller On/Off X X X X X X X X X X

Chiller Status (Chiller Run Mode) X X X X X X X X X X

Chiller Tons X X X X X X X X X X

Chiller Voltage X X X

Clear Alarms – Network X X X X X X X X X X

Circuit Actual Capacity X X X X X X X X X

Compressor Current X X

Compressor Discharge Refrigerant Temp X X X X X X X X X

Compressor Full Load X X X X X X X X X

Compressor Off Auto X X X X X X X X

Compressor Oil Feed Pressure X X X X X X X X

Compressor Oil Level Status X X X X X X X

Compressor Percent RLA X X

Compressor Power X X

D-EOMOC002(04)09-15EN - 7/35
STREAM
WATER
ATLAS

EWWD

GIZMO
ACZC

ACZH

AWS

MNG
ADZ

PFS
Data Point

Compressor Run Hours X X X X X X X X X

Compressor Starts X X X X X X X X X

Compressor Status X X X X X X X X

Compressor Suction Refrigerant Temperature X X X X X X X X X

Compressor VFD Output X X

Compressor Voltage X X

Condenser Approach Temperature X X X X X X X X X

Condenser Entering Water Temp X X

Condenser Flow Switch Status ? ? X

Condenser Leaving Water Temp X X

Condenser Pump Run Hours X X

Condenser Pump Status X X

Condenser Refrigerant Pressure X X X X X X X X X

Condenser Saturated Refrigerant Temperature X X X X X X X X X

Cool Setpoint – Network X X X X X X X X X X

Date X X X X X X X X X X

Day of Week X X X X X X X X X X

Evaporator Approach Temp X X X X X X X X X

Evaporator Entering Water Temperature X X X X X X X X X X

Evaporator Flow Switch Status X X X X X X X X X X

Evaporator Leaving Water Temperature X X X X X X X X X X

Evaporator Pump Run Hours X

Evaporator Pump Status X X X X X X X X X

Evaporator Refrigerant Pressure X X X X X X X X X

Evaporator Saturated Refrigerant Temperature X X X X X X X X X

Evaporator SuperHeat Setpoint X X X X X X X X X

Evaporator SuperHeat Temperature X X X X X X X X X X

EXV Position X X X X X X X X X

Fault Alarm Code X X X X X X X X X X

Fault Alarm Index X X X X X X X X X X

Heat Recovery Enable - Network X

Heat Recovery Ent Water Temperature X X

Heat Recovery Leaving Water Temperature X X

Heat Setpoint – Network X X X X X X X

Hour X X X X X X X X X X

Ice Setpoint - Network X X X X X X X X X X

Liquid Temperature X

Minute X X X X X X X X X X

Month X X X X X X X X X X

Noise Reduction Auto On X X X X X X X X

Noise Reduction Status X X X X X X X X

D-EOMOC002(04)09-15EN - 8/35
STREAM
WATER
ATLAS

EWWD

GIZMO
ACZC

ACZH

AWS

MNG
ADZ

PFS
Data Point

Number of Circuits X X X X X X X X X X

Number of Compressors X X X X X X X X X X

Outdoor Air Temperature X X X X X X X X

Outdoor Fan Speed X X X X X X X X

Outdoor Fan Status X X X X X X X X

Power Factor X X X

Power Input X X X

Problem Alarm Code X X X X X X X X X X

Problem Alarm Index X X X X X X X X X X

Refrigerant Type X X X X X X X X X X

Run Enabled X X X X X X X X X X

Second X X X X X X X X X X

Units X X X X X X X X X X

Warning Alarm Code X X X X X X X X X X

Warning Alarm Index X X X X X X X X X X

Year X X X X X X X X X X

Comprehensive Data Points List


Table 3 contains the complete list of Modbus data points available from the MicroTech III Chiller Unit
Controller. The data points in boldface represent the minimum integration data points as identified in Table 1.
Table 5 lists the available chiller alarm objects.

Table 3. MicroTech III Unit Controller Modbus Comprehensive Data Point List
H.R.1

R/W2

Data Point Range/Description

Active Capacity Limit Output 14 R 0 - 100%

Active Energy 1900 R Enabled whit Power meter optional

Active Setpoint 12 R ACZC: -9.5 to 15.6°C (14.9 to 60.0 °F)

ACZH: -9.5 to 55.0°C (14.9 to 131.0 °F)

ATLAS: -8.0 to 50.0°C (17.6 to 122.0°F)

AWS: -8.0 to 50.0°C (17.6 to 122.0°F)

EWWD: -9.4 to 60.0°C (15.0 to 140.0°F)

GIZMO:-15.0 to 55.0 (5.0 to 131 °F)

MNG: -9.4 to 15.6°C (15.0 to 60.0 °F)

PFS: -9.4 to 65.0°C (15.0 to 149.0°F)

WATER STREAM: -9.4 to 65.0°C (15.0 to 149.0°F)

Actual Capacity 13 R 0 - 100%

Alarm Digital Output 5 R 0=No Alarm, 1=Alarm

Application Software Version [1] 334 R -

1
Holding Register (4xxxx)
2
Read/Write

D-EOMOC002(04)09-15EN - 9/35
H.R.1

R/W2
Data Point Range/Description

Application Software Version [5] 338 R -

Capacity Limit Setpoint - Network 38 RW 0 - 100%

Chiller Capacity Limited 4 R 0=Not Limited, 1=Limited

Chiller Current 25 R

Chiller Enable Output 2 R 0=Disable, 1=Enable

Chiller Enable Setpoint 9 RW 0=Disable, 1=Enable, 2=Null

Chiller Local/Remote 1 R 0=Remote, 1=Local

Chiller Location [1] 318 RW -

Chiller Location [10] 327 RW -

Chiller Mode Output 11 R ACZC: 0=Null, 1= Ice, 2= Cool

ACZH: 0=Null, 1= Ice, 2=Cool/Heat

ATLAS: 0=Null, 1= Ice, 2=Cool

AWS: 0=Null, 1=Ice, 2=Cool

EWWD: 0=Null, 1=Ice, 2=Cool, 3=Heat

GIZMO: 0 = Ice, 1 = Cool, 2 = Heat

MNG: 0=Null, 1= Ice , 2=Cool, 3=Heat

PFS: 0=Null, 1=Cool, 2=Ice, 3=Heat

WATER STREAM: 0=Ice, 1=Cool, 2=Heat

Chiller Mode Setpoint – Network 34 RW ACZC: 0=Null, 1= Ice, 2=Cool

ACZH: 0=Null, 1= Ice, 2=Cool, 3=Heat

ADZ: 0=Null, 1= Cool, 2=Ice

ATLAS: 0=Null, 1= Ice, 2=Cool

AWS: 0=Null, 1= Ice, 2=Cool

EWWD: 0=Null, 1=Ice, 2 = Cool, 3 = Heat

GIZMO: 0=Null, 1=Ice, 2=Cool, 3=Heat, 4 = Cool/Heat Recovery

MNG: 0=Null, 1=Cool , 2= Ice, 3=Heat

PFS: 0=Null, 1=Cool, 2=Ice, 3=Heat

WATER STREAM: 0=Null, 1=Ice, 2=Cool, 3=Heat

Chiller Model 317 R 0=Centrifugal, 1=Water Cooled, 2=Air Cooled, 3=Heat Pump, 9=Other

Chiller On/Off 8 R 0=Off, 1=On

Chiller Status (Chiller Run Mode) 15 R 1=Off, 2=Start, 3=Run, 4=Pre Shutdown, 5=Service

Chiller Tons 1609 R

Chiller Voltage 26 R Enabled whit Power meter optional

Clear Alarms – Network 10 RW 0=Normal, 1=Clear Alarms, 2=Null/Normal

Circuit #1 Comp #1 - Actual Capacity 1840 R

Circuit #1 Comp #2 - Actual Capacity (PFS) 1826 R

Circuit #2 Comp #1 - Actual Capacity 1800 R

Circuit #3 Comp #1 - Actual Capacity 1761 R

Circuit #1 Comp #1 - Current 70 R 0 to10.000 Amps

Circuit #2 Comp #1 - Current 109 R 0 to10.000 Amps

Circuit #3 Comp #1 - Current 148 R 0 to10.000 Amps

Circuit #1 Comp #1 - Discharge Refrigerant Temp 68 R -40 to 121°C (-40 to 250°F)

D-EOMOC002(04)09-15EN - 10/35
H.R.1

R/W2
Data Point Range/Description

Circuit #1 Comp #2 - Discharge Refrigerant Temp 81 R -40 to 121°C (-40 to 250°F)

Circuit #2 Comp #1 - Discharge Refrigerant Temp 107 R -40 to 121°C (-40 to 250°F)

Circuit #3 Comp #1 - Discharge Refrigerant Temp 146 R -40 to 121°C (-40 to 250°F)

Circuit #1 Comp #1 - Full Load 1842 R

Circuit #1 Comp #2 - Full Load 1828 R

Circuit #2 Comp #1 - Full Load 1802 R

Circuit #3 Comp #1 - Full Load 1763 R

Circuit #1 Comp #1 - Off Auto 1841 RW

Circuit #1 Comp #2 - Off Auto 1827 RW

Circuit #1 Comp #3 - Off Auto 1814 RW

Circuit #2 Comp #1 - Off Auto 1801 RW

Circuit #2 Comp #2 - Off Auto 1788 RW

Circuit #2 Comp #3 - Off Auto 1775 RW

Circuit #3 Comp #1 - Off Auto 1762 RW

Circuit #1 Comp #1 - Oil Feed Pressure 1849 R -40 to 121 kPa (-5.801473 to 17.54946 psi)

Circuit #2 Comp #1 - Oil Feed Pressure 1809 R -40 to 121 kPa (-5.801473 to 17.54946 psi)

Circuit #1 Comp #1 - Oil Feed Pressure 1846 R -40 to 121 kPa (-5.801473 to 17.54946 psi)

Circuit #1 Comp #2 - Oil Feed Pressure 1832 R -40 to 121 kPa (-5.801473 to 17.54946 psi)

Circuit #3 Comp #1 - Oil Feed Pressure 1770 R -40 to 121 kPa (-5.801473 to 17.54946 psi)

Circuit #1 Comp #1 - Oil Level Status 1851 R

Circuit #2 Comp #1 - Oil Level Status 1811 R

Circuit #3 Comp #1 - Oil Level Status 1772 R

Circuit #1 Comp #1 - Percent RLA 69 R 0-110%

Circuit #2 Comp #1 - Percent RLA 108 R 0-110%

Circuit #3 Comp #1 - Percent RLA 147 R 0-110%

Circuit #1 Comp #1 – Power 72 R 0-3500 kW

Circuit #2 Comp #1 - Power 111 R 0-3500 kW

Circuit #3 Comp #1 - Power 150 R 0-3500 kW

Circuit #1 Comp #1 - Run Hours (ACZC, ACZH, ADZ, 74 RW 0-999.999


ATLAS, AWS, GIZMO, WATER STREAM)

Circuit #1 Comp #1 - Run Hours (EWWD, MNG, PFS) 74 R 0-999.999

Circuit #1 Comp #2 - Run Hours (ACZC, ACZH, ADZ, 87 RW 0-999.999


GIZMO, WATER STREAM)

Circuit #1 Comp #2 - Run Hours (PFS) 87 R 0-999.999

Circuit #1 Comp #3 - Run Hours (ACZC, ACZH, ADZ, 100 RW 0-999.999


WATER STREAM)

Circuit #2 Comp #1 - Run Hours (ACZC, ACZH, ADZ, 113 RW 0-999.999


ATLAS, AWS, WATER STREAM)

Circuit #2 Comp #1 - Run Hours (EWWD,MNG) 113 R 0-999.999

Circuit #2 Comp #2 - Run Hours (ACZC, ACZH, ADZ, 126 RW 0-999.999


WATER STREAM)

Circuit #2 Comp #3 - Run Hours (ACZC, ACZH, ADZ, 139 RW 0-999.999


WATER STREAM)

Circuit #3 Comp #1 - Run Hours (AWS) 152 RW 0-999.999

Circuit #3 Comp #1 - Run Hours (EWWD) 152 R 0-999.999

Circuit #1 Comp #1 – Starts (ACZC, ACZH, ADZ, ATLAS, 73 RW 0 – 65.535

D-EOMOC002(04)09-15EN - 11/35
H.R.1

R/W2
Data Point Range/Description

AWS, GIZMO, WATER STREAM)

Circuit #1 Comp #1 – Starts (EWWD, MNG, PFS) 73 R 0 – 65.535

Circuit #1 Comp #2 – Starts (ACZC, ACZH, ADZ, 86 RW 0 - 65.535


GIZMO, WATER STREAM)

Circuit #1 Comp #2 – Starts (PFS) 86 R 0 - 65.535

Circuit #1 Comp #3 – Starts (ACZC, ACZH, ADZ, 99 RW 0 - 65.535


WATER STREAM)

Circuit #2 Comp #1 – Starts (ACZC, ACZH, ADZ, ATLAS, 112 RW 0 – 65.535


AWS, WATER STREAM)

Circuit #2 Comp #1 – Starts (EWWD, MNG) 112 R 0 – 65.535

Circuit #2 Comp #2 - Starts (ACZC, ACZH, ADZ, WATER 125 RW 0 - 65.535


STREAM)

Circuit #2 Comp #3 - Starts (ACZC, ACZH, ADZ, WATER 138 RW 0 - 65.535


STREAM)

Circuit #3 Comp #1 – Starts (AWS) 151 RW 0 – 65.535

Circuit #3 Comp #1 – Starts (EWWD) 151 R 0 – 65.535

Circuit #1 Comp #1 – Status 1852 R 0 = Off, 1 = On

Circuit #1 Comp #2 – Status 1838 R 0 = Off, 1 = On

Circuit #1 Comp #3 – Status 1825 R

Circuit #2 Comp #1 - Status 1812 R 0 = Off, 1 = On

Circuit #2 Comp #2 - Status 1799 R 0 = Off, 1 = On

Circuit #2 Comp #3 - Status 1786 R

Circuit #3 Comp #1 - Status 1773 R

Circuit #1 - Suction Refrigerant Temp 65 R -40 to 110° C (-40 to 230° F)

Circuit #1 Comp #2 - Suction Refrigerant Temp 78 R -40 to 110° C (-40 to 230° F)

Circuit #2 Comp #1 - Suction Refrigerant Temp 104 R -40 to 110° C (-40 to 230° F)

Circuit #3 Comp #1 - Suction Refrigerant Temp 143 R -40 to 110° C (-40 to 230° F)

Circuit #1 Comp #1 - VFD Output 1845 R

Circuit #2 Comp #1 - VFD Output 1805 R

Circuit #3 Comp #1 - VFD Output 1766 RW

Circuit #1 Comp #1 – Voltage 71 R 0 to 15.000 V

Circuit #2 Comp #1 - Voltage 110 R 0 to 15.000 V

Circuit #3 Comp #1 - Voltage 149 R 0 to 15.000 V

Circuit #1 - Condenser Approach Temp 1987 R 0 to10 d°C (0 to 50 d°F)

Circuit #2 - Condenser Approach Temp 1971 R

Circuit #3 - Condenser Approach Temp 1955 R

Condenser Entering Water Temp 19 R -40 to 110°C (-4 0 to 230°F)

Condenser Flow Switch Status 7 R 0=No Flow, 1=Flow

Condenser Leaving Water Temp 20 R -40 to 110°C (-40 to 230°F)

Condenser Pump Run Hours 297 R 0-999.999

Condenser Pump Status 299 R 0=Pump Off Request, 1=Pump On Request

Circuit #1 - Condenser Refrigerant Pressure 39 R 0 to 2827 kPa (4826 kPa for R410A) - 0 to 410 psi (700 psi for R410A)

Circuit #2 - Condenser Refrigerant Pressure 43 R 0 to 2827 kPa (4826 kPa for R410A) - 0 to 410 psi (700 psi for R410A)

Circuit #3 - Condenser Refrigerant Pressure 47 R 0 to 2827 kPa (4826 kPa for R410A) - 0 to 410 psi (700 psi for R410A)

Circuit #1 - Condenser Saturated Refrigerant Temp 40 R -26.1 to 85°C (-14.98-185°F)

D-EOMOC002(04)09-15EN - 12/35
H.R.1

R/W2
Data Point Range/Description

Circuit #2 - Condenser Saturated Refrigerant Temp 44 R -26.1 to 85°C (-14.98-185°F)

Circuit #3 - Condenser Saturated Refrigerant Temp 48 R -26.1 to 85°C (-14.98-185°F)

Cool Setpoint – Network 35 RW ACZC: -9.5 to 15.6 °C (14.9 to 60.08°F)

ACZH: -9.5 to 15.6 °C (14.9 to 60.08°F)

ATLAS: -8.0 to 15.0 °C (17.6 to 59.0 °F)

AWS: -8.0 to 15.0 °C (17.6 to 59.0 °F)

EWWD: -3.9 to 15.6 °C (24.98 to 60.08 °F)

GIZMO: -15.0 to 15.0 °C (5.0 to 59.0°F)

MNG: -3.9 to 15.6 °C (24.98 to 60.08 °F)

PFS: -3.9 to 15.6 °C (24.98 to 60.08 °F)

WATER STREAM: -15.0 to 15.0 °C (5.0 to 59.0°F)

Date 311 RW -

Day of Week 312 RW 0 (Monday) – 6 (Sunday).Calculated by the controller.

Circuit #1 - Evaporator Approach Temp 1988 R 0 to10 d°C (0 to 50 d°F)

Circuit #2 - Evaporator Approach Temp 1972 R 0 to10 d°C (0 to 50 d°F)

Circuit #3 - Evaporator Approach Temp 1956 R 0 to10 d°C (0 to 50 d°F)

Evaporator Entering Fluid Temperature 16 R -40 to 110°C (-40 to 230°F)

Evaporator Flow Switch Status 6 R 0=No Flow, 1=Flow

Evaporator Leaving Fluid Temperature 17 R -40 to 110°C (-40 to 230°F)

Evaporator Pump #1 Run Hours (ACZC, ACZH, ADZ, 303 RW 0-999.999


ATLAS, AWS, GIZMO, WATER STREAM)

Evaporator Pump #1 Run Hours (EWWD, MNG, PFS) 303 R 0-999.999

Evaporator Pump #2 Run Hours (ACZC, ACZH, ADZ, 306 RW 0-999.999


ATLAS, AWS, GIZMO, WATER STREAM)

Evaporator Pump #2 Run Hours (EWWD, MNG, PFS) 306 R 0-999.999

Evaporator Pump #1 Status 305 R 0=Pump Off Request, 1=Pump On Request

Evaporator Pump #2 Status 308 R 0=Pump Off Request, 1=Pump On Request

Circuit #1 - Evaporator Refrigerant Pressure 41 R -2413 to 2413 kPa (-349.97 to 349.97 psi)

Circuit #2 - Evaporator Refrigerant Pressure 45 R -2413 to 2413 kPa (-349.97 to 349.97 psi)

Circuit #3 - Evaporator Refrigerant Pressure 49 RW -2413 to 2413 kPa (-349.97 to 349.97 psi)

Circuit #1 - Evaporator Saturated Refrigerant Temp 42 R -26.1 to 85°C (-14.98 to 185°F)

Circuit #2 - Evaporator Saturated Refrigerant Temp 46 R -26.1 to 85°C (-14.98 to 185°F)

Circuit #3 - Evaporator Saturated Refrigerant Temp 50 R -26.1 to 85°C (-14.98 to 185°F)

Evaporator SuperHeat Setpoint 1897 R

Evaporator SuperHeat Temp 1899 R

Circuit #1 - EXV Position 1982 R 0 to 110%

Circuit #2 - EXV Position 1966 R

Circuit #3 - EXV Position 1950 R

Fault Alarm Code 33 R 0=No Alarms


32551=COMP SHUTDOWN–Low pressure ratio Circ #1, Comp #1
32583=COMP SHUTDOWN – Low pressure ratio Circ #2, Comp #1
32615=COMP SHUTDOWN–Low pressure ratio Circ #3, Comp #1
32651=COMP SHUTDOWN – Minimum Delta Pressure Circuit #1
32652= COMP SHUTDOWN – Minimum Delta Pressure Circuit #2
32653= COMP SHUTDOWN – Minimum Delta Pressure Circuit #3
32771=COMP SHUTDOWN-Outside Air Temp Sensor Fault,
33063=COMP SHUTDOWN-Current Overload Circ #1, Comp #1
33095=COMP SHUTDOWN-Current Overload Circ #2, Comp #1

D-EOMOC002(04)09-15EN - 13/35
H.R.1

R/W2
Data Point Range/Description

33127= COMP SHUTDOWN-Current Overload Circ #3, Comp #1


34087= COMP SHUTDOWN– Motor Protector Circ #1 Comp #1
34119= COMP SHUTDOWN– Motor Protector Circ #2 Comp #1
34599=COMP SHUTDOWN–Motor Temp High Circ #1, Comp #1
34631=COMP SHUTDOWN-Motor Temp High Circ #2, Comp #1
34663=COMP SHUTDOWN–Motor Temp High Circ #3, Comp #1
34855= COMP SHUTDOWN–Motor Temp Sensor Fault Circ #1, Comp #1
34887= COMP SHUTDOWN–Motor Temp Sensor Fault Circ #2, Comp #1
34919= COMP SHUTDOWN–Motor Temp Sensor Fault Circ #3, Comp #1
36387=CIRC SHUTDOWN – Condenser Pressure Sensor Circ #1 Fault
36391=COMP SHUTDOWN-Condenser Pressure Sensor Fault Circ #1, Comp #1
36419=CIRC SHUTDOWN – Condenser Pressure Sensor Circ #2 Fault
36423=COMP SHUTDOWN-Condenser Pressure Sensor Fault Circ #2, Comp #1
36455=COMP SHUTDOWN-Condenser Pressure Sensor Fault Circ #3, Comp #1
37155=CIRC SHUTDOWN – Condenser Pressure High Circ #1 Fault
37159=COMP SHUTDOWN-Condenser Pressure High Circ #1, Comp #1
37187=CIRC SHUTDOWN – Condenser Pressure High Circ #2 Fault
37191=COMP SHUTDOWN-Condenser Pressure High Circ #2, Comp #1
37223=COMP SHUTDOWN-Condenser Pressure High Circ #3, Comp #1
37671=COMP SHUTDOWN-Discharge Temp Sensor Fault Circ #1, Comp #1
37703=COMP SHUTDOWN-Discharge Temp Sensor Fault Circ #2, Comp #1
37735=COMP SHUTDOWN-Discharge Temp Sensor Fault Circ #3, Comp #1
37927=COMP SHUTDOWN-Discharge Temp High Circ #1, Comp #1
37959=COMP SHUTDOWN-Discharge Temp High Circ #2, Comp #1
37991=COMP SHUTDOWN-Discharge Temp High Circ #3, Comp #1
38403=UNIT SHUTDOWN-Evaporator Water Flow Loss
38659=UNIT SHUTDOWN–Evaporator Leaving Water Temp Low (Freeze)
38915=COMP SHUTDOWN-Evaporator Pressure Low
39203=CIRC SHUTDOWN – Low Evaporator Pressure Circ #1 Fault
39207=COMP SHUTDOWN-Evaporator Pressure Low Circ #1, Comp #1
39235=CIRC SHUTDOWN – Low Evaporator Pressure Circ #2 Fault
39239=COMP SHUTDOWN–Evaporator Pressure Low Circ #2, Comp #1
39271=COMP SHUTDOWN-Evaporator Pressure Low Circ #3, Comp #1
39715=CIRC SHUTDOWN – Evaporator Pressure Sensor Circ #1 Fault
39719=COMP SHUTDOWN-Evaporator Pressure Sensor Fault Circ #1, Comp #1
39747=CIRC SHUTDOWN – Evaporator Pressure Sensor Circ #2 Fault
39751=COMP SHUTDOWN-Evaporator Pressure Sensor Fault Circ #2, Comp #1
39783=COMP SHUTDOWN-Evaporator Pressure Sensor Fault Circ #3, Comp #1
41255=COMP LOCKOUT- Num of Allowed Re-Starts Exceeded Circ #1, Comp #1
41287=COMP LOCKOUT- Num of Allowed Re-Starts Exceeded Circ #2, Comp #1
41319=COMP LOCKOUT- Num of Allowed Re-Starts Exceeded Circ #3, Comp #1
41475=UNIT SHUTDOWN-Evaporator Leaving Water Temp Sensor Fault
41731=UNIT SHUTDOWN-Evaporator Entering Water Temp Sensor Failure
42535=COMP SHUTDOWN-Mechanical High Pressure Circ #1, Comp #1
42567=COMP SHUTDOWN-Mechanical High Pressure Circ #2, Comp #1
42599=COMP SHUTDOWN-Mechanical High Pressure Circ #3, Comp #1
44327=COMP SHUTDOWN-Oil Feed Pressure Sensor Fault Circ #1, Comp #1
44359=COMP SHUTDOWN-Oil Feed Pressure Sensor Fault Circ #2, Comp #1
44391=COMP SHUTDOWN-Oil Feed Pressure Sensor Fault Circ #3, Comp #1
45059=SHUTDOWN-Phase Voltage Protection
45351=COMP SHUTDOWN–Starter Fault Comp Circ #1, Comp #1
45383=COMP SHUTDOWN–Starter Fault Comp Circ #2, Comp #1
45415=COMP SHUTDOWN–Starter Fault Comp Circ #3, Comp #1
46887=COMP SHUTDOWN-Suction Temp Sensor Fault Circ #1, Comp #1
46919=COMP SHUTDOWN-Suction Temp Sensor Fault Circ #2, Comp #1
46951=COMP SHUTDOWN-Suction Temp Sensor Fault Circ #3, Comp #1
47911=COMP SHUTDOWN–Mechanical Low Pressure Circ #1, Comp #1
47943=COMP SHUTDOWN–Mechanical Low Pressure Circ #2, Comp #1
47975=COMP SHUTDOWN–Mechanical Low Pressure Circ #3, Comp #1
48131=Unit Controller offline
48163=Controller board offline Circ #1
48195=Controller board offline Circ #2
48227=Controller board offline Circ #3
48911=Circuit Global Alarm, Circuit #1
48912=Circuit Global Alarm, Circuit #2
48913=Circuit Global Alarm, Circuit #3
48419=COMP SHUTDOWN–No Pressure Change After Start Circ #1
48451=COMP SHUTDOWN–No Pressure Change After Start Circ #2
48483=COMP SHUTDOWN–No Pressure Change After Start Circ #3
48675=COMP SHUTDOWN–No Pressure at Startup Circ #1
48707=COMP SHUTDOWN–No Pressure at Startup Circ #2
48739=COMP SHUTDOWN–No Pressure at Startup Circ #3
48935=COMP SHUTDOWN-Slide position sensor fault Circ #1, Comp#1

D-EOMOC002(04)09-15EN - 14/35
H.R.1

R/W2
Data Point Range/Description

48967=COMP SHUTDOWN-Slide position sensor fault Circ #2, Comp#1


48999=COMP SHUTDOWN-Slide position sensor fault Circ #3, Comp#1
49155=UNIT STOP–Emergency Stop Alarm
49411=UNIT STOP–Evaporator Water Temps Inverted
49667=UNIT STOP–External Alarm
49923=Evaporator Leaving Water Temp 1 Sensor Fault
50179=Evaporator Leaving Water Temp 2 Sensor Fault
50435=CIRC SHUTDOWN-Evaporator 1 Freeze Protection
50691=CIRC SHUTDOWN-Evaporator 2 Freeze Protection
50983=COMP SHUTDOWN-COMP VFD Fault Circ #1, Comp #1
51015=COMP SHUTDOWN-COMP VFD Fault Circ #2, Comp #1
51047=COMP SHUTDOWN-COMP VFD Fault Circ #3, Comp #1
51239=COMP SHUTDOWN-COMP VFD Over Heat Fault Circ #1, Comp #1
51271=COMP SHUTDOWN-COMP VFD Over Heat Fault Circ #2, Comp #1
51303=COMP SHUTDOWN-COMP VFD Over Heat Fault Circ #3, Comp #1
51495=COMP SHUTDOWN-COM ERROR With COMP VFD Circ #1, Comp #1
51527=COMP SHUTDOWN-COM ERROR With COMP VFD Circ #2, Comp #1
51559=COMP SHUTDOWN-COM ERROR With COMP VFD Circ #3, Comp #1
51755 = COMP SHUTDOWN -Low Discharge Superheat Circ #1, Comp #1
51783 = COMP SHUTDOWN -Low Discharge Superheat Circ #2, Comp #1
51815 = COMP SHUTDOWN -Low Discharge Superheat Circ #3, Comp #1
58371= UNIT STOP - PVM GFP Fault
58403= CIRC SHUTDOWN- PVM GFP Circ #1 Fault
58435= CIRC SHUTDOWN- PVM GFP Circ #2 Fault
58915=COMP SHUTDOWN-Refrig Charge Circ #1
58947=COMP SHUTDOWN-Refrig Charge Circ #2
58979=COMP SHUTDOWN-Refrig Charge Circ #3

Fault Alarm Index 30 R 0=No Alarms


127=COMP SHUTDOWN–Low pressure ratio #n
128=COMP SHUTDOWN-Outside Air Temp Sensor Fault
129=COMP SHUTDOWN-Current Overload Circuit #n, Comp #n
135=COMP SHUTDOWN–Motor Temp High Circuit #n
136=COMP SHUTDOWN–Motor Temp Sensor Fault #n
142=COMP SHUTDOWN-Condenser Pressure Sensor Fault #n
145=COMP SHUTDOWN-Condenser Pressure High #n
147=COMP SHUTDOWN-Discharge Temp Sensor Fault #n
148=COMP SHUTDOWN-Discharge Temp High #n
150=UNIT SHUTDOWN-Evaporator Water Flow Loss
151=UNIT SHUTDOWN–Evaporator Leaving Water Temp Low (Freeze)
153=COMP SHUTDOWN-Evaporator Pressure Low #n,
155=COMP SHUTDOWN-Evaporator Pressure Sensor Fault #n
161=COMP LOCKOUT-Number of Allowed Re-Starts Exceeded #n
162=UNIT SHUTDOWN-Evaporator Leaving Water Temp Sensor Fault
163=UNIT SHUTDOWN-Evaporator Entering Water Temp Sensor Failure
166=COMP SHUTDOWN-Mechanical High Pressure #n
172=COM SHUTDOWN-Oil Delta Pressure High Circuit #1, Comp #1
173=COMP SHUTDOWN-Oil Feed Pressure Sensor Fault #n
176=SHUTDOWN–Phase Voltage Protection
177=COMP SHUTDOWN–Starter Fault Comp #n
183=COMP SHUTDOWN-Suction Temp Sensor Fault #n
187=COMP SHUTDOWN–Mechanical Low Pressure #n
188=Controller board offline Circuit #n
189=COMP SHUTDOWN –No Pressure Change After Start
190=COMP SHUTDOWN–No Pressure at Startup
191=CIRCUIT SHUTDOWN–Evaporator Freeze Protection
192=UNIT STOP–Emergency Stop Alarm
193=UNIT STOP–Evaporator Water Temps Inverted
194=UNIT STOP–External Alarm
195=Evaporator Leaving Water Temp 1 Sensor Fault
196=Evaporator Leaving Water Temp 2 Sensor Fault
197=CIRCUIT SHUTDOWN-Evaporator 1 Freeze Protection
198=CIRCUIT SHUTDOWN-Evaporator 2 Freeze Protection
199=COMP SHUTDOWN-COMP VFD Fault Circuit #n, Comp #n
200=COMP SHUTDOWN-COMP VFD Over Heat Fault Circuit #n, Comp #n
201=COMP SHUTDOWN-COM ERROR With COMP VFD Circuit #n, Comp #n
202=COMP SHUTDOWN-Low Discharge Superheat Circuit #n, Comp #n
230=COMP SHUTDOWN-Refrig Charge Circuit #n
251=CIRCUIT STOP – Global Alarm, Circuit #1
252=CIRCUIT STOP – Global Alarm, Circuit #2
253= CIRCUIT STOP – Global Alarm, Circuit #3
261=CIRCUIT SHUTDOWN - Minimum Delta Pressure Circuit #1
262= CIRCUIT SHUTDOWN - Minimum Delta Pressure Circuit #2
263= CIRCUIT SHUTDOWN - Minimum Delta Pressure Circuit #3

D-EOMOC002(04)09-15EN - 15/35
H.R.1

R/W2
Data Point Range/Description

Heat Recovery Enable - Network 18 RW 0=Disable, 1=Enable

Heat Recovery Entering Water Temp 22 R Enabled whit Heat Recovery option

Heat Recovery Leaving Water Temp 23 R Enabled whit Heat Recovery option

Heat Setpoint – Network 37 RW ACZH: 25.0 to 55.0 °C (77.0 to 131°F)

ATLAS: 30.0 to 50.0°C (86.0 to 122 °F)

AWS: 25.0 to 55.0 °C (77.0 to 131°F)

EWWD: 25.0 to 60.0 °C (77.0 to 140 °F)

GIZMO: 25.0 to 55.0 °C (77.0 to 131°F)

PFS: 25.0 to 65.0 °C (77.0 to 149°F)

WATER STREAM: 25.0 to 50.0 °C (77.0 to 122°F)

Hour 313 RW 0-23

Ice Setpoint - Network 36 RW ACZC: -9.5 to 4.4 °C (14.9 to 39.9°F)

ACZH: -9.5 to 4.4 °C (14.9 to 39.9°F)

ADZ: -9.5 to 4.4 °C (14.9 to 39.9°F)

ATLAS: -8.0 to 4.0 °C (17.6 to 39.2 °F)

AWS: -8.0 to 4.0 °C (17.6 to 39.2 °F)

EWWD: -9.4 to 3.4 °C (15.08 to 38.12 °F)

GIZMO: -15 to 4 °C (5.0 to 39.2 °F)

MNG: -9.4 to 3.4 °C (15.08 to 38.12 °F)

PFS: -9.4 to 3.4 °C (15.08 to 38.12 °F)

WATER STREAM: -15 to 4 °C (5.0 to 39.2 °F)

Liquid Temp 1984 R

Minute 314 RW 0-59

Month 310 RW 12/01/2015

Noise Reduction Auto On 1998 RW

Noise Reduction Status 2000 R

Number of Circuits 1607 R

Number of Comps 1608 R

Outdoor Air Temp 24 R -40 to 110°C (-40 to 230°F)

Circuit #1 - Outdoor Fan Speed 1986 R

Circuit #2 - Outdoor Fan Speed 1970 R

Circuit #3 - Outdoor Fan Speed 1954 R

Circuit #1 - Outdoor Fan Status 1997 R

Circuit #2 - Outdoor Fan Status 1981 R

Circuit #3 - Outdoor Fan Status 1965 RW

Power Factor 1902 R Enabled with Power meter optional

Power Input 27 R Enabled with Power meter optional

Problem Alarm Code 32 R 0=No Alarms


16418=RESTART DELAYED - Power Loss While Running Circuit #1
16450=RESTART DELAYED - Power Loss While Running Circuit #2
16482=RESTART DELAYED - Power Loss While Running Circuit #3
16642=START INHIBITED - Ambient Temp Low
16898=INHIBIT LOAD – Condenser Pressure High
17186=INHIBIT LOAD – Condenser Pressure High Circuit #1
17218=INHIBIT LOAD – Condenser Pressure High Circuit #2
17250=INHIBIT LOAD – Condenser Pressure High Circuit #3

D-EOMOC002(04)09-15EN - 16/35
H.R.1

R/W2
Data Point Range/Description

17282=INHIBIT LOAD –Condenser Pressure High Circuit #1


17730=UNLOAD Condenser Pressure High Circuit #2
17762=UNLOAD Condenser Pressure High Circuit #3
17794=UNLOAD LOAD - Evaporator Pressure Low Circuit #1
19522=INHIBIT LOAD - Evaporator Pressure Low Circuit #2
19554=INHIBIT LOAD - Evaporator Pressure Low Circuit #3
19586=INHIBIT LOAD - Evaporator Pressure Low Circuit #1
20034=UNLOAD - Evaporator Pressure Low Circuit #2
20066=UNLOAD - Evaporator Pressure Low Circuit #3
20098=UNLOAD - Evaporator
20262=UNLOAD-Comp Motor Current High Circuit #1, Comp #1
20294=UNLOAD-Comp Motor Current High Circuit #2, Comp #1
20326=UNLOAD-Comp Motor Current High Circuit #3, Comp #1
20738=PUMP #2 START ATTEMPTED - Evaporator Pump #1 Failure
20994=PUMP #1 START ATTEMPTED - Evaporator Pump #2 Failure
21542=INHIBIT LOAD-Comp Motor Current High Circuit #1, Comp #1
21574=INHIBIT LOAD-Comp Motor Current High Circuit #2, Comp #1
21606= INHIBIT LOAD-Comp Motor Current High Circuit #3, Comp #1

Problem Alarm Index 29 R 0=No Alarms


64=RESTART DELAYED-Power Loss While Running Circuit #n
65=START INHIBITED - Ambient Temp Low
67=INHIBIT LOAD – Condenser Pressure High Circuit #n
69=UNLOAD – Condenser Pressure High Circuit #n
76=INHIBIT LOAD - Evaporator Pressure Low Circuit #n
78=UNLOAD - Evaporator Pressure Low Circuit #n
79=UNLOAD - Comp Motor Current High Circuit #n, Comp #n
81=PUMP #2 START ATTEMPTED - Evaporator Pump #1 Failure
82=PUMP #1 START ATTEMPTED - Evaporator Pump #2 Failure
84= INHIBIT LOAD-Comp Motor Current High Circuit #n, Comp #n
Refrigerant Type 1606 R

Run Enabled 3 R 0=Off, 1= Run Allowed

Second 315 RW 0-59

Units 316 RW 0=English, 1=Metric

Warning Alarm Code 31 R 0=No Alarms


513=Evaporator Entering Water Temp Sensor Failure
2049=Bad setpoint override input
2305=Bad demand limit input
2401=Circuit 1 failed pump down Hi Press
2402=Circuit 2 Failed pump down Hi Press
2403=Circuit 3 Failed pump down Hi Press
2817=Unit power restore
3105=Circuit 1 failed pumpdown
3137=Circuit 2 Failed pumpdown
3169=Circuit 3 failed pumpdown
3201=Circuit 4 failed pumpdown
3329=External Event
3585=Bad Current Limit Input
3841=Option Controller Communication Failed
4128=Circuit 1 Low Refrigerant Charge
4160=Circuit 2 Low Refrigerant Charge
4192=Circuit 3 Low Refrigerant Charge
4352=Chiller Network Communication Failure

Warning Alarm Index 28 R 0=No Alarms


8=Bad setpoint override input
9=Bad demand limit input
11=Unit power restore
12=Circuit failed pumpdown
13=External Event
14 = Bad Current Limit Input
15=Option Controller Communication Failed
16=Low Refrigerant Charge
17=Chiller Network Communication Failure
21= Circuit 1 failed pump down Hi Press
22= Circuit 2 failed pump down Hi Press
23= Circuit 3 failed pump down Hi Press
Year 309 RW -

D-EOMOC002(04)09-15EN - 17/35
Alarm Points

Alarm Points for Chiller Models


Table 4 contains the list of Modbus alarm points available from the MicroTech III Chiller Unit Controller
depending on the chiller model and corresponding unit controller application software. Application software
name is available in the unit HMI: see in Main Menu, “About Chiller”.

Table 4. MicroTech III Unit Controller Alarm Points List for Chiller Model

STREAM
WATER
ATLAS

EWWD

GIZMO
ACZC

ACZH

AWS

MNG
ADZ

PFS
Alarm Point

Bad Current Limit Input Warning X X X X X

Bad demand limit input Warning X X X X X X X X X X

Bad setpoint override input Warning X X X X X X X X X X

Circuit Controller board offline Fault X X X X X X X X X

Circuit Failed pumpdown - High Pressure X

Circuit Failed pumpdown Warning X X X X X X X X X

Circuit Global Alarm X

Circuit INHIBIT LOAD - High Current Problem X X X X X X X X

Circuit INHIBIT LOAD - High Pressure Problem X X X X X X X X

Circuit INHIBIT LOAD - Low Pressure Problem X X X X

Circuit Option Fan Alarm Warning X

Circuit SHUTDOWN – Evap Pressure Sensor Fault X X X X X X X X X

Circuit SHUTDOWN – Low Evap Pressure Fault X X X X X X X X X

Circuit SHUTDOWN – Minimum Delta Pressure X

Circuit SHUTDOWN – No Pressure at Startup Fault X X X X X X X X

Circuit SHUTDOWN – No Pressure Change After Start X X X X X X X X X X

Circuit SHUTDOWN – Phase Voltage Protection Fault X X X X X X X X

CIRCUIT UNLOAD - High Pressure Problem X X X X

CIRCUIT UNLOAD - Low Pressure Problem X X X X

Comp LOCKOUT - Allowed Re-Starts Exceeded Fault X X X X X X X X X

Comp SHUTDOWN - COM ERROR With VFD Fault X X X X X X X

Comp SHUTDOWN - Discharge Temp High Fault X X X X X X X X X X

Comp SHUTDOWN - Discharge Temp Sensor Fault X X X X X X X X X X

Comp SHUTDOWN - Low pressure ratio Fault X X X X X X X X X

Comp SHUTDOWN - Mechanical High Pressure Fault X X X X X X X X X X

Comp SHUTDOWN - Mechanical Low Pressure Fault X X X X X X X X X

Comp SHUTDOWN – Motor Protector Fault X X X X

Comp SHUTDOWN - Motor Temp High Fault X X X X X X X X X

Comp SHUTDOWN - Motor Temp Sensor Fault X X X X X X X X X

Comp SHUTDOWN - Oil Delta Pressure High Fault X X X X X X X X X

Comp SHUTDOWN - Oil Feed Pressure Sensor Fault X X X X X X X X X

D-EOMOC002(04)09-15EN - 18/35
STREAM
WATER
ATLAS

EWWD

GIZMO
ACZC

ACZH

AWS

MNG
ADZ

PFS
Alarm Point

Comp SHUTDOWN - Slide position Sensor Fault X X X X X X

Comp SHUTDOWN - Starter Fault X X X X X X X X X

Comp SHUTDOWN - Suction Temp Sensor Fault X X X X X X X X X X

Comp SHUTDOWN - VFD Fault X X X X X X X

Comp SHUTDOWN - VFD Over Heat Fault X X X X X X X

Comp SHUTDOWN -Current Overload Fault X X X X X X X X

Comp SHUTDOWN-Low Discharge Superheat Fault X X X X X X

Condenser Ent Water Temp Sensor Fault X X

Condenser Leav Water Temp Sensor Fault X X X

Evap Ent Water Temp Sensor Fault X X X X X

Evap Leav Water Temp Sensor Fault X X X X X X X X

Evap Pump #1 Failure - Pump #2 Start Attempted Problem X X X X X X X

Evap Pump #2 Failure - Pump #1 Start Attempted Problem X X X X X X X

External event Warning X X X X X X X X X X

Option Fan Controller Communication Failed Warning X

Option Controller Communication Failed Warning X X X X X

Circuit RESTART DELAYED - Power Loss While Running Problem X X X X X X X X X

CIRCUIT SHUTDOWN – Condenser Pressure High Fault X X X X X X X X X X

CIRCUIT SHUTDOWN – Condenser Pressure Sensor Fault X X X X X X X X X

START INHIBITED - Ambient Temp Low Problem X X X X X X X X X

Unit Power Restore Warning X X X X X

UNIT INHIBIT LOAD - High Pressure Problem X

UNIT INHIBIT LOAD - Low Pressure Problem

UNIT RESTART DELAYED - Power Loss While Running Problem X

UNIT SHUTDOWN - Condenser Flow Loss X

UNIT SHUTDOWN - Condenser High Pressure X

UNIT SHUTDOWN - Discharge High Temp X

UNIT SHUTDOWN - Evap Ent Water Temp Sensor Fault X X X X X

UNIT SHUTDOWN - Evap Freeze Protection Fault X X X X X X X X

UNIT SHUTDOWN - Evap Leav Water Temp Low X X X X X X X X X X

UNIT SHUTDOWN - Evap Leav Water Temp Sensor Fault X X X X X X X X X X

UNIT SHUTDOWN - Evap Low Pressure X

UNIT SHUTDOWN – Evap Pressure Sensor Fault X

UNIT SHUTDOWN - Evap Water Flow Loss X X X X X X X X X X

UNIT SHUTDOWN - Outside Air Temp Sensor Fault X X X X X X X X X

UNIT SHUTDOWN – Phase Voltage Protection Fault X X X X X X X

UNIT SHUTDOWN – Phase Voltage Protection Fault X X X X X

UNIT STOP - Emergency Stop Alarm X X X X X X X X X

UNIT STOP - Evap Water Temps Inverted X X X X X X X X X X

UNIT STOP - External Alarm X X X X X X X X X X

UNIT UNLOAD - High Pressure Problem X

D-EOMOC002(04)09-15EN - 19/35
STREAM
WATER
ATLAS

EWWD

GIZMO
ACZC

ACZH

AWS

MNG
ADZ

PFS
Alarm Point

UNIT UNLOAD - Low Pressure Problem X

CIRCUIT UNLOAD - Hi Current Problem X X X X X X X X X

Unit Controller board offline Fault X X X X X X X X

UNIT SHUTDOWN – Condenser Pressure Sensor Fault X

UNIT SHUTDOWN - Low Pressure Ratio X

Comprehensive Alarm Points List


Table 5 contains the complete list of Modbus Alarm points available from the MicroTech III Chiller Unit
Controller. Detailed description of all Microtech III Alarms available to the network will be included in next
release of this document.

Table 5. MicroTech III Unit Controller Modbus Comprehensive Alarm Point List
Alarm Point H.R.3 R/W Range

Bad Current Limit Input Warning 814 R 0=Normal, 1=Alarm

Bad demand limit input Warning 378 R 0=Normal, 1=Alarm

Bad setpoint override input Warning 377 R 0=Normal, 1=Alarm

Circuit #1 - Controller board offline Fault 723 R 0=Normal, 1=Alarm

Circuit #2 - Controller board offline Fault 724 R 0=Normal, 1=Alarm

Circuit #3 - Controller board offline Fault 725 R 0=Normal, 1=Alarm

Circuit #1 - Failed pumpdown - High Pressure 841 R 0=Normal, 1=Alarm

Circuit #2 - Failed pumpdown - High Pressure 842 R 0=Normal, 1=Alarm

Circuit #1 - Failed pumpdown Warning 741 R 0=Normal, 1=Alarm

Circuit #2 - Failed pumpdown Warning 742 R 0=Normal, 1=Alarm

Circuit #3 - Failed pumpdown Warning 743 R 0=Normal, 1=Alarm

Circuit #1 - SHUTDOWN - Global Alarm 911 R 0=Normal, 1=Alarm

Circuit #2 - SHUTDOWN - Global Alarm 912 R 0=Normal, 1=Alarm

Circuit #1 - INHIBIT LOAD - High Current Problem 780 R 0=Normal, 1=Alarm

Circuit #2 - INHIBIT LOAD - High Current Problem 782 R 0=Normal, 1=Alarm

Circuit #3 - INHIBIT LOAD - High Current Problem 784 R 0=Normal, 1=Alarm

Circuit #1 - INHIBIT LOAD - High Pressure Problem 390 R 0=Normal, 1=Alarm

Circuit #2 - INHIBIT LOAD - High Pressure Problem 391 R 0=Normal, 1=Alarm

Circuit #3 - INHIBIT LOAD - High Pressure Problem 392 R 0=Normal, 1=Alarm

Circuit #1 - INHIBIT LOAD - Low Pressure Problem 411 R 0=Normal, 1=Alarm

Circuit #2 - INHIBIT LOAD - Low Pressure Problem 412 R 0=Normal, 1=Alarm

Circuit #3 - INHIBIT LOAD - Low Pressure Problem 413 R 0=Normal, 1=Alarm

Circuit #1 - Option Fan Alarm Warning 901 R 0=Normal, 1=Alarm

Circuit #2 - Option Fan Alarm Warning 902 R 0=Normal, 1=Alarm

Circuit #1 - SHUTDOWN – Evaporator Pressure Sensor Fault 552 R 0=Normal, 1=Alarm

Circuit #2 - SHUTDOWN – Evaporator Pressure Sensor Fault 554 R 0=Normal, 1=Alarm

3
Holding Register (4xxxx)

D-EOMOC002(04)09-15EN - 20/35
3
Alarm Point H.R. R/W Range

Circuit #3 - SHUTDOWN - Evaporator Pressure Sensor Fault 556 R 0=Normal, 1=Alarm

Circuit #1 - SHUTDOWN – Low Evaporator Pressure Fault 545 R 0=Normal, 1=Alarm

Circuit #2 - SHUTDOWN – Low Evaporator Pressure Fault 547 R 0=Normal, 1=Alarm

Circuit #3 - SHUTDOWN - Low Evaporator Pressure Fault 549 R 0=Normal, 1=Alarm

Circuit #1 - SHUTDOWN – Low Evaporator Pressure Fault 461 R 0=Normal, 1=Alarm

Circuit #2 - SHUTDOWN – Low Evaporator Pressure Fault 462 R 0=Normal, 1=Alarm

Circuit #1 - SHUTDOWN – No Pressure at Startup Fault 711 R 0=Normal, 1=Alarm

Circuit #2 - SHUTDOWN – No Pressure at Startup Fault 712 R 0=Normal, 1=Alarm

Circuit #3 - SHUTDOWN – No Pressure at Startup Fault 713 R 0=Normal, 1=Alarm

Circuit #1 - SHUTDOWN – No Pressure Change After Start 747 R 0=Normal, 1=Alarm

Circuit #2 - SHUTDOWN – No Pressure Change After Start 748 R 0=Normal, 1=Alarm

Circuit #3 - SHUTDOWN – No Pressure Change After Start 749 R 0=Normal, 1=Alarm

Circuit #1 - SHUTDOWN – Phase Voltage Protection Fault (ATLAS, AWS, EWWD, MNG) 751 R 0=Normal, 1=Alarm

Circuit #1 - SHUTDOWN – Phase Voltage Protection Fault (ACZC, ACZH, ADZ) 817 R 0=Normal, 1=Alarm

Circuit #2 - SHUTDOWN – Phase Voltage Protection Fault (ATLAS, AWS, EWWD, MNG) 752 R 0=Normal, 1=Alarm

Circuit #2 - SHUTDOWN – Phase Voltage Protection Fault (ACZC, ACZH, ADZ) 818 R 0=Normal, 1=Alarm

Circuit #3 - SHUTDOWN – Phase Voltage Protection Fault (AWS) 753 R 0=Normal, 1=Alarm

Circuit #1 - UNLOAD - High Pressure Problem 395 R 0=Normal, 1=Alarm

Circuit #2 - UNLOAD - High Pressure Problem 396 R 0=Normal, 1=Alarm

Circuit #3 - UNLOAD - High Pressure Problem 397 R 0=Normal, 1=Alarm

Circuit #1 - UNLOAD - Low Pressure Problem 416 R 0=Normal, 1=Alarm

Circuit #2 - UNLOAD - Low Pressure Problem 417 R 0=Normal, 1=Alarm

Circuit #3 - UNLOAD - Low Pressure Problem 418 R 0=Normal, 1=Alarm

Circuit #1 Comp #1 - LOCKOUT - Number of Allowed Re-Starts Exceeded Fault 583 R 0=Normal, 1=Alarm

Circuit #2 Comp #1 - LOCKOUT - Number of Allowed Re-Starts Exceeded Fault 585 R 0=Normal, 1=Alarm

Circuit #3 Comp #1 - LOCKOUT - Number of Allowed Re-Starts Exceeded Fault 587 R 0=Normal, 1=Alarm

Circuit #1 Comp #1 - SHUTDOWN - COM ERROR With VFD Fault 774 R 0=Normal, 1=Alarm

Circuit #2 Comp #1 - SHUTDOWN - COM ERROR With VFD Fault 776 R 0=Normal, 1=Alarm

Circuit #3 Comp #1 - SHUTDOWN - COM ERROR With VFD Fault 778 R 0=Normal, 1=Alarm

Circuit #1 Comp #1 - SHUTDOWN - Discharge Temp High Fault 535 R 0=Normal, 1=Alarm

Circuit #1 Comp #2 - SHUTDOWN - Discharge Temp High Fault (PFS) 536 R 0=Normal, 1=Alarm

Circuit #2 Comp #1 - SHUTDOWN - Discharge Temp High Fault 537 R 0=Normal, 1=Alarm

Circuit #3 Comp #1 - SHUTDOWN - Discharge Temp High Fault 539 R 0=Normal, 1=Alarm

Circuit #1 Comp #1 - SHUTDOWN - Discharge Temp Sensor Fault 529 R 0=Normal, 1=Alarm

Circuit #1 Comp #2 - SHUTDOWN - Discharge Temp Sensor Fault (PFS) 530 R 0=Normal, 1=Alarm

Circuit #2 Comp #1 - SHUTDOWN - Discharge Temp Sensor Fault 531 R 0=Normal, 1=Alarm

Circuit #3 Comp #1 - SHUTDOWN - Discharge Temp Sensor Fault 533 R 0=Normal, 1=Alarm

Circuit #1 Comp #1 - SHUTDOWN - Low pressure ratio Fault 440 R 0=Normal, 1=Alarm

Circuit #2 Comp #1 - SHUTDOWN - Low pressure ratio Fault 442 R 0=Normal, 1=Alarm

Circuit #3 Comp #1 - SHUTDOWN - Low pressure ratio Fault 444 R 0=Normal, 1=Alarm

Circuit #1 Comp #1 - SHUTDOWN - Mechanical High Pressure Fault 601 R 0=Normal, 1=Alarm

Circuit #1 Comp #2 - SHUTDOWN - Mechanical High Pressure Fault (PFS) 602 R 0=Normal, 1=Alarm

Circuit #2 Comp #1 - SHUTDOWN - Mechanical High Pressure Fault 603 R 0=Normal, 1=Alarm

D-EOMOC002(04)09-15EN - 21/35
3
Alarm Point H.R. R/W Range

Circuit #3 Comp #1 - SHUTDOWN - Mechanical High Pressure Fault 605 R 0=Normal, 1=Alarm

Circuit #1 Comp #1 - SHUTDOWN - Mechanical Low Pressure Fault 717 R 0=Normal, 1=Alarm

Circuit #1 Comp #2 - SHUTDOWN - Mechanical Low Pressure Fault (PFS) 718 R 0=Normal, 1=Alarm

Circuit #2 Comp #1 - SHUTDOWN - Mechanical Low Pressure Fault 719 R 0=Normal, 1=Alarm

Circuit #3 Comp #1 - SHUTDOWN - Mechanical Low Pressure Fault 721 R 0=Normal, 1=Alarm

Circuit #1 Comp #1 - SHUTDOWN – Motor Protector Fault 466 R 0=Normal, 1=Alarm

Circuit #1 Comp #2 - SHUTDOWN – Motor Protector Fault 467 R 0=Normal, 1=Alarm

Circuit #1 Comp #3 - SHUTDOWN – Motor Protector Fault 470 R 0=Normal, 1=Alarm

Circuit #2 Comp #1 - SHUTDOWN – Motor Protector Fault 468 R 0=Normal, 1=Alarm

Circuit #2 Comp #2 - SHUTDOWN – Motor Protector Fault 469 R 0=Normal, 1=Alarm

Circuit #2 Comp #3 - SHUTDOWN – Motor Protector Fault 471 R 0=Normal, 1=Alarm

Circuit #1 Comp #1 - SHUTDOWN - Motor Temp High Fault 478 R 0=Normal, 1=Alarm

Circuit #1 Comp #2 - SHUTDOWN - Motor Temp High Fault (PFS) 479 R 0=Normal, 1=Alarm

Circuit #2 Comp #1 - SHUTDOWN - Motor Temp High Fault 480 R 0=Normal, 1=Alarm

Circuit #3 Comp #1 - SHUTDOWN - Motor Temp High Fault 482 R 0=Normal, 1=Alarm

Circuit #1 Comp #1 - SHUTDOWN - Motor Temp Sensor Fault 734 R 0=Normal, 1=Alarm

Circuit #1 Comp #2 - SHUTDOWN - Motor Temp Sensor Fault (PFS) 735 R 0=Normal, 1=Alarm

Circuit #2 Comp #1 - SHUTDOWN - Motor Temp Sensor Fault 736 R 0=Normal, 1=Alarm

Circuit #3 Comp #1 - SHUTDOWN - Motor Temp Sensor Fault 738 R 0=Normal, 1=Alarm

Circuit #1 Comp #1 - SHUTDOWN - Oil Delta Pressure High Fault 637 R 0=Normal, 1=Alarm

Circuit #1 Comp #2 - SHUTDOWN - Oil Delta Pressure High Fault (PFS) 638 R 0=Normal, 1=Alarm

Circuit #2 Comp #1 - SHUTDOWN - Oil Delta Pressure High Fault 639 R 0=Normal, 1=Alarm

Circuit #3 Comp #1 - SHUTDOWN - Oil Delta Pressure High Fault 641 R 0=Normal, 1=Alarm

Circuit #1 Comp #1 - SHUTDOWN - Oil Feed Pressure Sensor Fault 643 R 0=Normal, 1=Alarm

Circuit #1 Comp #1 - SHUTDOWN - Oil Feed Pressure Sensor Fault (PFS) 649 R 0=Normal, 1=Alarm

Circuit #1 Comp #2 - SHUTDOWN - Oil Feed Pressure Sensor Fault (PFS) 650 R 0=Normal, 1=Alarm

Circuit #2 Comp #1 - SHUTDOWN - Oil Feed Pressure Sensor Fault 645 R 0=Normal, 1=Alarm

Circuit #3 Comp #1 - SHUTDOWN - Oil Feed Pressure Sensor Fault 647 R 0=Normal, 1=Alarm

Circuit #1 Comp #1 - SHUTDOWN -Slide position Sensor Fault 756 R 0=Normal, 1=Alarm

Circuit #1 Comp #2 - SHUTDOWN - Slide position Sensor Fault (PFS) 757 R 0=Normal, 1=Alarm

Circuit #2 Comp #1 - SHUTDOWN - Slide position Sensor Fault 758 R 0=Normal, 1=Alarm

Circuit #3 Comp #1 - SHUTDOWN - Slide position Sensor Fault 760 R 0=Normal, 1=Alarm

Circuit #1 Comp #1 - SHUTDOWN - Starter Fault 662 R 0=Normal, 1=Alarm

Circuit #1 Comp #2 - SHUTDOWN - Starter Fault (PFS) 663 R 0=Normal, 1=Alarm

Circuit #2 Comp #1 - SHUTDOWN - Starter Fault 664 R 0=Normal, 1=Alarm

Circuit #3 Comp #1 - SHUTDOWN - Starter Fault 666 R 0=Normal, 1=Alarm

Circuit #1 Comp #1 - SHUTDOWN - Suction Temp Sensor Fault 698 R 0=Normal, 1=Alarm

Circuit #1 Comp #2 - SHUTDOWN - Suction Temp Sensor Fault (PFS) 699 R 0=Normal, 1=Alarm

Circuit #2 Comp #1 - SHUTDOWN - Suction Temp Sensor Fault 700 R 0=Normal, 1=Alarm

Circuit #3 Comp #1 - SHUTDOWN - Suction Temp Sensor Fault 702 R 0=Normal, 1=Alarm

Circuit #1 Comp #1 - SHUTDOWN - VFD Fault 762 R 0=Normal, 1=Alarm

Circuit #2 Comp #1 - SHUTDOWN - VFD Fault 764 R 0=Normal, 1=Alarm

Circuit #3 Comp #1 - SHUTDOWN - VFD Fault 766 R 0=Normal, 1=Alarm

D-EOMOC002(04)09-15EN - 22/35
3
Alarm Point H.R. R/W Range

Circuit #1 Comp #1 - SHUTDOWN - VFD Over Heat Fault 768 R 0=Normal, 1=Alarm

Circuit #2 Comp #1 - SHUTDOWN - VFD Over Heat Fault 770 R 0=Normal, 1=Alarm

Circuit #3 Comp #1 - SHUTDOWN - VFD Over Heat Fault 772 R 0=Normal, 1=Alarm

Circuit #1 Comp #1 - SHUTDOWN - Current Overload Fault 447 R 0=Normal, 1=Alarm

Circuit #2 Comp #1 - SHUTDOWN - Current Overload Fault 449 R 0=Normal, 1=Alarm

Circuit #3 Comp #1 - SHUTDOWN - Current Overload Fault 451 R 0=Normal, 1=Alarm

Circuit #1 Comp #1 - SHUTDOWN - Low Discharge Superheat Fault 808 R 0=Normal, 1=Alarm

Circuit #1 Comp #2 - SHUTDOWN - Low Discharge SuperHeat Fault (PFS) 809 R 0=Normal, 1=Alarm

Circuit #2 Comp #1 - SHUTDOWN - Low Discharge SuperHeat Fault 810 R 0=Normal, 1=Alarm

Circuit #3 Comp #1 - SHUTDOWN - Low Discharge Superheat Fault 812 R 0=Normal, 1=Alarm

Condenser Entering Water Temp Sensor Fault (EWWD) 365 R 0=Normal, 1=Alarm

Condenser Entering Water Temp Sensor Fault (PFS) 541 R 0=Normal, 1=Alarm

Condenser Leaving Water Temp Sensor Fault 368 R 0=Normal, 1=Alarm

Evaporator Entering Water Temp Sensor Fault 366 R 0=Normal, 1=Alarm

Evaporator Leaving Water Temp Sensor Fault 590 R 0=Normal, 1=Alarm

Evaporator Pump #1 Failure - Pump #2 Start Attempted Problem 430 R 0=Normal, 1=Alarm

Evaporator Pump #2 Failure - Pump #1 Start Attempted Problem 431 R 0=Normal, 1=Alarm

External event Warning 745 R 0=Normal, 1=Alarm

Option Fan Alarm Controller Communication Failed Warning 900 R 0=Normal, 1=Alarm

Option Controller Communication Failed Warning 815 R 0=Normal, 1=Alarm

Circuit #1 - RESTART DELAYED - Power Loss While Running Problem 384 R 0=Normal, 1=Alarm

Circuit #2 - RESTART DELAYED - Power Loss While Running Problem 385 R 0=Normal, 1=Alarm

Circuit #3 - RESTART DELAYED - Power Loss While Running Problem 386 R 0=Normal, 1=Alarm

Circuit #1 - SHUTDOWN – Condenser Pressure High Fault 517 R 0=Normal, 1=Alarm

Circuit #2 - SHUTDOWN – Condenser Pressure HighFault 519 R 0=Normal, 1=Alarm

Circuit #3 - SHUTDOWN - Condenser Pressure High Fault 521 R 0=Normal, 1=Alarm

Circuit #1 Comp #1 - SHUTDOWN – Condenser Pressure Sensor Fault 509 R 0=Normal, 1=Alarm

Circuit #2 Comp #1 - SHUTDOWN - Condenser Pressure Sensor Fault 511 R 0=Normal, 1=Alarm

Circuit #3 Comp #1 - SHUTDOWN - Condenser Pressure Sensor Fault 513 R 0=Normal, 1=Alarm

START INHIBITED - Ambient Temp Low Problem 388 R 0=Normal, 1=Alarm

Unit Power Restore Warning 740 R 0=Normal, 1=Alarm

UNIT INHIBIT LOAD - High Pressure Problem 389 R 0=Normal, 1=Alarm

UNIT INHIBIT LOAD - Low Pressure Problem 410 R 0=Normal, 1=Alarm

UNIT RESTART DELAYED - Power Loss While Running Problem 379 R 0=Normal, 1=Alarm

UNIT SHUTDOWN - Condenser Flow Loss 515 R 0=Normal, 1=Alarm

UNIT SHUTDOWN - Condenser High Pressure 516 R 0=Normal, 1=Alarm

UNIT SHUTDOWN - Evaporator Entering Water Temp Sensor Fault 755 R 0=Normal, 1=Alarm

UNIT SHUTDOWN - Evaporator Freeze Protection Fault 592 R 0=Normal, 1=Alarm

UNIT SHUTDOWN - Evaporator Leaving Water Temp Low (Freeze) 543 R 0=Normal, 1=Alarm

UNIT SHUTDOWN - Evaporator Leaving Water Temp Sensor Fault 589 R 0=Normal, 1=Alarm

UNIT SHUTDOWN - Evaporator Low Pressure (PFS) 544 R 0=Normal, 1=Alarm

UNIT SHUTDOWN - Evaporator Pressure Sensor Fault (PFS) 551 R 0=Normal, 1=Alarm

UNIT SHUTDOWN - Evaporator Water Flow Loss 542 R 0=Normal, 1=Alarm

D-EOMOC002(04)09-15EN - 23/35
3
Alarm Point H.R. R/W Range

UNIT SHUTDOWN - Outside Air Temp Sensor Fault 446 R 0=Normal, 1=Alarm

UNIT SHUTDOWN – Phase Voltage Protection (ATLAS, AWS, EWWD, MNG, PFS) 661 R 0=Normal, 1=Alarm

UNIT SHUTDOWN – Phase Voltage Protection (ACZC, ACHZ, ADZ) 816 R 0=Normal, 1=Alarm

UNIT STOP - Emergency Stop Alarm 798 R 0=Normal, 1=Alarm

UNIT STOP - Evaporator Water Temps Inverted 799 R 0=Normal, 1=Alarm

UNIT STOP - External Alarm 800 R 0=Normal, 1=Alarm

UNIT UNLOAD - High Pressure Problem 394 R 0=Normal, 1=Alarm

UNIT UNLOAD - Low Pressure Problem 415 R 0=Normal, 1=Alarm

Circuit #1 Comp #1 - UNLOAD - Hi Current Problem 420 R 0=Normal, 1=Alarm

Circuit #2 Comp #1 - UNLOAD - Hi Current Problem 422 R 0=Normal, 1=Alarm

Circuit #3 Comp #1 - UNLOAD - Hi Current Problem 424 R 0=Normal, 1=Alarm

Unit Controller board offline Fault 746 R 0=Normal, 1=Alarm

UNIT SHUTDOWN – Condenser Pressure Sensor Fault (PFS) 508 R 0=Normal, 1=Alarm

UNIT SHUTDOWN - Low Pressure Ratio 441 R 0=Normal, 1=Alarm

D-EOMOC002(04)09-15EN - 24/35
Appendix A – ASCII Characters Conversion Table
This table lists the ASCII characters and their decimal and hexadecimal numbers. The MicroTech III
Chiller Unit Controller does not support the characters in boldface type. Also, non-printing characters,
with the exception of the (Space) character, are not listed in this table and are not supported. Characters not
supported are translated to a space.

Table 6. ASCII Characters Conversion Table

Char Decimal Hexadecimal Char Decimal Hexadecimal Char Decimal Hexadecimal


(Space) 32 0x20 @ 64 0x40 ` 96 0x60
! 33 0x21 A 65 0x41 a 97 0x61
“ 34 0x22 B 66 0x42 b 98 0x62
# 35 0x23 C 67 0x43 c 99 0x63
$ 36 0x24 D 68 0x44 d 100 0x64
% 37 0x25 E 69 0x45 e 101 0x65
& 38 0x26 F 70 0x46 f 102 0x66
‘ 39 0x27 G 71 0x47 g 103 0x67
( 40 0x28 H 72 0x48 h 104 0x68
) 41 0x29 I 73 0x49 I 105 0x69
* 42 0x2a J 74 0x4a j 106 0x6a
+ 43 0x2b K 75 0x4b k 107 0x6b
‘ 44 0x2c L 76 0x4c l 108 0x6c
- 45 0x2d M 77 0x4d m 109 0x6d
. 46 0x2e N 78 0x4e n 110 0x6e
/ 47 0x2f O 79 0x4f o 111 0x6f
0 48 0x30 P 80 0x50 p 112 0x70
1 49 0x31 Q 81 0x51 q 113 0x71
2 50 0x32 R 82 0x52 r 114 0x72
3 51 0x33 S 83 0x53 s 115 0x73
4 52 0x34 T 84 0x54 t 116 0x74
5 53 0x35 U 85 0x55 u 117 0x75
6 54 0x36 V 86 0x56 v 118 0x76
7 55 0x37 W 87 0x57 w 119 0x77
8 56 0x38 X 88 0x58 x 120 0x78
9 57 0x39 Y 89 0x59 y 121 0x79
: 58 0x3a Z 90 0x5a z 122 0x7a
; 59 0x3b [ 91 0x5b { 123 0x7b
< 60 0x3c \ 92 0x5c | 124 0x7c
= 61 0x3d ] 93 0x5d } 125 0x7d
> 62 0x3e ^ 94 0x5e ~ 126 0x7e
? 63 0x3f _ 95 0x5f

D-EOMOC002(04)09-15EN - 25/35
Appendix B – Overall Registers Table
This section summarizes all Data/Alarm Points Registers discussed above in the document and listed by
Holding Register address.

Table 7. Overall Registers Table


Holding Register
Data Point / Alarm Point
(4xxxx)
Chiller Local/Remote 1
Chiller Enable Output 2
Run Enabled 3
Chiller Capacity Limited 4
Alarm Digital Output 5
Evaporator Flow Switch Status 6
Condenser Flow Switch Status 7
Chiller On/Off 8
Chiller Enable Setpoint 9
Clear Alarms – Network 10
Chiller Mode Output 11
Active Setpoint 12
Actual Capacity 13
Active Capacity Limit Output 14
Chiller Status (Chiller Run Mode) 15
Evaporator Entering Water Temp 16
Evaporator Leaving Water Temperature 17
Heat Recovery Enable - Network 18
Condenser Entering Water Temp 19
Condenser Leaving Water Temp 20
Heat Recovery Ent Water Temperature 22
Heat Recovery Leaving Water Temperature 23
Outdoor Air Temperature 24
Chiller Current 25
Chiller Voltage 26
Power Input 27
Warning Alarm Index 28
Problem Alarm Index 29
Fault Alarm Index 30
Warning Alarm Code 31
Problem Alarm Code 32
Fault Alarm Code 33
Chiller Mode Setpoint – Network 34
Cool Setpoint – Network 35
Ice Setpoint - Network 36

D-EOMOC002(04)09-15EN - 26/35
Holding Register
Data Point / Alarm Point
(4xxxx)
Heat Setpoint – Network 37
Capacity Limit Setpoint - Network 38
Circuit #1 - Condenser Refrigerant Pressure 39
Circuit #1 - Condenser Saturated Refrigerant Temp 40
Circuit #1 - Evaporator Refrigerant Pressure 41
Circuit #1 - Evaporator Saturated Refrigerant Temp 42
Circuit #2 - Condenser Refrigerant Pressure 43
Circuit #2 - Condenser Saturated Refrigerant Temp 44
Circuit #2 - Evaporator Refrigerant Pressure 45
Circuit #2 - Evaporator Saturated Refrigerant Temp 46
Circuit #3 - Condenser Refrigerant Pressure 47
Circuit #3 - Condenser Saturated Refrigerant Temp 48
Circuit #3 - Evaporator Refrigerant Pressure 49
Circuit #3 - Evaporator Saturated Refrigerant Temp 50
Circuit #1 - Suction Refrigerant Temp 65
Circuit #1 Comp #1 - Discharge Refrigerant Temp 68
Circuit #1 Comp #1 - Percent RLA 69
Circuit #1 Comp #1 - Current 70
Circuit #1 Comp #1 – Voltage 71
Circuit #1 Comp #1 – Power 72
Circuit #1 Comp #1 – Starts (ACZC, ACZH, ADZ, ATLAS, AWS, GIZMO, WATER STREAM) 73
Circuit #1 Comp #1 – Starts (EWWD, MNG, PFS) 73
Circuit #1 Comp #1 - Run Hours (ACZC, ACZH, ADZ, ATLAS, AWS, GIZMO, WATER STREAM) 74
Circuit #1 Comp #1 - Run Hours (EWWD, MNG, PFS) 74
Circuit #1 Comp #2 - Suction Refrigerant Temp 78
Circuit #1 Comp #2 - Discharge Refrigerant Temp 81
Circuit #1 Comp #2 – Starts (ACZC, ACZH, ADZ, GIZMO, WATER STREAM) 86
Circuit #1 Comp #2 – Starts (PFS) 86
Circuit #1 Comp #2 - Run Hours (ACZC, ACZH, ADZ, GIZMO, WATER STREAM) 87
Circuit #1 Comp #2 - Run Hours (PFS) 87
Circuit #1 Comp #3 – Starts (ACZC, ACZH, ADZ, WATER STREAM) 99
Circuit #1 Comp #3 - Run Hours (ACZC, ACZH, ADZ, WATER STREAM) 100
Circuit #2 Comp #1 - Suction Refrigerant Temp 104
Circuit #2 Comp #1 - Discharge Refrigerant Temp 107
Circuit #2 Comp #1 - Percent RLA 108
Circuit #2 Comp #1 - Current 109
Circuit #2 Comp #1 - Voltage 110
Circuit #2 Comp #1 - Power 111
Circuit #2 Comp #1 – Starts (ACZC, ACZH, ADZ, ATLAS, AWS, WATER STREAM) 112
Circuit #2 Comp #1 – Starts (EWWD, MNG) 112
Circuit #2 Comp #1 - Run Hours (ACZC, ACZH, ADZ, ATLAS, AWS, WATER STREAM) 113
Circuit #2 Comp #1 - Run Hours (EWWD,MNG) 113

D-EOMOC002(04)09-15EN - 27/35
Holding Register
Data Point / Alarm Point
(4xxxx)
Circuit #2 Comp #2 - Starts (ACZC, ACZH, ADZ, WATER STREAM) 125
Circuit #2 Comp #2 - Run Hours (ACZC, ACZH, ADZ, WATER STREAM) 126
Circuit #2 Comp #3 - Starts (ACZC, ACZH, ADZ, WATER STREAM) 138
Circuit #2 Comp #3 - Run Hours (ACZC, ACZH, ADZ, WATER STREAM) 139
Circuit #3 Comp #1 - Suction Refrigerant Temp 143
Circuit #3 Comp #1 - Discharge Refrigerant Temp 146
Circuit #3 Comp #1 - Percent RLA 147
Circuit #3 Comp #1 - Current 148
Circuit #3 Comp #1 - Voltage 149
Circuit #3 Comp #1 - Power 150
Circuit #3 Comp #1 – Starts (AWS) 151
Circuit #3 Comp #1 – Starts (EWWD) 151
Circuit #3 Comp #1 - Run Hours (AWS) 152
Circuit #3 Comp #1 - Run Hours (EWWD) 152
Condenser Pump Run Hours 297
Condenser Pump Status 299
Evaporator Pump #1 Run Hours (ACZC, ACZH, ADZ, ATLAS, AWS, GIZMO, WATER STREAM) 303
Evaporator Pump #1 Run Hours (EWWD, MNG, PFS) 303
Evaporator Pump #1 Status 305
Evaporator Pump #2 Run Hours (ACZC, ACZH, ADZ, ATLAS, AWS, GIZMO, WATER STREAM) 306
Evaporator Pump #2 Run Hours (EWWD, MNG, PFS) 306
Evaporator Pump #2 Status 308
Year 309
Month 310
Date 311
Day of Week 312
Hour 313
Minute 314
Second 315
Units 316
Chiller Model 317
Chiller Location [1] 318
Chiller Location [10] 327
Application Software Version [1] 334
Application Software Version [5] 338
Condenser Entering Water Temp Sensor Fault (EWWD) 365
Evap Ent Water Temp Sensor Fault 366
Condenser Leav Water Temp Sensor Fault 368
Bad setpoint override input Warning 377
Bad demand limit input Warning 378
UNIT RESTART DELAYED - Power Loss While Running Problem 379
Circuit #1 - RESTART DELAYED - Power Loss While Running Problem 384

D-EOMOC002(04)09-15EN - 28/35
Holding Register
Data Point / Alarm Point
(4xxxx)
Circuit #2 - RESTART DELAYED - Power Loss While Running Problem 385
Circuit #3 - RESTART DELAYED - Power Loss While Running Problem 386
START INHIBITED - Ambient Temp Low Problem 388
UNIT INHIBIT LOAD - High Pressure Problem 389
Circuit #1 - INHIBIT LOAD - High Pressure Problem 390
Circuit #2 - INHIBIT LOAD - High Pressure Problem 391
Circuit #3 - INHIBIT LOAD - High Pressure Problem 392
UNIT UNLOAD - High Pressure Problem 394
Circuit #1 - UNLOAD - High Pressure Problem 395
Circuit #2 - UNLOAD - High Pressure Problem 396
Circuit #3 - UNLOAD - High Pressure Problem 397
UNIT INHIBIT LOAD - Low Pressure Problem 410
Circuit #1 - INHIBIT LOAD - Low Pressure Problem 411
Circuit #2 - INHIBIT LOAD - Low Pressure Problem 412
Circuit #3 - INHIBIT LOAD - Low Pressure Problem 413
UNIT UNLOAD - Low Pressure Problem 415
Circuit #1 - UNLOAD - Low Pressure Problem 416
Circuit #2 - UNLOAD - Low Pressure Problem 417
Circuit #3 - UNLOAD - Low Pressure Problem 418
Circuit #1 Comp #1 - UNLOAD - Hi Current Problem 420
Circuit #2 Comp #1 - UNLOAD - Hi Current Problem 422
Circuit #3 Comp #1 - UNLOAD - Hi Current Problem 424
Evap Pump #1 Failure - Pump #2 Start Attempted Problem 430
Evap Pump #2 Failure - Pump #1 Start Attempted Problem 431
Circuit #1 Comp #1 - SHUTDOWN - Low pressure ratio Fault 440
UNIT SHUTDOWN - Low Pressure Ratio 441
Circuit #2 Comp #1 - SHUTDOWN - Low pressure ratio Fault 442
Circuit #3 Comp #1 - SHUTDOWN - Low pressure ratio Fault 444
UNIT SHUTDOWN - Outside Air Temp Sensor Fault 446
Circuit #1 Comp #1 - SHUTDOWN - Current Overload Fault 447
Circuit #2 Comp #1 - SHUTDOWN - Current Overload Fault 449
Circuit #3 Comp #1 - SHUTDOWN - Current Overload Fault 451
Circuit #1 - SHUTDOWN – Low Evaporator Pressure Fault 461
Circuit #2 - SHUTDOWN – Low Evaporator Pressure Fault 462
Circuit #1 Comp #1 - SHUTDOWN – Motor Protector Fault 466
Circuit #1 Comp #2 - SHUTDOWN – Motor Protector Fault 467
Circuit #2 Comp #1 - SHUTDOWN – Motor Protector Fault 468
Circuit #2 Comp #2 - SHUTDOWN – Motor Protector Fault 469
Circuit #1 Comp #3 - SHUTDOWN – Motor Protector Fault 470
Circuit #2 Comp #3 - SHUTDOWN – Motor Protector Fault 471
Circuit #1 Comp #1 - SHUTDOWN - Motor Temp High Fault 478
Circuit #1 Comp #2 - SHUTDOWN - Motor Temp High Fault (PFS) 479

D-EOMOC002(04)09-15EN - 29/35
Holding Register
Data Point / Alarm Point
(4xxxx)
Circuit #2 Comp #1 - SHUTDOWN - Motor Temp High Fault 480
Circuit #3 Comp #1 - SHUTDOWN - Motor Temp High Fault 482
UNIT SHUTDOWN – Condenser Pressure Sensor Fault 508
Circuit #1 Comp #1 - SHUTDOWN – Condenser Pressure Sensor Fault 509
Circuit #2 Comp #1 - SHUTDOWN - Condenser Pressure Sensor Fault 511
Circuit #3 Comp #1 - SHUTDOWN - Condenser Pressure Sensor Fault 513
UNIT SHUTDOWN - Condenser Flow Loss 515
UNIT SHUTDOWN - Condenser High Pressure 516
Circuit #1 - SHUTDOWN – Condenser Pressure High Fault 517
Circuit #2 - SHUTDOWN – Condenser Pressure HighFault 519
Circuit #3 - SHUTDOWN - Condenser Pressure High Fault 521
Circuit #1 Comp #1 - SHUTDOWN - Discharge Temp Sensor Fault 529
Circuit #1 Comp #2 - SHUTDOWN - Discharge Temp Sensor Fault (PFS) 530
Circuit #2 Comp #1 - SHUTDOWN - Discharge Temp Sensor Fault 531
Circuit #3 Comp #1 - SHUTDOWN - Discharge Temp Sensor Fault 533
Circuit #1 Comp #1 - SHUTDOWN - Discharge Temp High Fault 535
Circuit #1 Comp #2 - SHUTDOWN - Discharge Temp High Fault (PFS) 536
Circuit #2 Comp #1 - SHUTDOWN - Discharge Temp High Fault 537
Circuit #3 Comp #1 - SHUTDOWN - Discharge Temp High Fault 539
Condenser Entering Water Temp Sensor Fault (PFS) 541
UNIT SHUTDOWN - Evap Water Flow Loss 542
UNIT SHUTDOWN - Evap Leav Water Temp Low 543
UNIT SHUTDOWN - Evap Low Pressure 544
Circuit #1 - SHUTDOWN – Low Evaporator Pressure Fault 545
Circuit #2 - SHUTDOWN – Low Evaporator Pressure Fault 547
Circuit #3 - SHUTDOWN - Low Evaporator Pressure Fault 549
UNIT SHUTDOWN – Evap Pressure Sensor Fault 551
Circuit #1 - SHUTDOWN – Evaporator Pressure Sensor Fault 552
Circuit #2 - SHUTDOWN – Evaporator Pressure Sensor Fault 554
Circuit #3 - SHUTDOWN - Evaporator Pressure Sensor Fault 556
Circuit #1 Comp #1 - LOCKOUT - Number of Allowed Re-Starts Exceeded Fault 583
Circuit #2 Comp #1 - LOCKOUT - Number of Allowed Re-Starts Exceeded Fault 585
Circuit #3 Comp #1 - LOCKOUT - Number of Allowed Re-Starts Exceeded Fault 587
UNIT SHUTDOWN - Evap Leav Water Temp Sensor Fault 589
Evap Leav Water Temp Sensor Fault 590
UNIT SHUTDOWN - Evap Freeze Protection Fault 592
Circuit #1 Comp #1 - SHUTDOWN - Mechanical High Pressure Fault 601
Circuit #1 Comp #2 - SHUTDOWN - Mechanical High Pressure Fault (PFS) 602
Circuit #2 Comp #1 - SHUTDOWN - Mechanical High Pressure Fault 603
Circuit #3 Comp #1 - SHUTDOWN - Mechanical High Pressure Fault 605
Circuit #1 Comp #1 - SHUTDOWN - Oil Delta Pressure High Fault 637
Circuit #1 Comp #2 - SHUTDOWN - Oil Delta Pressure High Fault (PFS) 638

D-EOMOC002(04)09-15EN - 30/35
Holding Register
Data Point / Alarm Point
(4xxxx)
Circuit #2 Comp #1 - SHUTDOWN - Oil Delta Pressure High Fault 639
Circuit #3 Comp #1 - SHUTDOWN - Oil Delta Pressure High Fault 641
Circuit #1 Comp #1 - SHUTDOWN - Oil Feed Pressure Sensor Fault 643
Circuit #2 Comp #1 - SHUTDOWN - Oil Feed Pressure Sensor Fault 645
Circuit #3 Comp #1 - SHUTDOWN - Oil Feed Pressure Sensor Fault 647
Circuit #1 Comp #1 - SHUTDOWN - Oil Feed Pressure Sensor Fault (PFS) 649
Circuit #1 Comp #2 - SHUTDOWN - Oil Feed Pressure Sensor Fault (PFS) 650
UNIT SHUTDOWN – Phase Voltage Protection Fault 661
Circuit #1 Comp #1 - SHUTDOWN - Starter Fault 662
Circuit #1 Comp #2 - SHUTDOWN - Starter Fault (PFS) 663
Circuit #2 Comp #1 - SHUTDOWN - Starter Fault 664
Circuit #3 Comp #1 - SHUTDOWN - Starter Fault 666
Circuit #1 Comp #1 - SHUTDOWN - Suction Temp Sensor Fault 698
Circuit #1 Comp #2 - SHUTDOWN - Suction Temp Sensor Fault (PFS) 699
Circuit #2 Comp #1 - SHUTDOWN - Suction Temp Sensor Fault 700
Circuit #3 Comp #1 - SHUTDOWN - Suction Temp Sensor Fault 702
Circuit #1 - SHUTDOWN – No Pressure at Startup Fault 711
Circuit #2 - SHUTDOWN – No Pressure at Startup Fault 712
Circuit #3 - SHUTDOWN – No Pressure at Startup Fault 713
Circuit #1 Comp #1 - SHUTDOWN - Mechanical Low Pressure Fault 717
Circuit #1 Comp #2 - SHUTDOWN - Mechanical Low Pressure Fault (PFS) 718
Circuit #2 Comp #1 - SHUTDOWN - Mechanical Low Pressure Fault 719
Circuit #3 Comp #1 - SHUTDOWN - Mechanical Low Pressure Fault 721
Circuit #1 - Controller board offline Fault 723
Circuit #2 - Controller board offline Fault 724
Circuit #3 - Controller board offline Fault 725
Circuit #1 Comp #1 - SHUTDOWN - Motor Temp Sensor Fault 734
Circuit #1 Comp #2 - SHUTDOWN - Motor Temp Sensor Fault (PFS) 735
Circuit #2 Comp #1 - SHUTDOWN - Motor Temp Sensor Fault 736
Circuit #3 Comp #1 - SHUTDOWN - Motor Temp Sensor Fault 738
Unit Power Restore Warning 740
Circuit #1 - Failed pumpdown Warning 741
Circuit #2 - Failed pumpdown Warning 742
Circuit #3 - Failed pumpdown Warning 743
External event Warning 745
Unit Controller board offline Fault 746
Circuit #1 - SHUTDOWN – No Pressure Change After Start 747
Circuit #2 - SHUTDOWN – No Pressure Change After Start 748
Circuit #3 - SHUTDOWN – No Pressure Change After Start 749
Circuit #1 - SHUTDOWN – Phase Voltage Protection Fault (ATLAS, AWS, EWWD, MNG) 751
Circuit #2 - SHUTDOWN – Phase Voltage Protection Fault (ATLAS, AWS, EWWD, MNG) 752
Circuit #3 - SHUTDOWN – Phase Voltage Protection Fault (AWS) 753

D-EOMOC002(04)09-15EN - 31/35
Holding Register
Data Point / Alarm Point
(4xxxx)
UNIT SHUTDOWN - Evap Ent Water Temp Sensor Fault 755
Circuit #1 Comp #1 - SHUTDOWN -Slide position Sensor Fault 756
Circuit #1 Comp #2 - SHUTDOWN - Slide position Sensor Fault (PFS) 757
Circuit #2 Comp #1 - SHUTDOWN - Slide position Sensor Fault 758
Circuit #3 Comp #1 - SHUTDOWN - Slide position Sensor Fault 760
Circuit #1 Comp #1 - SHUTDOWN - VFD Fault 762
Circuit #2 Comp #1 - SHUTDOWN - VFD Fault 764
Circuit #3 Comp #1 - SHUTDOWN - VFD Fault 766
Circuit #1 Comp #1 - SHUTDOWN - VFD Over Heat Fault 768
Circuit #2 Comp #1 - SHUTDOWN - VFD Over Heat Fault 770
Circuit #3 Comp #1 - SHUTDOWN - VFD Over Heat Fault 772
Circuit #1 Comp #1 - SHUTDOWN - COM ERROR With VFD Fault 774
Circuit #2 Comp #1 - SHUTDOWN - COM ERROR With VFD Fault 776
Circuit #3 Comp #1 - SHUTDOWN - COM ERROR With VFD Fault 778
Circuit #1 - INHIBIT LOAD - High Current Problem 780
Circuit #2 - INHIBIT LOAD - High Current Problem 782
Circuit #3 - INHIBIT LOAD - High Current Problem 784
UNIT STOP - Emergency Stop Alarm 798
UNIT STOP - Evap Water Temps Inverted 799
UNIT STOP - External Alarm 800
Circuit #1 Comp #1 - SHUTDOWN - Low Discharge Superheat Fault 808
Circuit #1 Comp #2 - SHUTDOWN - Low Discharge SuperHeat Fault (PFS) 809
Circuit #2 Comp #1 - SHUTDOWN - Low Discharge SuperHeat Fault 810
Circuit #3 Comp #1 - SHUTDOWN - Low Discharge Superheat Fault 812
Bad Current Limit Input Warning 814
Option Controller Communication Failed Warning 815
UNIT SHUTDOWN – Phase Voltage Protection Fault 816
Circuit #1 - SHUTDOWN – Phase Voltage Protection Fault (ACZC, ACZH, ADZ) 817
Circuit #2 - SHUTDOWN – Phase Voltage Protection Fault (ACZC, ACZH, ADZ) 818
Circuit #1 - Failed pumpdown - High Pressure 841
Circuit #2 - Failed pumpdown - High Pressure 842
Option Fan Controller Communication Failed Warning 900
Circuit #1 - Option Fan Alarm Warning 901
Circuit #2 - Option Fan Alarm Warning 902
Circuit #1 - SHUTDOWN - Global Alarm 911
Circuit #2 - SHUTDOWN - Global Alarm 912
Refrigerant Type 1606
Number of Circuits 1607
Number of Compressors 1608
Chiller Tons 1609
Circuit #3 Comp #1 - Actual Capacity 1761
Circuit #3 Comp #1 - Off Auto 1762

D-EOMOC002(04)09-15EN - 32/35
Holding Register
Data Point / Alarm Point
(4xxxx)
Circuit #3 Comp #1 - Full Load 1763
Circuit #3 Comp #1 - VFD Output 1766
Circuit #3 Comp #1 - Oil Feed Pressure 1770
Circuit #3 Comp #1 - Oil Level Status 1772
Circuit #3 Comp #1 - Status 1773
Circuit #2 Comp #3 - Off Auto 1775
Circuit #2 Comp #3 - Status 1786
Circuit #2 Comp #2 - Off Auto 1788
Circuit #2 Comp #2 - Status 1799
Circuit #2 Comp #1 - Actual Capacity 1800
Circuit #2 Comp #1 - Off Auto 1801
Circuit #2 Comp #1 - Full Load 1802
Circuit #2 Comp #1 - VFD Output 1805
Circuit #2 Comp #1 - Oil Feed Pressure 1809
Circuit #2 Comp #1 - Oil Level Status 1811
Circuit #2 Comp #1 - Status 1812
Circuit #1 Comp #3 - Off Auto 1814
Circuit #1 Comp #3 – Status 1825
Circuit #1 Comp #2 - Actual Capacity (PFS) 1826
Circuit #1 Comp #2 - Off Auto 1827
Circuit #1 Comp #2 - Full Load 1828
Circuit #1 Comp #2 - Oil Feed Pressure 1832
Circuit #1 Comp #2 – Status 1838
Circuit #1 Comp #1 - Actual Capacity 1840
Circuit #1 Comp #1 - Off Auto 1841
Circuit #1 Comp #1 - Full Load 1842
Circuit #1 Comp #1 - VFD Output 1845
Circuit #1 Comp #1 - Oil Feed Pressure 1846
Circuit #1 Comp #1 - Oil Feed Pressure 1849
Circuit #1 Comp #1 - Oil Level Status 1851
Circuit #1 Comp #1 – Status 1852
Evaporator SuperHeat Setpoint 1897
Evaporator SuperHeat Temperature 1899
Active Energy 1900
Power Factor 1902
Circuit #3 - EXV Position 1950
Circuit #3 - Outdoor Fan Speed 1954
Circuit #3 - Condenser Approach Temp 1955
Circuit #3 - Evaporator Approach Temp 1956
Circuit #3 - Outdoor Fan Status 1965
Circuit #2 - EXV Position 1966
Circuit #2 - Outdoor Fan Speed 1970

D-EOMOC002(04)09-15EN - 33/35
Holding Register
Data Point / Alarm Point
(4xxxx)
Circuit #2 - Condenser Approach Temp 1971
Circuit #2 - Evaporator Approach Temp 1972
Circuit #2 - Outdoor Fan Status 1981
Circuit #1 - EXV Position 1982
Liquid Temperature 1984
Circuit #1 - Outdoor Fan Speed 1986
Circuit #1 - Condenser Approach Temp 1987
Circuit #1 - Evaporator Approach Temp 1988
Circuit #1 - Outdoor Fan Status 1997
Noise Reduction Auto On 1998
Noise Reduction Status 2000

D-EOMOC002(04)09-15EN - 34/35
The present publication is drawn up by of information only and does not constitute an offer binding upon Daikin Applied Europe S.p.A..
Daikin Applied Europe S.p.A. has compiled the content of this publication to the best of its knowledge. No express or implied warranty is
given for the completeness, accuracy, reliability or fitness for particular purpose of its content, and the products and services presented
therein. Specification are subject to change without prior notice. Refer to the data communicated at the time of the order. Daikin Applied
Europe S.p.A. explicitly rejects any liability for any direct or indirect damage, in the broadest sense, arising from or related to the use
and/or interpretation of this publication. All content is copyrighted by Daikin Applied Europe S.p.A.

D-EOMOC002(04)09-15EN - 35/35
APPENDIX-N
(Instruments Calibration to be attached)
APPENDIX-O
A100- APOLLO DATA CENTRE

INSPECTION & TEST PLAN

ITPC SCOPE START-UP COMMISSIONING OF AIR COOLED CHILLERS ITP NO. HWI-APO-CN-MSS-0009-01 DATE 26/11/2020 DISCIPLINE MECHANICAL

REFERENC SPECIFICATION

Controlling Documents
Acceptance Criteria (Tolerance Inspection & Test Verifying Records (Forms, Checklist, Test 3rd
S/N Activity Description (Drawings,specs, SC MC CNS PM Remarks
Parameters) Method/Equipment Reports) Party
Contract)

1 Genral
Contract Specification, MEP Contractor
All the documents to have minimum status of – No
1.1 Commissioning Method Statement. Mechanical Schematics, Method As per Check List Review of Documents H H S/H S/R R
objection with comments (B)
statement
All the documents to have minimum status of – No
1.2 Commissioning Test Sheets MS attachments As per Check List Review of Documents H H S/H S/R R
objection with comments (B)
All the documents to have minimum status of – No
1.3 Commissioning Risk Assessment RA attachments As per Check List Review of Documents H H S/H S/R R
objection with comments (B)

2 START-UP COMMISSIONING OF AIR COOLED CHILLERS

Pre-Start Up Check List" & " Power


Approved Material, Installation, Shop
2.1 Pre-Commissioning for AIR COOLED CHILLERS Quality Guidelines Installation & Power Check Refer to method statement and Test report sheet H H S/H S/R W
Drawing

Testing & Commissioning forAIR COOLED Approved Material, Installation, Shop Chiller Start Up Form
2.2 Commissioning check Refer to method statement and Test report sheet H H S/H S/R W
CHILLERS Drawing

Chiller Start Up Form & Chiller


Approved Material, Installation, Shop
2.3 Witnessing for AIR COOLED CHILLERS Safety test Report Commissioning check Refer to method statement and Test report sheet H H S/H S/R W
Drawing

ACTION CODE:

H (Hold Point)- the responsible party has to perform this check/inspection/test and it needs to be successful in order to proceed to the next stage of the construction.

W (Witness Point)- the responsible party has to be informed that check/inspection/test is going to be performed but its presence and signature is not obligatory to move on the next stage

R (Review)-the responsible party has to only review the record/document that check/inspection/test has been done and it passed.

S(Surveillance)- the responsible party has to conduct random visual check/inspection of the activity without formal request for inspection

LEGEND : SUPPLIER CONSULTANT HUAWEI REEFTECH

PREPARED BY REVIEWED BY APROVED BY PREPARED BY

NAME NAME NAME NADIR KHAN NAME EDMOND


DESIGNATION DESIGNATION DESIGNATION DESIGNATION CM
CM
DATE DATE DATE DATE 26/11/20
SIGNATURE SIGNATURE SIGNATURE SIGNATURE
APPENDIX-P
La proprietà del presente disegno e' di Dis./Dwg. Codice /Part. No.
Denominazione / Identification
DAIKIN APPLIED EUROPE S.p.A.
La riproduzione, anche se parziale, e la diffusione
Tolleranza generale
senza autorizzazione sono vietate a termini di legge. Ver./Check General Tolerance
This document is reserved property of Data/Date Foglio-Sheet Scala-Scale
DAIKIN APPLIED EUROPE S.p.A.
Appr./Passed
Reproduction or use for any purpose
without authorization is strictly forbidden by law.

To be updated by Daikin for Phase 3

DISEGNATO AL CAD - VIETATO APPORTARE MODIFICHE A MANO. / DRAWING BY CAD - DO NOT MANUALLY MODIFY THIS DRAWING.
La proprietà del presente disegno e' di
Denominazione / Identification Dis./Dwg. Codice /Part. No.
DAIKIN APPLIED EUROPE S.p.A. Tolleranza generale
La riproduzione, anche se parziale, e la diffusione
senza autorizzazione sono vietate a termini di legge. Ver./Check General Tolerance
This document is reserved property of Data/Date Foglio-Sheet Scala-Scale
DAIKIN APPLIED EUROPE S.p.A.
Appr./Passed
Reproduction or use for any purpose
without authorization is strictly forbidden by law.

To be updated by Daikin for Phase 3

DISEGNATO AL CAD - VIETATO APPORTARE MODIFICHE A MANO. / DRAWING BY CAD - DO NOT MANUALLY MODIFY THIS DRAWING.
APPENDIX-Q
QTA.MOD.0055_AWS

AUDIT CHECKLIST REV.001


22/05/2017

MODELLO / MODEL: CONFERMA/ORDER N°: DATA/DATE:


EWADC12C-PS011 OV18-06250
CH-19C00218-KKKKXX
20 3 2019

ITEM CONTROLLO OK
Homogeneous paint and color , Scratches , Damages , Item burnt , Rust , Cleaning
SHEET METALS 3
Sheet metals , Fan section , Compressor , Evaporator , Fixed screws and bolts , Fixed screw cabin , Application
ASSEMBLYNG rivets , Blunt tip screws channel fan section , Electrical wiring-capillaries no contact hot parts , Connections In /
Out free of obstacles
3
Vertical assembly , Verification model, Bar and S/N , Guarantee seal , Year and month validity start
SECURITY VALVES 3
Homogeneous paint and color , Cover conduit , Presence of all the fixing screws , Tightening cable gland
FANS 3
Homogeneous paint , Oil level , Verification code and S/N , Check oil label and correct data , Removing label
COMPRESSORS nitrogen presence , Delivery pipe tap closed , Suction tap open , Caps blind tightening , Verification heater Volt
and Watt
3

To be updated by Daikin for Phase 3


No contact with metal parts , No contact between pipes , Braze welding cleaning and quality , Absence of deep
ASSEMBLED PIPES cuts and creases , Taps closed and cap presence , Blind caps on attacks Schraeder 3
Braze welding , Rotalock , Oil sight compressor , Antivibration compressor , Taps , Expansion valves , Deitratore
PROTECTION TECTIL filter 3
Color
SIGHTGLASS 3
Fixing , Labels tightening torque
LIFTING BRACKETS 3
Verify code and S/N , Dents , Deformation excessive diaphragms
COILS 3
Verify code and S/N , Precence label In/Out and position , Removing drain plugs
EVAPORATOR 3
Integrity , Cleaning , Bonding , Present on suction pipes , Present on piping liquid line
INSULATION 3
Temperature sensors entered with thermal paste , Gaskets transducers in the seat , Flow switch incoming if not
SENSORS present pump , Flow switch exit if present pump , Verification Bar pressure switches 3
Electrical cables not in contact with sharp metal , Cable fixing with cable ties , Wires under stress , No wires
ELETTRIC CABLES contact with hot pipes 3
Internal plate code / model / Volt / Hz , Removing jumpers used for testing , Voltage cables with stranded copper
ELECTRIC PANEL
by the sheath , Cable wiring tidy , Mechanical operation emergency button , Paint of fuses , Paint on pins fixing
power cables , Caps on the holes present on panel roof , Rubber caps on unused holes , Closing doors
3
alignment
Label identifying Daikin , Warning label , Type Gas label , Multilinguage Gas label , Label quantity Gas for circuit
INNER LABEL ELECTRIC
PANEL
, Check identifying chiller label data , Check weight on label identifying 3
Label identifying Daikin , Logo , Label lifting points , Check identifying SN/CH label data , Check weight on label
CHILLER EXTERNAL LABEL identifying 3
Compilation of RM with annotations and signatures , Dimension drawing and verification code with RM da ,
CHILLER DOCUMENTS
Electric scheme and verification code and revision , Compiling HATA with S/N and signatures , Certificates of
safety valves and check S/N , Certificates evaporators and check S/N , Dielectric tests performed , Dimension
3
drawing and verification code with RM da , Language manual
Check the back of the RM , Check notes for ancillaries not in the catalog , Cabin soundproofing for XN version ,

OPTIONAL
XN version spacers neoprene anchor bolts compress. , XN version insulation sandwich on piping liquid , LN
version insulation sandwich suction pipes , Verification requested special treatment battery , Mod Bus Card ,
3
Verification required special insulation , Victaulic for each connection , Gaskets for each connection , Boxes
vibration kit and verification code
PED - standard
TEST TYPE AND
CERTIFICATIONS 3
Microprocessor manual in languge , Multilingual Installation Manual , Certificates CE , Electric scheme ,
DOCUMENTS
ACCOMPANYING
Dimension drawing , Evaporator manual 3
Keys P.E. and evaporator caps on handle switch , Photo chiller four sides, inside P.E., optional , Seals on locks
FINAL AUDIT electrical panel , Label OK/QC 3

RILASCIO MACCHINA QC 20/03/19


QTA.MOD.0055_AWS

AUDIT CHECKLIST REV.001


22/05/2017

MODELLO / MODEL: CONFERMA/ORDER N°: DATA/DATE:


EWADC12C-PS011 OV18-06250
CH-19C00219-KKKKXX
26 3 2019

ITEM CONTROLLO OK
Homogeneous paint and color , Scratches , Damages , Item burnt , Rust , Cleaning
SHEET METALS 3
Sheet metals , Fan section , Compressor , Evaporator , Fixed screws and bolts , Fixed screw cabin , Application
ASSEMBLYNG rivets , Blunt tip screws channel fan section , Electrical wiring-capillaries no contact hot parts , Connections In /
Out free of obstacles
3
Vertical assembly , Verification model, Bar and S/N , Guarantee seal , Year and month validity start
SECURITY VALVES 3
Homogeneous paint and color , Cover conduit , Presence of all the fixing screws , Tightening cable gland
FANS 3
Homogeneous paint , Oil level , Verification code and S/N , Check oil label and correct data , Removing label
COMPRESSORS nitrogen presence , Delivery pipe tap closed , Suction tap open , Caps blind tightening , Verification heater Volt
and Watt
3
No contact with metal parts , No contact between pipes , Braze welding cleaning and quality , Absence of deep
ASSEMBLED PIPES cuts and creases , Taps closed and cap presence , Blind caps on attacks Schraeder 3
PROTECTION TECTIL To be updated by Daikin for Phase 3 3
Braze welding , Rotalock , Oil sight compressor , Antivibration compressor , Taps , Expansion valves , Deitratore
filter

Color
SIGHTGLASS 3
Fixing , Labels tightening torque
LIFTING BRACKETS 3
Verify code and S/N , Dents , Deformation excessive diaphragms
COILS 3
Verify code and S/N , Precence label In/Out and position , Removing drain plugs
EVAPORATOR 3
Integrity , Cleaning , Bonding , Present on suction pipes , Present on piping liquid line
INSULATION 3
Temperature sensors entered with thermal paste , Gaskets transducers in the seat , Flow switch incoming if not
SENSORS present pump , Flow switch exit if present pump , Verification Bar pressure switches 3
Electrical cables not in contact with sharp metal , Cable fixing with cable ties , Wires under stress , No wires
ELETTRIC CABLES contact with hot pipes 3
Internal plate code / model / Volt / Hz , Removing jumpers used for testing , Voltage cables with stranded copper
ELECTRIC PANEL
by the sheath , Cable wiring tidy , Mechanical operation emergency button , Paint of fuses , Paint on pins fixing
power cables , Caps on the holes present on panel roof , Rubber caps on unused holes , Closing doors
3
alignment
Label identifying Daikin , Warning label , Type Gas label , Multilinguage Gas label , Label quantity Gas for circuit
INNER LABEL ELECTRIC
PANEL
, Check identifying chiller label data , Check weight on label identifying 3
Label identifying Daikin , Logo , Label lifting points , Check identifying SN/CH label data , Check weight on label
CHILLER EXTERNAL LABEL identifying 3
Compilation of RM with annotations and signatures , Dimension drawing and verification code with RM da ,
CHILLER DOCUMENTS
Electric scheme and verification code and revision , Compiling HATA with S/N and signatures , Certificates of
safety valves and check S/N , Certificates evaporators and check S/N , Dielectric tests performed , Dimension
3
drawing and verification code with RM da , Language manual
Check the back of the RM , Check notes for ancillaries not in the catalog , Cabin soundproofing for XN version ,

OPTIONAL
XN version spacers neoprene anchor bolts compress. , XN version insulation sandwich on piping liquid , LN
version insulation sandwich suction pipes , Verification requested special treatment battery , Mod Bus Card ,
3
Verification required special insulation , Victaulic for each connection , Gaskets for each connection , Boxes
vibration kit and verification code
PED - standard
TEST TYPE AND
CERTIFICATIONS 3
Microprocessor manual in languge , Multilingual Installation Manual , Certificates CE , Electric scheme ,
DOCUMENTS
ACCOMPANYING
Dimension drawing , Evaporator manual 3
Keys P.E. and evaporator caps on handle switch , Photo chiller four sides, inside P.E., optional , Seals on locks
FINAL AUDIT electrical panel , Label OK/QC 3

RILASCIO MACCHINA QC 26/03/19


QTA.MOD.0055_AWS

AUDIT CHECKLIST REV.001


22/05/2017

MODELLO / MODEL: CONFERMA/ORDER N°: DATA/DATE:


EWADC12C-PS011 OV18-06250
CH-19C00220-KKKKXX
21 3 2019

ITEM CONTROLLO OK
Homogeneous paint and color , Scratches , Damages , Item burnt , Rust , Cleaning
SHEET METALS 3
Sheet metals , Fan section , Compressor , Evaporator , Fixed screws and bolts , Fixed screw cabin , Application
ASSEMBLYNG rivets , Blunt tip screws channel fan section , Electrical wiring-capillaries no contact hot parts , Connections In /
Out free of obstacles
3
Vertical assembly , Verification model, Bar and S/N , Guarantee seal , Year and month validity start
SECURITY VALVES 3
Homogeneous paint and color , Cover conduit , Presence of all the fixing screws , Tightening cable gland
FANS 3
Homogeneous paint , Oil level , Verification code and S/N , Check oil label and correct data , Removing label
COMPRESSORS nitrogen presence , Delivery pipe tap closed , Suction tap open , Caps blind tightening , Verification heater Volt
and Watt
3
No contact with metal parts , No contact between pipes , Braze welding cleaning and quality , Absence of deep
ASSEMBLED PIPES cuts and creases , Taps closed and cap presence , Blind caps on attacks Schraeder 3
PROTECTION TECTIL
To be updated by Daikin for Phase 3
Braze welding , Rotalock , Oil sight compressor , Antivibration compressor , Taps , Expansion valves , Deitratore
filter 3
Color
SIGHTGLASS 3
Fixing , Labels tightening torque
LIFTING BRACKETS 3
Verify code and S/N , Dents , Deformation excessive diaphragms
COILS 3
Verify code and S/N , Precence label In/Out and position , Removing drain plugs
EVAPORATOR 3
Integrity , Cleaning , Bonding , Present on suction pipes , Present on piping liquid line
INSULATION 3
Temperature sensors entered with thermal paste , Gaskets transducers in the seat , Flow switch incoming if not
SENSORS present pump , Flow switch exit if present pump , Verification Bar pressure switches 3
Electrical cables not in contact with sharp metal , Cable fixing with cable ties , Wires under stress , No wires
ELETTRIC CABLES contact with hot pipes 3
Internal plate code / model / Volt / Hz , Removing jumpers used for testing , Voltage cables with stranded copper
ELECTRIC PANEL
by the sheath , Cable wiring tidy , Mechanical operation emergency button , Paint of fuses , Paint on pins fixing
power cables , Caps on the holes present on panel roof , Rubber caps on unused holes , Closing doors
3
alignment
Label identifying Daikin , Warning label , Type Gas label , Multilinguage Gas label , Label quantity Gas for circuit
INNER LABEL ELECTRIC
PANEL
, Check identifying chiller label data , Check weight on label identifying 3
Label identifying Daikin , Logo , Label lifting points , Check identifying SN/CH label data , Check weight on label
CHILLER EXTERNAL LABEL identifying 3
Compilation of RM with annotations and signatures , Dimension drawing and verification code with RM da ,
CHILLER DOCUMENTS
Electric scheme and verification code and revision , Compiling HATA with S/N and signatures , Certificates of
safety valves and check S/N , Certificates evaporators and check S/N , Dielectric tests performed , Dimension
3
drawing and verification code with RM da , Language manual
Check the back of the RM , Check notes for ancillaries not in the catalog , Cabin soundproofing for XN version ,

OPTIONAL
XN version spacers neoprene anchor bolts compress. , XN version insulation sandwich on piping liquid , LN
version insulation sandwich suction pipes , Verification requested special treatment battery , Mod Bus Card ,
3
Verification required special insulation , Victaulic for each connection , Gaskets for each connection , Boxes
vibration kit and verification code
PED - standard
TEST TYPE AND
CERTIFICATIONS 3
Microprocessor manual in languge , Multilingual Installation Manual , Certificates CE , Electric scheme ,
DOCUMENTS
ACCOMPANYING
Dimension drawing , Evaporator manual 3
Keys P.E. and evaporator caps on handle switch , Photo chiller four sides, inside P.E., optional , Seals on locks
FINAL AUDIT electrical panel , Label OK/QC 3

RILASCIO MACCHINA QC 21/03/19


QTA.MOD.0055_AWS

AUDIT CHECKLIST REV.001


22/05/2017

MODELLO / MODEL: CONFERMA/ORDER N°: DATA/DATE:


EWADC12C-PS011 OV18-06250
CH-19C00221-KKKKXX
22 3 2019

ITEM CONTROLLO OK
Homogeneous paint and color , Scratches , Damages , Item burnt , Rust , Cleaning
SHEET METALS 3
Sheet metals , Fan section , Compressor , Evaporator , Fixed screws and bolts , Fixed screw cabin , Application
ASSEMBLYNG rivets , Blunt tip screws channel fan section , Electrical wiring-capillaries no contact hot parts , Connections In /
Out free of obstacles
3
Vertical assembly , Verification model, Bar and S/N , Guarantee seal , Year and month validity start
SECURITY VALVES 3
Homogeneous paint and color , Cover conduit , Presence of all the fixing screws , Tightening cable gland
FANS 3
Homogeneous paint , Oil level , Verification code and S/N , Check oil label and correct data , Removing label
COMPRESSORS nitrogen presence , Delivery pipe tap closed , Suction tap open , Caps blind tightening , Verification heater Volt
and Watt
3
No contact with metal parts , No contact between pipes , Braze welding cleaning and quality , Absence of deep
ASSEMBLED PIPES cuts and creases , Taps closed and cap presence , Blind caps on attacks Schraeder 3
Braze welding , Rotalock , Oil sight compressor , Antivibration compressor , Taps , Expansion valves , Deitratore
PROTECTION TECTIL filter 3

To be updated by Daikin for Phase 3


Color
SIGHTGLASS 3
Fixing , Labels tightening torque
LIFTING BRACKETS 3
Verify code and S/N , Dents , Deformation excessive diaphragms
COILS 3
Verify code and S/N , Precence label In/Out and position , Removing drain plugs
EVAPORATOR 3
Integrity , Cleaning , Bonding , Present on suction pipes , Present on piping liquid line
INSULATION 3
Temperature sensors entered with thermal paste , Gaskets transducers in the seat , Flow switch incoming if not
SENSORS present pump , Flow switch exit if present pump , Verification Bar pressure switches 3
Electrical cables not in contact with sharp metal , Cable fixing with cable ties , Wires under stress , No wires
ELETTRIC CABLES contact with hot pipes 3
Internal plate code / model / Volt / Hz , Removing jumpers used for testing , Voltage cables with stranded copper
ELECTRIC PANEL
by the sheath , Cable wiring tidy , Mechanical operation emergency button , Paint of fuses , Paint on pins fixing
power cables , Caps on the holes present on panel roof , Rubber caps on unused holes , Closing doors
3
alignment
Label identifying Daikin , Warning label , Type Gas label , Multilinguage Gas label , Label quantity Gas for circuit
INNER LABEL ELECTRIC
PANEL
, Check identifying chiller label data , Check weight on label identifying 3
Label identifying Daikin , Logo , Label lifting points , Check identifying SN/CH label data , Check weight on label
CHILLER EXTERNAL LABEL identifying 3
Compilation of RM with annotations and signatures , Dimension drawing and verification code with RM da ,
CHILLER DOCUMENTS
Electric scheme and verification code and revision , Compiling HATA with S/N and signatures , Certificates of
safety valves and check S/N , Certificates evaporators and check S/N , Dielectric tests performed , Dimension
3
drawing and verification code with RM da , Language manual
Check the back of the RM , Check notes for ancillaries not in the catalog , Cabin soundproofing for XN version ,

OPTIONAL
XN version spacers neoprene anchor bolts compress. , XN version insulation sandwich on piping liquid , LN
version insulation sandwich suction pipes , Verification requested special treatment battery , Mod Bus Card ,
3
Verification required special insulation , Victaulic for each connection , Gaskets for each connection , Boxes
vibration kit and verification code
PED - standard
TEST TYPE AND
CERTIFICATIONS 3
Microprocessor manual in languge , Multilingual Installation Manual , Certificates CE , Electric scheme ,
DOCUMENTS
ACCOMPANYING
Dimension drawing , Evaporator manual 3
Keys P.E. and evaporator caps on handle switch , Photo chiller four sides, inside P.E., optional , Seals on locks
FINAL AUDIT electrical panel , Label OK/QC 3

RILASCIO MACCHINA QC 22/03/19


QTA.MOD.0055_AWS

AUDIT CHECKLIST REV.001


22/05/2017

MODELLO / MODEL: CONFERMA/ORDER N°: DATA/DATE:


EWADC12C-PS012 OV18-06403
CH-19C00242-KKKKXX
22 3 2019

ITEM CONTROLLO OK
Homogeneous paint and color , Scratches , Damages , Item burnt , Rust , Cleaning
SHEET METALS 3
Sheet metals , Fan section , Compressor , Evaporator , Fixed screws and bolts , Fixed screw cabin , Application
ASSEMBLYNG rivets , Blunt tip screws channel fan section , Electrical wiring-capillaries no contact hot parts , Connections In /
Out free of obstacles
3
Vertical assembly , Verification model, Bar and S/N , Guarantee seal , Year and month validity start
SECURITY VALVES 3
Homogeneous paint and color , Cover conduit , Presence of all the fixing screws , Tightening cable gland
FANS 3
Homogeneous paint , Oil level , Verification code and S/N , Check oil label and correct data , Removing label
COMPRESSORS nitrogen presence , Delivery pipe tap closed , Suction tap open , Caps blind tightening , Verification heater Volt
and Watt
3
No contact with metal parts , No contact between pipes , Braze welding cleaning and quality , Absence of deep
ASSEMBLED PIPES cuts and creases , Taps closed and cap presence , Blind caps on attacks Schraeder 3
Braze welding , Rotalock , Oil sight compressor , Antivibration compressor , Taps , Expansion valves , Deitratore
3
To be updated by Daikin for Phase 3 3
PROTECTION TECTIL filter

Color
SIGHTGLASS

Fixing , Labels tightening torque


LIFTING BRACKETS 3
Verify code and S/N , Dents , Deformation excessive diaphragms
COILS 3
Verify code and S/N , Precence label In/Out and position , Removing drain plugs
EVAPORATOR 3
Integrity , Cleaning , Bonding , Present on suction pipes , Present on piping liquid line
INSULATION 3
Temperature sensors entered with thermal paste , Gaskets transducers in the seat , Flow switch incoming if not
SENSORS present pump , Flow switch exit if present pump , Verification Bar pressure switches 3
Electrical cables not in contact with sharp metal , Cable fixing with cable ties , Wires under stress , No wires
ELETTRIC CABLES contact with hot pipes 3
Internal plate code / model / Volt / Hz , Removing jumpers used for testing , Voltage cables with stranded copper
ELECTRIC PANEL
by the sheath , Cable wiring tidy , Mechanical operation emergency button , Paint of fuses , Paint on pins fixing
power cables , Caps on the holes present on panel roof , Rubber caps on unused holes , Closing doors
3
alignment
Label identifying Daikin , Warning label , Type Gas label , Multilinguage Gas label , Label quantity Gas for circuit
INNER LABEL ELECTRIC
PANEL
, Check identifying chiller label data , Check weight on label identifying 3
Label identifying Daikin , Logo , Label lifting points , Check identifying SN/CH label data , Check weight on label
CHILLER EXTERNAL LABEL identifying 3
Compilation of RM with annotations and signatures , Dimension drawing and verification code with RM da ,
CHILLER DOCUMENTS
Electric scheme and verification code and revision , Compiling HATA with S/N and signatures , Certificates of
safety valves and check S/N , Certificates evaporators and check S/N , Dielectric tests performed , Dimension
3
drawing and verification code with RM da , Language manual
Check the back of the RM , Check notes for ancillaries not in the catalog , Cabin soundproofing for XN version ,

OPTIONAL
XN version spacers neoprene anchor bolts compress. , XN version insulation sandwich on piping liquid , LN
version insulation sandwich suction pipes , Verification requested special treatment battery , Mod Bus Card ,
3
Verification required special insulation , Victaulic for each connection , Gaskets for each connection , Boxes
vibration kit and verification code
PED - standard
TEST TYPE AND
CERTIFICATIONS 3
Microprocessor manual in languge , Multilingual Installation Manual , Certificates CE , Electric scheme ,
DOCUMENTS
ACCOMPANYING
Dimension drawing , Evaporator manual 3
Keys P.E. and evaporator caps on handle switch , Photo chiller four sides, inside P.E., optional , Seals on locks
FINAL AUDIT electrical panel , Label OK/QC 3

RILASCIO MACCHINA QC 22/03/19


QTA.MOD.0055_AWS

AUDIT CHECKLIST REV.001


22/05/2017

MODELLO / MODEL: CONFERMA/ORDER N°: DATA/DATE:


EWADC12C-PS012 OV18-06403
CH-19C00243-KKKKXX
25 3 2019

ITEM CONTROLLO OK
Homogeneous paint and color , Scratches , Damages , Item burnt , Rust , Cleaning
SHEET METALS 3
Sheet metals , Fan section , Compressor , Evaporator , Fixed screws and bolts , Fixed screw cabin , Application
ASSEMBLYNG rivets , Blunt tip screws channel fan section , Electrical wiring-capillaries no contact hot parts , Connections In /
Out free of obstacles
3
Vertical assembly , Verification model, Bar and S/N , Guarantee seal , Year and month validity start
SECURITY VALVES 3
Homogeneous paint and color , Cover conduit , Presence of all the fixing screws , Tightening cable gland
FANS 3
Homogeneous paint , Oil level , Verification code and S/N , Check oil label and correct data , Removing label
COMPRESSORS nitrogen presence , Delivery pipe tap closed , Suction tap open , Caps blind tightening , Verification heater Volt
and Watt
3
No contact with metal parts , No contact between pipes , Braze welding cleaning and quality , Absence of deep
ASSEMBLED PIPES cuts and creases , Taps closed and cap presence , Blind caps on attacks Schraeder 3
Braze welding , Rotalock , Oil sight compressor , Antivibration compressor , Taps , Expansion valves , Deitratore
PROTECTION TECTIL filter 3
SIGHTGLASS To be updated by Daikin for Phase 3
Color
3
Fixing , Labels tightening torque
LIFTING BRACKETS 3
Verify code and S/N , Dents , Deformation excessive diaphragms
COILS 3
Verify code and S/N , Precence label In/Out and position , Removing drain plugs
EVAPORATOR 3
Integrity , Cleaning , Bonding , Present on suction pipes , Present on piping liquid line
INSULATION 3
Temperature sensors entered with thermal paste , Gaskets transducers in the seat , Flow switch incoming if not
SENSORS present pump , Flow switch exit if present pump , Verification Bar pressure switches 3
Electrical cables not in contact with sharp metal , Cable fixing with cable ties , Wires under stress , No wires
ELETTRIC CABLES contact with hot pipes 3
Internal plate code / model / Volt / Hz , Removing jumpers used for testing , Voltage cables with stranded copper
ELECTRIC PANEL
by the sheath , Cable wiring tidy , Mechanical operation emergency button , Paint of fuses , Paint on pins fixing
power cables , Caps on the holes present on panel roof , Rubber caps on unused holes , Closing doors
3
alignment
Label identifying Daikin , Warning label , Type Gas label , Multilinguage Gas label , Label quantity Gas for circuit
INNER LABEL ELECTRIC
PANEL
, Check identifying chiller label data , Check weight on label identifying 3
Label identifying Daikin , Logo , Label lifting points , Check identifying SN/CH label data , Check weight on label
CHILLER EXTERNAL LABEL identifying 3
Compilation of RM with annotations and signatures , Dimension drawing and verification code with RM da ,
CHILLER DOCUMENTS
Electric scheme and verification code and revision , Compiling HATA with S/N and signatures , Certificates of
safety valves and check S/N , Certificates evaporators and check S/N , Dielectric tests performed , Dimension
3
drawing and verification code with RM da , Language manual
Check the back of the RM , Check notes for ancillaries not in the catalog , Cabin soundproofing for XN version ,

OPTIONAL
XN version spacers neoprene anchor bolts compress. , XN version insulation sandwich on piping liquid , LN
version insulation sandwich suction pipes , Verification requested special treatment battery , Mod Bus Card ,
3
Verification required special insulation , Victaulic for each connection , Gaskets for each connection , Boxes
vibration kit and verification code
PED - standard
TEST TYPE AND
CERTIFICATIONS 3
Microprocessor manual in languge , Multilingual Installation Manual , Certificates CE , Electric scheme ,
DOCUMENTS
ACCOMPANYING
Dimension drawing , Evaporator manual 3
Keys P.E. and evaporator caps on handle switch , Photo chiller four sides, inside P.E., optional , Seals on locks
FINAL AUDIT electrical panel , Label OK/QC 3

RILASCIO MACCHINA QC 25/03/19


QTA.MOD.0055_AWS

AUDIT CHECKLIST REV.001


22/05/2017

MODELLO / MODEL: CONFERMA/ORDER N°: DATA/DATE:


EWADC12C-PS012 OV18-06403
CH-19C00244-KKKKXX
22 3 2019

ITEM CONTROLLO OK
Homogeneous paint and color , Scratches , Damages , Item burnt , Rust , Cleaning
SHEET METALS 3
Sheet metals , Fan section , Compressor , Evaporator , Fixed screws and bolts , Fixed screw cabin , Application
ASSEMBLYNG rivets , Blunt tip screws channel fan section , Electrical wiring-capillaries no contact hot parts , Connections In /
Out free of obstacles
3
Vertical assembly , Verification model, Bar and S/N , Guarantee seal , Year and month validity start
SECURITY VALVES 3
Homogeneous paint and color , Cover conduit , Presence of all the fixing screws , Tightening cable gland
FANS 3
Homogeneous paint , Oil level , Verification code and S/N , Check oil label and correct data , Removing label
COMPRESSORS nitrogen presence , Delivery pipe tap closed , Suction tap open , Caps blind tightening , Verification heater Volt
and Watt
3
No contact with metal parts , No contact between pipes , Braze welding cleaning and quality , Absence of deep
ASSEMBLED PIPES cuts and creases , Taps closed and cap presence , Blind caps on attacks Schraeder 3

To be updated by Daikin for Phase 3


Braze welding , Rotalock , Oil sight compressor , Antivibration compressor , Taps , Expansion valves , Deitratore
PROTECTION TECTIL filter 3
Color
SIGHTGLASS 3
Fixing , Labels tightening torque
LIFTING BRACKETS 3
Verify code and S/N , Dents , Deformation excessive diaphragms
COILS 3
Verify code and S/N , Precence label In/Out and position , Removing drain plugs
EVAPORATOR 3
Integrity , Cleaning , Bonding , Present on suction pipes , Present on piping liquid line
INSULATION 3
Temperature sensors entered with thermal paste , Gaskets transducers in the seat , Flow switch incoming if not
SENSORS present pump , Flow switch exit if present pump , Verification Bar pressure switches 3
Electrical cables not in contact with sharp metal , Cable fixing with cable ties , Wires under stress , No wires
ELETTRIC CABLES contact with hot pipes 3
Internal plate code / model / Volt / Hz , Removing jumpers used for testing , Voltage cables with stranded copper
ELECTRIC PANEL
by the sheath , Cable wiring tidy , Mechanical operation emergency button , Paint of fuses , Paint on pins fixing
power cables , Caps on the holes present on panel roof , Rubber caps on unused holes , Closing doors
3
alignment
Label identifying Daikin , Warning label , Type Gas label , Multilinguage Gas label , Label quantity Gas for circuit
INNER LABEL ELECTRIC
PANEL
, Check identifying chiller label data , Check weight on label identifying 3
Label identifying Daikin , Logo , Label lifting points , Check identifying SN/CH label data , Check weight on label
CHILLER EXTERNAL LABEL identifying 3
Compilation of RM with annotations and signatures , Dimension drawing and verification code with RM da ,
CHILLER DOCUMENTS
Electric scheme and verification code and revision , Compiling HATA with S/N and signatures , Certificates of
safety valves and check S/N , Certificates evaporators and check S/N , Dielectric tests performed , Dimension
3
drawing and verification code with RM da , Language manual
Check the back of the RM , Check notes for ancillaries not in the catalog , Cabin soundproofing for XN version ,

OPTIONAL
XN version spacers neoprene anchor bolts compress. , XN version insulation sandwich on piping liquid , LN
version insulation sandwich suction pipes , Verification requested special treatment battery , Mod Bus Card ,
3
Verification required special insulation , Victaulic for each connection , Gaskets for each connection , Boxes
vibration kit and verification code
PED - standard
TEST TYPE AND
CERTIFICATIONS 3
Microprocessor manual in languge , Multilingual Installation Manual , Certificates CE , Electric scheme ,
DOCUMENTS
ACCOMPANYING
Dimension drawing , Evaporator manual 3
Keys P.E. and evaporator caps on handle switch , Photo chiller four sides, inside P.E., optional , Seals on locks
FINAL AUDIT electrical panel , Label OK/QC 3

RILASCIO MACCHINA QC 22/03/19


QTA.MOD.0055_AWS

AUDIT CHECKLIST REV.001


22/05/2017

MODELLO / MODEL: CONFERMA/ORDER N°: DATA/DATE:


EWADC12C-PS012 OV18-06403
CH-19C00245-KKKKXX
25 3 2019

ITEM CONTROLLO OK
Homogeneous paint and color , Scratches , Damages , Item burnt , Rust , Cleaning
SHEET METALS 3
Sheet metals , Fan section , Compressor , Evaporator , Fixed screws and bolts , Fixed screw cabin , Application
ASSEMBLYNG rivets , Blunt tip screws channel fan section , Electrical wiring-capillaries no contact hot parts , Connections In /
Out free of obstacles
3
Vertical assembly , Verification model, Bar and S/N , Guarantee seal , Year and month validity start
SECURITY VALVES 3
Homogeneous paint and color , Cover conduit , Presence of all the fixing screws , Tightening cable gland
FANS 3
Homogeneous paint , Oil level , Verification code and S/N , Check oil label and correct data , Removing label
COMPRESSORS nitrogen presence , Delivery pipe tap closed , Suction tap open , Caps blind tightening , Verification heater Volt
and Watt
3
No contact with metal parts , No contact between pipes , Braze welding cleaning and quality , Absence of deep
ASSEMBLED PIPES cuts and creases , Taps closed and cap presence , Blind caps on attacks Schraeder 3
Braze welding , Rotalock , Oil sight compressor , Antivibration compressor , Taps , Expansion valves , Deitratore

To be updated by Daikin for Phase 33


PROTECTION TECTIL filter 3
Color
SIGHTGLASS

Fixing , Labels tightening torque


LIFTING BRACKETS 3
Verify code and S/N , Dents , Deformation excessive diaphragms
COILS 3
Verify code and S/N , Precence label In/Out and position , Removing drain plugs
EVAPORATOR 3
Integrity , Cleaning , Bonding , Present on suction pipes , Present on piping liquid line
INSULATION 3
Temperature sensors entered with thermal paste , Gaskets transducers in the seat , Flow switch incoming if not
SENSORS present pump , Flow switch exit if present pump , Verification Bar pressure switches 3
Electrical cables not in contact with sharp metal , Cable fixing with cable ties , Wires under stress , No wires
ELETTRIC CABLES contact with hot pipes 3
Internal plate code / model / Volt / Hz , Removing jumpers used for testing , Voltage cables with stranded copper
ELECTRIC PANEL
by the sheath , Cable wiring tidy , Mechanical operation emergency button , Paint of fuses , Paint on pins fixing
power cables , Caps on the holes present on panel roof , Rubber caps on unused holes , Closing doors
3
alignment
Label identifying Daikin , Warning label , Type Gas label , Multilinguage Gas label , Label quantity Gas for circuit
INNER LABEL ELECTRIC
PANEL
, Check identifying chiller label data , Check weight on label identifying 3
Label identifying Daikin , Logo , Label lifting points , Check identifying SN/CH label data , Check weight on label
CHILLER EXTERNAL LABEL identifying 3
Compilation of RM with annotations and signatures , Dimension drawing and verification code with RM da ,
CHILLER DOCUMENTS
Electric scheme and verification code and revision , Compiling HATA with S/N and signatures , Certificates of
safety valves and check S/N , Certificates evaporators and check S/N , Dielectric tests performed , Dimension
3
drawing and verification code with RM da , Language manual
Check the back of the RM , Check notes for ancillaries not in the catalog , Cabin soundproofing for XN version ,

OPTIONAL
XN version spacers neoprene anchor bolts compress. , XN version insulation sandwich on piping liquid , LN
version insulation sandwich suction pipes , Verification requested special treatment battery , Mod Bus Card ,
3
Verification required special insulation , Victaulic for each connection , Gaskets for each connection , Boxes
vibration kit and verification code
PED - standard
TEST TYPE AND
CERTIFICATIONS 3
Microprocessor manual in languge , Multilingual Installation Manual , Certificates CE , Electric scheme ,
DOCUMENTS
ACCOMPANYING
Dimension drawing , Evaporator manual 3
Keys P.E. and evaporator caps on handle switch , Photo chiller four sides, inside P.E., optional , Seals on locks
FINAL AUDIT electrical panel , Label OK/QC 3

RILASCIO MACCHINA QC 25/03/19


To be updated by Daikin for Phase 3
To be updated by Daikin for Phase 3

You might also like